House Plans Erf 17236 Final
House Plans Erf 17236 Final
3000
SEWER LINE
ALL FOUNDATION MUST BE CAST IN STRICT ACCORDANCE WITH THE
YARD
requirements of Municipal and Local
ENGINEER'S DETAIL AND SPECIFICATION. FOR ALL STRUCTURAL WORK 3000mm building line D FOUL WATER PIPES
Authorities concerned are to be adhered to.
THE CONTRACTOR MUST REFER TO THE ENGINEER'S DRAWINGS AND ANY 2000
TD WM DW
EN-SUITE
EN-SUITE
DISCREPANCIES BETWEEN THE ENGINEERS DRAWINGS AND THE 4. Natural light and ventilation area of all
ARCHITECTS DRAWINGS MUST BE REPORTED BEFORE CONSTRUCTION PANTRY SCULLERY WASTE WATER PIPES
COMMENCES. BCB
openings in accordance of floor area and
INSPECTION EYE SANS 10400 Part O natural light area:
DRESSING
WALLS TO BE PLASTERED AND PAINTED: PAINT & COLOUR TO LATER
COVERED STOEP
pitch line of stairs and shop-fronts to be safety
SPECIFICATION.
DECKING
FORMAL LOUNGE ERF 17235 glass.
STORMWATER LEGEND:
WEEP HOLES
WEEP HOLES AT 2 BRICK INTERVALS AT ALL FLOOR SLAB LEVELS AND
2000
B
DECKING 160mmØ STORMWATER CHANNEL & PIPES 6. All safety glazing panels shall be etched with
BEDROOM 1
OVER ALL WINDOWS AND EXTERIOR DOORS. STEPPED DPC TO LATER POOL glazing marking and this to be visible at all
WATERPROOFING DETAIL. 110mmØ UPVC STORMWATER PIPE times.
B DECKING
600 X 600 ACCESS HATCH TO TANK 8. No part of construction may encroach building
GROUND FLOOR - FLOOR CONSTRUCTION
FLOOR FINISH (AS INDICATED ON PLANS) ON 30MM SCREED ON 100MM
lines.
MESH RC CONCRETE SURFACE BED (AS DETAILED AND SPECIFIED BY THE 29 723mm BOUNDARY LINE 110mmØ UPVC OVERFLOW PIPE
ENGINEER), ON GUNDLE USB GREEN CO EX 250µM DAMP PROOF 4000
MEMBRANE TO SANS MARK 952-1985 TYPE C LAID WITH MINIMUM 150MM 110mmØ UPVC DRAINING OUTLET Revisions: ( See clouded areas)
OVERLAPS AND SEALED WITH GUNPLAS PRESSURE SENSITIVE TAPE ON
ATTALIA STREET
50MM SAND BLINDING ON 150MM LAYERS OF THICK 95% MOD AASTHO
WELL COMPACTED GROUND / FILL AS SPECIFIED BY THE ENGINEER.
SITE PLAN 75mmØ RAIN WATER PIPE WITH STANDARD 280
No. Date Description
RWP
FIRST FLOOR - FLOOR CONSTRUCTION
SCALE 1: 200 X 280mm BRICK GULLY.
.. .... .....
FLOOR FINISH (AS INDICATED ON PLANS) ON 30 mm CEMENT SCREED ON
REINFORCED CONCRETE SLAB. CONCRETE SLAB TO BE CONSTRUCTED IN
STRICT ACCORDANCE WITH THE ENGINEER'S DETAILED AND .....
.. ....
SPECIFICATION.
BOUNDARY WALLS:
270
MEMBRANE FINISHED WITH TWO COATS OF BITUMENOUS ALUMINIUM 137 VENTILATED GREYWATER INLET FROM
PAINT. COVER WITH A 60MM THICK LAYER OF 19 - 25MM BROWN STONE
STORAGE GREYWATER INLET FROM KITCHEN & SCULLERY.
2590
2590
UNDER BATHROOMS.
CHIPS. WATERPROOFING TO BE INSTALLED BY AN APPROVED DERBIGUM 110MM Ø UPVC VENT PIPE
STAIRS
Tiles
IE
270
INSTALLED BY A SPECIALIST SUB-CONTRACTOR. 900
136.5
270
138.5
350
379
1660
D8
110 1660
SPACED NOT MORE THAN 350MM APART. Tiles
ENTRANCE D1 W2 W2 270
1770
2270
1
B B
EXISTING BOUNDARY WALL TO REMAIN
D9 EN-SUITE
110
Tiles 1 1 2 W10
EAVES AND RAINWATER GOODS SKYLIGHT ABOVE 2 Tiles 1
OGEE SEAMLESS ALUMINIUM GUTTER, 125 X 85 X 0.6MM THICK (COLOUR : 136 RAINWATER / GREY
MH WATER TANK RAINWATER INLET FROM 138
230
4840
FASCIA (PAINTED DARK GREY TO MATCH ROOF COLOUR)THAT IS FIXED TO
MH D7 (30 000L) BACKYARD.
230MM FIRE WALL
1330
1
A 22 X 150mm SA PINE FASCIA PLAN . INSTALL ALUMINIUM MESH LEAF RAINWATER INLET FROM
TRAP SET OVER GUTTER WITH 100 X75MM RACTANGULAR FLUTED CONCRETE ROOFS. CLIENT:
ALUMINIUM DOWNPIPE. FIXED TO WALL WITH HOLDERBATS. SEAL FIRE DOOR TO BE FITTED 137.5 - BASE LEVEL
2420
GUTTERS AND DOWNPIPES ON THE INSIDE WITH SILICONE SEALER. WITH SELF-CLOSING DEVICE. 600 X 600MM ACCESS HATCH.
135.5
DRIVEWAY 1920 3000 LE ROUX PROJECTS
Exposed aggregate
DRAINAGE 110
6920
6040
interlocking pavers
6570
350
350
WASTEPIPES TO BE 50Ø mm PVC D6 ERF 17235 PROJECT TITLE:
5920
4800
2930
D3
3150
ALL DRAINAGE BELOW SURFACE BED AND PENETRATING THROUGH 7500 POOL ABOVE RAINWATER INLET FROM 2
FOUNDATION WALLS TO BE ENCASED IN min 500mm THK CONC.
110MM Ø UPVC SEWER PIPE
TO CONNECT TO MUNICIPAL
DECK ABOVE. 136.5 17236, FAIRHAVEN,
SLOW BENDS TO ALL JUNCTIONS HAPPENING BELOW SURFACE BED. SEWER LINE RAINWATER INLET FROM
W1 CONCRETE ROOFS AND DECK SOMERSET WEST.
270
270
600
350
136
270
WATER SUPPLY HEADER COURSE EDGE WINDOW ABOVE MUNICIPAL SEWER LINE
POTABLE WATER RINGMAIN AROUND HOUSE TO BE SAME Ø AS MAIN COLOUR: TABLE MOUNTAIN SANDSTONE 4000mm building line RAINWATER PIPE TO BE W1
MH
134 FITTED TO SOFFIT OF SLAB. 2 DRAWING TITLE:
SUPPLY TO PROPERTY. (MINIMUM 25mmØ) 6480 4935 135.5
2500 720
SUPPLY LINES INSIDE HOUSE TO BE 20mmØ.
7730 270
SHUTOFF COCKS TO BE INSTALLED BEFORE ALL ITEMS SUCH AS WASH 270 270
SITE AND LOWER GROUND
4000
133
133 29 723mm BOUNDARY LINE 134 134.5 134.59
4000
133.5
PROJECT No.: SCALE:
02 JB ..
NOTE: · Indicate height in terms of D.M.S in addition to height
IT REMAINS THE RESPONSIBILITY OF THE HOME restriction of estate.
OWNER TO ADHERE TO ALL THE STIPULATIONS LOWER GROUND FLOOR DRAWINGS REVISED FOR RESUBMISSION 2017.08.29: · Ground floor of dwelling not to be raised more than 1.5m
· Ground floor of dwelling not to be raised more than 1.5m FOR SUBMISSION
IN THE FHCE ARCHITECTURAL GUIDELINES. SCALE 1:100 above E.G.L.
above E.G.L.
· Indicate height of any retaining wall structure in accordance
· New Guest bedroom - Lower Ground Floor Level. with requirements of D.M.S.
This drawing and all the information contained thereon is the
property of Dennis Moss Partnership and may not be copied
or disclosed to a third party without their written consent.
General Notes:
FOUNDATIONS: LEGEND:
ALL FOUNDATION MUST BE CAST IN STRICT ACCORDANCE 1. Contractor and Sub-Contractors to check all
SPECIFICATION NOTES: A ERF 17237
WITH THE ENGINEER'S DETAIL AND SPECIFICATION. FOR ALL
STRUCTURAL WORK THE CONTRACTOR MUST REFER TO
NEW COVERED AREAS
levels and dimensions on site before any work
C THE ENGINEER'S DRAWINGS AND ANY DISCREPANCIES
is commenced and any discrepancies to be
LEVELS:
270
1300
110
3085
110
1300
110
3200 4340
230
4050
270
1500
110
3850
270
BETWEEN THE ENGINEERS DRAWINGS AND THE TO BE DEMOLISHED reported to the Architect immediately.
LEVELS:
REFER TO SECTIONS. 1200 ARCHITECTS DRAWINGS MUST BE REPORTED BEFORE
REFER TO SECTIONS. 900 900
470
1160 1370 900 1260 1200 2740 1200 2590 2400 3330 900 595 1100
CONSTRUCTION COMMENCES. NEW WALLS 2. Figured dimensions to be taken in preference
FOUNDATIONS 139.5 to scaled measurements and large scale
139 29 723mm BOUNDARY LINE 140 140.5 BOUNDARY LINE
ALL FOUNDATIONS TO BE AT A MINIMUM DEPTH OF 750mm. 138.73 140.63 details supercede small scale drawings.
INTERNAL WALLS : R.C. STRIP FOUNDATION TO ENG'S
110MM Ø UPVC SEWER PIPE TO 1800mm BOUNDARY WALL 1800mm BOUNDARY WALL
DESIGN & DETAIL. BOUNDARY WALLS: BUILDING LINE
3000
W4 THE BASEMENT LEVEL.
2 YARD requirements of Municipal and Local
ALL FOUNDATION MUST BE CAST IN STRICT ACCORDANCE WITH THE IE.
FOUL WATER PIPES Authorities concerned are to be adhered to.
ENGINEER'S DETAIL AND SPECIFICATION. FOR ALL STRUCTURAL WORK 3000mm building line
GREYWATER OUTLET SYSTEM TO W4 IE. G W4 W4 RWP
THE CONTRACTOR MUST REFER TO THE ENGINEER'S DRAWINGS AND ANY RWP
BE DESIGNED BY SPECIALIST. 138 1 3G 4 WASTE WATER PIPES 4. Natural light and ventilation area of all
DISCREPANCIES BETWEEN THE ENGINEERS DRAWINGS AND THE INCLUDE ALL NECESSARY PUMPS
270
270
ARCHITECTS DRAWINGS MUST BE REPORTED BEFORE CONSTRUCTION AND FILTERS IN QUOTATION. 140 openings in accordance of floor area and
COMMENCES. W5 W5 W5 D2 TD WM DW INSPECTION EYE
1000
IE. SANS 10400 Part O natural light area:
EN-SUITE
EN-SUITE
940
1 2 3 1
WALL CONSTRUCTION
min.10% of floor area and natural ventilation:
D8 139.5 G GULLY
2400
SCULLERY D3
min. 5% of floor area.
Tiles
Tiles
900
D9
800
INTERNAL WALLS TO BE 110 mm OR 230mm AS SHOWN ON PLAN. PANTRY 7 1
G 1 D9 Tiles Tiles
2
137.5 - BASE LEVEL
4140
EXTERNAL WALLS TO BE 270 mm NFP CLAY BRICK WALLS WITH 50 mm MH
5. All glazing to comply with requirements of
4370
4370
BCB
1150
1450
CAVITY AS SHOWN ON PLAN. REFER TO FLOOR PLANS FOR THE POSITION 1010
SABS 0137 - access doors and sidelights to
230
AND THICKNESS OF WALLS. PROVIDE BRICKFORCE REINFORCEMENT AT RWP
110MM Ø UPVC SEWER BEDROOM 3 have safety glass. Windows lower than 500mm
270
EVERY FOURTH COURSE AND BUTTERFLY WALL TIES IN ALL CAVITY BEDROOM 2 Tiles FR/FZ 139
PIPE TO CONNECT TO
WALLS AT A RATE OF 1 WALL TIE PER METER SQUARE.
MUNICIPAL SEWER LINE
Carpet Carpet FAMILY/TV ROOM W2 2000 from floor, windows lower than 1800mm above
900
D8 D8 5
4 D10 pitch line of stairs and shop-fronts to be safety
WALLS TO BE PLASTERED AND PAINTED: PAINT & COLOUR TO LATER 137 3 1 OPEN-PLAN KITCHEN
3120
glass.
30
230
SPECIFICATION. DINING ROOM Tiles
2590
STAIRCASE:
Treads: 250mm 3310 110 1170 2000 1400 Tiles
1770
W2 350 350 330
2040
WEEP HOLES Raisers: 170mm
3 410 PASSAGE
110
3600 4780 6. All safety glazing panels shall be etched with
900 1200 1980 795 2065 725 900 890
270
270
138.5
380
WATERPROOFING DETAIL. LINEN D5
D8
270
600
110
370
2
110
1800 156
1500
BRAAI 510
200
900 1200 900
LINTELS W3 Concrete roof W9 270 700 7. All cavities below floor level to be filled with
1230
1130
W8
600
PRESTRESSED PRECAST CONC. LINTELS OVER ALL WINDOWS, DOORS 1 with stone chips 1 concrete and dpc's to be stepped.
B below
1 1 B
260
AND OTHER OPENINGS PROJECTING NOT LESS THAN 200MM INTO THE Concrete roof
270
270
270
3600
MH MH D8 skylight
DRESSING
138
270 lines.
4870
above
GROUND FLOOR - FLOOR CONSTRUCTION Tiles 6
815
D5 330
1870
FLOOR FINISH (AS INDICATED ON PLANS) ON 30MM SCREED ON 100MM MH
2200
STACK & VENT PIPE W4 1
Carpet
900
MESH RC CONCRETE SURFACE BED (AS DETAILED AND SPECIFIED BY THE COVERED STOEP
3370
5 DECKING
ENGINEER), ON GUNDLE USB GREEN CO EX 250µM DAMP PROOF
MEMBRANE TO SANS MARK 952-1985 TYPE C LAID WITH MINIMUM 150MM
Tiles
137.5 - BASE LEVEL
Revisions: ( See clouded areas)
330
2475 1015 900 600
800
OVERLAPS AND SEALED WITH GUNPLAS PRESSURE SENSITIVE TAPE ON DRIVEWAY FORMAL LOUNGE
270
270
135.5
No. Date Description
7400
Tiles
230
50MM SAND BLINDING ON 150MM LAYERS OF THICK 95% MOD AASTHO Exposed aggregate
630
BOUNDARY WALLS: interlocking pavers 270 330 4130 D4
WELL COMPACTED GROUND / FILL AS SPECIFIED BY THE ENGINEER.
6040
1
1060
270
EXISTING BOUNDARY WALLS TO BE plinth wall plinth wall
.. .... .....
PROTECTED DURING EXCAVATION OF ERF 17235
plinth wall
FIRST FLOOR - FLOOR CONSTRUCTION 7500
THE BASEMENT LEVEL. 5000 137
FLOOR FINISH (AS INDICATED ON PLANS) ON 30 mm CEMENT SCREED ON DECKING
2000 W2 230 270
900
REINFORCED CONCRETE SLAB. CONCRETE SLAB TO BE CONSTRUCTED IN 135 4 270 230
STRICT ACCORDANCE WITH THE ENGINEER'S DETAILED AND BEDROOM 1 .. .... .....
SPECIFICATION. Carpet
110MM Ø UPVC SEWER 1345 2400 1355 POOL
925
PIPE TO CONNECT TO 136.5
plinth wall
WINDOWS AND DOORS MUNICIPAL SEWER LINE D2 .. .... .....
270
270
WINDOWS AND EXTERIOR DOORS TO BE FITTED WITH GLAZING AS 2
SPECIFIED ON THE FENESTRATION SCHEDULE AND MUST BE DECKING
DRIVEWAY PAVING: 134.5
MANUFACTURED BY APPROVED SUB CONTRACTOR. ALL EXTERIOR DOORS 110MM Ø UPVC SEWER
HERRINGBONE PATTERN WITH 136 PIPE TO CONNECT TO .. .... .....
& WINDOWS INCLUDING GARAGE DOOR TO BE POWDER COATED
HEADER COURSE EDGE RETAINING WALL RETAINING WALL RETAINING WALL MUNICIPAL SEWER LINE
(COLOUR: STONE GREY- ANP17030) ALUMINIUM UNITS AS SPECIFIED ON
THE DOOR AND WINDOW SCHEDULE. COLOUR: TABLE MOUNTAIN SANDSTONE 4000mm building line
134 2500 5100 2650 MH 135.5
ALL INTERNAL DOORS TO BE SEMI-SOLID TIMBER HARDWOOD DOORS,
MANUFACTURED BY "SWARTLAND GROUP" OR APPROVED EQUIVALENT. 270 STORMWATER LEGEND:
WHERE THE PLASTER MEETS THE DOOR & WINDOW FRAMES, THE JOINT
4000
MUST BE SEALED WITH CLEAR SILICON EXTERNALLY AND "PAINTERS MATE AS INDICATED, ALLOW FOR TWO110MM Ø HDPE SLEEVES BELOW 135 160mmØ STORMWATER CHANNEL & PIPES
ACRYLIC SEALANT" INTERNALLY. 133.5 THEIR DRIVE WAY COMPLETE WITH DRAW WIRES.
MH THE SLEEVES ARE TO BE SITUATED NEXT TO EACH OTHER AT 400MM
110mmØ UPVC STORMWATER PIPE
WINDOW SILLS FROM THE KERB EDGE AND ARE TO EXTEND A MINIMUM A 1000MM
INTERNALLY : 22mm MERANTI SILLS - TO LATER DETAIL BEYOND THE EDGE OF THE DRIVEWAY SURFACE.
800
11000
1200
9000
300 300
EAVES AND RAINWATER GOODS
1020
GUTTERS AND DOWNPIPES ON THE INSIDE WITH SILICONE SEALER. GROUND FLOOR LEVEL 2
T.O.C. 139 080
LE ROUX PROJECTS
DRAINAGE
680
PROJECT TITLE:
WASTEPIPES TO BE 50Ø mm PVC
GROUND FLOOR LEVEL 1
SOILPIPES TO BE 110Ø mm PVC T.O.C. 138 400
VENTPIPES TO BE 50Ø mm PVC
INSPECTION EYES TO BE INSTALLED AT ALL BENDS AND JUNCTIONS. BASE LEVEL
NEW RESIDENCE ON ERF
3167
3400
680
WATER SUPPLY T.O.C. 134 320
110 2017.08.29
DRAWINGS REVISED FOR RESUBMISSION 2017.07.27: REV. DRAWN: CHECKED:
· Indicate height in terms of D.M.S in addition to height 02 JB ..
restriction of estate.
NOTE: DRAWINGS REVISED FOR RESUBMISSION 2017.08.29: · Ground floor of dwelling not to be raised more than 1.5m
IT REMAINS THE RESPONSIBILITY OF THE HOME · Ground floor of dwelling not to be raised more than 1.5m above E.G.L.
OWNER TO ADHERE TO ALL THE STIPULATIONS above E.G.L. · Indicate height of any retaining wall structure in accordance
FOR SUBMISSION
IN THE FHCE ARCHITECTURAL GUIDELINES. · New Guest bedroom - Lower Ground Floor Level. with requirements of D.M.S.
This drawing and all the information contained thereon is the
property of Dennis Moss Partnership and may not be copied
or disclosed to a third party without their written consent.
General Notes:
FLAT ROOF CONSTRUCTION EAVES AND RAINWATER GOODS
STORMWATER LEGEND: 1. Contractor and Sub-Contractors to check all
SPECIFICATION NOTES: 10° PITCH. ROOF SHEETING: ROOF SHEETING: GALV. 0.53MM KLIPLOK METAL ROOF
SHEETING (COLOUR : CHROMADECK - DARK GREY) ON SUPER SISALATION 405 ON 76
X 50MM SA PINE PURLINS @ MAX. 900MM c/c SPACING ON ENGINEER'S DESIGNED S.A.
A ERF 17237 C GREYWATER OUTLET SYSTEM TO
BE DESIGNED BY SPECIALIST.
OGEE SEAMLESS ALUMINIUM GUTTER, 125 X 85 X 0.6MM THICK (COLOUR :
CHROMADECK - DARK GREY) SECURED TO 12 X 200MM UNPRESSED FASCIA levels and dimensions on site before any work
(PAINTED DARK GREY TO MATCH ROOF COLOUR)THAT IS FIXED TO A 22 X 160mmØ STORMWATER CHANNEL & PIPES is commenced and any discrepancies to be
PINE MONO PITCH ROOF TRUSSES ON 114 X 38mm S.A.PINE WALL PLATE. INSTALL INCLUDE ALL NECESSARY PUMPS 150mm SA PINE FASCIA PLAN . INSTALL ALUMINIUM MESH LEAF TRAP SET
LEVELS: 100mm ISOTHERM OR EQUAL APPROVED INSULATION, THROUGHOUT ABOVE ALL AND FILTERS IN QUOTATION. OVER GUTTER WITH 100 X75MM RACTANGULAR FLUTED ALUMINIUM
reported to the Architect immediately.
CEILINGS. ROOF TRUSSES TO BE CONSTRUCTED IN STRICTLY ACCORDING TO THE DOWNPIPE. FIXED TO WALL WITH HOLDERBATS. SEAL GUTTERS AND
110mmØ UPVC STORMWATER PIPE
REFER TO SECTIONS.
ENGINEER'S DETAIL AND SPECIFICATION. (REFER TO SECTIONS FOR MORE DOWNPIPES ON THE INSIDE WITH SILICONE SEALER.
INFORMATION.)
139.5 2. Figured dimensions to be taken in preference
FOUNDATIONS 29 723mm BOUNDARY LINE
IE INSPECTION EYE
138.73
139 NEW 1800mm BOUNDARY WALL 140 140.5 to scaled measurements and large scale
ALL FOUNDATIONS TO BE AT A MINIMUM DEPTH OF 750mm. 140.63
INTERNAL WALLS : R.C. STRIP FOUNDATION TO ENG'S RAINWATER CATCHMENTS PIT details supercede small scale drawings.
DESIGN & DETAIL. 138.5
EAVES AND RAINWATER GOODS
140.5
EXTERNAL WALLS : R.C. STRIP FOUNDATION TO ENG'S 600 X 600 ACCESS HATCH TO TANK 3. All work to be done in accordance National
OGEE SEAMLESS ALUMINIUM GUTTER, 125 X
3000
DESIGN & DETAIL. YARD Building Regulations SANS 10400 and all
85 X 0.6MM THICK (COLOUR : CHROMADECK -
DARK GREY) SECURED TO 12 X 200MM 110mmØ UPVC OVERFLOW PIPE requirements of Municipal and Local
ALL FOUNDATION MUST BE CAST IN STRICT ACCORDANCE WITH THE UNPRESSED FASCIA (PAINTED DARK GREY TO
ENGINEER'S DETAIL AND SPECIFICATION. FOR ALL STRUCTURAL WORK MATCH ROOF COLOUR)THAT IS FIXED TO A 22
3000mm building line RWP Authorities concerned are to be adhered to.
THE CONTRACTOR MUST REFER TO THE ENGINEER'S DRAWINGS AND ANY 110mmØ UPVC DRAINING OUTLET
X 150mm SA PINE FASCIA PLAN . INSTALL 138 RWP RWP RWP
DISCREPANCIES BETWEEN THE ENGINEERS DRAWINGS AND THE ALUMINIUM MESH LEAF TRAP SET OVER 4. Natural light and ventilation area of all
ARCHITECTS DRAWINGS MUST BE REPORTED BEFORE CONSTRUCTION GUTTER WITH 100 X75MM RACTANGULAR 140
FLUTED ALUMINIUM DOWNPIPE. FIXED TO RWP
75mmØ RAIN WATER PIPE WITH STANDARD 280 openings in accordance of floor area and
COMMENCES.
WALL WITH HOLDERBATS. SEAL GUTTERS X 280mm BRICK GULLY. SANS 10400 Part O natural light area:
AND DOWNPIPES ON THE INSIDE WITH 139.5
WALL CONSTRUCTION min.10% of floor area and natural ventilation:
SILICONE SEALER.
INTERNAL WALLS TO BE 110 mm OR 230mm AS SHOWN ON PLAN. min. 5% of floor area.
WHERE THE PLASTER MEETS THE DOOR & WINDOW FRAMES, THE JOINT
135 FASCIA PLAN . INSTALL ALUMINIUM MESH LEAF TRAP
MUST BE SEALED WITH CLEAR SILICON EXTERNALLY AND "PAINTERS MATE 133.5 SET OVER GUTTER WITH 100 X75MM RACTANGULAR
ACRYLIC SEALANT" INTERNALLY. FLUTED ALUMINIUM DOWNPIPE. FIXED TO WALL WITH
HOLDERBATS. SEAL GUTTERS AND DOWNPIPES ON
WINDOW SILLS THE INSIDE WITH SILICONE SEALER.
INTERNALLY : 22mm MERANTI SILLS - TO LATER DETAIL
EXTERNALLY : PLASTERED & PAINTED SILLS - TO LATER DETAIL 133
133 29 723mm BOUNDARY LINE 134 134.5 134.59
FLAT ROOF CONSTRUCTION 4000
10° PITCH. ROOF SHEETING: ROOF SHEETING: GALV. 0.53MM KLIPLOK 133.5
METAL ROOF SHEETING (COLOUR : CHROMADECK - DARK GREY) ON
SUPER SISALATION 405 ON 76 X 50MM SA PINE PURLINS @ MAX. 900MM c/c
SPACING ON ENGINEER'S DESIGNED S.A. PINE MONO PITCH ROOF TO CONNECT TO DRAWINGS REVISED FOR RESUBMISSION 2017.07.27:
TRUSSES ON 114 X 38mm S.A.PINE WALL PLATE. INSTALL 100mm ISOTHERM TO CONNECT TO · Indicate height in terms of D.M.S in addition to height
ESTATE STORM A ATTALIA STREET
OR EQUAL APPROVED INSULATION, THROUGHOUT ABOVE ALL CEILINGS.
ROOF TRUSSES TO BE CONSTRUCTED IN STRICTLY ACCORDING TO THE WATER SYSTEM C ESTATE STORM restriction of estate.
ENGINEER'S DETAIL AND SPECIFICATION. (REFER TO SECTIONS FOR MORE WATER SYSTEM · Ground floor of dwelling not to be raised more than 1.5m
EAVES AND RAINWATER GOODS
INFORMATION.) OGEE SEAMLESS ALUMINIUM GUTTER, 125 X 85 X 0.6MM THICK (COLOUR TO LATER above E.G.L.
SPECIFICATION) SECURED TO 12 X 200MM UNPRESSED FASCIA THAT IS FIXED TO A 22 X
· Indicate height of any retaining wall structure in accordance
CONCRETE ROOF CONSTRUCTION
ROOF TO BE SCREEDED TO 1:50 FALL TOWARDS FULLBORE OUTLETS.
ROOF PLAN 150mm SA PINE FASCIA PLAN . INSTALL ALUMINIUM MESH LEAF TRAP SET OVER GUTTER
WITH 100 X75MM RACTANGULAR FLUTED ALUMINIUM DOWNPIPE. FIXED TO WALL WITH with requirements of D.M.S.
SOFFITS OF ALL EXPOSED SLABS TO BE SKIMMED. ROOF TO BE
WATERPROOFED WITH DERBIGUM SP4 DUAL REINFORCED BITUMEN
SCALE 1:100 HOLDERBATS. SEAL GUTTERS AND DOWNPIPES ON THE INSIDE WITH SILICONE SEALER.
INSPECTION EYES TO BE INSTALLED AT ALL BENDS AND JUNCTIONS. NEW RESIDENCE ON ERF
ALL DRAINAGE BELOW SURFACE BED AND PENETRATING THROUGH
FOUNDATION WALLS TO BE ENCASED IN min 500mm THK CONC. INSTALL 100mm
ISOTHERM OR EQUAL
17236, FAIRHAVEN,
SLOW BENDS TO ALL JUNCTIONS HAPPENING BELOW SURFACE BED.
MIN. FALL OF PIPES AT 1:60
APPROVED
INSULATION,
SOMERSET WEST.
THROUGHOUT ABOVE
JOINTS TO BE SEALED
WATER SUPPLY ALL CEILINGS.
WITH SILICONE SEALANT.
POTABLE WATER RINGMAIN AROUND HOUSE TO BE SAME Ø AS MAIN 230
DRAWING TITLE:
SUPPLY TO PROPERTY. (MINIMUM 25mmØ)
SUPPLY LINES INSIDE HOUSE TO BE 20mmØ.
SHUTOFF COCKS TO BE INSTALLED BEFORE ALL ITEMS SUCH AS WASH
BASINS, BATHS, SHOWERS, GEYSERS AND TOILETS. OGEE SEAMLESS ALUMINIUM GUTTER,
ROOF PLAN, STORM
125 X 85 X 0.6MM THICK (COLOUR : DARK
GREY) SECURED TO 22 X 228mm SA PINE
ENGINEER'S DESIGNED S.A. PINE MONO PITCH ROOF
TRUSSES ON 114 X 38mm S.A.PINE WALL PLATE. ROOF
WATER AND RAINWATER
FASCIA PLANK . INSTALL ALUMINIUM TRUSSES TO BE CONSTRUCTED IN STRICTLY ACCORDING HARVESTING LAYOUT
74
MESH LEAF TRAP SET OVER GUTTER TO THE ENGINEER'S DETAIL AND SPECIFICATION. (REFER
WITH 100 X75MM RACTANGULAR FLUTED TO SECTIONS FOR MORE INFORMATION.)
ALUMINIUM DOWNPIPE (COLOUR : DARK
GREY). FIXED TO WALL WITH
450 450
HOLDERBATS. SEAL GUTTERS AND
DOWNPIPES ON THE INSIDE WITH OVERHANGS PROJECT No.: SCALE:
SILICONE SEALER. OVERHANGS
V4209 1:100
DRAWING No.: DATE:
150 2017.08.29
NOTE: REV. DRAWN: CHECKED:
SPECIFICATION NOTES: SHEETING (COLOUR : CHROMADECK - DARK GREY) ON SUPER SISALATION 405 ON 76
X 50MM SA PINE PURLINS @ MAX. 900MM c/c SPACING ON ENGINEER'S DESIGNED S.A.
FOUNDATIONS:
ALL FOUNDATION MUST BE CAST IN STRICT ACCORDANCE
WITH THE ENGINEER'S DETAIL AND SPECIFICATION. FOR ALL
levels and dimensions on site before any work
is commenced and any discrepancies to be
PINE MONO PITCH ROOF TRUSSES ON 114 X 38mm S.A.PINE WALL PLATE. INSTALL
100mm ISOTHERM OR EQUAL APPROVED INSULATION, THROUGHOUT ABOVE ALL STRUCTURAL WORK THE CONTRACTOR MUST REFER TO reported to the Architect immediately.
LEVELS: CEILINGS. ROOF TRUSSES TO BE CONSTRUCTED IN STRICTLY ACCORDING TO THE 300 300 THE ENGINEER'S DRAWINGS AND ANY DISCREPANCIES
REFER TO SECTIONS. ENGINEER'S DETAIL AND SPECIFICATION. (REFER TO SECTIONS FOR MORE BETWEEN THE ENGINEERS DRAWINGS AND THE 2. Figured dimensions to be taken in preference
INFORMATION.) ARCHITECTS DRAWINGS MUST BE REPORTED BEFORE
FOUNDATIONS
to scaled measurements and large scale
CONSTRUCTION COMMENCES.
ALL FOUNDATIONS TO BE AT A MINIMUM DEPTH OF 750mm. details supercede small scale drawings.
INTERNAL WALLS : R.C. STRIP FOUNDATION TO ENG'S GROUND FLOOR LEVEL 2 300
WALL PLATE 142 310
DESIGN & DETAIL. 3. All work to be done in accordance National
300
9000
EXTERNAL WALLS : R.C. STRIP FOUNDATION TO ENG'S
Building Regulations SANS 10400 and all
1020
DESIGN & DETAIL. GROUND FLOOR LEVEL 1
WALL PLATE 141 290 requirements of Municipal and Local
ALL FOUNDATION MUST BE CAST IN STRICT ACCORDANCE WITH THE Authorities concerned are to be adhered to.
ENGINEER'S DETAIL AND SPECIFICATION. FOR ALL STRUCTURAL WORK
THE CONTRACTOR MUST REFER TO THE ENGINEER'S DRAWINGS AND ANY N.G.L.
4. Natural light and ventilation area of all
2210
DISCREPANCIES BETWEEN THE ENGINEERS DRAWINGS AND THE
139.00 openings in accordance of floor area and
2890
ARCHITECTS DRAWINGS MUST BE REPORTED BEFORE CONSTRUCTION
GROUND FLOOR LEVEL 2
COMMENCES. T.O.C. 139 080
139.00 SANS 10400 Part O natural light area:
139.00 min.10% of floor area and natural ventilation:
WALL CONSTRUCTION
680
min. 5% of floor area.
INTERNAL WALLS TO BE 110 mm OR 230mm AS SHOWN ON PLAN. 139.00 N.G.L.
11000
FLOOR FINISH (AS INDICATED ON PLANS) ON 30 mm CEMENT SCREED ON 450 450 INFORMATION.)
REINFORCED CONCRETE SLAB. CONCRETE SLAB TO BE CONSTRUCTED IN 450
GROUND FLOOR LEVEL 2 .. .... .....
STRICT ACCORDANCE WITH THE ENGINEER'S DETAILED AND WALL PLATE 142 310
SPECIFICATION. 450
9000
450
1020
1800mm HIGH
(COLOUR: STONE GREY- ANP17030) ALUMINIUM UNITS AS SPECIFIED ON
2890
BOUNDARY WALL
THE DOOR AND WINDOW SCHEDULE. GROUND FLOOR LEVEL 2
T.O.C. 139 080
680
SUPER SISALATION 405 ON 76 X 50MM SA PINE PURLINS @ MAX. 900MM c/c T.O.C. 134 320
134.50
SPACING ON ENGINEER'S DESIGNED S.A. PINE MONO PITCH ROOF
134.00
TRUSSES ON 114 X 38mm S.A.PINE WALL PLATE. INSTALL 100mm ISOTHERM
OR EQUAL APPROVED INSULATION, THROUGHOUT ABOVE ALL CEILINGS. 1:6 133.50 N.G.L.
ROOF TRUSSES TO BE CONSTRUCTED IN STRICTLY ACCORDING TO THE
133.00
ENGINEER'S DETAIL AND SPECIFICATION. (REFER TO SECTIONS FOR MORE
INFORMATION.) NORTH WEST ELEVATION
CONCRETE ROOF CONSTRUCTION SCALE 1:100
ROOF TO BE SCREEDED TO 1:50 FALL TOWARDS FULLBORE OUTLETS.
SOFFITS OF ALL EXPOSED SLABS TO BE SKIMMED. ROOF TO BE
WATERPROOFED WITH DERBIGUM SP4 DUAL REINFORCED BITUMEN
MEMBRANE FINISHED WITH TWO COATS OF BITUMENOUS ALUMINIUM
PAINT. COVER WITH A 60MM THICK LAYER OF 19 - 25MM BROWN STONE
CHIPS. WATERPROOFING TO BE INSTALLED BY AN APPROVED DERBIGUM
APPLICATOR ALL APPLIED ACCORDING TO MANUFACTURERS & MAX. HEIGHT ABOVE BASE LEVEL
ENGINEER'S SPEC. WHERE REQUIRED, DECKING BOARD MUST BE Top of roof - 148 500
INSTALLED BY A SPECIALIST SUB-CONTRACTOR.
CEILING CONSTRUCTION
CEILINGS: 9MM CEILING BOARDS NAILED TO 38 X 38MM BRANDERING
SPACED NOT MORE THAN 350MM APART. FLAT ROOF CONSTRUCTION MAX. HEIGHT ABOVE BASE LEVEL
Top of wallplate 146 500
10° PITCH. ROOF SHEETING: ROOF SHEETING: GALV. 0.53MM KLIPLOK METAL ROOF
EAVES AND RAINWATER GOODS SHEETING (COLOUR : CHROMADECK - DARK GREY) ON SUPER SISALATION 405 ON 76
OGEE SEAMLESS ALUMINIUM GUTTER, 125 X 85 X 0.6MM THICK (COLOUR : X 50MM SA PINE PURLINS @ MAX. 900MM c/c SPACING ON ENGINEER'S DESIGNED S.A.
CHROMADECK - DARK GREY) SECURED TO 12 X 200MM UNPRESSED PINE MONO PITCH ROOF TRUSSES ON 114 X 38mm S.A.PINE WALL PLATE. INSTALL
FASCIA (PAINTED DARK GREY TO MATCH ROOF COLOUR)THAT IS FIXED TO 100mm ISOTHERM OR EQUAL APPROVED INSULATION, THROUGHOUT ABOVE ALL
A 22 X 150mm SA PINE FASCIA PLAN . INSTALL ALUMINIUM MESH LEAF CEILINGS. ROOF TRUSSES TO BE CONSTRUCTED IN STRICTLY ACCORDING TO THE CLIENT:
TRAP SET OVER GUTTER WITH 100 X75MM RACTANGULAR FLUTED ENGINEER'S DETAIL AND SPECIFICATION. (REFER TO SECTIONS FOR MORE 450 450
INFORMATION.)
ALUMINIUM DOWNPIPE. FIXED TO WALL WITH HOLDERBATS. SEAL
GUTTERS AND DOWNPIPES ON THE INSIDE WITH SILICONE SEALER. LE ROUX PROJECTS
DRAINAGE
11000
450 BOUNDARY WALL
450 PROJECT TITLE:
WASTEPIPES TO BE 50Ø mm PVC GROUND FLOOR LEVEL 2 1800mm HIGH BOUNDARY
WALL PLATE 142 310 WALL
SOILPIPES TO BE 110Ø mm PVC
9000
VENTPIPES TO BE 50Ø mm PVC
NEW RESIDENCE ON ERF
1020
DRAWING TITLE:
POTABLE WATER RINGMAIN AROUND HOUSE TO BE SAME Ø AS MAIN
SUPPLY TO PROPERTY. (MINIMUM 25mmØ)
2635
138.00
SUPPLY LINES INSIDE HOUSE TO BE 20mmØ. T.O.C. 138 400
BASINS, BATHS, SHOWERS, GEYSERS AND TOILETS. BASE LEVEL LOWER GROUND FLOOR LEVEL BASE LEVEL
N.G.L.
3400
134.00
· New Guest bedroom - Lower Ground Floor Level. PROJECT No.: SCALE:
V4209 1:100
DRAWING No.: DATE:
200 2017.08.29
SOUTH EAST ELEVATION DRAWINGS REVISED FOR RESUBMISSION 2017.07.27:
REV. DRAWN: CHECKED:
02 JB ..
SCALE 1:100 · Indicate height in terms of D.M.S in addition to height
NOTE: restriction of estate.
IT REMAINS THE RESPONSIBILITY OF THE HOME · Ground floor of dwelling not to be raised more than 1.5m
OWNER TO ADHERE TO ALL THE STIPULATIONS above E.G.L.
FOR SUBMISSION
IN THE FHCE ARCHITECTURAL GUIDELINES. · Indicate height of any retaining wall structure in accordance
with requirements of D.M.S. This drawing and all the information contained thereon is the
property of Dennis Moss Partnership and may not be copied
or disclosed to a third party without their written consent.
MAX. HEIGHT ABOVE BASE LEVEL
Top of wallplate 146 500 General Notes:
FLAT ROOF CONSTRUCTION CEILING CONSTRUCTION 1. Contractor and Sub-Contractors to check all
EAVES AND RAINWATER GOODS
SPECIFICATION NOTES: 10° PITCH. ROOF SHEETING: ROOF SHEETING: GALV. 0.53MM KLIPLOK
METAL ROOF SHEETING (COLOUR : CHROMADECK - DARK GREY) ON
SUPER SISALATION 405 ON 76 X 50MM SA PINE PURLINS @ MAX. 900MM
CEILINGS: 9MM CEILING
BOARDS NAILED TO 38 X 38MM
OGEE SEAMLESS ALUMINIUM GUTTER, 125 X 85 X 0.6MM THICK (COLOUR :
CHROMADECK - DARK GREY) SECURED TO 12 X 200MM UNPRESSED
levels and dimensions on site before any work
is commenced and any discrepancies to be
BRANDERING SPACED NOT
c/c SPACING ON ENGINEER'S DESIGNED S.A. PINE MONO PITCH ROOF FASCIA (PAINTED DARK GREY TO MATCH ROOF COLOUR)THAT IS FIXED TO
TRUSSES ON 114 X 38mm S.A.PINE WALL PLATE. INSTALL 100mm
MORE THAN 350MM APART.
A 22 X 150mm SA PINE FASCIA PLAN . INSTALL ALUMINIUM MESH LEAF reported to the Architect immediately.
LEVELS: 450
ISOTHERM OR EQUAL APPROVED INSULATION, THROUGHOUT ABOVE ALL TRAP SET OVER GUTTER WITH 100 X75MM RACTANGULAR FLUTED
REFER TO SECTIONS.
CEILINGS. ROOF TRUSSES TO BE CONSTRUCTED IN STRICTLY ALUMINIUM DOWNPIPE. FIXED TO WALL WITH HOLDERBATS. SEAL 2. Figured dimensions to be taken in preference
ACCORDING TO THE ENGINEER'S DETAIL AND SPECIFICATION. (REFER TO GUTTERS AND DOWNPIPES ON THE INSIDE WITH SILICONE SEALER.
FOUNDATIONS SECTIONS FOR MORE INFORMATION.) 450 450 450 to scaled measurements and large scale
ALL FOUNDATIONS TO BE AT A MINIMUM DEPTH OF 750mm. details supercede small scale drawings.
INTERNAL WALLS : R.C. STRIP FOUNDATION TO ENG'S GROUND FLOOR LEVEL 2
WALL PLATE 142 310
DESIGN & DETAIL.
450 3. All work to be done in accordance National
9000
EXTERNAL WALLS : R.C. STRIP FOUNDATION TO ENG'S 450
6500
Building Regulations SANS 10400 and all
1020
DESIGN & DETAIL. GROUND FLOOR LEVEL 1
WALL PLATE 141 290
requirements of Municipal and Local
ALL FOUNDATION MUST BE CAST IN STRICT ACCORDANCE WITH THE
Authorities concerned are to be adhered to.
ENGINEER'S DETAIL AND SPECIFICATION. FOR ALL STRUCTURAL WORK BOUNDARY WALL DPC
THE CONTRACTOR MUST REFER TO THE ENGINEER'S DRAWINGS AND ANY
DPC EN-SUITE
1800mm HIGH
2210
DISCREPANCIES BETWEEN THE ENGINEERS DRAWINGS AND THE BOUNDARY WALL 4. Natural light and ventilation area of all
2890
ARCHITECTS DRAWINGS MUST BE REPORTED BEFORE CONSTRUCTION STAIRCASE openings in accordance of floor area and
GROUND FLOOR LEVEL 2
COMMENCES. T.O.C. 139 080 SANS 10400 Part O natural light area:
139.00
WALL CONSTRUCTION
N.G.L. min.10% of floor area and natural ventilation:
680
INTERNAL WALLS TO BE 110 mm OR 230mm AS SHOWN ON PLAN. 139.50
DPC DPC min. 5% of floor area.
935
GROUND FLOOR LEVEL 1 DPM
T.O.C. 138 400
EXTERNAL WALLS TO BE 270 mm NFP CLAY BRICK WALLS WITH 50 mm 138.00
CONCRETE ROOF 5. All glazing to comply with requirements of
CAVITY AS SHOWN ON PLAN. REFER TO FLOOR PLANS FOR THE POSITION
AND THICKNESS OF WALLS. PROVIDE BRICKFORCE REINFORCEMENT AT
137.50
137.00 SKIMMED SOFFIT SABS 0137 - access doors and sidelights to
BASE LEVEL BASE LEVEL
have safety glass. Windows lower than 500mm
3400
EVERY FOURTH COURSE AND BUTTERFLY WALL TIES IN ALL CAVITY 137 500 136.50 137 500
WALLS AT A RATE OF 1 WALL TIE PER METER SQUARE. 4000 from floor, windows lower than 1800mm above
pitch line of stairs and shop-fronts to be safety
WALLS TO BE PLASTERED AND PAINTED: PAINT & COLOUR TO LATER 136.00
SPECIFICATION. LOWER GROUND FLOOR LEVEL 135.50 glass.
T.O.C. 135 000
DPC
GARAGE FLOOR LEVEL
WEEP HOLES 135.00 6. All safety glazing panels shall be etched with
680
DPM T.O.C. 134 320
WALL TO BE CONSTRUCTED 134.50
WEEP HOLES AT 2 BRICK INTERVALS AT ALL FLOOR SLAB LEVELS AND glazing marking and this to be visible at all
OVER ALL WINDOWS AND EXTERIOR DOORS. STEPPED DPC TO LATER IN STRICT ACCORDANCE 134.00
WATERPROOFING DETAIL. WITH THE ENGINEERS DETAIL
1:8 times.
SECTION A-A
1:6 133.50
AND SPECIFICATION.
LINTELS 133.00 7. All cavities below floor level to be filled with
PRESTRESSED PRECAST CONC. LINTELS OVER ALL WINDOWS, DOORS
AND OTHER OPENINGS PROJECTING NOT LESS THAN 200MM INTO THE
SCALE 1:100 STAIRCASE: concrete and dpc's to be stepped.
Treads: 250mm MAX. HEIGHT ABOVE BASE LEVEL
BRICKWORK ON BOTH SIDES. EXTERIOR WALL FOUNDATIONS:
Raisers: 170mm Top of roof - 148 500
ALL FOUNDATIONS TO BE AT A MINIMUM DEPTH OF 750mm. 8. No part of construction may encroach building
GROUND FLOOR - FLOOR CONSTRUCTION EXTERNAL WALLS FOUNDATIONS TO BE R.C. STRIP lines.
FLOOR FINISH (AS INDICATED ON PLANS) ON 30MM SCREED ON 100MM FOUNDATION TO ENG'S DESIGN & DETAIL.
MESH RC CONCRETE SURFACE BED (AS DETAILED AND SPECIFIED BY THE
FOUNDATIONS: FLAT ROOF CONSTRUCTION
ENGINEER), ON GUNDLE USB GREEN CO EX 250µM DAMP PROOF
MEMBRANE TO SANS MARK 952-1985 TYPE C LAID WITH MINIMUM 150MM ALL FOUNDATION MUST BE CAST IN STRICT ACCORDANCE 10° PITCH. ROOF SHEETING: ROOF SHEETING: GALV. 0.53MM KLIPLOK MAX. HEIGHT ABOVE BASE LEVEL
Top of wallplate 146 500
Revisions: ( See clouded areas)
METAL ROOF SHEETING (COLOUR : CHROMADECK - DARK GREY) ON
OVERLAPS AND SEALED WITH GUNPLAS PRESSURE SENSITIVE TAPE ON WITH THE ENGINEER'S DETAIL AND SPECIFICATION. FOR ALL SUPER SISALATION 405 ON 76 X 50MM SA PINE PURLINS @ MAX. 900MM
50MM SAND BLINDING ON 150MM LAYERS OF THICK 95% MOD AASTHO STRUCTURAL WORK THE CONTRACTOR MUST REFER TO c/c SPACING ON ENGINEER'S DESIGNED S.A. PINE MONO PITCH ROOF
No. Date Description
WELL COMPACTED GROUND / FILL AS SPECIFIED BY THE ENGINEER. THE ENGINEER'S DRAWINGS AND ANY DISCREPANCIES TRUSSES ON 114 X 38mm S.A.PINE WALL PLATE. INSTALL 100mm
BETWEEN THE ENGINEERS DRAWINGS AND THE ISOTHERM OR EQUAL APPROVED INSULATION, THROUGHOUT ABOVE ALL
ARCHITECTS DRAWINGS MUST BE REPORTED BEFORE CEILINGS. ROOF TRUSSES TO BE CONSTRUCTED IN STRICTLY
.. .... .....
FIRST FLOOR - FLOOR CONSTRUCTION
FLOOR FINISH (AS INDICATED ON PLANS) ON 30 mm CEMENT SCREED ON CONSTRUCTION COMMENCES. ACCORDING TO THE ENGINEER'S DETAIL AND SPECIFICATION. (REFER TO
REINFORCED CONCRETE SLAB. CONCRETE SLAB TO BE CONSTRUCTED IN SECTIONS FOR MORE INFORMATION.)
STRICT ACCORDANCE WITH THE ENGINEER'S DETAILED AND .. .... .....
SPECIFICATION. 300
1700
11000
WINDOWS AND DOORS
.. .... .....
9000
MANUFACTURED BY APPROVED SUB CONTRACTOR. ALL EXTERIOR DOORS SKIMMED SOFFIT
.. .... .....
& WINDOWS INCLUDING GARAGE DOOR TO BE POWDER COATED GROUND FLOOR LEVEL 1 OVERFLOW OVERFLOW SKIMMED SOFFIT
BOUNDARY LINE
(COLOUR: STONE GREY- ANP17030) ALUMINIUM UNITS AS SPECIFIED ON WALL PLATE 141 290
CONCRETE ROOF CONCRETE ROOF CONSTRUCTION
THE DOOR AND WINDOW SCHEDULE. SKIMMED SOFFIT ROOF TO BE SCREEDED TO 1:50 FALL TOWARDS FULLBORE OUTLETS.
EXISTING BOUNDARY WALL TO REMAIN
Fixed Fixed
3230
Panel Panel
SOFFITS OF ALL EXPOSED SLABS TO BE SKIMMED. ROOF TO BE
ALL INTERNAL DOORS TO BE SEMI-SOLID TIMBER HARDWOOD DOORS, BRAAI WATERPROOFED WITH DERBIGUM SP4 DUAL REINFORCED BITUMEN
FORMAL LOUNGE
2210
DRESSING
MEMBRANE FINISHED WITH TWO COATS OF BITUMENOUS ALUMINIUM
2890
2890
BOUNDARY LINE
WHERE THE PLASTER MEETS THE DOOR & WINDOW FRAMES, THE JOINT PAINT. COVER WITH A 60MM THICK LAYER OF 19 - 25MM BROWN STONE
MUST BE SEALED WITH CLEAR SILICON EXTERNALLY AND "PAINTERS MATE GROUND FLOOR LEVEL 2 EN-SUITE
T.O.C. 139 080 CHIPS. WATERPROOFING TO BE INSTALLED BY AN APPROVED DERBIGUM
ACRYLIC SEALANT" INTERNALLY. DPC APPLICATOR ALL APPLIED ACCORDING TO MANUFACTURERS &
255
1450
DPC
680
950
GUEST BEDROOM ENGINEER'S SPEC. WHERE REQUIRED, DECKING BOARD MUST BE
1320
N.G.L.
WINDOW SILLS DPC 138.50 INSTALLED BY A SPECIALIST SUB-CONTRACTOR.
INTERNALLY : 22mm MERANTI SILLS - TO LATER DETAIL GROUND FLOOR LEVEL 1 CONCRETE WATER HARVESTING TANK EN-SUITE
T.O.C. 138 400 OVERFLOW LEVEL
EXTERNALLY : PLASTERED & PAINTED SILLS - TO LATER DETAIL ROOF SKIMMED SOFFIT SKYLIGHT ABOVE 138.00
1480
SKIMMED SOFFIT
137.50
2295
137.00
1500
BASE LEVEL LOWER GROUND FLOOR LEVEL BASE LEVEL
10° PITCH. ROOF SHEETING: ROOF SHEETING: GALV. 0.53MM KLIPLOK TANKING:
3400
255
3825
SUPER SISALATION 405 ON 76 X 50MM SA PINE PURLINS @ MAX. 900MM c/c FLOOR LEVEL AS PER SPECIALIST'S
SPACING ON ENGINEER'S DESIGNED S.A. PINE MONO PITCH ROOF ENTRANCE LOBBY
Subsoil drain
DETAIL AND SPECIFICATION.
STORE/GYM
TRUSSES ON 114 X 38mm S.A.PINE WALL PLATE. INSTALL 100mm ISOTHERM LOWER GROUND FLOOR LEVEL
T.O.C. 135 000
OR EQUAL APPROVED INSULATION, THROUGHOUT ABOVE ALL CEILINGS. T.O.C. 135.000
680
DPM T.O.C. 134 320
ENGINEER'S DETAIL AND SPECIFICATION. (REFER TO SECTIONS FOR MORE
INFORMATION.) DPM DPM
WATER HARVASTING TANK
30 000L RAINWATER AND GREYWATER COLLECTION TANK. IN ADDITION TO HOT WATER PIPE INSULATION:
CONCRETE ROOF CONSTRUCTION SECTION B-B STANDARD FITTINGS, ALLOW FOR FULLY SUBMERSIBLE PUMP WITH FLOAT
SWITCH AND MANUAL INPUT SWITCH, FILTERS, STAINLESS STEEL STEPS
ROOF TO BE SCREEDED TO 1:50 FALL TOWARDS FULLBORE OUTLETS. · HOT WATER HEATING SYSTEMS
SCALE 1:100
Subsoil drain Subsoil drain Subsoil drain
SOFFITS OF ALL EXPOSED SLABS TO BE SKIMMED. ROOF TO BE WITH EPOXY FIXING TO WALL (AT 600 X 600mm ACCESS PANEL),
· All hot water services to comply with SANS 204 clause 4.5.2.1. to 4.5.2.9.
WATERPROOFED WITH DERBIGUM SP4 DUAL REINFORCED BITUMEN INTERIOR WALL FOUNDATIONS: EMERGENCY OVERFLOW OUTLET AND DRAIN OUTLET. WATER
EXTERIOR WALL FOUNDATIONS:
MEMBRANE FINISHED WITH TWO COATS OF BITUMENOUS ALUMINIUM ALL FOUNDATIONS TO BE AT A MINIMUM DEPTH OF 750mm. DISTRIBUTION SYSTEM TO BE DESIGNED BY SPECIALIST · All Hot Water Geysers to be insulated with 'Saint Gobain Isover' or similar
ALL FOUNDATIONS TO BE AT A MINIMUM DEPTH OF 750mm.
PAINT. COVER WITH A 60MM THICK LAYER OF 19 - 25MM BROWN STONE EXTERNAL WALLS FOUNDATIONS TO BE R.C. STRIP MAX. HEIGHT ABOVE BASE LEVEL SUBCONTRACTOR. SABS approved Geyser Blanket, a Flexible Foil Faced Glasswool blanket
EXTERNAL WALLS FOUNDATIONS TO BE R.C. STRIP Top of roof - 148 500
CHIPS. WATERPROOFING TO BE INSTALLED BY AN APPROVED DERBIGUM FOUNDATION TO ENG'S DESIGN & DETAIL. FOUNDATION TO ENG'S DESIGN & DETAIL. with a R-value of 1.25 m2.K/W. The thermal insulation blanket to be installed
APPLICATOR ALL APPLIED ACCORDING TO MANUFACTURERS & strictly in accordance to the manufacturers specifications in order to comply
ENGINEER'S SPEC. WHERE REQUIRED, DECKING BOARD MUST BE with SANS 10400-XA:2011 clause 4.1.4.
CEILING CONSTRUCTION
INSTALLED BY A SPECIALIST SUB-CONTRACTOR.
CEILINGS: 9MM CEILING BOARDS NAILED TO 38 · All hot water pipes to be insulated with 'Saint Gobain Isover' or similar SABS
FLAT ROOF CONSTRUCTION X 38MM BRANDERING SPACED NOT MORE approved Snap On Geyser Pipe Insulation with minimum R-Value
CEILING CONSTRUCTION MAX. HEIGHT ABOVE BASE LEVEL
10° PITCH. ROOF SHEETING: ROOF SHEETING: GALV. 0.53MM THAN 350MM APART. Top of wallplate 146 500 requirements in accordance with SANS 10400-XA:2011, clause 4.1.3 &
CEILINGS: 9MM CEILING BOARDS NAILED TO 38 X 38MM BRANDERING
KLIPLOK METAL ROOF SHEETING (COLOUR : CHROMADECK -
SPACED NOT MORE THAN 350MM APART. DARK GREY) ON SUPER SISALATION 405 ON 76 X 50MM SA PINE
clause 4.1.4. Table 1 that requires all exposed hot water pipes with an
PURLINS @ MAX. 900MM c/c SPACING ON ENGINEER'S DESIGNED internal diameter of 80mm and smaller must be insulated with material
CONCRETE ROOF CONSTRUCTION
EAVES AND RAINWATER GOODS S.A. PINE MONO PITCH ROOF TRUSSES ON 114 X 38mm S.A.PINE providing a minimum R-value of 1.00 and pipes with an internal diameter of
ROOF TO BE SCREEDED TO 1:50 FALL TOWARDS FULLBORE OUTLETS. SOFFITS OF ALL
OGEE SEAMLESS ALUMINIUM GUTTER, 125 X 85 X 0.6MM THICK (COLOUR : WALL PLATE. INSTALL 100mm ISOTHERM OR EQUAL APPROVED 80mm and larger to be insulated with a material providing a minimum
INSULATION, THROUGHOUT ABOVE ALL CEILINGS.
EXPOSED SLABS TO BE SKIMMED. ROOF TO BE WATERPROOFED WITH DERBIGUM SP4
CHROMADECK - DARK GREY) SECURED TO 12 X 200MM UNPRESSED R-value of 1.50.
ROOF TRUSSES TO BE CONSTRUCTED IN STRICTLY ACCORDING DUAL REINFORCED BITUMEN MEMBRANE FINISHED WITH TWO COATS OF BITUMENOUS
FASCIA (PAINTED DARK GREY TO MATCH ROOF COLOUR)THAT IS FIXED TO
TO THE ENGINEER'S DETAIL AND SPECIFICATION. (REFER TO 450 450 ALUMINIUM PAINT. COVER WITH A 60MM THICK LAYER OF 19 - 25MM BROWN STONE
A 22 X 150mm SA PINE FASCIA PLAN . INSTALL ALUMINIUM MESH LEAF
SECTIONS FOR MORE INFORMATION.) CHIPS. WATERPROOFING TO BE INSTALLED BY AN APPROVED DERBIGUM APPLICATOR CLIENT:
TRAP SET OVER GUTTER WITH 100 X75MM RACTANGULAR FLUTED
ALL APPLIED ACCORDING TO MANUFACTURERS & ENGINEER'S SPEC. WHERE REQUIRED,
ALUMINIUM DOWNPIPE. FIXED TO WALL WITH HOLDERBATS. SEAL
450 DECKING BOARD MUST BE INSTALLED BY A SPECIALIST SUB-CONTRACTOR.
GUTTERS AND DOWNPIPES ON THE INSIDE WITH SILICONE SEALER.
LE ROUX PROJECTS
11000
450
GROUND FLOOR LEVEL 2 SUN PROTECTION AWNING
DRAINAGE WALL PLATE 142 310 DPC EPOXY COATER MILD STEEL
CONCRETE ROOF
9000
WASTEPIPES TO BE 50Ø mm PVC LOUVERED AWNING AS PER LATER PROJECT TITLE:
DETAIL.
1020
N.G.L.
BOUNDARY WALL
FOUNDATION WALLS TO BE ENCASED IN min 500mm THK CONC. DINING ROOM COVERED STOEP
2890
139.00
SOMERSET WEST.
1335
680
DPM
595
SHUTOFF COCKS TO BE INSTALLED BEFORE ALL ITEMS SUCH AS WASH 137 500 137 500
BASINS, BATHS, SHOWERS, GEYSERS AND TOILETS. 136.50
1300
136.00
680
EAVES AND RAINWATER GOODS 135.00 134.50 T.O.C. 134 320
OGEE SEAMLESS ALUMINIUM GUTTER, 125 X 85 X 134.00
· Ground floor of dwelling not to be raised more than 1.5m
0.6MM THICK (COLOUR : CHROMADECK - DARK above E.G.L.
SECTION C-C GREY) SECURED TO 12 X 200MM UNPRESSED
FASCIA (PAINTED DARK GREY TO MATCH ROOF
· New Guest bedroom - Lower Ground Floor Level. PROJECT No.: SCALE:
TRAP SET OVER GUTTER WITH 100 X75MM R.C. STRIP FOUNDATION TO 300 2017.08.30
RACTANGULAR FLUTED ALUMINIUM DOWNPIPE. ENG'S DESIGN & DETAIL. NO
FIXED TO WALL WITH HOLDERBATS. SEAL FOUNDATION TO PROTRUDE DRAWINGS REVISED FOR RESUBMISSION 2017.07.27: REV. DRAWN: CHECKED:
02 JB ..
GUTTERS AND DOWNPIPES ON THE INSIDE WITH BOUNDARY LINES. · Indicate height in terms of D.M.S in addition to height
SILICONE SEALER.
NOTE: restriction of estate.
IT REMAINS THE RESPONSIBILITY OF THE HOME · Ground floor of dwelling not to be raised more than 1.5m
OWNER TO ADHERE TO ALL THE STIPULATIONS above E.G.L. FOR SUBMISSION
IN THE FHCE ARCHITECTURAL GUIDELINES. · Indicate height of any retaining wall structure in accordance
with requirements of D.M.S.
This drawing and all the information contained thereon is the
property of Dennis Moss Partnership and may not be copied
or disclosed to a third party without their written consent.