This design change notice proposes changes to the type of equipment used for the 35kV transmission system for the Vung Ang II Thermal Power Plant. The changes are being made to comply with requirements from the Ky Anh power company. The proposed changes include using different cable models, greasing cable conductors, changing insulator and surge arrester manufacturers and models, and increasing the creepage distance and voltage ratings of certain equipment. The changes are described in the document and specifications will be revised to incorporate the changes.
Original Description:
Design to change
Original Title
VA2-OM-DCN-23-A-0019 DCN for Change the Type of Equipment of 35kV System
This design change notice proposes changes to the type of equipment used for the 35kV transmission system for the Vung Ang II Thermal Power Plant. The changes are being made to comply with requirements from the Ky Anh power company. The proposed changes include using different cable models, greasing cable conductors, changing insulator and surge arrester manufacturers and models, and increasing the creepage distance and voltage ratings of certain equipment. The changes are described in the document and specifications will be revised to incorporate the changes.
This design change notice proposes changes to the type of equipment used for the 35kV transmission system for the Vung Ang II Thermal Power Plant. The changes are being made to comply with requirements from the Ky Anh power company. The proposed changes include using different cable models, greasing cable conductors, changing insulator and surge arrester manufacturers and models, and increasing the creepage distance and voltage ratings of certain equipment. The changes are described in the document and specifications will be revised to incorporate the changes.
VA2-OM-DCN-23-A-0019 Rev. A Change the type of equipment of 35kV system
REASONS FOR CHANGE:
The equipment mentioned in the document: “VA2-OM-TS-05 Technical Specification of 35kV Transmission line electrical equipment” isn't complying with Ky Anh power company (EVN) requirement (See attachment-1 Page 2~4). So, the contractor changes to meet Ky Anh power company's requirements with equipment/material as below: - Cable CXV/SE/DSTA 3x50mm2 - Cable ACSR95 - Polymer suspension insulator 35kV - Polymer pin Insulators 35kV - Surge arresters 35 kV AS PER DESIGN: DESCRIPTION OF CHANGE: 1. Refer to the document No item: VA2-OM-TS-05: Technical Specification of 35kV Transmission line electrical Equipments_rev.4 1. Cable: CXV/SE/DSTA- 3C x 50mm2 1. Cable: CXV/XLPE/CTS/PVC/DSTA- 3C x - Manufacturer: CADIVI 50mm2 - Voltage rate: 18/30 (36) kV - Manufacturer: CADI-SUN - Nominal area: 50 mm2 - Voltage rate: 20/35 (40.5) kV - Nominal area: 50 mm2 - Conductor waterproofing
2. Cable ACSR95 2. Cable ACKP95.
- Nominal area: 95/141 mm2 - Nominal area: 95/16 mm2 - All the conductor is greased except the outer layer 3. Polymer suspension insulator 35kV 3. Polymer suspension insulator 35kV - Manufacturer: NCT Viet Nam - Manufacturer: VINA Electric - Model: CS-35 - Model: DN 36SD - Creepage distance: 25/31mm2 - Creepage distance: 1010 mm
- Manufacturer: Dong Hai - Manufacture: VINA Electric - Model: Line post 35 - Model: PP-36 - Minimum creepage distance: 875 mm - Minimum creepage distance: 1059 mm
SUB-CONTRACTOR: PREPARED BY NAME: TRAN DUC HIEP DATE: 22 Jun 2023 HCA CONTRACTOR:
REPLY COMMENT BY NAME: NGUYEN THANH TAM DATE: 23 Jun 2023
OWNER’S COMMENTS:
APPROVED BY NAME: DATE:
OE CONSENT NAME: DATE:
NAME: Owner CONSENT NAME: DATE: DOCUMENT INCORPORATION (LIST OR DESIGN DOCUMENT(S) REVISED TO INCORPORATE DCN) DOCUMENT NO. REV NO. REMARKS/TITLE To reduce the capacity of the submission file, the VA2-OM-TS-05 Technical Specification of Rev4 contractor only captured the technical catalog related to 35kV Transmission line electrical Equipment equipment which proposed to change. 1. Cable 3C x 50mm2 ORIGINAL ORIGINAL DCN 2. Cable AC 1Cx95mm2 ORIGINAL DCN DCN 3. Polymer suspension insulator 35kV ORIGINAL DCN 4. Polymer pin insulators 35kV ORIGINAL DCN 5. Surge arresters 35kV ORIGINAL DCN