Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 01/01/2022
E-Mail:
Specifier's comments:
1 Input data
Anchor type and diameter: HST3-R M16 hef2
Effective embedment depth: hef,act = 85 mm, hnom = 98 mm
Material: A4
Evaluation Service Report: ER-578
Issued I Valid: 2/21/2020 | 2/28/2021
Proof: Design method ACI 318-14 / Mech.
Stand-off installation: eb = 0 mm (no stand-off); t = 25 mm
Anchor plate: lx x ly x t = 400 mm x 400 mm x 25 mm; (Recommended plate thickness: not calculated
Profile: L profile, L 100 x 10; (L x W x T) = 100 mm x 100 mm x 10 mm
Base material: uncracked concrete, , fc' = 2.756 psi; h = 1.000 mm
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id Profis Anchor 2.9.4
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 01/01/2022
E-Mail:
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 43,750 52,050 85 OK
Pullout Strength* N/A N/A N/A N/A
Concrete Breakout Strength** 350,000 81,066 432 not recommended
* anchor having the highest loading **anchor group (anchors in tension)
Variables
Ase,N [mm2] futa [N/mm2]
95 730,00
Calculations
Nsa [kN]
69,400
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
69,400 0,750 52,050 43,750
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id Profis Anchor 2.9.4
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 01/01/2022
E-Mail:
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-14 Eq. (17.4.2.1b)
f Ncbg ³ Nua ACI 318-14 Table 17.3.1.1
ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
ANc0 = 9 h2ef ACI 318-14 Eq. (17.4.2.1c)
( )
1
y ec,N = 2 e'N £ 1,0 ACI 318-14 Eq. (17.4.2.4)
1+
3 hef
y ed,N = 0,7 + 0,3 (
ca,min
1,5hef £ )
1,0 ACI 318-14 Eq. (17.4.2.5b)
y cp,N = MAX (
ca,min 1,5hef
cac
,
cac )
£ 1,0 ACI 318-14 Eq. (17.4.2.7b)
1,5
Nb = kc l a √fc hef
'
ACI 318-14 Eq. (17.4.2.2a)
Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
85 0 0 110 1,000
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
247.500 65.025 1,000 1,000 0,959 0,996 34,308
Results
Ncbg [kN] f concrete f Ncbg [kN] Nua [kN]
124,717 0,650 81,066 350,000
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id Profis Anchor 2.9.4
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 01/01/2022
E-Mail:
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 3,536 39,780 9 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 28,284 174,604 17 OK
Concrete edge failure in direction x+** 28,284 22,637 125 not recommended
* anchor having the highest loading **anchor group (relevant anchors)
Variables
Ase,V [mm2] futa [N/mm2]
95 730,00
Calculations
Vsa [kN]
61,200
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
61,200 0,650 39,780 3,536
( )
1
y ec,N = 2 e'N £ 1,0 ACI 318-14 Eq. (17.4.2.4)
1+
3 hef
y ed,N = 0,7 + 0,3 (
ca,min
1,5hef £ )
1,0 ACI 318-14 Eq. (17.4.2.5b)
y cp,N = MAX (
ca,min 1,5hef
cac
,
cac )
£ 1,0 ACI 318-14 Eq. (17.4.2.7b)
1,5
Nb = kc l a √fc hef
'
ACI 318-14 Eq. (17.4.2.2a)
Variables
kcp hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm]
2 85 0 0 110
Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
247.500 65.025 1,000 1,000 0,959 0,996 34,308
Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
249,434 0,700 174,604 28,284
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id Profis Anchor 2.9.4
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 01/01/2022
E-Mail:
Vcbg = (AA ) y
Vc
Vc0
ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-14 Eq. (17.5.2.1b)
f Vcbg ³ Vua ACI 318-14 Table 17.3.1.1
AVc see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b)
AVc0 = 4,5 c2a1 ACI 318-14 Eq. (17.5.2.1c)
( )
1
y ec,V = 2e'v £ 1,0 ACI 318-14 Eq. (17.5.2.5)
1+
3ca1
y ed,V = 0,7 + 0,3 ( ca2
1,5ca1 £
1,0) ACI 318-14 Eq. (17.5.2.6b)
y h,V = √
1,5ca1
ha ³
1,0 ACI 318-14 Eq. (17.5.2.8)
(( ) )
0,2
l 1,5
Vb = 7 e √da l a √f'c ca1 ACI 318-14 Eq. (17.5.2.2a)
da
Variables
ca1 [mm] ca2 [mm] ecV [mm] y c,V ha [mm]
130 110 2 1,400 1.000
Calculations
AVc [mm2] AVc0 [mm2] y ec,V y ed,V y h,V Vb [kN]
97.500 76.050 0,988 0,869 1,000 20,978
Results
Vcbg [kN] f concrete f Vcbg [kN] Vua [kN]
32,338 0,700 22,637 28,284
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid anchor plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
• Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference
ACI 318-14, Section 17.8.1.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id Profis Anchor 2.9.4
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 01/01/2022
E-Mail:
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HST3-R M16 hef2
Profile: L profile, L 100 x 10; (L x W x T) = 100 mm x 100 mm x 10 mm Maximum installation torque: 0,110 kNm
Hole diameter in the fixture: df = 18 mm Hole diameter in the base material: 16 mm
Plate thickness (input): 25 mm Hole depth in the base material: 108 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 160 mm
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions
for use is required.
200 200
60
3 7 4
200
140
6 x
10
5
120
200
1
10
8 2
60
80 120 120 80
Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 -120 -130 130 370 120 380 5 120 -10 370 130 240 260
2 120 -140 370 130 110 390 6 -120 0 130 370 250 250
3 -120 140 130 370 390 110 7 0 140 250 250 390 110
4 120 140 370 130 390 110 8 0 -140 250 250 110 390
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.id Profis Anchor 2.9.4
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 01/01/2022
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
HST3 (-R) subject to:
Anchor size M8 M10 M12 M16 M20 M24
Hammer drilling*
DD-30W, DD-EC1
Setting tool*
Setting tool HS-SC -
- TE-CD, TE-YD