You are on page 1of 2

Data sheet for three-phase squirrel cage motor

SIMOTICS HV M
Article number 1RN6502-6HJ30-Z
Options A65+G50+K09+K97+L54+M13+M52

Client order no.: Item no.:


Order no.: Consignment no.:
Offer no.: Project:
Remarks:

General data Environmental conditions


Standards/specifications IEC 60034 Coolant temperature 25 °C
Usage area Safe area Ambient temperature -5 °C … 40 °C
Type of explosion protection None Installation altitude 1.000 m

Electrical data Mechanical data


Rated power P N 2.500 kW Type of construction IM B3
Rated voltage U N 4,16 kV Degree of protection IP 55
Voltage fluctuations +- 5 % (IEC 60034-1, range A) Shaft height 500
Frequency f N 60 Hz Method of cooling IC81W
Frequency fluctuations +- 2% (IEC 60034-1, range A) Cooling rate water # 276 l/min
Stator circuit Star Type of insulation MICALASTIC - VPI
Rated current I N 418.9 A Rotor winding material Copper
Number of poles 6 Bearing design Rolling contact bearing
Rated speed n N 1188 1/min Bearing DE NU1034 M1 / 6034 C3
Rated torque M N 20097 Nm Bearing NDE NU 1028
Partial load P / P N 5/4 4/4 3/4 2/4 Direction of rotation Clockwise (view on DE)
Efficiency η % 95.5 96.3 96.9 97.0 Sound pressure level L pA (1m), Tolerance +3dB
Power factor cos φ 0.85 0.86 0.85 0.80 - no-load 78 dB(A)
DOL operation - load 82 dB(A)
Mode of operation continuous operation (S1) Measuring surface level L s 18 dB(A)
Thermal class 155 (F), utilized to thermal class 130 (B) Coating (paint finish) Standard coating
Starting / rated current I A /I N 4.5 Color, paint shade RAL 7030
Tolerance I A /I N + 20% (IEC 60034) Total weight # 6350 kg
Starting / rated torque M A / M N 0.65 Rotor weight 1500 kg
Breakdown/rated torque M K / M N 2.0 Dynamic foundation load at 2- pole terminal short circuit
Moment of inertia J 61 kg.m² downward / upward 127 kN / -69 kN
Save stall time hot / cold 12.0 s / 16.0 s Type of terminal box
Perm. no. of consecutive starts, cold/warm * 3/2 Type of terminal box 1XB8751
* at max.external moment of inertia 1060 kg.m² Terminal box, Star connection without
* U /U N ≥ 90 %, M Last ~ n ², M Last /M N ≤ 90.0 % Factory location
Factory location Germany

# This values apply to catalogue design with standard environmental conditions.

Offer no. , Item no. Page 1 of 2 Version: 2018.10


Technical data are subject to change\! There may be discrepancies between calculated and rating plate values. Generiert: 30.11.2018 16:08:15
Special design

A65 6 embedded resistance thermometers Pt 100 without lightning arresters for 3- or 4-wire connection from terminals
G50 Shock pulse measurement (SPM), measuring nipple at D.E. and N.D.E.
K09 Terminal box on right-hand side, view from D.E.
K97 Clockwise rotation
L54 Terminal box 1XB8 751, 6 terminals with cable glands for 2 cable entries for connection to power supply
M13 Anti-condensation heating 220-240V (min. 200V, max. 264V)
M52 Separate auxiliary terminal box for anti-condensation heating

Offer no. , Item no. Page 2 of 2 Version: 2018.10


Technical data are subject to change\! There may be discrepancies between calculated and rating plate values. Generiert: 30.11.2018 16:08:15