Harmonics Design Studio

Project information Company information


Name : Private Name : Harmonics Design Studio
Place : - Street : -
Customer na - City : -
me:
Revision : - Zip code : -
Phone number : 0096181236957
Web site : -
W0
22 kV
250 / 750 MVA

MVQA 0
Fusarc CF / 50 A

Source 0
MVWD 0
10 m
1 x 300 Al

TA 0
Trihal
1000 kVA
22 kV / 400 V
TN-S

WD 0
15 m
Ph :7x300 Al
Ne :7x150 Al
PE :7x150 Cu

QA 0
MTZ1 16H1
MDB
No preference Micrologic 5.0 X
1600 A / 4P4d WC 1
Undefined
0

QA 3
NSX250B
Micrologic 5.2 E
250 A / 4P4d
Feeder circuit 3

WD 3
80 m
Ph :2x240 Cu
Ne :2x120 Cu
PE :1x240 Cu

QA 3bis
NSX250B
UC 5
Micrologic 5.2 E
No preference
250 A / 4P4d WC 4
Undefined
0

QA 6 QA 7 QA 8 QA 9
iC60L iC60L NG125N iC60L
C C C C
10 A / 4P4d 32 A / 4P4d 125 A / 4P4d 40 A / 4P4d
Load 6

Load 7

Load 8

Load 9

WD 6 WD 7 WD 8 WD 9
10 m 10 m 10 m 10 m
Ph :1x10 Cu Ph :1x10 Cu Ph :1x95 Cu Ph :1x25 Cu
Ne :1x10 Cu Ne :1x10 Cu Ne :1x50 Cu Ne :1x16 Cu
PE :1x10 Cu PE :1x10 Cu PE :1x50 Cu PE :1x25 Cu

LP-GF-01 LP-GF-02 LP-GF-03 LP-GF-04


5.8 kVA 19 kVA 70 kVA 24 kVA
P.F. : 0.85 P.F. : 0.85 P.F. : 0.85 P.F. : 0.85
Nbr. of circuits : 1 Nbr. of circuits : 1 Nbr. of circuits : 1 Nbr. of circuits : 1
Ku : 1 Ku : 1 Ku : 1 Ku : 1
W0
22 kV
Ik3M:21.7 kA
Ik3m:6.56 kA

MVQA 0

Source 0
MVWD 0
10 m
Iz : 484 A

TA 0
1000 kVA
22 kV / 400 V
TN-S
ukrT : 6 %
WD 0
15 m
Iz : 3000 A
Σ∆u3p : 0.199 %
Σ∆u2p : 0 %
Σ∆u1p : 0 %
QA 0
Ik3M : 23 kA
MDB
Ik1m : 18.6 kA
No preference
Iefmin : 19.1 kA
Undefined WC 1
0 Ik3M:23 kA
Ik1m:18.6 kA
Iefmin : 19.1 kA

QA 3
Ik3M : 23 kA
Ik1m : 18.6 kA
Iefmin : 19.1 kA
Feeder circuit 3

WD 3
80 m
Iz : 651 A
Σ∆u3p : 0.574 %
Σ∆u2p : 0 %
Σ∆u1p : 0 %
QA 3bis
Ik3M : 17 kA
UC 5
Ik1m : 9.6 kA
No preference
Iefmin : 8.75 kA WC 4
Undefined
0 Ik3M:17 kA
Ik1m:9.6 kA
Iefmin : 8.75 kA

QA 6 QA 7 QA 8 QA 9
Ik3M : 17 kA Ik3M : 17 kA Ik3M : 17 kA Ik3M : 17 kA
Ik1m : 9.6 kA Ik1m : 9.6 kA Ik1m : 9.6 kA Ik1m : 9.6 kA
Iefmin : 8.75 kA Iefmin : 8.75 kA Iefmin : 8.75 kA Iefmin : 8.75 kA
Load 6

Load 7

Load 8

Load 9

WD 6 WD 7 WD 8 WD 9
10 m 10 m 10 m 10 m
Iz : 75 A Iz : 75 A Iz : 298 A Iz : 127 A
Σ∆u3p : 0.648 % Σ∆u3p : 0.818 % Σ∆u3p : 0.685 % Σ∆u3p : 0.701 %
Σ∆u2p : 0 % Σ∆u2p : 0 % Σ∆u2p : 0 % Σ∆u2p : 0 %
Σ∆u1p : 0 % Σ∆u1p : 0 % Σ∆u1p : 0 % Σ∆u1p : 0 %
LP-GF-01 LP-GF-02 LP-GF-03 LP-GF-04
5.8 kVA 19 kVA 70 kVA 24 kVA
Ik3M:9.2 kA Ik3M:9.2 kA Ik3M:15.5 kA Ik3M:13.2 kA
Ik1m:3.39 kA Ik1m:3.39 kA Ik1m:7.55 kA Ik1m:5.07 kA
Iefmin : 3.37 kA Iefmin : 3.37 kA Iefmin : 7.12 kA Iefmin : 5.52 kA
W0
22 kV

MVQA 0

Source 0
MVWD 0
10 m

TA 0
1000 kVA
22 kV / 400 V
TN-S

WD 0
15 m

QA 0
MTZ1 16H1
MDB
Micrologic 5.0 X
No preference
1600 A / 4P4d
NA WC 1
NA

QA 3
NSX250B
Micrologic 5.2 E
250 A / 4P4d
Feeder circuit 3

WD 3
80 m

QA 3bis
NSX250B
UC 5
Micrologic 5.2 E
No preference
250 A / 4P4d WC 4
NA
NA

QA 6 QA 7 QA 8 QA 9
iC60L iC60L NG125N iC60L
C C C C
10 A / 4P4d 32 A / 4P4d 125 A / 4P4d 40 A / 4P4d
Load 6

Load 7

Load 8

Load 9

WD 6 WD 7 WD 8 WD 9
10 m 10 m 10 m 10 m

LP-GF-01 LP-GF-02 LP-GF-03 LP-GF-04


5.8 kVA 19 kVA 70 kVA 24 kVA
W0
22 kV
250 / 750 MVA

MVQA 0
Fusarc CF / 50 A

Source 0
MVWD 0
10 m
1 x 300 Al

TA 0
Trihal
1000 kVA
22 kV / 400 V
TN-S

WD 0
15 m
Ph :7x300 Al
Ne :7x150 Al
PE :7x150 Cu

QA 0
MTZ1 16H1
MDB
No preference Micrologic 5.0 X
1600 A / 4P4d WC 1
Undefined
0

QA 3
NSX250B
Micrologic 5.2 E
250 A / 4P4d
Feeder circuit 3

WD 3
80 m
Ph :2x240 Cu
Ne :2x120 Cu
PE :1x240 Cu

QA 3bis
NSX250B
UC 5
Micrologic 5.2 E
No preference
250 A / 4P4d WC 4
Undefined
0

QA 6 QA 7 QA 8 QA 9
iC60L iC60L NG125N iC60L
C C C C
10 A / 4P4d 32 A / 4P4d 125 A / 4P4d 40 A / 4P4d
Load 6

Load 7

Load 8

Load 9

WD 6 WD 7 WD 8 WD 9
10 m 10 m 10 m 10 m
Ph :1x10 Cu Ph :1x10 Cu Ph :1x95 Cu Ph :1x25 Cu
Ne :1x10 Cu Ne :1x10 Cu Ne :1x50 Cu Ne :1x16 Cu
PE :1x10 Cu PE :1x10 Cu PE :1x50 Cu PE :1x25 Cu

LP-GF-01 LP-GF-02 LP-GF-03 LP-GF-04


5.8 kVA 19 kVA 70 kVA 24 kVA
P.F. : 0.85 P.F. : 0.85 P.F. : 0.85 P.F. : 0.85
Nbr. of circuits : 1 Nbr. of circuits : 1 Nbr. of circuits : 1 Nbr. of circuits : 1
Ku : 1 Ku : 1 Ku : 1 Ku : 1
Eng. Tarek Kamar
Phone: 0096181236957
Mobile:

Installation calculation report

PROJECT_1
Full

Harmonics Design Studio


Page 2/27

Company information

Name : Harmonics Design Studio


Street : -
City : -
Zip code : -
Phone number : 0096181236957
Web site :

Project information

Name : Private
Place : MENA
Customer name: Confidential
Revision : 00

Project: PROJECT_1 21/06/2023


Page 3/27

Content

1 Project description.................................................................................................................. 4
1.1 Project general settings................................................................................................................... 4

1.2 Settings for wiring device calculation............................................................................................ 4

1.3 List of loads...................................................................................................................................... 4

2 Installation general design.....................................................................................................6


2.1 List of devices.................................................................................................................................. 6

3 Calculation notes.................................................................................................................. 14
3.1 Source circuits............................................................................................................................... 14

3.2 Generator circuits.......................................................................................................................... 23

3.3 LV Source circuits.......................................................................................................................... 23

3.4 UPS circuits.................................................................................................................................... 23

3.5 Surge Arrester circuits.................................................................................................................. 24

3.6 Capacitor bank circuits.................................................................................................................. 24

3.7 Feeder circuits................................................................................................................................ 24

3.8 LV Transformer circuits................................................................................................................. 26

3.9 Couplers circuits............................................................................................................................ 27

3.10 Generic load circuits................................................................................................................. 28

3.11 Lighting load circuits................................................................................................................ 28

3.12 Power socket load circuits....................................................................................................... 29

3.13 Motor starter combination........................................................................................................ 29

3.14 Busbar circuits.......................................................................................................................... 30

3.15 Busbar trunking system circuits............................................................................................. 30

3.16 Busbar trunking system circuits............................................................................................. 30

3.17 Lighting Busbar trunking system circuits..............................................................................30

Project: PROJECT_1 21/06/2023


Page 4/27

1 Project description
1.1 Project general settings
Installation standard IEC60364

Calculation standard TR50480


Circuit breaker standard IEC 60947-2
Frequency 50 Hz

1.2 Settings for wiring device calculation


Maximal CSA 300 mm²

1.3 List of loads


1.3.1 Generic loads
Name Sr (kVA) Pr (kW) Ir (A) Cos Nbr Polarity Non linear load THDi 3 (%)
LP-GF- 5.8 4.93 8.37 0.85 1 3Ph+N No 0
01
LP-GF- 19 16.2 27.4 0.85 1 3Ph+N No 0
02
LP-GF- 70 59.5 101 0.85 1 3Ph+N No 0
03
LP-GF- 24 20.4 34.6 0.85 1 3Ph+N No 0
04

Project: PROJECT_1 21/06/2023


Page 5/27

2 Installation general design


2.1 List of devices
2.1.1 MV/LV transformer
Name Nbr Range Insulation Sr (kVA) ukrT (%) Connection U2 (V) SEA Rb (m)
TA 0 1 Trihal Resin 1000 6 D 420 TN-S 10000

2.1.2 LV switchboards and busbar


Switchboard name Range Rating (A) IP
MDB No preference 0.00 Undefined
UC 5 No preference 0.00 Undefined

Busbar name Switchboard Ks Polarity SEA Equipotential bounding


name
WC 1 MDB 1 3Ph+N TN-S With
WC 4 UC 5 1 3Ph+N TN-S Without

2.1.3 Circuit breaker


Name Nbr Range - Rating Poles Trip RCD RCD class PowerTag PowerTag Energy
Designation (A) unit/Curve Energy ConnectionType
Designation
QA 0 1 Masterpact 1600 4P4d Micrologic
MTZ1 - 5.0 X
MTZ1 16H1
QA 3 1 Compact 250 4P4d Micrologic
NSX - 5.2 E
NSX250B
QA 1 Compact 250 4P4d Micrologic
3bis NSX - 5.2 E
NSX250B
QA 6 1 Acti9 iC60 - 10 4P4d C
iC60L
QA 7 1 Acti9 iC60 - 32 4P4d C
iC60L
QA 8 1 Acti9 NG125 125 4P4d C
- NG125N
QA 9 1 Acti9 iC60 - 40 4P4d C
iC60L

2.1.4 Cable schedule


Name Nbr Incomer Feeder Type Insulation L (m) L1/L2/L3 N PE/PEN
WD 3 1 QA 3 QA 3bis Multi-core XLPE 80 2x240 2x120 1x240 Copper
Copper Copper
WD 0 1 TA 0 QA 0 Multi-core XLPE 15 7x300 7x150 7x150 Copper
Aluminium Aluminium
WD 9 1 QA 9 LP-GF- Multi-core XLPE 10 1x25 1x16 1x25 Copper
04 Copper Copper
WD 8 1 QA 8 LP-GF- Multi-core XLPE 10 1x95 1x50 1x50 Copper
03 Copper Copper
WD 7 1 QA 7 LP-GF- Multi-core XLPE 10 1x10 1x10 1x10 Copper
02 Copper Copper
WD 6 1 QA 6 LP-GF- Multi-core XLPE 10 1x10 1x10 1x10 Copper
01 Copper Copper

Project: PROJECT_1 21/06/2023


Page 6/27

NOTICE
RISK OF INACCURATE DATA RESULTS

 Make sure that you have provided all the required inputs for the conductor sizing.
 It is recommended to refer to the cable manufacturer's catalogue before making
the selection.

Failure to follow these instructions can result in incorrect bill of material and loss
of business.

2.1.5 MV Cable
Name Nbr Designation CSA (mm²) Icc (A) In (A) Un (kV)
MVWD 0 1 NA 1 x 300 Al 26.6 484 24

Project: PROJECT_1 21/06/2023


Page 7/27

3 Calculation notes

3.1 Source circuits


3.1.1 Circuit Source 0
MV power supply W0
Max. upstream short circuit power 750 MVA
Min. upstream short circuit power 250 MVA
MV fuse MVQA 0
Parameters
Type of standard DIN
Range Fusarc CF
Ib 26 A
Type of Equipment SM6
Rating 50 A
Insulation voltage 24 kV
Assigned voltage 22 kV
Ikmax MV 21.65 kA
Ikmin MV 5.4 kA
Ikmin LV from MV 204.69 A
Fusing time Ikmin LV 3.29 s
MV Cable MVWD 0
Parameters
Length 10 m
Type of cable Multi core
Ib 26 A
Nb of conductor per phase 1
Cross section area 1 x 300 Al mm²
Core Aluminium
Short circuit withstand 26.6 kA
Assigned voltage 22 kV
Insulation voltage 24 kV

MV/LV transformer TA 0
Range Trihal
Technology Resin
Rated power 1000 kVA
ukrT 6%
Type of losses AoAk
PkrT 9 kW
System earthing arrangement TN-S
MV Connection D
LV Connection yn
No load secondary voltage Ur0 420V
Ur LV 400V
Rb (neutral grounding) NA
Ra (mass grounding) NA
Sizing information UkrT and PkrT calculated by system
Cable WD 0
Parameters
Length 15 m
Max length NA
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Project: PROJECT_1 21/06/2023
Page 8/27

Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Ib 1443 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.91
Standard table reference B-52-20
User correction factor 1
Overall factor 0.91

Selected phase
Cross section area 7x300 mm²
Core Aluminium
Iz under real conditions 3000 A
Iz’ 3297 A
Selected neutral
Cross section area 7x150 mm²
Core Aluminium
Iz under real conditions 1936 A
Iz’ 2128 A
Selected PE
Cross section area 7x150 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 23.05 19.96 22.55 16.50 18.57 19.06 NA 22.07

Synthesis for all operating mode


(kA) 23.05 19.96 22.55 16.50 18.57 19.06 NA 22.07

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 0
Ib 1443 A
Distance from origin NA

Sizing Information Sized by system


Range Masterpact MTZ1
Designation MTZ1 16H1
Circuit breaker rating 1600 A
Breaking capacity 42 kA
TNS One pole breaking capacity 42 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.0 X
Project: PROJECT_1 21/06/2023
Page 9/27

Trip unit rating 1600 A


Long delay settings
Ir 1472 (Setting: 0.92) A
Tr 24 s
Short delay settings
Isd current 11776 A
Tsd 0.4 s
Instantaneous tripping
Ii current 19200 (Setting: 12) A
Ti current 0.05 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


MVQA 0 6071 A
Fusarc CF / 50A

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 171.473 171.473 171.473 0

Synthesis for all operating mode


(A) 171.473 171.473 171.473 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.199 0.199
UL1L2 (%) 0.230 0.230
UL2L3 (%) 0.230 0.230
UL3L1 (%) 0.230 0.230
UL1N (%) 0.199 0.199
UL2N (%) 0.199 0.199
UL3N (%) 0.199 0.199

3.2 Feeder circuits


3.2.1 Circuit Feeder circuit 3
Circuit breaker QA 3
Ib 171 A
Distance from origin NA

Project: PROJECT_1 21/06/2023


Page 10/27

Sizing Information Sized by system


Range Compact NSX
Designation NSX250B
Circuit breaker rating 250 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.2 E
Trip unit rating 250 A
Long delay settings
Ir 172 A
Tr 4s
Short delay settings
Isd current 1720 A
Tsd 0.4 s
Instantaneous tripping
Ii current 3000 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 0 Total Selectivity
MTZ1 16H1
Micrologic 5.0 X
1600 A / 4P4d

Cable WD 3
Parameters
Length 80 m
Max length NA
Installation method 8
B2
Multi-core cable in cable trunking on a
wooden wall run horizontally
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Ib 171 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1

Project: PROJECT_1 21/06/2023


Page 11/27

Standard table reference B-52-14


Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 0.8
Standard table reference B-52-17
User correction factor 1
Overall factor 0.8

Selected phase
Cross section area 2x240 mm²
Core Copper
Iz under real conditions 651 A
Iz’ 814 A
Selected neutral
Cross section area 2x120 mm²
Core Copper
Iz under real conditions 429 A
Iz’ 536 A
Selected PE
Cross section area 1x240 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 17.05 14.76 12.16 12.12 9.57 8.75 NA 10.14

Synthesis for all operating mode


(kA) 17.05 14.76 12.16 12.12 9.57 8.75 NA 10.14

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker QA 3bis


Ib 171 A
Distance from origin NA

Sizing Information Sized by system


Range Compact NSX
Designation NSX250B
Circuit breaker rating 250 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation Micrologic 5.2 E
Trip unit rating 250 A
Long delay settings
Ir 172 A
Tr 4s
Short delay settings
Isd current 1720 A
Tsd 0.4 s
Instantaneous tripping
Project: PROJECT_1 21/06/2023
Page 12/27

Ii current 3000 A
Ti current 50 s

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 3 No Selectivity
NSX250B
Micrologic 5.2 E
250 A / 4P4d

Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 171.473 171.473 171.473 0

Synthesis for all operating mode


(A) 171.473 171.473 171.473 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.574 0.374
UL1L2 (%) 0.662 0.432
UL2L3 (%) 0.662 0.432
UL3L1 (%) 0.662 0.432
UL1N (%) 0.574 0.374
UL2N (%) 0.574 0.374
UL3N (%) 0.574 0.374

Project: PROJECT_1 21/06/2023


Page 13/27

3.3 Generic load circuits

3.3.1 Circuit Load 6


Circuit breaker QA 6
Ib 8.37 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 10 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 10 A
Long delay settings
Ir 10 A
Tr NA
Short delay settings
Isd current 80 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 3bis Total Selectivity
NSX250B
Micrologic 5.2 E
250 A / 4P4d

Cable WD 6
Parameters
Length 10 m
Max length 268 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Project: PROJECT_1 21/06/2023
Page 14/27

Type of cable Multi-core


Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Ib 8A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 9.16 7.93 4.87 5.70 3.39 3.37 NA 3.90

Synthesis for all operating mode


(kA) 9.16 7.93 4.87 5.70 3.39 3.37 NA 3.90

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge LP-GF-01
U 400 V
S 5.8 kVA
P 4.93 kW
I 8.37 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Project: PROJECT_1 21/06/2023
Page 15/27

Sensitivity to over voltage NA


Design current
IL1 IL2 IL3 IN

Operating mode Normal


(A) 8.372 8.372 8.372 0

Synthesis for all operating mode


(A) 8.372 8.372 8.372 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.648 0.075
UL1L2 (%) 0.748 0.086
UL2L3 (%) 0.748 0.086
UL3L1 (%) 0.748 0.086
UL1N (%) 0.648 0.075
UL2N (%) 0.648 0.075
UL3N (%) 0.648 0.075

Synthesis for all operating mode


U3L (%) 0.648
UL1L2 (%) 0.748
UL2L3 (%) 0.748
UL3L1 (%) 0.748
UL1N (%) 0.648
UL2N (%) 0.648
UL3N (%) 0.648

Project: PROJECT_1 21/06/2023


Page 16/27

3.3.2 Circuit Load 7


Circuit breaker QA 7
Ib 27.4 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 32 A
Breaking capacity 20 kA
TNS One pole breaking capacity 20 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 32 A
Long delay settings
Ir 32 A
Tr NA
Short delay settings
Isd current 256 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 3bis Total Selectivity
NSX250B
Micrologic 5.2 E
250 A / 4P4d

Cable WD 7
Parameters
Length 10 m
Max length 81 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: PROJECT_1 21/06/2023
Page 17/27

Ib 27 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected neutral
Cross section area 1x10 mm²
Core Copper
Iz under real conditions 75 A
Iz’ 75 A
Selected PE
Cross section area 1x10 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 9.16 7.93 4.87 5.70 3.39 3.37 NA 3.90

Synthesis for all operating mode


(kA) 9.16 7.93 4.87 5.70 3.39 3.37 NA 3.90

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge LP-GF-02
U 400 V
S 19 kVA
P 16.2 kW
I 27.4 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: PROJECT_1 21/06/2023
Page 18/27

(A) 27.424 27.424 27.424 0

Synthesis for all operating mode


(A) 27.424 27.424 27.424 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.818 0.244
UL1L2 (%) 0.944 0.282
UL2L3 (%) 0.944 0.282
UL3L1 (%) 0.944 0.282
UL1N (%) 0.818 0.244
UL2N (%) 0.818 0.244
UL3N (%) 0.818 0.244

Synthesis for all operating mode


U3L (%) 0.818
UL1L2 (%) 0.944
UL2L3 (%) 0.944
UL3L1 (%) 0.944
UL1N (%) 0.818
UL2N (%) 0.818
UL3N (%) 0.818

Project: PROJECT_1 21/06/2023


Page 19/27

3.3.3 Circuit Load 8


Circuit breaker QA 8
Ib 101 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 NG125
Designation NG125N
Circuit breaker rating 125 A
Breaking capacity 25 kA
TNS One pole breaking capacity 25 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 125 A
Long delay settings
Ir 125 A
Tr NA
Short delay settings
Isd current 1000 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 3bis Total Selectivity
NSX250B
Micrologic 5.2 E
250 A / 4P4d

Cable WD 8
Parameters
Length 10 m
Max length 179 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: PROJECT_1 21/06/2023
Page 20/27

Ib 101 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x95 mm²
Core Copper
Iz under real conditions 298 A
Iz’ 298 A
Selected neutral
Cross section area 1x50 mm²
Core Copper
Iz under real conditions 192 A
Iz’ 192 A
Selected PE
Cross section area 1x50 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 15.51 13.44 9.91 10.87 7.55 7.12 NA 8.25

Synthesis for all operating mode


(kA) 15.51 13.44 9.91 10.87 7.55 7.12 NA 8.25

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge LP-GF-03
U 400 V
S 70 kVA
P 59.5 kW
I 101 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: PROJECT_1 21/06/2023
Page 21/27

(A) 101.036 101.036 101.036 0

Synthesis for all operating mode


(A) 101.036 101.036 101.036 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.685 0.111
UL1L2 (%) 0.791 0.128
UL2L3 (%) 0.791 0.128
UL3L1 (%) 0.791 0.128
UL1N (%) 0.685 0.111
UL2N (%) 0.685 0.111
UL3N (%) 0.685 0.111

Synthesis for all operating mode


U3L (%) 0.685
UL1L2 (%) 0.791
UL2L3 (%) 0.791
UL3L1 (%) 0.791
UL1N (%) 0.685
UL2N (%) 0.685
UL3N (%) 0.685

Project: PROJECT_1 21/06/2023


Page 22/27

3.3.4 Circuit Load 9


Circuit breaker QA 9
Ib 34.6 A
Distance from origin NA

Sizing Information Sized by system


Range Acti9 iC60
Designation iC60L
Circuit breaker rating 40 A
Breaking capacity 20 kA
TNS One pole breaking capacity 20 kA
IT One pole breaking capacity NA
Reinforced breaking capacity NA
Pole & protected pole 4P4d
Trip unit designation C
Trip unit rating 40 A
Long delay settings
Ir 40 A
Tr NA
Short delay settings
Isd current 320 A
Tsd NA
Instantaneous tripping
Ii current NA
Ti current NA

Selectivity Results
UpStream Selectivity Limit

Operating mode Normal


QA 3bis Total Selectivity
NSX250B
Micrologic 5.2 E
250 A / 4P4d

Cable WD 9
Parameters
Length 10 m
Max length 157 m
Installation method 31
E
Multi-core cables on horizontal
perforated tray
Type of cable Multi-core
Nb of additional touching circuits NA
Insulation XLPE
Ambient temperature 30 °C
Level of third harmonic THDI NA %
Project: PROJECT_1 21/06/2023
Page 23/27

Ib 35 A
Sizing constraint Iz
Sizing Information Sized with Ir
Correction factors
Temperature factor 1
Standard table reference B-52-14
Soil thermal resistivity factor 1
Standard table reference B-52-16
Loaded neutral factor 1
Standard table reference E-52-1
Touching conductor factor 1
Standard table reference B-52-20
User correction factor 1
Overall factor 1

Selected phase
Cross section area 1x25 mm²
Core Copper
Iz under real conditions 127 A
Iz’ 127 A
Selected neutral
Cross section area 1x16 mm²
Core Copper
Iz under real conditions 100 A
Iz’ 100 A
Selected PE
Cross section area 1x25 mm²
Core Copper

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 13.16 11.40 7.07 8.76 5.07 5.52 NA 6.39

Synthesis for all operating mode


(kA) 13.16 11.40 7.07 8.76 5.07 5.52 NA 6.39

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge LP-GF-04
U 400 V
S 24 kVA
P 20.4 kW
I 34.6 A
cos 0.85
Polarity 3Ph+N
Phase connection
Number of circuit 1
Ku (Normal) 1
Harmonic generator No
THDI3 NA
Sensitivity to over voltage NA
Design current
IL1 IL2 IL3 IN

Operating mode Normal


Project: PROJECT_1 21/06/2023
Page 24/27

(A) 34.641 34.641 34.641 0

Synthesis for all operating mode


(A) 34.641 34.641 34.641 NA
Voltage drop
Cumulated from upstream Circuit

Operating mode Normal


U3L (%) 0.701 0.127
UL1L2 (%) 0.809 0.147
UL2L3 (%) 0.809 0.147
UL3L1 (%) 0.809 0.147
UL1N (%) 0.701 0.127
UL2N (%) 0.701 0.127
UL3N (%) 0.701 0.127

Synthesis for all operating mode


U3L (%) 0.701
UL1L2 (%) 0.809
UL2L3 (%) 0.809
UL3L1 (%) 0.809
UL1N (%) 0.701
UL2N (%) 0.701
UL3N (%) 0.701

Project: PROJECT_1 21/06/2023


Page 25/27

3.4 Busbar circuits


3.4.1 Circuit WC 1
Busbar WC 1
Parameters
Switchboard Name MDB
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type

Feeder circuit 3 QA 3 NSX250B

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal


(kA) 23.05 19.96 22.55 16.52 18.64 19.08 NA 22.09

Synthesis for all operating mode


(kA) 23.05 19.96 22.55 16.52 18.64 19.08 NA 22.09

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

3.4.2 Circuit WC 4
Busbar WC 4
Parameters
Switchboard Name UC 5
Switchboard Range No preference
Rating (A) NA
IP Undefined
Feeder
Circuit name Protection name Protection type

Load 6 QA 6 iC60L

Load 7 QA 7 iC60L

Load 8 QA 8 NG125N

Load 9 QA 9 iC60L

Short circuit current


Ik3max Ik2max Ik1max Ik2min Ik1min Iefmin Ief2min Iefmax

Operating mode Normal

Project: PROJECT_1 21/06/2023


Page 26/27

(kA) 17.05 14.76 12.16 12.12 9.57 8.75 NA 10.14

Synthesis for all operating mode


(kA) 17.05 14.76 12.16 12.12 9.57 8.75 NA 10.14

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

</IF>

Project: PROJECT_1 21/06/2023


Page 27/27

NOTICE
RISK OF INACCURATE DATA RESULTS.

 Configure the software correctly to get accurate reports and/or data results.
 Do not rely solely on software messages and reports to determine if the
system is functioning correctly.
 Make sure that you have entered the correct inputs for the required
components.
 Review the calculated results and solutions provided by the software before
submitting the report.

Failure to follow these instructions can result in incorrect bill of material and
loss of business.