MOV Controls
Objectives
• Describe the operation and standard electrical
circuits for both torque and limit controlled valves.
• Describe the electrical and mechanical components
that make up typical motor actuator controls.
• Determine proper motor actuator control switch set
points.

College of Engineering
Limitorque Electrical Controls

College of Engineering
Typical Wiring Diagram

College of Engineering
Components
• Power Supply – supply the energy required to
operate the MOV
• Motor – converts electrical power to mechanical
power. Reversing any two leads will reverse the
direction of motor rotation.
• Overload Heater Coils (Thermal Overload Relays)
– protect the motor in the event of excessive motor
current.
• Reversing Starter – two separate functions
– Interchange power leads which change the direction
of motor rotation
– Provide mechanical and electrical interlocks that
prevent the contacts for both directions being closed
at the same time

College of Engineering
Components - Continued
• Control Transformer – reduce the control voltage
to a lower and safer level
• Stop Pushbutton – breaks the control circuit,
causing starter dropout and halting actuator function
• Open and Close Pushbuttons – initiate operation
of the control circuit, which results in energizing the
actuator motor
• Seal-in Contacts – allows the pushbuttons to be
released without having the actuator stop
• Remote/Local Switch – determines the location of
control for the actuator, either local or remote

College of Engineering
Components - Continued
• Overload Contacts – protect the circuit from an
overload condition by interrupting the control circuit
• Electrical Interlock Contacts – part of the
contactor auxiliary contacts, prevent both the open
and close contactors from operating at the same
time
• Lights – provide approximate valve position
information to plant operators

College of Engineering
Geared Limit Switch
• The geared limit switch counts the rotation of the
drive sleeve or worm shaft in order to keep track of
valve position.
– Shut off power to the actuator motor at the proper
stroke position
– Turn indicating lights on and off and the proper stroke
position
– Provide electrical interlocks and bypasses as required

College of Engineering
Standard Limit Switch

College of Engineering
Four-Train Limit Switch

College of Engineering
Limit Switch Control Functions

(View From Bottom


of the Limit Switch)

College of Engineering
Limit Switch Setting
• Each rotor is set separately for a particular valve
stroke position
• The valve must be moved to the desired stroke
position and then the limit switch rotor set.

College of Engineering
End View of Rotors

College of Engineering
Limit Switch Conditions

(View From Bottom


of the Limit Switch)

College of Engineering
Torque Switch
The torque switch has two possible functions
• On torque controlled valves, it is used to ensure that
the valve has sufficient torque applied to the valve
stem to guarantee seating
• On limit controlled valves, it is used to ensure that
the actuator and valve are protected from possible
excessive torque

College of Engineering
Leaf Type Torque Switch

College of Engineering
Knee Type Torque Switch
(Old Style)

College of Engineering
Knee Type Torque Switch
(New Style)

College of Engineering
Actuator Motors
• High rated starting torque
– Sized to provide the the torque required by the valve
– Delivers this torque over a relative short time period
• Short duty cycle
– For ac – 15 minutes
– For dc – 5 minutes
• Totally enclosed non-ventilated (TENV)

College of Engineering
Typical ac Motors
• Three phase, 230/460 VAC, squirrel cage induction
motors
• Factory lubricated sealed bearings
• Three insulation classes
– Class B – 125°C, mild environment
– Class RH – 175°C, harsh environment
– Class LR – 250°C, very high temperature, harsh
environments
• Three speeds – 900, 1800, 3600 rpm

College of Engineering
Typical ac Motor
Performance
Curve

College of Engineering
Typical dc Motors
• 125/250V dc compound-wound motors
• A compound-wound motor is a compromise
between
– Shunt-wound motor – good speed regulation
– Series-wound motor – higher starting torque, but poor
speed regulation
• Motor speed is inversely related to torque. Speed
may be 2300 rpm at no load and 1550 at 20% load.

College of Engineering
Typical dc Motor
Performance
Curve

College of Engineering
Rotork Electrical Controls

College of Engineering
Rotork Components
• Motor – Three phase, 220 VAC, squirrel cage
induction motors. A winding thermostat is included
in the “A” range and “NA-4” actuators for
overload protection.
– Class B – 125°C
– Class F – 155°C
– Class H – 175°C
• Starter – Houses mechanically and electrically
interlocked reversing contactors
– Two normally open auxiliary contacts
– Opening and closing coils
– Fused control transformer.

College of Engineering
Rotork Components - Continued
• Integral Controls – open/stop/close pushbutton
with lockable local/off/remote selector switch.
• Position Indication – mechanical three-position
indicator shows open, intermediate, and closed
conditions.
• Torque and Limit Switches – open and close
torque or position limit switches plus two auxiliary
limit switches at each end of travel.

College of Engineering
Syncropak Electrical Schematic

College of Engineering
Front View of Switch Mechanism
(Nuclear)

College of Engineering
Switch Mechanism (Nuclear)

College of Engineering
Cross Section of Limit Switch
Assembly

College of Engineering
Typical Limit Switch Drive
Arrangements

College of Engineering
Switch Terminal Connections
(Nuclear)

College of Engineering