Fusarc CF / 50 A
Source 0
MVWD 0
10 m
1 x 300 Al
TA 0
Trihal
1000 kVA
22 kV / 400 V
TN-S
WD 0
15 m
Ph :7x300 Al
Ne :7x150 Al
PE :7x150 Cu
QA 0
MTZ1 16H1
MDB
No preference Micrologic 5.0 X
1600 A / 4P4d WC 1
Undefined
0
QA 3
NSX250B
Micrologic 5.2 E
250 A / 4P4d
Feeder circuit 3
WD 3
80 m
Ph :2x240 Cu
Ne :2x120 Cu
PE :1x240 Cu
QA 3bis
NSX250B
UC 5
Micrologic 5.2 E
No preference
250 A / 4P4d WC 4
Undefined
0
QA 6 QA 7 QA 8 QA 9
iC60L iC60L NG125N iC60L
C C C C
10 A / 4P4d 32 A / 4P4d 125 A / 4P4d 40 A / 4P4d
Load 6
Load 7
Load 8
Load 9
WD 6 WD 7 WD 8 WD 9
10 m 10 m 10 m 10 m
Ph :1x10 Cu Ph :1x10 Cu Ph :1x95 Cu Ph :1x25 Cu
Ne :1x10 Cu Ne :1x10 Cu Ne :1x50 Cu Ne :1x16 Cu
PE :1x10 Cu PE :1x10 Cu PE :1x50 Cu PE :1x25 Cu
MVQA 0
Source 0
MVWD 0
10 m
Iz : 484 A
TA 0
1000 kVA
22 kV / 400 V
TN-S
ukrT : 6 %
WD 0
15 m
Iz : 3000 A
Σ∆u3p : 0.199 %
Σ∆u2p : 0 %
Σ∆u1p : 0 %
QA 0
Ik3M : 23 kA
MDB
Ik1m : 18.6 kA
No preference
Iefmin : 19.1 kA
Undefined WC 1
0 Ik3M:23 kA
Ik1m:18.6 kA
Iefmin : 19.1 kA
QA 3
Ik3M : 23 kA
Ik1m : 18.6 kA
Iefmin : 19.1 kA
Feeder circuit 3
WD 3
80 m
Iz : 651 A
Σ∆u3p : 0.574 %
Σ∆u2p : 0 %
Σ∆u1p : 0 %
QA 3bis
Ik3M : 17 kA
UC 5
Ik1m : 9.6 kA
No preference
Iefmin : 8.75 kA WC 4
Undefined
0 Ik3M:17 kA
Ik1m:9.6 kA
Iefmin : 8.75 kA
QA 6 QA 7 QA 8 QA 9
Ik3M : 17 kA Ik3M : 17 kA Ik3M : 17 kA Ik3M : 17 kA
Ik1m : 9.6 kA Ik1m : 9.6 kA Ik1m : 9.6 kA Ik1m : 9.6 kA
Iefmin : 8.75 kA Iefmin : 8.75 kA Iefmin : 8.75 kA Iefmin : 8.75 kA
Load 6
Load 7
Load 8
Load 9
WD 6 WD 7 WD 8 WD 9
10 m 10 m 10 m 10 m
Iz : 75 A Iz : 75 A Iz : 298 A Iz : 127 A
Σ∆u3p : 0.648 % Σ∆u3p : 0.818 % Σ∆u3p : 0.685 % Σ∆u3p : 0.701 %
Σ∆u2p : 0 % Σ∆u2p : 0 % Σ∆u2p : 0 % Σ∆u2p : 0 %
Σ∆u1p : 0 % Σ∆u1p : 0 % Σ∆u1p : 0 % Σ∆u1p : 0 %
LP-GF-01 LP-GF-02 LP-GF-03 LP-GF-04
5.8 kVA 19 kVA 70 kVA 24 kVA
Ik3M:9.2 kA Ik3M:9.2 kA Ik3M:15.5 kA Ik3M:13.2 kA
Ik1m:3.39 kA Ik1m:3.39 kA Ik1m:7.55 kA Ik1m:5.07 kA
Iefmin : 3.37 kA Iefmin : 3.37 kA Iefmin : 7.12 kA Iefmin : 5.52 kA
W0
22 kV
MVQA 0
Source 0
MVWD 0
10 m
TA 0
1000 kVA
22 kV / 400 V
TN-S
WD 0
15 m
QA 0
MTZ1 16H1
MDB
Micrologic 5.0 X
No preference
1600 A / 4P4d
NA WC 1
NA
QA 3
NSX250B
Micrologic 5.2 E
250 A / 4P4d
Feeder circuit 3
WD 3
80 m
QA 3bis
NSX250B
UC 5
Micrologic 5.2 E
No preference
250 A / 4P4d WC 4
NA
NA
QA 6 QA 7 QA 8 QA 9
iC60L iC60L NG125N iC60L
C C C C
10 A / 4P4d 32 A / 4P4d 125 A / 4P4d 40 A / 4P4d
Load 6
Load 7
Load 8
Load 9
WD 6 WD 7 WD 8 WD 9
10 m 10 m 10 m 10 m
MVQA 0
Fusarc CF / 50 A
Source 0
MVWD 0
10 m
1 x 300 Al
TA 0
Trihal
1000 kVA
22 kV / 400 V
TN-S
WD 0
15 m
Ph :7x300 Al
Ne :7x150 Al
PE :7x150 Cu
QA 0
MTZ1 16H1
MDB
No preference Micrologic 5.0 X
1600 A / 4P4d WC 1
Undefined
0
QA 3
NSX250B
Micrologic 5.2 E
250 A / 4P4d
Feeder circuit 3
WD 3
80 m
Ph :2x240 Cu
Ne :2x120 Cu
PE :1x240 Cu
QA 3bis
NSX250B
UC 5
Micrologic 5.2 E
No preference
250 A / 4P4d WC 4
Undefined
0
QA 6 QA 7 QA 8 QA 9
iC60L iC60L NG125N iC60L
C C C C
10 A / 4P4d 32 A / 4P4d 125 A / 4P4d 40 A / 4P4d
Load 6
Load 7
Load 8
Load 9
WD 6 WD 7 WD 8 WD 9
10 m 10 m 10 m 10 m
Ph :1x10 Cu Ph :1x10 Cu Ph :1x95 Cu Ph :1x25 Cu
Ne :1x10 Cu Ne :1x10 Cu Ne :1x50 Cu Ne :1x16 Cu
PE :1x10 Cu PE :1x10 Cu PE :1x50 Cu PE :1x25 Cu
PROJECT_1
Full
Company information
Project information
Name : Private
Place : MENA
Customer name: Confidential
Revision : 00
Content
1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4
3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14
1 Project description
1.1 Project general settings
Installation standard IEC60364
NOTICE
RISK OF INACCURATE DATA RESULTS
Make sure that you have provided all the required inputs for the conductor sizing.
It is recommended to refer to the cable manufacturer's catalogue before making
the selection.
Failure to follow these instructions can result in incorrect bill of material and loss
of business.
2.1.5 MV Cable
Name Nbr Designation CSA (mm²) Icc (A) In (A) Un (kV)
MVWD 0 1 NA 1 x 300 Al 26.6 484 24
3 Calculation notes
MV/LV transformer TA 0
Range Trihal
Technology Resin
Rated power 1000 kVA
ukrT 6%
Type of losses AoAk
PkrT 9 kW
System earthing arrangement TN-S
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Cable WD 0
Parameters
Length 15 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Project: PROJECT_1 21/06/2023
Page 8/27
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Ib 1443 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.91
Standard table reference B-52-20
User correction factor 1
Overall factor 0.91
Selected phase
Cross section area 7x300 mm²
Core Aluminium
Iz under real conditions 3000 A
Iz’ 3297 A
Selected neutral
Cross section area 7x150 mm²
Core Aluminium
Iz under real conditions 1936 A
Iz’ 2128 A
Selected PE
Cross section area 7x150 mm²
Core Copper
Circuit breaker QA 0
Ib 1443 A
Distance from origin NA
Selectivity Results
UpStream Selectivity Limit
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Cable WD 3
Parameters
Length 80 m
Max length NA
Installation method 8
B2
Multi-core cable in cable trunking on a
wooden wall run horizontally
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Ib 171 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Selected phase
Cross section area 2x240 mm²
Core Copper
Iz under real conditions 651 A
Iz’ 814 A
Selected neutral
Cross section area 2x120 mm²
Core Copper
Iz under real conditions 429 A
Iz’ 536 A
Selected PE
Cross section area 1x240 mm²
Core Copper
Ii current 3000 A
Ti current 50 s
Selectivity Results
UpStream Selectivity Limit
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Cable WD 6
Parameters
Length 10 m
Max length 268 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Project: PROJECT_1 21/06/2023
Page 14/27
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge LP-GF-01
U 400 V
S 5.8 kVA
P 4.93 kW
I 8.37 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Project: PROJECT_1 21/06/2023
Page 15/27
Selectivity Results
UpStream Selectivity Limit
Cable WD 7
Parameters
Length 10 m
Max length 81 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: PROJECT_1 21/06/2023
Page 17/27
Ib 27 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper
Charge LP-GF-02
U 400 V
S 19 kVA
P 16.2 kW
I 27.4 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Cable WD 8
Parameters
Length 10 m
Max length 179 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: PROJECT_1 21/06/2023
Page 20/27
Ib 101 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x95 mm²
Core Copper
Iz under real conditions 298 A
Iz’ 298 A
Selected neutral
Cross section area 1x50 mm²
Core Copper
Iz under real conditions 192 A
Iz’ 192 A
Selected PE
Cross section area 1x50 mm²
Core Copper
Charge LP-GF-03
U 400 V
S 70 kVA
P 59.5 kW
I 101 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
Selectivity Results
UpStream Selectivity Limit
Cable WD 9
Parameters
Length 10 m
Max length 157 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: PROJECT_1 21/06/2023
Page 23/27
Ib 35 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1
Selected phase
Cross section area 1x25 mm²
Core Copper
Iz under real conditions 127 A
Iz’ 127 A
Selected neutral
Cross section area 1x16 mm²
Core Copper
Iz under real conditions 100 A
Iz’ 100 A
Selected PE
Cross section area 1x25 mm²
Core Copper
Charge LP-GF-04
U 400 V
S 24 kVA
P 20.4 kW
I 34.6 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN
3.4.2 Circuit WC 4
Busbar WC 4
Parameters
Switchboard Name UC 5
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type
Load 6 QA 6 iC60L
Load 7 QA 7 iC60L
Load 8 QA 8 NG125N
Load 9 QA 9 iC60L
</IF>
NOTICE
RISK OF INACCURATE DATA RESULTS.
Configure the software correctly to get accurate reports and/or data results.
Do not rely solely on software messages and reports to determine if the
system is functioning correctly.
Make sure that you have entered the correct inputs for the required
components.
Review the calculated results and solutions provided by the software before
submitting the report.
Failure to follow these instructions can result in incorrect bill of material and
loss of business.