]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ [ ] اﻟﻤﻘﺪﻣﮫ [
**Introduction:
*Installation steps for electrical power plant
** اﻟﻤﺮاﺣﻞ اﻟﺘﻰ ﺗﻤﺮ ﺑﮭﺎ ﺗﺮﻛﯿﺒﺎت ﻣﺤﻄﺎت ﺗﻮﻟﯿﺪ اﻟﻄﺎﻗﺔ اﻟﻜﮭﺮﺑﯿﺔ-:
** وﺳﻮف ﻧﺘﻨﺎول ﻓﻰ ھﺬه اﻟﻤﺬﻛﺮة اﻹﺧﺘﺒﺎرات اﻟﺨﺎﺻﮫ ﺑﺒﻌﺾ اﻟﻤﻜﻮﻧﺎت اﻟﻜﮭﺮﺑﺎﺋﯿﺔ اﻟﺮﺋﯿﺴﯿﺔ ﻟﻤﺤﻄﺎت
ﺗﻮﻟﯿﺪ اﻟﻄﺎﻗﺔ اﻟﻜﮭﺮﺑﯿﺔ أﺛﻨﺎء ﻣﺮاﺣﻞ ﺗﻨﻔﯿﺬ اﻟﻤﺸﺮوع :
1
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
2
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
ﯾﺘﻢ إﺟﺮاء ھﺬا اﻻﺧﺘﺒﺎر ﻋﻠﻰ اﻟﻤﺤﻮل ﻟﻤﻌﺮﻓﺔ ﻧﺴﺒﺔ اﻟﺘﺤﻮﯾﻞ ﺑﯿﻦ ﻃﺮﻓﯿﮫ وﻧﺴﺒﺔ اﻟﺨﻄﺄ ﺑﯿﻦ اﻟﻘﯿﻤﺔ اﻟﺘﺼﻤﯿﻤﯿﺔ واﻟﻘﯿﻤﺔ
Tap ( وﯾﺘﻢ إﺟﺮاء اﻻﺧﺘﺒﺎر ﻋﻠﻰ ﺟﻤﯿﻊ ﻧﻘﺎطI) excitation current اﻟﻔﻌﻠﯿﺔ وﻛﺬﻟﻚ
ﻃﺮﯾﻘﺔ اﻻﺧﺘﺒﺎر
وذﻟﻚ80V أو40V ﻣﻦ ﺧﻼل اﻟﺠﮭﺎز وھﻮ ﯾﺤﺘﻮى ﻋﻠﻰ ﻗﯿﻤﺘﯿﻦ ﯾﺘﻢ اﺧﺘﯿﺎر إﺣﺪاھﻤﺎHV ﯾﺘﻢ ﺣﻘﻦ ﺟﮭﺪ ﻋﻠﻰ ﺟﮭﺔ
. HV Side ( اﻟﻤﻮﺻﻞ ﻋﻠﻰR, S, T, N) ﻣﻦ ﺧﻼل ﻛﺎﺑﻞ اﻟﺤﻘﻦ و ﯾﺤﺘﻮى ﻋﻠﻰ أرﺑﻌﺔ أﻃﺮاف
( R, S, T, N) ﻣﻦ ﺧﻼل ﻛﺎﺑﻞ أﺧﺮ ﺧﺎص ﺑﺎﻟﻘﯿﺎس ﯾﺤﺘﻮى ﻋﻠﻰ أرﺑﻊ أﻃﺮافL V Side ﻗﯿﺎس اﻟﺠﮭﺪ ﻋﻠﻰ
. LV Side ﻋﻠﻰ
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
: ﻃﺮﯾﻘﺔ اﻟﺘﻮﺻﯿﻞ
R 1 2 Transformer
Power 3 4 5 ……. N r Megger three phase TTR
s
S HV cable
t
L V cable
T
1 2 3 4 5 ……. N n
Taping
: ﺟﮭﺎز اﻻﺧﺘﺒﺎر
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
: ﺟﺪول اﻟﻨﺘﺎﺋﺞ
Tap
Ratio
Iexc.(mA)
Iexc.(mA)
Iexc.(mA)
Dev. (%)
Dev. (%)
Dev.(%)
No.
Ratio
Ratio
1 10.592 10.502 -0.19 2.09 10.504 -0.17 1.74 10.51 -0.07 3.22
2 10.386 10.367 -0.18 2.12 10373 -0.13 1.85 5
10.37 -0.07 3.30
8
…
…
…
9 9.4285 9.4195 -0.09 2.50 9.4243 -0.04 2.16 9.428 0.0 3.84
10 9.2917 9.2859 9
-0.06 2.56 9.2871 -0.05 2.19 5
9.296 0.05 3.91
3
….
….
….
….
….
….
….
….
….
….
….
20 7.9243 7.9359 0.15 3.28 7.9367 0.16 2.87 7.945 0.27 5.10
21 7.7876 7.8016 0.18 3.40 7.8022 0.19 2.98 8
7.809 0.28 5.25
7
± 0.5% أﻗﻞ ﻣﻦDev % ﯾﺠﺐ أن ﺗﻜﻮن ﻗﯿﻤﺔ
( وإذا أﻋﻄﻰ ﻧﻔﺲ اﻟﻨﺘﺎﺋﺞ ﯾﺘﻢTTR) ﯾﺠﺐ إﻋﺎدة اﻻﺧﺘﺒﺎر ﺑﺠﮭﺎز أﺧﺮ± 0.5% وﻓﻰ ﺣﺎﻟﺔ وﺟﻮد اﻟﻘﯿﻤﮫ أﻛﺒﺮ ﻣﻦ
. رﻓﺾ اﻟﻤﺤﻮل
وﻋﻨﺪL V side وﻛﺬﻟﻚ ﻋﻠﻰH V side ﯾﺘﻢ إﺟﺮاء اﺧﺘﺒﺎر ﻣﻘﺎوﻣﺔ اﻟﻤﻠﻔﺎت اﻟﻤﻮﺟﻮدة داﺧﻞ اﻟﻤﺤﻮل ﻋﻠﻰ ال
وذﻟﻚ ﻟﻤﻌﺮﻓﺔ ﻗﯿﻤﺔ اﻟﻤﻘﺎوﻣﺔ واﻟﺘﻤﺎﺛﻞ ﺑﯿﻦ اﻟﻤﻠﻔﺎت وﺗﻌﺘﻤﺪ ﻋﻠﻰ درﺟﺔ ﺣﺮارة اﻟﺰﯾﺖtap changer ﺟﻤﯿﻊ ﻧﻘﺎط
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
ﯾﺘﻢ ﺣﻘﻦ ﺗﯿﺎر وﯾﺘﻢ ﺗﺤﺪﯾﺪ ﻗﯿﻤﺔ ھﺬا اﻟﺘﯿﺎر ﻣﻦ اﻟﺠﮭﺎز ﺑﺎﺧﺘﯿﺎر ﻗﯿﻤﺔ ﻣﻦ ارﺑﻌﺔ وھﻰ
) (5A,500mA,50mA,5mAوﯾﻘﻮم اﻟﺠﮭﺎز ﺑﺤﻘﻦ ھﺬة اﻟﻘﯿﻤﺔ ﺑﺎﻟﺘﺪرﯾﺞ ﺣﺘﻰ ﯾﺼﻞ اﻟﻰ 100%ﻣﻦ ھﺬة اﻟﻘﯿﻤﺔ
وﻗﯿﺎس اﻟﺠﮭﺪ اﻟﻤﺘﻮﻟﺪ ﻋﻠﯿﮭﺎ ﺛﻢ ﺣﺴﺎب ﻗﯿﻤﺔ اﻟﻤﻘﺎوﻣﺔ ﻣﻦ ﺧﻼل اﻟﺠﮭﺪ واﻟﺘﯿﺎروﺗﻈﮭﺮ ھﺬة اﻟﻘﯿﻤﺔ ﻣﺒﺎﺷﺮة ﻋﻠﻰ اﻟﺸﺎﺷﺔ
وﺑﺠﻮارھﺎ ﻟﻤﺒﺔ ) (ledوﺗﻌﻄﻰ اﻟﻮﺣﺪة 0 mΩ, 0 Ωوﻋﻨﺪﻣﺎ ﺗﻈﮭﺮ ﻏﯿﺮ واﺿﺤﺔ ﯾﺘﻢ ﺗﻐﯿﯿﺮ rangeﻣﻦ ﺧﻼل
ﻣﺆﺷﺮ اﻟﻘﯿﺎس وﯾﺤﺘﻮى اﻟﺠﮭﺎز ﻋﻠﻰ وﺣﺪﺗﯿﻦ ﻗﯿﺎس resistance A, B
ﯾﺘﻢ ﺣﺴﺎب ﻗﯿﻤﺔ Rﻋﻨﺪ درﺟﺔ ﺣﺮارة 75 °Cدرﺟﺔ وذﻟﻚ ﻣﻦ اﻟﻘﺎﻧﻮن اﻟﺘﺎﻟﻰ
KIT -AVO
R 1 2 Transformer
Power 3 4 5 ……. N r Potential input Test current Potential input
)30 VDC (A output )30 VDC (B
S s
t
T 1 2 3 4 5 ……. N
n
Taping
6
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
-: ﺟﮭﺎز اﻻﺧﺘﺒﺎر
: ﺟﺪول اﻟﻨﺘﺎﺋﺞ
MEASUREMENT OF DC RESISTANCE
...
...
...
...
...
...
...
...
...
...
...
...
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
ﯾﺘﻢ إﺟﺮاء اﺧﺘﺒﺎر megger testﻋﻠﻰ اﻟﻤﺤﻮل وذﻟﻚ ﻟﻤﻌﺮﻓﺔ ﺷﺪة اﻟﻌﺰل ﻟﻠﻤﻠﻔﺎت ﺑﯿﻨﮭﺎ وﺑﯿﻦ ﺑﻌﻀﮭﺎ اﻟﺒﻌﺾ وﺑﯿﻨﮭﺎ
وﺑﯿﻦ ﺟﺴﻢ اﻟﻤﺤﻮل )اﻟﻘﻠﺐ اﻟﺤﺪﯾﺪى( وھﻞ ﯾﻮﺟﺪ ﻗﺼﺮ أم ﻻ .
ﯾﺘﻢ ﻋﻤﻞ ﻗﺼﺮ shortﻋﻠﻰ ﻣﻠﻔﺎت L V , H Vﺛﻢ ﯾﺘﻢ ﺗﻮﺻﯿﻞ ﻣﻠﻔﺎت L Vﻣﻊ اﻻرض ) (L V + groundوﯾﺘﻢ
ﺗﻮﺻﯿﻞ ﺟﮭﺎز )(+
meggerﻋﻠﻰ H Vﻋﻠﻰ ﺟﮭﺪ 5 KVإذا ﻛﺎن أﻛﺒﺮ ﻣﻦ ذﻟﻚ او ﻓﻰ ﺣﺪود ذﻟﻚ 5 KVو )(-ﻋﻠﻰ ground
واﻟﺤﻘﻦ ﻟﻤﺪة دﻗﯿﻘﺔ إذا ﻛﺎﻧﺖ اﻟﻘﯿﻤﺔ أﻛﺒﺮ ﻣﻦ 1 GΩﺗﻜﻮن ﻣﻘﺒﻮﻟﺔ ﺛﻢ ﯾﺘﻢ ﺗﻜﺮار ذﻟﻚ اﻻﺧﺘﺒﺎر ﻋﻠﻰ L V sideﺑـــ
1 KVﺛﻢ ﯾﺘﻢ ﺗﻮﺻﯿﻞ ) (+ﻋﻠﻰ H Vو ) (-ﻋﻠﻰ L Vﻋﻠﻰ ﺟﮭﺪ . 5 KV
وﯾﺠﺐ ﻋﻨﺪ اﺧﺘﺒﺎر اﻟﻌﺰل أﺧﺬ ﻗﺮاءة اﻟﻌﺰل ﻋﻨﺪ اﻟﺪﻗﯿﻘﺔ اﻷوﻟﻰ ﺛﻢ أﺧﺬ ﻗﺮاءة اﻟﻌﺰل ﻋﻨﺪ اﻟﺪﻗﯿﻘﺔ اﻟﻌﺎﺷﺮة وﺣﺴﺎب
polarization indexﻟﻠﻌﺰل وﯾﺠﺐ أن ﯾﻜﻮن أﻛﺒﺮ ﻣﻦ ) (1.3وﯾﺠﺐ أن ﺗﺰﯾﺪ ﻗﯿﻤﺔ اﻟﻌﺰل ﻣﻊ اﻟﺰﻣﻦ
8
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
MEGGER
S s
t
T 1 2 3 4 5 ……. N
n
Taping
LV HV
HV LV
9
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
: ﺟﮭﺎز اﻻﺧﺘﺒﺎر
: ﺟﺪول اﻟﻨﺘﺎﺋﺞ
LV-(HV+) 1000
HV-LV 5000
ﯾﺘﻢ إﺟﺮاء ھﺬا اﻻﺧﺘﺒﺎر ﻋﻠﻰ اﻟﻮﻗﺎﯾﺔ اﻟﻤﯿﻜﺎﻧﯿﻜﯿﺔ ﻋﻠﻰ اﻟﻤﺤﻮﻻت ﻟﻠﺘﺄﻛﺪ ﻣﻦ ﻋﻤﻠﮭﺎ ﺑﺎﻟﺸﻜﻞ اﻟﺼﺤﯿﺢ وھﻲ ﻣﺤﺴﺎت درﺟﺔ
اﻟﺤﺮارة ﻋﻠﻰ ﻣﻠﻔﺎت اﻟﻤﺤﻮل وﻛﺬﻟﻚ ﻣﺤﺲ درﺟﺔ ﺣﺮارة اﻟﺰﯾﺖ
10
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
ﻃﺮﯾﻘﺔ اﻻﺧﺘﺒﺎر:
ﯾﺘﻢ ﻓﻚ sensorاﻟﺨﺎص ﺑﺪرﺟﺔ ﺣﺮارة اﻟﺰﯾﺖ او اﻟﻤﻠﻔﺎت ووﺿﻌﮫ ﻓﻲ اﻟﺘﺠﻮﯾﻒ اﻟﻤﺨﺼﺺ ﻟﮫ ﻓﻲ اﻟﻐﻼﯾﺔ ﺣﺴﺐ
ﺣﺠﻤﮫ .ﺛﻢ ﯾﺘﻢ ﺗﻮﺻﯿﻞ ھﺬه اﻟﻐﻼﯾﺔ ﺑﺠﮭﺎز اﻟﺘﺤﻜﻢ ﻓﻲ درﺟﺔ ﺣﺮارة اﻟﻐﻼﯾﺔ ) (omegaواﺧﺬ ﻗﺮاءة اﻟﻌﺪاد وﻟﺘﻜﻦ 40
درﺟﺔ وﯾﺘﻢ ﺿﺒﻂ اﻟﺠﮭﺎز ﻋﻠﻰ درﺟﺔ ﺣﺮارة وﻟﺘﻜﻦ 50درﺟﺔ واﻻﻧﺘﻈﺎر ﺣﺘﻰ ﺗﺼﻞ اﻟﻐﻼﯾﺔ ﻟﮭﺬه اﻟﻘﯿﻤﺔ واﺧﺬ ﻗﺮاءة
اﻟﻌﺪاد وﻟﯿﻜﻦ 49درﺟﺔ وﺣﺴﺎب ﻣﻘﺪار اﻟﺨﻄﺄ .وﺗﻜﺮار اﻟﺘﺠﺮﺑﺔ ﻋﻠﻰ اﻟﻘﯿﻢ اﻟﺘﺎﻟﯿﺔ ℃ 120 ℃ ، 100 ℃ ، 80و
℃ 140
Control cable
Remove
Transformer
°C Sensor
Omega Boiler
B Roman
ﺟﮭﺎز اﻻﺧﺘﺒﺎر :
ﺟﺪول اﻟﻨﺘﺎﺋﺞ:
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
وﻏﺎﻟﺒﺎ ﯾﻜﻮن ﻣﺤﺲ sensorﻋﻠﻰ اﻟﻤﻠﻔﺎت ﻣﻦ ﺟﮭﺔ LV sideإذا ﻛﺎﻧﺖ اﻟﻤﺤﻮﻻت ﺻﻐﯿﺮة وﻓﻲ ﺣﺎﻟﺔ اﻟﻤﺤﻮﻻت
اﻟﻜﺒﯿﺮة ﯾﻜﻮن ﻋﻠﻰ ﻛﻞ ﻣﻦ LVو HV
ﯾﺘﻢ ھﺬا اﻻﺧﺘﺒﺎر ﻟﺘﺤﺪﯾﺪ ﻗﯿﻤﺔ ﺷﺪة ﻋﺰل اﻟﺰﯾﺖ داﺧﻞ اﻟﻤﺤﻮل وﻣﻌﺮﻓﺔ ھﺬة اﻟﻘﯿﻢ ﻓﻲ اﻟﺤﺪود اﻟﻤﻘﺒﻮﻟﺔ أم ﻻ
ﺑﺎﻟﻨﺴﺒﺔ ﻟﻠﺰﯾﺖ اﻟﺠﺪﯾﺪ ﯾﻜﻮن أﻛﺒﺮ ﻣﻦ 50 KVوﺑﺎﻟﻨﺴﺒﺔ ﻟﻠﺰﯾﺖ اﻟﻘﺪﯾﻢ ﯾﻜﻮن أﻛﺒﺮ ﻣﻦ 40 KV
ﻃﺮﯾﻘﺔ اﻻﺧﺘﺒﺎر:
ﯾﺘﻢ ﺗﺠﻔﯿﻒ ﺑﻮﺗﻘﺔ اﻟﺠﮭﺎز وﺿﺒﻂ اﻟﺠﮭﺎز ﻋﻠﻰ ﻣﺴﺎﻓﺔ ﻣﻘﺪارھﺎ ) (2.5 mmواﺧﺬ ﻋﯿﻨﺔ ﻣﻦ اﻟﻤﺤﻮل ﺑﻌﺪ ﺗﮭﺮﯾﺐ ﺟﺰء
ﻣﻦ اﻟﺰﯾﺖ أوﻻ ﺛﻢ أﺧﺬ ﻋﯿﻨﺔ اﻟﺰﯾﺖ ﺑﻌﺪ ذﻟﻚ ووﺿﻌﮭﺎ ﻓﻲ ﺑﻮﺗﻘﺔ اﻟﺠﮭﺎز واﻹﻧﺘﻈﺎر ﻟﻤﺪة 5دﻗﺎﺋﻖ ﻟﺘﺮﺳﯿﺐ اﻟﺰﯾﺖ ﺛﻢ
ﺑﺪء اﻻﺧﺘﺒﺎر وأﺧﺬ 6ﻗﺮاءات وﺑﯿﻦ ﻛﻞ ﻗﺮاءة واﻷﺧﺮى ﻣﺪة دﻗﯿﻘﺘﯿﻦ وﺣﺴﺎب ﻣﺘﻮﺳﻂ ھﺬه اﻟﻘﺮاءات
Process
ﺟﮭﺎز اﻻﺧﺘﺒﺎر:
12
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
:ﺟﺪول اﻟﻨﺘﺎﺋﺞ
MINIMUM STRENGTH 50 KV
13
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
BREAKDOWNV BREAKDOWN
SAMPLE LOCATION TEST
)OLTAGE (kV )VOLTAGE (kV
1 71.7
2 88.8
3 77.2 76.7
4 78.7
TRANSFORMER TOP 5 70.6
6 72.9
1 77.1
2 76.8
TRANSFORMER 3 65.8 70.7
BOTTOM 4 74.0
5 66.4
6 63.8
1 72.9
2 69.7
O. L. T. C 3 73.4 64.1
4 56.5
5 43.2
6 69.1
1 49.0
2 60.5
CONSERVATOR 3 60.9 60.2
4 59.4
5 67.3
6 64.1
1
2
CABLE BOX 3
4
5
6
ﯾﻘﺒﻞ اﻟﻌﺰل إذا ﻛﺎن أﻛﺒﺮ ﻣﻦ 50 KV
ﻣﻠﺤﻮﻇﺔ :ﻓﻲ اﻟﻤﺤﻮﻻت اﻟﻜﺒﯿﺮة ﯾﺘﻢ أﺧﺬ أﻛﺜﺮ ﻣﻦ ﻋﯿﻨﺔ ﻣﻦ اﻟﺘﻨﻚ اﻟﺮﺋﯿﺴﻲ ،ﺗﻨﻚ اﻟﺘﻤﺪد وﺗﻨﻚ tapping
14
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
OLTC ﻣﻦ .3
اﻟﺨﺎص ﺑﺎﻟﺘﻨﻚ اﻟﺮﺋﯿﺴﻲconservator ﺗﻨﻚ .4
OLTC اﻟﺨﺎصconservator ﺗﻨﻚ .5
cable box اﻟﺨﺎصconservator ﺗﻨﻚ .6
( وھﺬا ﯾﺘﻮﻗﻒ ﻋﻠﻰ ﻃﺒﯿﻌﺔ اﻟﻘﻠﺐIron loss ) ﯾﺘﻢ ھﺬا اﻻﺧﺘﺒﺎر ﺑﻤﻌﺮﻓﺔ اﻟﻤﻔﺎﻗﯿﺪ اﻟﺤﺪﯾﺪﯾﺔ ﻟﻘﻠﺐ اﻟﻤﺤﻮل
.اﻟﺤﺪﯾﺪي )ﺷﺮاﺋﺢ اﻟﺼﻠﺐ اﻟﺴﯿﻠﻜﻮﻧﻲ( وﻋﻠﻰ ﻣﺪى اﻟﻌﺰل ﻟﮫ وﺿﻐﻄﺔ
ﻣﻔﺘﻮح وﻗﯿﺎس اﻟﺘﯿﺎرLV وﺗﺮكHV ( ﻋﻠﻰ3∅) ﯾﺘﻢ ﺗﻮﺻﯿﻞ اﻟﻤﺤﻮل ﻋﻠﻰ ﻣﺼﺪر ﺟﮭﺪ
15
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
:ﺟﺪول اﻟﻨﺘﺎﺋﺞ
Criteria value <± 5 % between test and factory test report FAT
. وﻗﯿﺎس اﻟﺘﯿﺎر اﻟﺬى ﯾﻤﺮ ﻓﻰ ھﺬا اﻟﺤﻘﻦ2U1,2U2 ﻋﻠﻰ220V single phase ﯾﺘﻢ ﺣﻘﻦ ﺟﮭﺪ
WI=√3 (I*V)
16
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
ﯾﺘﻢ إﺟﺮاء ھﺬا اﻻﺧﺘﺒﺎر ﻟﺘﺤﺪﯾﺪ زاوﯾﺔ اﻹزاﺣﺔ ﺑﯿﻦ اﻟﻤﻠﻔﺎت اﻻﺑﺘﺪاﺋﯿﺔ واﻟﻤﻠﻔﺎت اﻟﺜﺎﻧﻮﯾﺔ vector groupﻓﻲ
اﻟﻤﺤﻮﻻت وذﻟﻚ ﻟﻠﺘﻮﺻﯿﻞ ﻋﻠﻰ اﻟﺸﺒﻜﺔ واﻟﺪﺧﻮل ﻓﻲ اﻟﺨﺪﻣﺔ.
ﯾﺘﻢ ﺗﺠﮭﯿﺰ ﻣﺼﺪر ﺟﮭﺪ three phaseﺑﺄي ﻗﯿﻤﺔ 220 v ,380 v,480 vوﺗﻮﺻﯿﻠﮫ ﻋﻠﻰ ) (3∅ -C.Bﺛﻢ
ﻋﻠﻰ terminalﺛﻢ ﻋﻠﻰ HV sideوﻋﻤﻞ short circuitﻋﻠﻰ phase R in HV and LV
)(1U&2Uورﺟﻮع ﺑﻜﺎﺑﻼت ﻣﻦ LVﻋﻠﻰ terminalﻟﻠﻘﯿﺎس ﻋﻠﯿﮭﺎ .
17
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
: ﺟﺪول اﻟﻨﺘﺎﺋﺢ
1U-1V
1V-1W
1W-1U
1U-1N
MEASURE: (VOLTS)
TERMINAL VOLTAGE (V) TERMINAL VOLTAGE (V) TERMINAL VOLTAGE (V)
2W
N
2V 1V
1W
18
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
2. Dyn11
2V
2W
1W
1V
3. Dyn5
2V
1U
2U
1V
1W
4. YNd1
2W
2V
1V
1W
5. YNd11
1U, 2U
19
2V
2W
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
6. YNd5
2U, 1U
1V
1W
7. DNy7
2V
1V-2V = 1W-2V=1W-2W > 1V-2W
2W
2U, 1U
2V
1W
8. Dyn7
2V
20
2U, 1U 2W
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
ﯾﺘﻢ إﺟﺮاء ھﺬا اﻻﺧﺘﺒﺎر ﻟﻠﺘﺄﻛﺪ ﻣﻦ ارﺗﻔﺎع درﺟﺔ ﺣﺮارة اﻟﻤﺒﯿﻦ ﻋﻠﻰ زﯾﺎدة اﻟﺘﯿﺎر اﻟﻤﺎر ﻓﯿﮫ ﻣﻦ ﺧﻼل current
. transformer
ﯾﺠﺐ أن ﺗﻜﻮن ﻗﯿﻤﺔ درﺟﺔ اﻟﺤﺮارة أﻋﻠﻰ ﻓﻲ ﻣﺒﯿﻦ اﻟﺤﺮارة اﻟﺨﺎص windingﻣﻦ ﻣﺒﯿﻦ درﺟﺔ ﺣﺮارة اﻟﺰﯾﺖ .ﻟﺬﻟﻚ
ﯾﺠﺐ وﺿﻊ ﻣﺸﻐﻞ ﻧﻈﺎم اﻟﺘﺒﺮﯾﺪ )اﻟﻤﺮاوح ( fansﻋﻠﻰ ﻣﺒﯿﻦ winding temperature
ﯾﺘﻢ ﺣﻘﻦ ﺗﯿﺎر ﻋﻠﻰ secondary injection for winding temperature indicationوأﺧﺬ درﺟﺔ
اﻟﺤﺮارة ﻗﺒﻞ اﻟﺤﻘﻦ ﺛﻢ ﻛﻞ 5دﻗﺎﺋﻖ ﯾﺘﻢ أﺧﺬ اﻟﻘﺮاءة ﺣﺘﻰ ﯾﺼﻞ اﻟﺰﻣﻦ اﻟﻰ 45دﻗﯿﻘﺔ وﯾﻼﺣﻆ ﻓﻲ اﻟﺒﺪاﯾﺔ ﻛﻮن اﻟﺰﯾﺎدة
ﻛﺒﯿﺮة ﺛﻢ ﺑﻌﺪ ذﻟﻚ ﺗﻘﻞ ﺣﺘﻰ ﺗﺼﻞ إﻟﻰ اﻟﺜﺒﺎت وﻻ ﺗﺘﻐﯿﺮ ﻣﻊ زﯾﺎدة اﻟﺰﻣﻦ.
وﯾﺘﻢ اﻟﺤﻘﻦ ﺑﻘﯿﻤﺔ 1A,2A,5A rated value for secﺣﺴﺐ ﻣﺤﻮل اﻟﺘﯿﺎر
21
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
: ﻃﺮﯾﻘﺔ اﻟﺘﻮﺻﯿﻞ
Terminal
HV side
LV side
Transformer
Plan
Transformer
Indicator
0 1
SVERKER760
Elevation
:ﺟﮭﺎز اﻻﺧﺘﺒﺎر
22
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
:ﺟﺪول اﻟﻨﺘﺎﺋﺞ
Reading
Time (min) Temp. reading lv2
0 44
5 54
10 63
15 67
20 70
25 70,5
30 70,5
35 71
40 71
45 71
9 - Function checks :
ﯾﺘﻢ إﺟﺮاء ھﺬا اﻻﺧﺘﺒﺎر ﻟﻠﺘﺄﻛﺪ ﻣﻦ اﻻﺟﮭﺰة اﻟﻤﯿﻜﺎﻧﯿﻜﯿﺔ اﻟﻤﻮﺟﻮدة ﻋﻠﻰ اﻟﻤﺤﻮل ﺗﻌﻤﻞ ﺟﯿﺪا واﻟﺘﻮﺻﯿﻼت ﺑﯿﻨﮭﺎ وﺑﯿﻦ
. ﺧﻠﯿﺔ اﻟﺘﺤﻜﻢ ﺟﯿﺪة وﻣﻮﺻﻠﺔ وﺳﻠﯿﻤﺔ
: ﻃﺮﯾﻘﺔ اﻻﺧﺘﺒﺎر
1-Buchholz relay
: ﻟﻠﺘﺄﻛﺪ ﻣﻦ ﻋﻤﻠﮫ ﺑﻄﺮﯾﻘﺔ ﺻﺤﯿﺤﺔ وﯾﺘﻢ ھﺬا ﻛﺎﻟﺘﺎﻟﻲBR ﯾﺘﻢ ﻋﻤﻞ اﺧﺘﺒﺎر
23
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
(1اﻟﻀﻐﻂ ﻋﻠﻰ ﺳﻮﺳﺘﺔ اﻟﻌﻮاﻣﺔ ﻧﺼﻒ ﺿﻐﻄﺔ واﻟﻘﯿﺎس ﻋﻠﻰ ﻧﻘﻄﺔ alarmھﻞ أﺻﺒﺤﺖ closeأم ﻣﺎ زاﻟﺖ
(buzz) openوﻓﻲ ﺣﺎﻟﺔ closeﺗﻜﻮن اﻟﻤﺮﺣﻠﺔ اﻻوﻟﻰ )(ok
(2اﺳﺘﻜﻤﺎل اﻟﻀﻐﻂ ﻋﻠﻰ اﻟﺴﻮﺳﺘﺔ ﺣﺘﻰ اﻟﻨﮭﺎﯾﺔ واﻟﻘﯿﺎس ﻋﻠﻰ ﻧﻘﻄﺔ tripوﻛﺬﻟﻚ alarmھﻞ أﺻﺒﺤﺖ closeأم
ﻻ وﺣﺎﻟﺔ closeﯾﻜﻮن اﻟﺠﮭﺎز ﯾﻌﻤﻞ ﺟﯿﺪا .
ﻣﻠﺤﻮﻇﺔ :ﻓﺘﺢ اﻟﻐﻄﺎء اﻟﻤﻮﺟﻮد ﻋﻠﻰ اﻟﺴﻮﺳﺘﺔ ﺣﺘﻰ ﯾﺘﻢ اﻟﻀﻐﻂ ﺛﻢ ﺗﺮﻛﯿﺒﺔ ﻣﺮة أﺧﺮى وﻛﺬﻟﻚ اﻟﻨﻈﺮ اﻟﻰ اﻟﻌﻮاﻣﺎت
اﻟﺪاﺧﻠﯿﺔ .
ﯾﻮﺟﺪ limit switchﻣﺮﻛﺐ ﻋﻠﻰ diaphragmﯾﺤﺘﻮي ﻋﻠﻰ ﺳﻮﺳﺘﺔ إﺣﺪاھﻤﺎ tripواﻟﺜﺎﻧﯿﺔ restﻟﮫ .
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
اﺧﺘﺒﺎر ﻟﻌﺪاد ﻣﺴﺘﻮى اﻟﺰﯾﺖ ﻣﻊ اﻧﺨﻔﺎض اﻟﺰﯾﺖ ﯾﻌﻄﻲ alarmوﻣﻊ زﯾﺎدة اﻻﻧﺨﻔﺎض ﯾﻌﻄﻲ tripوﯾﺘﻢ ھﺬا
اﻻﺧﺘﺒﺎر ﻋﻦ ﻃﺮﯾﻖ :
(1ﻓﻚ اﻟﻌﺪاد وﻟﻔﮫ وھﻮ ﻣﻼﺻﻖ ﻣﻊ اﻟﻘﺎﻋﺪة ﺣﺘﻰ ﯾﻠﻒ اﻟﻤﺆﺷﺮ اﻟﻰ اﻟﻘﯿﻤﺔ اﻟﻤﻨﺨﻔﻀﺔ ﺛﻢ اﺳﺘﻜﻤﺎل اﻟﻠﻒ ﻋﻠﻰ trip
رﺳـــــﻢ ﻣـــﺆﺷﺮ close
(2ﻓﻚ اﻟﻐﻄﺎء اﻟﺰﺟﺎﺟﻲ ﻟﻠﻌﺪاد وﺗﺤﺮﯾﻚ اﻟﻤﺆﺷﺮ ﻻﺳﻔﻞ ﺑﺎﻟﯿﺪ ﺣﺘﻰ A,T
ﯾﺘﻢ ﻓﻚ اﻟﻐﻄﺎء اﻟﺰﺟﺎﺟﻲ وﺗﺤﺮﯾﻚ اﻟﻤﺆﺷﺮ ﻓﻲ إﺗﺠﺎه زﯾﺎدة اﻟﺤﺮارة ﺣﺘﻰ ﻧﻘﻄﺔ alarmﺗﻐﻠﻖ ﺛﻢ اﻟﺰﯾﺎدة ﻓﻲ اﻻرﺗﻔﺎع
ﺣﺘﻰ ﻧﻘﻄﺔ tripﺗﻐﻠﻖ.
وﯾﻤﻜﻦ إﺟﺮاء ھﺬا اﻻﺧﺘﺒﺎر ﻣﻊ calibration of winding or oilوﻗﯿﺎس اﻟﻨﻘﺎط ﻋﻨﺪ اﻟﻮﺻﻮل اﻟﻰ ﺣﺪود A,T
25
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
:ﺟﺪول اﻟﻨﺘﺎﺋﺞ
AUXILIARY EQUIPMENT:
IR 500V (M ) FUNCTION
DESCRIPTION ACROSS TO
CONTACTS EARTH
TRAFO. MAX-.X13;7,39
OLTC MAX-.X13;9,40
MIN.X13;10,38
.3 OIL LEVEL INDC.
VENT OLTC
ALARM -13.13,43
7. OIL TEMPERATURE
ALARM X13;15,45
8. WINDING TEMP. LV
TRIP- X13;29,59
26
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
ALARM -13;14,44
9. WINDING TEMP. HV
TRIP -X13;28,58
STAGE 1:
ALARM :105° C
TRIP:120° C
STAGE 1:
INDICATOR LV STAGE 2:
MAN: Fan Start: 90° C
TYPE:
ALARM :105° C
SERIAL #:
TRIP:120° C
STAGE 1:
STAGE 2:
ALARM :90° C
TRIP: 105° C
27
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
ALARM
15 BUCHHOLZ RELAY
X13;2,32
CABLE BOX HV1
TRIP X13;22,52
ALARM
16 BUCHHOLZ RELAY
X13;3,33
CABLE BOX HV2
TRIP X13;23,53
ALARM
17 BUCHHOLZ RELAY
X13;4,34
CABLE BOX HV3
TRIP X13;24,54
ALARM
18 BUCHHOLZ RELAY
X13;5,35
CABLE BOX HV4
TRIP X13;25,55
وﺟﻤﯿﻊmanual وauto ﯾﺘﻢ إﺟﺮاء ھﺬا اﻻﺧﺘﺒﺎر ﻟﻠﺘﺄﻛﺪ ﻣﻦ ان ﻧﻈﺎم اﻟﺘﺒﺮﯾﺪ ﯾﻌﻤﻞ ﺑﺸﻜﻞ ﺻﺤﯿﺢ ﻋﻠﻰ وﺿﻊ
اﻟﻤﺮواح ﺗﻌﻤﻞ ﺑﺸﻜﻞ ﺳﻠﯿﻢ
◙Instrument device:- megger, multimeter, clap meter, stopwatch
28
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
ﻃﺮﯾﻘﺔ اﻻﺧﺘﺒﺎر:
ﻋﻤﻞ ﻗﯿﺎس اﻟﻌﺰل ﻋﻠﻰ ﺟﻤﯿﻊ اﻟﻤﺮواح megger test winding +ground
ﺗﺸﻐﯿﻞ اﻟﻤﺮوﺣﮫ وﻗﯿﺎس ﺗﯿﺎر اﻟﺒﺪء وﺗﯿﺎر اﻟﺘﺸﻐﯿﻞ ﺿﺒﻂ over current
ﻓﻚ أﺣﺪ أﻃﺮاف اﻟﺘﻮﺻﯿﻞ وﺗﺸﻐﯿﻞ اﻟﻤﻮﺗﻮر واﻟﺘﺄﻛﺪ ﻣﻦ اﻟﻔﺼﻞ tripوﻣﻌﺮﻓﺔ ﺗﯿﺎر اﻟﻔﺼﻞ وزﻣﻨﮫ ﯾﻌﻤﻞ ﻋﻠﻰ 2фﻓﻘﻂ
وذﻟﻚ ﯾﺘﻌﺪى ﺗﯿﺎر over loadوﯾﻜﻮن اﻟﺘﯿﺎر ﻓﻰ ھﺬه اﻟﺤﺎﻟﮫ 2ﺗﯿﺎر اﻟﺘﺸﻐﯿﻞ 2IRوﻻﯾﺪور اﻟﻤﻮﺗﻮر و ﯾﺠﺐ أن ﯾﻜﻮن
زﻣﻦ اﻟﻔﺼﻞ أﻗﻞ ﻣﻦ 60ﺛﺎﻧﯿﺔ
29
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
capacitanceﯾﺘﻢ إﺟﺮاء اﻻﺧﺘﺒﺎر ﻟﻤﻌﺮﻓﺔ ﺷﺪة ﻋﺰل اﻟﻤﻠﻔﺎت ﻋﻠﻰ اﻟﻤﺤﻮل وذﻟﻚ ﻋﻦ ﻃﺮﯾﻖ ﻗﯿﺎس
tanδ=cosδ وﻛﺬﻟﻚ
: ﻃﺮﯾﻘﺔ اﻻﺧﺘﺒﺎر
HV واﻟﺜﺎﻧﯿﮫcontrol ﺟﮭﺎز اﻟﻘﯿﺎس ﯾﺘﻜﻮن ﻣﻦ وﺣﺪﺗﯿﻦ إﺣﺪاھﻤﺎ
LV ﻋﻠﻰ أﻃﺮافshort circuit ﯾﺘﻢ ﻋﻤﻞ
Neutral وﯾﺘﻢ ﻓﺼﻞ اﻷرﺿﻲ ﻋﻦ ﻃﺮفHV ﻋﻠﻰshort circuit ﯾﺘﻢ ﻋﻤﻞ
10KV ﺟﮭﺪ اﻻﺧﺘﺒﺎر
: اﻻﺧﺘﺒﺎر اﻻول
RED CABLE ﻋﻦ ﻃﺮﯾﻖLV SIDE واﻟﻘﯿﺎس ﻣﻦHV SIDE ﻋﻠﻰ أﻃﺮافHVﯾﺘﻢ ﺗﻮﺻﯿﻞ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
وإﺟﺮاء ﺛﻼث اﺧﺘﺒﺎرات
1-GST (ground specimen test) GROUND
Measure for (CHG+CHL)
2-GST (ground specimen test) GUARD
Measure for (CHG)
1-UST (ungrounded specimen test)
Measure for (CHL)
Check test (test 1= test 2+ test 3)
: اﻻﺧﺘﺒﺎر اﻟﺜﺎﻧﻰ
HV side و اﻟﻘﯿﺎس ﻣﻦLV side ﻋﻠﻰ10KV ﻧﻔﺲ اﻻﺧﺘﺒﺎر اﻟﺴﺎﺑﻖ وﻟﻜﻦ ﯾﺘﻢ ﺣﻘﻦ
30
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
رﺳﻢ اﻟﺠﮭﺎز:
31
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
32
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
I
Ic
HV Lead CHG 33
Delta – 2000 CHL
test set δ
Lv lead
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
Calculate tan δ
Tan =
Sin = ∅
→ ≅0
∅ →≅ 90
∅
cos ≅ 1, tan∅ = , COS∅ =
∅
∅ ∅
Tan = = = cos∅.
1. power on
2. push new test key
3. select test ( UST,GST ug , GST)
4. start test with two safety key in cable pushed
5. increasing voltage slowly reach to 10KV
6. push measuring key and wait out resulted
7. decreasing voltage to zero
8. Power off.
34
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
Equivalent to
% Power
10KV
CAPACITANCE C (PF)
Insulation Tested Test Connections Factor
(windings) Equivalent to
Test Mode 2.5KV
Test
Test
Measured
20˚C PF
WATTS
C.F
mA
EN GND GAR US
G T
0.120
1 CHG+ GST H L T 10 11776.0 44.63 0.815
CHL
GND
35
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
PUSHING TESTS
Equivalent to
Pushing .NO.SER O.
% Power Factor 10 KV
Test CAPACITA
Test Test Equivalent to
No. NCE
2.5KV
Mode KV
C (PF)
Measu 20˚C
C.F mA Watts
red %PF
15 UST
16 UST
17 UST
LO .KV
18 UST
19 UST
20 UST
36
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
ﻣﻠﺤﻮﻇﺔ :ﯾﺠﺐ اﺧﺘﺒﺎر اﻟﺠﮭﺎز و اﻟﺘﻮﺻﯿﻞ ﻋﻠﻰ 2KVﻓﻘﻂ أوﻻ ﺛﻢ ﻋﻤﻞ اﻻﺧﺘﺒﺎر اﻟﺮﺋﯿﺴﻲ ﻋﻠﻰ ).(10kv
U
U Power
V supply
Short 220V
N
AC 1ф
v V
w W
HV LV
ﯾﺘﻢ ﺣﻘﻦ ﻓﻮﻟﺖ ﻋﻠﻰ HVوﻋﻤﻞ shortﻋﻤﻞ shortﻋﻠﻰ ﻧﻔﺲ اﻟﻤﻠﻒ ﺛﻢ ﻗﯿﺎس اﻟﺘﯿﺎر واﻟﺠﮭﺪ وﺣﺴﺎب اﻟﻤﻘﺎوﻣﺔ R
وﺣﺴﺎب اﻟﻤﻌﺎوﻗﺔ ﻣﻦ اﻟﻘﺎﻧﻮن.
% ∗
=Z% = x100=Z% per phase
% ∗
أو اﻟﻌﻜﺲ ﻣﻦ LVوﻋﻤﻞ SHORTﻋﻠﻰ HV
Z% Main =√3*Z% per phase
Z+=Z-
37
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
Tap Supply 1U-1N Short Supply 1V-1N Short Supply 1W-1N Short
2U1-2U2 2V1-2V2 2W1-2W2
U
U A
V Power
supply
N
380V
v V AC 3ф
w W
HV LV
star وذﻟﻚ اﻻﺧﺘﺒﺎر ﯾﺘﻢ ﻓﻰ ﺣﺎﻟﺔ ﺗﻮﺻﯿﻠﺔzero ﯾﺘﻢ إﺟﺮاء اﺧﺘﺒﺎر ﻗﯿﻤﺔ اﻟﻤﻌﺎوﻗﮫ ﻓﻰ ﺣﺎﻟﺔ
U
A
Power
N V supply
V 220V
W AC 1ф
: ﺟﺪول اﻟﻨﺘﺎﺋﺞ
38
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
Single phase voltage applied on HV side ,by keeping LV side OPEN
3V / I
Zo % * 100
rated , voltage / rated , current
ﯾﺘﻢ وﺿﻊ ﯾﺪ اﻟﺘﺪوﯾﺮ )اﻟﺘﻐﯿﺮ( ﯾﺪوﯾﺎ وﻣﺤﺎوﻟﺔ اﻟﺮﻓﻊ واﻟﺨﻔﺾ ﻛﮭﺮﺑﯿﺎ وﯾﺠﺐ اﻻ ﯾﺴﺘﺠﯿﺐ إﻟﻰ اﻷﻣﺮ
ﻛﮭﺮﺑﻰ
ﯾﺠﺐ اﻟﻮﺻﻮل اﻟﻰ اﺧﺮ tap Noوإﻋﻄﺎء أﻣﺮ رﻓﻊ ﺑﻌﺪھﺎ ﻓﯿﺠﺐ اﻻ ﯾﺴﺘﺠﯿﺐ ﻛﮭﺮﺑﯿﺎ
ﯾﺠﺐ اﻟﻮﺻﻮل اﻟﻰ tap.No1واﻟﺘﺪوﯾﺮ ﺑﺎﻟﯿﺪ ﻟﻠﺨﻔﺾ ﻓﺘﺪور اﻟﯿﺪ ﻋﺪة ﻣﺮات ﺛﻢ ﺗﻘﻒ
ﯾﺠﺐ اﻟﻮﺻﻮل اﻟﻰ آﺧﺮ tap Noواﻟﺘﺪوﯾﺮ ﺑﺎﻟﯿﺪ ﻟﻠﺮﻓﻊ ﻓﺘﺪور اﻟﯿﺪ ﻋﺪة ﻣﺮات ﺛﻢ ﺗﻘﻒ
ﯾﺠﺐ ﻋﻨﺪ اﻟﺪوران ﺑﺎﻟﯿﺪ أن ﯾﻔﺼﻞ ﻣﻔﺘﺎح main CBاﻟﺨﺎص ﺑﺘﺸﻐﯿﻠﮫ أوﺗﻮﻣﺎﺗﯿﻜﯿﺎ
ﯾﺠﺐ أن ﯾﻌﻤﻞ ﻧﻈﺎم اﻟﻔﻠﺘﺮة ﺑﻌﺪ ﺗﻐﯿﺮ ﻛﻞ tapإذا ﻛﺎن ھﺬا اﻟﻨﻈﺎم ﻣﺮﻛﺐ ﻋﻠﻰ اﻟﻤﺤﻮل
39
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م ( )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ
MANUFACTURER
_________________________________________________
TYPE ______________________SERIAL
NO.____________________________
MOTOR VOLTAGE_________________RATING
________________________
SERIAL NO.____________________________
REVOLUTIONS REQ’D TO CHANGE TAP_____________________________
(MANUAL OPERATION)
TAP CHANGER SELECTOR AND DIVERTER SWITCH
MANUFACTURER__________________________YEAR
__________________
TYPE ______________________ SERIAL NO.
___________________________
NO. OF TAPS_________________NORMAL
TAP_________________________
VOLTAGE
RANGE__________________________________________________
1 CHECK THE MECHANICL OPERATION
40
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
.1ﻗﯿﺎس ﻗﯿﻤﺔ اﻟﻀﻐﻂ ﻋﻨﺪ أﺳﻔﻞ ﻧﻘﻄﺔ ﻓﻲ اﻟﻤﺤﻮل .ﺛﻢ ﺣﻘﻦ ﻧﯿﺘﺮوﺟﯿﻦ أﻋﻠﻰ ﻋﻮاﻣﺔ ﺗﻨﻚ اﻟﺘﻤﺪد
conservatorﺣﺘﻰ ﯾﺼﻞ اﻟﻀﻐﻂ أﺳﻔﻞ اﻟﻤﺤﻮل إﻟﻰ 1.25 %ﻣﻦ اﻟﻘﯿﻤﺔ اﻷوﻟﻰ ﺑﻤﻌﻨﻰ زﯾﺎدة
25%ﺛﻢ ﺗﺮك اﻟﻤﺤﻮل ﻟﻤﺪة 24ﺳﺎﻋﺔ وﯾﺘﻢ اﻟﻔﺤﺺ ﻟﻤﻌﺮﻓﺔ ﻣﺎ إذا ﻛﺎن ھﻨﺎك ﺗﺴﺮﯾﺐ أوﺗﻨﻔﯿﺲ ﻣﻦ
أى ﻣﻜﺎن وﯾﺘﻢ اﻟﺘﺮﻛﯿﺰ ﻓﻰ اﻟﻔﺤﺺ ﻋﻠﻰ اﻟﺠﻮاﻧﺎت واﻟﻔﻼﻧﺸﺎت وﯾﻨﻈﺮ إﻟﻰ اﻟﻀﻐﻂ ﻋﻠﻰ اﻟﻤﺒﯿﻦ إذا ﻣﺎ
ﻗﻞ أم ﻣﺎزال ﺛﺎﺑﺘﺎ ،وﻓﻰ ﺣﺎﻟﺔ اﻟﺜﺒﺎت ﯾﻘﺒﻞ اﻟﻤﺤﻮل ،وﻓﻰ ﺣﺎﻟﺔ ﻏﯿﺮ ذﻟﻚ ﯾﺮﻓﺾ اﻻﺧﺘﺒﺎر وﻣﺨﺎﻃﺒﺔ
اﻟﺸﺮﻛﺔ اﻟﻤﺼﻨﻌﮫ ﻟﻠﻤﻌﺎﻟﺠﺔ أو اﻟﺮﻓﺾ اﻟﻜﻠﻰ .
ﯾﺘﻢ اﻟﻀﻐﻂ ﺑﻤﻘﺪار 0.35 barﻋﻠﻰ أﻋﻠﻰ ﺗﻨﻚ اﻟﺘﻤﺪد conservatorﺛﻢ ﯾﺘﺮك ﻟﻤﺪة 24ﺳﺎﻋﺔ ﺛﻢ ﯾﻔﺤﺺ
ﻣﺜﻞ اﻟﺴﺎﺑﻖ
ﻧﺴﺒﺔ 0.35ﯾﻌﺘﻤﺪ ﻋﻠﻰ اﻟﻤﺎﻟﻚ وﻓﻰ ﺑﻌﺾ اﻻﺣﯿﺎن ﺗﻘﺒﻞ ﻣﻦ 0.2ﻓﺼﺎﻋﺪ
وﯾﺴﺘﺨﺪم ھﺬا اﻻﺧﺘﺒﺎر ﻟﻠﺘﺄﻛﺪ ﻣﻦ ﺟﻮدة اﻟﺘﺼﻨﯿﻊ واﻟﻌﺰل واﻟﺘﺮﺑﯿﻂ وﻹﻛﺘﺸﺎف ﻧﻘﺎط اﻟﻀﻌﻒ ﻋﻠﻰ اﻟﻤﺤﻮل وإذا
ﻓﺸﻞ اﻻﺧﺘﺒﺎر ﯾﺮﻓﺾ اﻟﻤﺤﻮل
ﻋﻨﺪ اﻟﺤﻘﻦ ﯾﻜﻮن اﻟﺤﻘﻦ ﻋﻠﻰ ﺟﻤﯿﻊ اﻟﺘﻨﻜﺎت اﻟﻤﻮﺟﻮده ﻓﻰ اﻟﻤﺤﻮل conservatorﺑﺘﻮﺻﯿﻞ ﻣﺸﺘﺮك
واﻟﻀﻐﻂ ﻋﻠﯿﮭﻢ ﺟﻤﯿﻌﺎ ﻓﻰ ﻧﻔﺲ اﻟﻮﻗﺖ وﺑﻨﻔﺲ اﻟﻀﻐﻂ ،وﯾﻜﻮن اﻟﺤﻘﻦ ﻣﻦ ﻣﻜﺎن silica jellﺑﻌﺪ ﻧﺰوﻟﮫ ﻣﻦ
اﻟﻤﺎﺳﻮره.
41
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ )اﺧﺘﺒﺎرات ﻣﺤﻮﻻت اﻟﻘﺪرة اﻟﻜﮭﺮﺑﺎﺋﯿﺔ (
ﯾﺘﻢ إﺟﺮاء ھﺬا اﻻﺧﺘﺒﺎر ﻟﻠﺘﺄﻛﺪ ﻣﻦ ﺗﻮزﯾﻊ ﺧﻄﻮط اﻟﻔﯿﺾ اﻟﻤﻐﻨﺎﻃﯿﺴﻲ واﻟﻘﻮة اﻟﺪاﻓﻌﺔ اﻟﻜﮭﺮﺑﯿﺔ داﺧﻞ اﻟﻘﻠﺐ
اﻟﺤﺪﯾﺪي وﻋﺪم وﺟﻮد ﻓﻘﺪ ﻛﺒﯿﺮ ﻓﻲ اﻟﻤﺠﺎل اﻟﻤﻐﻨﺎﻃﯿﺴﻲ
U
U Power
V supply
V N 220V
V
AC 1ф
v V V
1U1 1W1
1V1
2U1 2W1
2V1
ﯾﺘﻢ ﺣﻘﻦ ﺟﮭﺪ ﻋﻠﻰ اﺣﺪ اﻟﻤﻠﻔﺎت ) (1Φ 220 vوﻗﯿﺎس اﻟﺠﮭﺪ ﻋﻠﻰ اﻟﻤﻠﻔﯿﻦ اﻟﺜﺎﻧﯿﯿﻦ ﻓﯿﺠﺐ أن ﯾﻜﻮن اﻟﺠﮭﺪ
اﻟﻤﺤﻘﻮن ﻋﻠﯿﺔ ﯾﺴﺎوي ﻣﺠﻤﻮع اﻟﺠﮭﺪﯾﻦ اﻻﺧﺮﯾﻦ وﯾﻜﻮن اﻟﺠﮭﺪ اﻟﻤﻘﺎﺑﻞ ﻟﻠﻤﻠﻒ اﻟﻤﺤﻘﻮن ﻋﻠﯿﮫ ﻓﻲ اﻟﺜﺎﻧﻮي
ﯾﺴﺎوي ﻣﺠﻤﻮع اﻟﺠﮭﺪﯾﻦ اﻻﺧﺮﯾﻦ ﻓﻲ اﻟﺜﺎﻧﻮي
Primary v1=v2+v3
Secondary v1=v2+v3
42
www.facebook.com/Electrical.engineering.community2050
! !!! !!!!! !!! !! !!!!!! ] [ ]اﺧﺘﺒﺎرات اﻟﻤﻮﻟﺪ اﻟﻜﮭﺮﺑﻰ
GENERATOR TESTS :
42
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م [ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
43
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م [ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
1. Timing test
2. Contact resistance
3. Megger test
4. Highpot test
وزﻣﻦ اﻟﻐﻠﻖ ﺛﻢ اﻟﻔﺘﺢ ﻣﺒﺎﺷﺮةCB وزﻣﻦ ﻓﺘﺢCB ﯾﺘﻢ إﺟﺮاء ھﺬا اﻻﺧﺘﺒﺎر ﻟﺘﺤﺪﯾﺪ زﻣﻦ ﻏﻠﻖ
-:ﻃﺮﯾﻘﺔ اﻟﺘﻮﺻﯿﻞ
Short
GCB
R S T
CC TC1 TC2
+Ve -Ve
R
Close
S
Jumper Trip
Timing tester
44
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م [ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
-: ﺟﮭﺎز اﻻﺧﺘﺒﺎر
1) <c> close
2) <o> open
3) <co> close open
4) <oc> open close
5) <coc>close open close
6) <oco> open close open
ﻟﻜﻞ اﻟﺴﻜﺎﻛﯿﻦ اﻟﺘﻰ ﺗﻌﻤﻞ ﻛﮭﺮﺑﯿﺎ وذﻟﻚ ﺑﻀﺒﻂ اﻟﺠﮭﺎز أﻋﻠﻰ ﻣﻦtiming ** ﯾﺠﺐ ﻋﻤﻞ اﺧﺘﺒﺎر
stop watch وإذا ﻟﻢ ﻧﺘﻤﻜﻦ ﯾﺘﻢ ﻋﻤﻞ اﻻﺧﺘﺒﺎر وﻗﯿﺎس اﻟﺰﻣﻦ ﺑـ. sheet زﻣﻦ ﻃﺒﺎﻋﺔ
45
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م [ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
:ﻃﺮﯾﻘﺔ اﻻﺧﺘﺒﺎر
. وﺗﻮﺻﯿﻠﮫ ﻋﻠﻰ اﻟﺠﮭﺎزCB ﻋﻠﻰ اﻟﺠﮭﺎز ﻛﻤﺎ ھﻮ ﻣﻮﺿﺢ ﺑﺎﻟﺮﺳﻢ ﻣﻊ ﻓﺼﻞ اﻟﻄﺮف اﻟﺜﺎﻧﻲCB ﺗﻮﺻﻞ أﻃﺮاف
وﻋﻤﻞ اﻻﺧﺘﺒﺎر ﻋﻠﻰ. close واﻟﻐﻠﻖopen [ TC1 ,TC2] ﻋﻠﻰ ﻣﻠﻔﺎﺗﮫ- ve ، ﻋﻠﻰ اﻟﺠﮭﺎز+ve DC ﺗﺤﻀﯿﺮ
. CC,CT2 ﺛﻢ ﻋﻤﻠﮫ ﻣﺮة أﺧﺮىCC,TC1
:ﺟﺪول اﻟﻨﺘﺎﺋﺞ
Operation PH - R PH - Y PH - B
Close 44.5 m.s 44.1 m.s 44.0 m.s
Open 78.7 m.s 79.2 m.s 79.2 m.s
Close - open 177.5 m.s 177.8 m.s 177.8 m.s
Operation PH - R PH - Y PH - B
Close 44.4 m.s 44.0 m.s 44.0 m.s
Open 76.1 m.s 76.5 m.s 76.5 m.s
Close - open 174.4 m.s 174.7 m.s 174.9 m.s
46
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ [
ﯾﺘﻢ إﺟﺮاء ھﺬا اﻻﺧﺘﺒﺎر ﻟﺘﺤﺪﯾﺪ ﻣﻘﺪار ﻣﻘﺎوﻣﺔ ﻧﻘﻄﺔ اﻟﺘﻮﺻﯿﻞ )اﻟﺘﻼﻣﺲ( داﺧﻞ CB
47
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ [
ﻃﺮﯾﻘﺔ اﻻﺧﺘﺒﺎر:
R = V/I ﯾﺘﻢ ﺣﻘﻦ ﺗﯿﺎر ﻣﻘﺪارة 100 Aوﻛﺬﻟﻚ ﯾﺘﻢ ﻗﯿﺎس اﻟﺠﮭﺪ وﻣﻨﮭﻢ ﯾﺘﻢ ﺣﺴﺎب ﻗﯿﻤﺔ )(R
ﻣﻠﺤﻮﻇﺔ :ﯾﺠﺐ أن ﺗﻜﻮن ﻗﯿﻤﺔ اﻟﻤﻘﺎوﻣﺔ أﻗﻞ ﻣﻦ 20 MΩﻋﻠﻰ CBﻓﻘﻂ وﺗﻜﻮن ﻋﻠﻰ اﻟﺪﺧﻞ واﻟﺨﺮج ﻣﻦ Bus bar
ﯾﺠﺐ أن ﺗﻜﻮن اﻗﻞ ﻣﻦ 40 MΩوذﻟﻚ ﻟﺪﺧﻮل اﻟﻜﻠﺴﺘﺮ )ﻧﻘﺎط اﻟﺘﻌﺸﯿﻖ ﺑﯿﻦ ﻃﺮﻓﻲ اﻟﺘﻼﻣﺲ ( ﻓﻲ اﻟﻘﯿﺎس.
ﺟﺪول اﻟﻨﺘﺎﺋﺞ:
.1وﺿﻊ اﻟﻤﻔﺘﺎح ﻋﻠﻰ وﺿﻊ offﺛﻢ اﻟﻀﻐﻂ ﻋﻠﻰ contactorاﻟﻐﻠﻖ ﻓﯿﺤﺪث closeﺛﻢ open
ﻣﺒﺎﺷﺮة وﯾﻜﻮن CBﻓﻲ وﺿﻊ OFFﻗﺒﻞ اﻻﺧﺘﺒﺎر
.2وﺿﻊ اﻟﻤﻔﺘﺎح ﻋﻠﻰ وﺿﻊ ONﺛﻢ اﻟﻀﻐﻂ ﻋﻠﻰ contactorاﻟﻔﺼﻞ ﻓﯿﺤﺪث اﻟﻔﺼﻞ ﻓﻘﻂ وﻻ ﯾﺤﺪث
ﻏﻠﻖ وﯾﻜﻮن CBﻓﻲ وﺿﻊ ONﻗﺒﻞ اﻻﺧﺘﺒﺎر
48
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م [ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
3. Megger test
:ﺟﺪول اﻟﻨﺘﺎﺋﺞ
Insulation test
Voltage applied = 5 k v
open, close
49
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ [
ﯾﺘﻢ إﺟﺮاء ھﺬا اﻻﺧﺘﺒﺎر اﺳﺎﺳًﺎ ﻋﻠﻰ اﻟﻜﺎﺑﻼت . Bus bar , Main CBوذﻟﻚ ﻟﻠﺘﺄﻛﺪ ﻣﻦ ﺳﻼﻣﺔ اﻟﻨﻈﺎم ﻋﻨﺪ زﯾﺎدة
اﻟﺠﮭﺪ ﻋﻠﯿﮭﺎ ﻷي ﺳﺒﺐ و ﺻﺎﻋﻘﺔ ﺟﻮﯾﺔ .
ﯾﺘﻢ ﺣﻘﻦ ﺟﮭﺪ ﻣﻘﺪاره 80 %ﻣﻦ ﺟﮭﺪ اﺧﺘﺒﺎر اﻟﻤﺼﻨﻊ .وﻓﻲ ﺣﺎﻟﺔ ﻋﺪم ﻣﻌﺮﻓﺔ ﺟﮭﺪ اﺧﺘﺒﺎر اﻟﻤﺼﻨﻊ ﯾﺘﻢ ﺣﻘﻦ ﺟﮭﺪ
ﻣﻘﺪاره (V rated/ph)*3+1
.
*3 +1 = 24KV
√
وﯾﻮﺟﺪ ﺛﻼث اﻧﻮاع اﺧﺘﺒﺎر high voltage test
ﻃﺮﯾﻘﺔ اﻟﺘﻮﺻﯿﻞ:
High voltage
C.B
Short
Output Control
50
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ [
أﺟﮭﺰة اﻻﺧﺘﺒﺎر:
51
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ [
ﻣﻠﺤﻮﻇﺔ:
-1ﺟﮭﺎز ﺣﻘﻦ ) (HVﻋﻠﻰ اﻟﻜﺎﺑﻼت ) (HVﯾﻘﻮم ﺑﺎﻟﺘﻐﯿﺮ ﻓﻰ ﻗﯿﻤﺔ اﻟﺘﺮدد frequencyﺣﺘﻰ ﯾﺼﻞ اﻟﻰ داﺋﺮة اﻟﺮﻧﯿﻦ
XL=XC ﻟﺬﻟﻚ ﯾﻜﻮن وﺣﺪة ﻣﻜﺜﻒ ﻓﻰ اﻟﺨﺮج ﻣﻦ اﻟﺠﮭﺎز
Z=R
-2وﯾﺘﻢ اﻟﺤﻘﻦ ﺑﮭﺬا اﻟﺘﺮدد:
Ph insulation
R – GND 1.1 T OHM
Y – GND 1.83 T OHM
B – GND 1.73 T OHM
ھﺬا اﻻﺧﺘﺒﺎر ﯾﺘﻢ ﻋﻤﻠﮫ ﺑﻌﺪ اﺧﺘﺒﺎر HVﻋﻠﻰ ) (GISوﯾﺴﺘﺨﺪم ھﺬا اﻻﺧﺘﺒﺎر ﻟﻠﺘﺄﻛﺪ ﻣﻦ ﺟﻮدة اﻟﺘﺼﻨﯿﻊ ﻟﻠﻌﻮازل
داﺧﻞ GISوﻋﺪم وﺟﻮد ﻓﻘﺎﻋﺎت داﺧﻞ اﻟﻌﻮازل
ﯾﺴﺘﺨﺪم ﺟﮭﺎز PDوﯾﻮﺻﻞ ﺑﺤﺴﺎس ) (sensorﻣﻊ ﺟﮭﺎز ) (high potواﻟﻘﯿﺎس ﻣﻨﮫ وﯾﺠﺐ ﻋﻨﺪ اﺳﺘﺨﺪام ھﺬا
اﻻﺧﺘﺒﺎر ﻋﺪم وﺟﻮد noiseﻓﻲ اﻟﻤﻜﺎن ﻣﺜﻞ اﻟﺠﻮال وﻏﯿﺮة .
اﻻﺧﺘﺒﺎر :
52
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م [ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
53
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م [ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
: ﻧﺘﺎﺋﺞ اﻻﺧﺘﺒﺎر
HV TEST
U TEST = 0.8 X 38 K V = 30 K V AC
(10KV) ( وذﻟﻚ ﻟﻠﺘﺄﻛﺪ ﻣﻦ ﻋﻮازل ﺳﻜﺎﻛﯿﻦ اﻷرﺿﻲ وھﻲ ﺗﺘﺤﻤﻞ10KV) ﯾﺘﻢ اﺳﺘﺨﺪام اﻻﺧﺘﺒﺎر اﻷول ﻋﻨﺪ ﺟﮭﺪ
. ﻣﻔﺘﻮﺣﺔshort وﻟﻜﻦ ﻧﻘﻄﺔ اﻟـclose ﻟﺬﻟﻚ ﺗﻜﻮن ﺟﻤﯿﻊ ﺳﻜﺎﻛﯿﻦ اﻷرﺿﻲ ﻓﻲ ﺣﺎﻟﺔ
All earthing switch (open) VT اﻻﺧﺘﺒﺎر اﻟﺜﺎﻧﻲ واﻟﺜﺎﻟﺚ ﻻﺧﺘﺒﺎر اﻟﻌﺰل ﻟﻠـ
All earthing open VT bus bar وﻋﻮازل اﻟـbus bar اﻻﺧﺘﺒﺎر اﻟﺮاﺑﻊ واﻟﺨﺎﻣﺲ واﻟﺴﺎدس ﻟﻠـ
Isolator open
54
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م [ ]اﺧﺘﺒﺎرات ﻣﻔﺎﺗﯿﺢ اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
Existing Link
open
cable
Link
open End End
Injection high
voltage
device
55
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.] م [ ]اﺧﺘﺒﺎرات ﻛﺎﺑﻼت اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
56
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.] م [ ]اﺧﺘﺒﺎرات ﻛﺎﺑﻼت اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
Pushing Pushing
Joint
R
Earthing box
57
www.facebook.com/Electrical.engineering.community2050
] م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ ]اﺧﺘﺒﺎرات ﻛﺎﺑﻼت اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ [
Remove
ﯾﺘﻢ ﻓﺘﺢ ﺟﻤﯿﻊ وﺻﻼت اﻟﺘﺄرﯾﺾ ﻓﻰ Earthing boxﻋﻠﻰ ﻃﻮل ﻣﺴﺎر اﻟﻜﺎﺑﻞ وذﻟﻚ ﻻﺧﺘﺒﺎر اﻟﻌﺰل اﻟﺨﺎرﺟﻰ ﻣﻊ
ﻣﺮاﻋﺎة ﻋﺪم ﺣﺪوث ﺟﮭﺪ ﻋﻠﻰ اﻟﻌﺎزل) (SVLوذﻟﻚ ﺑﺈزاﻟﺔ اﻟﻮﺻﻠﺔ اﻟﻤﻮﺟﻮدة ﺑﯿﻨﮫ وﺑﯿﻦ اﻟﺘﺠﻤﯿﻊ ﻟﻠﻜﺎﺑﻼت
ﯾﺘﻢ اﺳﺘﺨﺪام ﺳﯿﺎرة ) (HVاﻟﺘﻰ ﺗﻢ ﺷﺮﺣﮭﺎ ﻓﻲ اﻻﺧﺘﺒﺎر اﻟﺴﺎﺑﻖ ﻣﻊ ﻣﻼﺣﻈﺔ أن ھﺬا اﻻﺧﺘﺒﺎر ﯾﺤﺪث ﻋﻨﺪ داﺋﺮة اﻟﺮﻧﯿﻦ
) (resonanceوذﻟﻚ ﺑﺎﺳﺘﺨﺪام وﺣﺪة ﻣﻜﺜﻒ ﺗﻮﺿﻊ ﻓﻰ ﺧﺮج اﻟﺤﻘﻦ ﻣﻦ اﻟﺴﯿﺎرة وﻟﻜﻦ داﺧﻞ اﻟﺴﯿﺎرة ﻟﻤﻌﺎدﻟﺔ
XL = XCوذﻟﻚ ﯾﻜﻮن ﺑﺎﻟﺘﻐﯿﺮ ﻓﻰ اﻟﺠﮭﺪ ﺣﺘﻰ ﯾﺼﻞ اﻟﻰ ھﺬه اﻟﺤﺎﻟﮫ وﺑﻌﺪھﺎ ﯾﺒﺪأ اﻟﺤﻘﻦ ﻟﻤﺪة ﺳﺎﻋﺔ وﻛﺬﻟﻚ ﯾﺘﻢ
ﻋﻤﻞ shortﻋﻠﻰ) (SVLﻓﻰ junction boxﺣﺘﻰ ﻻﯾﺤﺪث ﻋﻠﯿﮫ ﺟﮭﺪ وﯾﺘﻢ ﻛﺴﺮه
Cable
Short
SVL
Time = 1 h
Status = 0k
58
www.facebook.com/Electrical.engineering.community2050
] م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ ]اﺧﺘﺒﺎرات ﻛﺎﺑﻼت اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ [
ﯾﺘﻢ ﻣﻦ ﺧﻼل ھﺬا اﻻﺧﺘﺒﺎر ﻣﻌﺮﻓﺔ ﻣﻘﺪار اﻟﻔﺎﻗﺪ ﻓﻰ sheathﺣﻮل اﻟﻜﺎﺑﻞ وھﻞ ھﻮ ﻓﻰ اﻟﺤﺪود اﻟﻤﺴﻤﻮح ﺑﮭﺎ أم ﻻ
وھﻰ ) (3%وإذا ﻛﺎﻧﺖ اﻟﻨﺴﺒﺔ ﻋﺎﻟﯿﺔ ﯾﺘﻢ اﻟﺘﻌﺪﯾﻞ ﻓﯿﮭﺎ ﻋﻦ ﻃﺮﯾﻖ ﺗﻐﯿﺮ اﻟﺘﻮﺻﯿﻼت ﺑﯿﻦ innerو outerﻓﻰ
junction boxﺑﺎﻟﺸﻜﻞ اﻟﺘﺎﻟﻰ:
ﻣﻦ
اﻟﻰ
ﻋﻠﻰ ﺟﻤﯿﻊ اﻟﻮﺻﻼت وﻋﻤﻞ اﻟﺘﺒﺎدﯾﻞ واﻟﺘﻮاﻓﯿﻖ ﻋﻠﯿﮭﺎ اﻟﻤﻮﺟﻮدة ﻋﻠﻰ ﻃﻮل ﻣﺴﺎر اﻟﻜﺎﺑﻞ
ﻃﺮﯾﻖ اﻻﺧﺘﺒﺎر:
ﻋﻠﻰ اﻟﻜﺎﺑﻼت وﻗﯿﺎس اﻟﺘﯿﺎرات ﻋﻠﻰ وﺻﻼت اﻟﺮﺑﻂ واﻟﻮﺻﻞ 100 A 3Фﯾﺘﻢ ﺣﻘﻦ ﺗﯿﺎر ﻣﻘﺪاره
SVL
وﯾﺘﻢ اﻷﺧﺬ ﻓﻲ اﻻﻋﺘﺒﺎر إذا ﻛﺎن ﯾﻮﺟﺪ ﻛﺎﺑﻞ آﺧﺮ ﻗﺮﯾﺐ ﻣﻨﮫ وﻋﻠﯿﮫ ﺟﮭﺪ ﺗﻜﻮن اﻟﻨﺴﺒﺔ أﻗﻞ ﻣﻦ ذﻟﻚ
ﻃﺮﯾﻘﺔ اﻟﺘﻮﺻﯿﻞ:
A short
59
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.] م [ ]اﺧﺘﺒﺎرات ﻛﺎﺑﻼت اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
وﻗﯿﺎس اﻟﺠﮭﺪ ﻋﻠﻰ اﻷﻃﺮاف ﻣﻊ وﺟﻮد ﻗﺼﺮ ﻋﻠﻰ ﻧﮭﺎﯾﺔ اﻟﻜﺎﺑﻞ ﻣﺜﻞ اﻻﺧﺘﺒﺎر اﻟﺴﺎﺑﻖ100 A ﯾﺘﻢ ﺣﻘﻦ ﺗﯿﺎر ﻣﻘﺪاره
Z= |Z |= |Z | Z+ = positive sequence
R : ﻃﺮﯾﻘﺔ اﻟﺘﻮﺻﯿﻞ
A
Injection S
current A V
T
: ﺟﺪول اﻟﻨﺘﺎﺋﺞ
60
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.] م [ ]اﺧﺘﺒﺎرات ﻛﺎﺑﻼت اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
VOLT(V) CURRENT(A)
R : ﻃﺮﯾﻘﺔ اﻟﺘﻮﺻﯿﻞ
S
A
T
A
V
Injection
current
: ﺟﺪول اﻟﻨﺘﺎﺋﺞ
61
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.] م [ ]اﺧﺘﺒﺎرات ﻛﺎﺑﻼت اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ
Example:
|Z0 | = 2.88
3. DC resistance (RDC):
R20 ċ = R t ċ * . ( )
ohm
current R
A V
Voltage
C P CP P
Yoka Gawa
: ﻣﻼﺣﻈﺎت
: transpose اﻟﺨﺎﺻﮫ ﺑﺎﻟﺘﺄرﯾﺾ ﻋﻨﺪ وﺻﻠﺔ اﻟﻜﺎﺑﻞ أوﻣﻊJunction box ** ﺷﻜﻞ
SVL
Inner
outer
Coaxial cable
R S T
62
www.facebook.com/Electrical.engineering.community2050
] م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ ]اﺧﺘﺒﺎرات ﻛﺎﺑﻼت اﻟﺠﮭﺪ اﻟﻌﺎﻟﻰ [
**ﻓﻰ اﻟﻮﺿﻊ اﻟﻄﺒﯿﻌﻰ ﻻﯾﻤﺮ ﺗﯿﺎر ﻓﻰ ھﺬه اﻟﻮﺻﻠﺔ وﻟﻜﻦ ﻋﻨﺪ ﺣﺪوث ﻛﺴﺮ ﻓﻰ اﻟﻌﺎزل ﯾﻤﺮ ﺗﯿﺎر ﻓﻰ ھﺬه اﻟﻮﺻﻠﺔ
وﯾﺼﻞ إﻟﻰ اﻻرض
**) (SVLﯾﻮﺿﻊ ھﺬا اﻟﻌﺎزل ﻟﺘﺤﺪﯾﺪ اﻟﻌﻄﻞ إذا ﺣﺪث ﻋﻠﻰ اﻟﻜﺎﺑﻞ.
واﻟﻌﻄﻞ ﯾﺤﺪث ﻧﺘﯿﺠﺔ وﺟﻮد ﻗﺼﺮﻋﻠﻰ اﻟﻜﺎﺑﻞ ﻣﻊ sheathوﺑﺎﻟﺘﺎﻟﻰ ﯾﻨﺘﻘﻞ اﻟﺠﮭﺪ اﻟﻰ sheathو ﺑﺎﻟﺘﺎﻟﻰ أﯾﻀﺎ
ﯾﺤﺪث ﻛﺴﺮ ﻋﻠﻰ ھﺬا اﻟﻌﺎزل.
وﯾﺤﺪد ھﺬا اﻟﻜﺴﺮ ﻣﻦ أى ﺟﮭﺔ )اﻟﺪاﺧﻞ أو اﻟﺨﺎرج ( ﻓﯿﺤﺪد اﻟﻜﺎﺑﻞ ﻣﻦ ﻗﺒﻞ اﻟﻮﺻﻠﺔ أم ﻣﻦ ﺑﻌﺪھﺎ .
وﻛﺬﻟﻚ إذا ﺣﺪﺛﺖ ﻧﻔﺲ اﻟﻤﺸﻜﻠﺔ ﻋﻠﻰ junctionﻓﯿﺤﺪد ﻣﻜﺎن اﻟﻌﻄﻞ ﻣﻦ ﺧﻼﻟﮭﺎ.
**ﻣﻮاﺻﻔﺎت)3.6KV&5KA(SVL
63
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م [ ]اﺧﺘﺒﺎر ﻣﻘﺎوﻣﺔ اﻻرﺿﻰ
64
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ ]اﺧﺘﺒﺎر ﻣﻘﺎوﻣﺔ اﻻرﺿﻰ [
Earthing resistance:
ﯾﺘﻢ اﺧﺘﺒﺎر ﻣﻘﺎوﻣﺔ ﺷﺒﻜﺔ اﻷرﺿﻰ ﻟﻠﺘﺄﻛﺪ ﻣﻦ ﺻﺤﺔ ﻋﻤﻠﯿﺔ اﻟﺘﺄرﯾﺾ وﯾﺘﻢ اﻻﺧﺘﺒﺎر ﻓﻰ أﻣﺎﻛﻦ ﻣﺘﻌﺪدة ﻓﻰ اﻟﺸﺒﻜﺔ
وﯾﻮﺿﻊ أﻣﺎﻛﻦ ﻟﮭﺬه اﻻﺧﺘﺒﺎرات ﻣﺜﻞ earth bit
اﻟﺤﺪ اﻻﻗﺼﻰ اﻟﻤﺴﻤﻮح ﺑﮫ ﻓﻰ ﺷﺮﻛﺔ اﻟﻜﮭﺮﺑﺎء اﻟﺴﻌﻮدﯾﺔ )(1Ωوﻟﻜﻦ ﻓﻰ أﻣﺎﻛﻦ أﺧﺮى ﯾﻜﻮن ﻣﺴﻤﻮح ﺑﺤﺪ أﻗﺼﻰ
) (5Ωﯾﺘﻢ ﺗﺤﺪﯾﺪ اﻷﻣﺎﻛﻦ اﻟﺘﻰ ﺗﻜﻮن ﻓﯿﮭﺎ اﻟﻤﻘﺎوﻣﺔ أى ﻣﻦ اﻟﺤﺪود اﻟﻤﺴﻤﻮح ﺑﮫ وﯾﺘﻢ اﻟﺘﺰوﯾﺪ ﺑﺄﻗﻄﺎب ﺗﺄرﯾﺾ) (earth
rodأو ﻣﻌﺎﻟﺠﺔ اﻟﺘﺮﺑﺔ ﻓﻰ ھﺬه اﻟﻤﻨﻄﻘﺔ ﻣﻦ ﻣﻠﺢ وﻣﺎء وﻓﺤﻢ
ﻃﺮﯾﻘﺔ اﻟﺘﻮﺻﯿﻞ:
Device rod
65
www.facebook.com/Electrical.engineering.community2050
[ ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ.]م [ ]اﺧﺘﺒﺎر ﻣﻘﺎوﻣﺔ اﻻرﺿﻰ
: ﺷﻜﻞ اﻟﺠﮭﺎز
66
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ ]اﺧﺘﺒﺎر ﻣﻘﺎوﻣﺔ اﻻرﺿﻰ [
ﻃﺮﯾﻘﺔ اﻻﺧﺘﺒﺎر:
ﺗﻮﺻﯿﻞ ) (cﻓﻰ device rodﻋﻠﻰ ﺑﻌﺪ 15 mﻓﻰ ﻧﻔﺲ اﻹﺗﺠﺎه اﻟﺴﺎﺑﻖ ﻓﻰ ﺟﮭﺔ واﺣﺪة ﻣﻦ اﻟﺠﮭﺎز وھﺬا
ھﻮ اﻟﻤﺴﺎﻋﺪ
اﻟﻀﻐﻂ ﻋﻠﻰ press onﻣﻊ اﺧﺘﯿﺎر selectorﻋﻠﻰ BATTﯾﺘﺤﺮك اﻟﻤﺆﺷﺮ اﻟﻰ ﻣﻨﻄﻘﺔ اﻟﺒﻄﺎرﯾﺔ ﻓﻲ أﻗﺼﻰ
اﻟﯿﺴﺎر
اﻟﻀﻐﻂ ﻋﻠﻰ press onﻣﻊ اﺧﺘﯿﺎر selectorﻋﻠﻰ Pﯾﺘﺤﺮك اﻟﻤﺆﺷﺮ اﻟﻰ P,C Chockﻓﻰ ﺣﺎﻟﺔ ﻋﺪم
اﻟﺘﺤﺮك ﯾﻜﻮن ﺗﻮﺻﯿﻞ ) rod (pﻏﯿﺮ ﺻﺤﯿﺢ
-4ﯾﺘﻢ اﻟﻀﻐﻂ ﻋﻠﻰ ) (press onﻓﯿﺘﻢ ﻗﺮاءة اﻟﺠﮭﺪ وﯾﺠﺐ ﺗﺤﺪﯾﺪ . (X1Ω , X10Ω , X100Ω) Rangeﺛﻢ
اﻟﺘﻐﯿﺮ ﻓﻲ اﻟﻤﺆﺷﺮ اﻷﯾﻤﻦ ﺣﺘﻰ ﯾﻌﻮد اﻟﺠﮭﺪ اﻟﻰ اﻟﺼﻔﺮ ﺛﻢ أﺧﺬ ھﺬه اﻟﻘﺮاءة وﺿﺮﺑﮭﺎ ﻓﻲ scaleاﻟﻤﺤﺪد ﺳﺎﺑﻘًﺎ
وإذا ﻟﻢ ﯾﻨﺰل اﻟﺠﮭﺪ ﯾﺘﻢ اﺧﺘﯿﺎر scaleأﻋﻠﻰ ﺛﻢ اﻟﺘﻐﯿﺮ ﻣﺮة أﺧﺮى .
ﺗﻜﻮن اﻟﻤﻘﺎوﻣﺔ اﻟﻤﻘﺮوءة ھﺬه ﺑــ ). (Ω
67
www.facebook.com/Electrical.engineering.community2050
]م .ﻣﺤﻤﺪ ﻛﻤﺎل اﻟﺠﻮﯾﻨﻰ[ ]ﺟﮭﺎز ﺗﻔﺮﯾﻊ ﺷﺤﻨﺔ اﻟﺒﻄﺎرﯾﺎت[
ﯾﺴﺘﺨﺪم ھﺬا اﻟﺠﮭﺎز ﻓﻰ ﺗﻔﺮﯾﻎ ﺷﺤﻨﺔ اﻟﺒﻄﺎرﯾﺎت ﻟﻌﻤﻞ ﺗﻨﺸﯿﻂ ﻟﮭﺎ .
ﻃﺮﯾﻘﺔ اﻟﺘﻮﺻﯿﻞ:
68