You are on page 1of 72

This document is the exclusive property of GE Grid Solutions and shall not be used, copied or communicated to third parties

without prior authorization

SSH TR
00 ORIGINAL ISSUE FA
30 NOV 2021 30 NOV 2021
DRAWN BY : CHECKED BY :
NO REVISION STATUS
DATE : DATE :

OWNER
PT PLN ( PERSERO )
UNIT INDUK PEMBANGUNAN SUMATERA BAGIAN SELATAN
Jl. Residen A. Rozak No. 2180, Sekojo Palembang 30118

CONTRACTOR
KONSORSIUM WIJATI-HASTA
Jl. Let Jend S Parman No. 52 Semarang 50232
Telp. 024 8441546 ( Hunting 7 Lines ) Fax. 024 8315360

PROJECT

PEMBANGUNAN EXTENSION IBT 3 GITET 500/275 KV MUARA ENIM ( PAKET ENIM 3 )

CONTRACT No : 0015.PJ/DAN.01.03/UIP SUMBAGSEL/2020, DATE : 16 DESEMBER 2020

DRAWING TITTLE

PROPOSAL PROTECTION RELAY SETTING


GITET 500 KV MUARA ENIM

SHEET : DESIGN BY DRAWN DESIGNED CHECKED APPROVED


30 NOV 2021 30 NOV 2021 30 NOV 2021 30 NOV 2021
1
SCALE :

NA SSH SSH TR AN

PAPER SIZE : DRAWING NO : REVISION NO :

A4 0015PJ-03ME-E/L-02-S7-206 00
CALCULATION NOTE 500kV MUARA ENIM S/S

1. 500/275/66kV 500MVA 3 BANKS POWER TRANSFORMER


1.1 DIFFERENTIAL TRANSFORMER PROTECTION MAIN 1
1.1.1 GENERAL DATA
1.1.1.1 Relay's Characteristics
Manufacturer : General Electric

Type : MICOM P643

Product Code : P64391TF6S0910M

Rated Current : in  1A

1.1.1.2 Enabling/disabling Differential Protection


No/Yes DIFF Enabled_USER= Yes
1.1.1.3 Transformer's Characteristic

Transformer Coupling :
YNa0  d1
HV side Voltage MAIN Vnom_primhvside  500kV

LV side Voltage MAIN Vnom_primlvside  275kV


TV side Voltage MAIN Vnom_primtvside  66kV

Z%  13.5% (Assumption)
3
Reference power :DIFF Sref  500  10 kV A
Rotary Field :MAIN Anti  Clockwise
Tap Changer position (no load)/increments MAIN tp  19 ti  0.8%
Higher Tap : Tap1  10.5%
(Assumption)
Lower Tap : TapN  15%

Inrush current/rated current


(as per manual 8 to 30 times of full load current): Kinr  10

1.1.1.4 Primary nominal currents and ratio of the main current transformers
Primary current Primary HV side 500kV : 600 / 1A Inom_CTprimhvside  600A

Primary LV side 275kV : 2000 / 1A Inom_CTprimlvside  1200A

Tertiary LV side 66kV : 2000 / 1A Inom_CTprimtvside  2000A

Rev. 00 IBT 3 1.1/1


CALCULATION NOTE 500kV MUARA ENIM S/S

Ratios Primary HV side : CThv  600

Primary LV side : CTlv  1200

Primary TV side : CTtv  2000

1.1.1.5 Errors
1.1.1.5.1 Misc Errors
Excitation Current Error : IExcERR  3%

Excitation current error are ignore, will be small compare IExcErrHi  0%


with other error at high current:

Rlyerr  5%
Relay Error
1.1.1.5.2 Current Errors
CTerrsmall  6%
CT is well out of saturation error based on CT test report,
(assumed)
CTerrlarge  6%
CT error at high current based on CT test report, (assumed)
1.1.1.5.3 Voltage Errors
Assumed VLTCerr  0.22%

1.1.2 NOMINAL RATING VALUES CALCULATION


HV mid tap voltage:
HVmid  Vnomhvside 1 
 Tap1  TapN
 2  HVmid  488.75 kV

HV full load current Sref


at mid tap voltage: Irefhv 
3  HVmid Irefhv  590.64 A

in secondary value:
Irefhv
Irefhvsec 
CT hv Irefhvsec  0.984 A

HV full load current on


Sref
Tap1  0.105 Ireftap1 

3  Vnomhvside 1  Tap1  Ireftap1  522.49 A

in secondary value:
Ireftap1
Ireftap1sec 
CThv
Ireftap1sec  0.87 A

Rev. 00 IBT 3 1.1/2


CALCULATION NOTE 500kV MUARA ENIM S/S

HV full load current on


TapN  0.15 Sref
IreftapN 

3  Vnomhvside 1  TapN  IreftapN  679.24 A

in secondary value
IreftapN
IreftapNsec  IreftapNsec  1.132 A
CT hv

LV full load current: Sref 3


Ireflv  Ireflv  1.05  10 A
3  Vnomlvside

Ireflv
Ireflvsec  Ireflvsec  0.87 A
CT lv

1.1.3 DIFFERENTIAL PROTECTION SETTING


1.1.3.1 Amplitude Matching Factors of HV and LV Windings
The matching factors must comply with the following conditions:

a. The matching factors must always be < 3

b. The ratio of the highest to the lower matching factors must be <5

c. The value of the lowest matching factors must be < 0.7


Calculated HV matching factor: Inomhv
Kamhv  Kamhv  1.016
Irefhv

Calculated LV matching factor:

Inomlv
Kamlv  Kamlv  1.143
Ireflv

1.1.3.2 Vector group matching


Vector group matching a-b: 0/11 DIFF Vector_grpendab  0
Vector group matching a-c: 0/11 DIFF Vector_grpendac  0
1.1.3.3 Zero-Sequence filtering
Zero sequence filtering of HV winding (a) : No / Yes DIFF Zeroseq . filt.a_en=Yes
Zero sequence filtering of LV winding (a) : No / Yes DIFF Zeroseq . filt.b_en=Yes

Rev. 00 IBT 3 1.1/3


CALCULATION NOTE 500kV MUARA ENIM S/S

1.1.3.4 Tripping Characteristics


1.1.3.4.1 Nominal rating HV/LV unbalanced current checking in regard with the Tap
Changer
HV corrected current on tap 1:
Ishv1  Kamhv Ireftap1sec Ishv1  0.885 A

HV corrected current on tap N:


IshvN  Kamlv IreftapNsec IshvN  1.294 A

LV corrected current: Islv  Kamlv Ireflvsec Islv  1 A

Id
at tap 1 Id1  Ishv1  Islv Id1  0.115 A

Id
at tap N IdN  IshvN  Islv IdN  0.294 A

Restraining current on tap 1:


IR1 
Ishv1  Islv IR1  0.942 A
2

Restraining current on tap N:


IRN 
IshvN  Islv IRN  1.147 A
2

Slope 1 Calculation:
ErrHi  1  IExcERR  Rlyerr  CT errsmall ErrHi  1.14

ErrLo 
1  CTerrsmall
1  VLTCerr ErrLo  0.938

m1 
ErrHi  ErrLo  0.194
0.5  ErrHi  ErrLo 

Slope 2 Calculation:

ErrHi2  1  IExcErrHi  Rlyerr  CTerrlarge  1.11

ErrLo2 
1  CTerrlarge  0.938
1  VLTCerr
m2 
ErrHi2  ErrLo2  0.168
0.5 ErrHi2  Err Lo2

Rev. 00 IBT 3 1.1/4


CALCULATION NOTE 500kV MUARA ENIM S/S

Idiff1  0.2 pu
Basic threshold value Idiff>
Setting defining the second knee of tripping characteristic IRm2  1 pu

Gradient of the tripping characteristic of differential protection


in the range 0.5Idiff1  IR  IRm2
m1  0.19
Recommendation m1 set:
m1set  0.3

Gradient of the tripping characteristic of the differential protection


in the range IR  IRm2
m2  0.168
Recommendation m2 set
m2set  0.8

Operating current at tap 1: Iop1  m1set IR1  0.283 A

Operating current at tap N:


   
Iop2  m1set IRm2a  m2set IRN  IRm2a   0.418 A

MICOM P643 tripping characteristics:

1
0.9
0.8
Differential Current

0.7
0.6
y 0.5
0.4
0.3
0.2
0.1
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
x

Restraint Current
We can check that there is enough stability with Idiff1  0.2 m1set  0.3 m2set  0.8

Rev. 00 IBT 3 1.1/5


CALCULATION NOTE 500kV MUARA ENIM S/S

1.1.3.5 Rapid (high set) differential protection


function
1.1.3.5.1 Inrush stabilization (harmonic restraint)
The fundamental wave I(fo) and second harmonic components I(2*fo) of the differential current
are determined. if the ratio I(2*fo)/I(fo) exceedss a specific adjustable value in at least one
measuring system, tripping is blocked optionally (Without/Phase Selective/Not Phase Selective).

Operating mode of the inrush stabilization function


Without / Phase-Selective / Not Phase-Selective DIFF Op.mode_harm=Phase-Selective
Operate value of the inrush stabilization function (from a harmonic analysis of a typical
magnetizing-inrush current)
10 / 50 % DIFF RushI2fo_Ifo  20%

6.1.3.5.2 Overfluxing Restraint


The differential current is filtered and fundamental I(fo) and fifth harmonic components I(5*fo)
are determined. if the ratio I(5*fo)/I(fo) exceeds the set value over I(5fo)/I(fo) in at least one
measuring system, and if the restraining current is smaller than 4. Iref, then tripping is blocked
selectively
Operating mode of the overfluxing restraint function: No / Yes DIFF Overflux . bl. en: Yes
Operate value of the overfluxing restraint function : 10 / 80 % DIFF OverI5fo_Ifo  35%
6.1.3.5.3 Adjustable High Set Threshold
Idiff>>
Maximum primary current: Ifo  IreftapN

Maximum fault current:


IreftapN
Ir  Ir  5031.37 A
Z%

In secondary value: Ir
ir  ir  8.386 A
CT hv

Correct value for deactivation of harmonic restraint and overfluxing ir Kamhv  8.519 A
restraint functions (refered to relevant reference current):
Chosen setting: 5 / 30 Iref DIFF Idiff2  10 pu

Rev. 00 IBT 3 1.1/6


CALCULATION NOTE 500kV MUARA ENIM S/S

1.2 RESTRICTED EARTH FAULT IBT 500/275/66 kV PROTECTION MAIN 1


1.2.1 GENERAL DATA
1. 2.1.1 Relay's Characteristics
Manufacturer : General Electric

Type : MICOM P643

Product Code : P64391TF6S0910M

Rated Current : in  1A

1.2.1.2 Enabling/disabling REF Protection


No/YEs REF Enabled_USER= Yes

1.2.1.3 Transformer's Characteristic

Transformer Coupling : YNa0  d1


Vnom_primhvside  500kV
HV side Voltage MAIN
Vnom_primlvside  275kV
LV side Voltage MAIN
Vnom_primtvside  66kV
TV side Voltage MAIN

Z%  13.5% (Assumption)
3
Reference power :DIFF Sref  500  10 kV A
Rotary Field :MAIN Anti  Clockwise
Tap Changer position (no load)/increments MAIN tp  19 ti  0.8%
Higher Tap : Tap1  10.5%
(Assumption)
Lower Tap : TapN  15%

Inrush current/rated current


(as per manual 8 to 30 times of full load current): Kinr  10

1.2.1.4 Primary nominal Diff. currents and ratio of the main current transformers
Primary current Primary HV side 500kV : 600 / 1A Inom_CTprimrhvside  600A

Primary LV side 275kV : 1200 / 1A Inom_CTprimrlvside  1200A

Tertiary LV side 66 kV : 2000 / 1A Inom_CTprimrtvside  2000A

Rev. 00 IBT 3 1.2/1


CALCULATION NOTE 500kV MUARA ENIM S/S

1.2.1.5 Primary nominal neutral currents and ratio of the main current transformers
Primary current Primary REF HV side 500kV : 600/1A Inom_CTprimhvside  600A

Primary REF LV side 275kV : 600/1A Inom_CTprimlvside  600A

Ratios NCT NCT HV side (Common) : CThv  600

NCT LV side (Common) : CTlv  600

NCT Star Connection side : CTtv  600

1.2.1.6 Errors
1.2.1.6.1 Misc Errors
Excitation Current Error : IExcERR  3%

Excitation current error are ignore, will be small compare IExcErrHi  0%


with other error at high current:

Rlyerr  5%
Relay Error
1.2.1.6.2 Current Errors
CTerrsmall  6%
CT is well out of saturation error based on CT test report,
(assumed)
CTerrlarge  6%
CT error at high current based on CT test report, (assumed)
1.2.1.6.3 Voltage Errors
Assumed VLTCerr  0.22%

1.2.2 NOMINAL RATING VALUES CALCULATION


HV mid tap voltage:
HVmid  Vnomhvside 1 
 Tap1  TapN
 2  HVmid  488.75 kV

HV full load current Sref


at mid tap voltage: Irefhv 
3  HVmid Irefhv  590.64 A

in secondary value:
Irefhv
Irefhvsec 
CT hv Irefhvsec  0.984 A

HV full load current on


Sref
Tap1  0.105 Ireftap1 

3  Vnomhvside 1  Tap1  Ireftap1  522.49 A

Rev. 00 IBT 3 1.2/2


CALCULATION NOTE 500kV MUARA ENIM S/S

in secondary value:
Ireftap1
Ireftap1sec 
CThv Ireftap1sec  0.87 A
HV full load current on
TapN  0.15 Sref
IreftapN 
 
3  Vnomhvside 1  TapN IreftapN  679.24 A

in secondary value
IreftapN
IreftapNsec  IreftapNsec  1.132 A
CT hv

LV full load current: Sref 3


Ireflv  Ireflv  1.05  10 A
3  Vnomlvside

Ireflv
Ireflvsec  Ireflvsec  1.75 A
CT lv

1.2.3 REF PROTECTION SETTING


1.2.3.1 Amplitude Matching Factors of HV and LV Windings
Inomhv  Inom_CTprimhvside

Inomlv  Inom_CTprimlvside

Calculated HV matching factor: Inomhv


Kamhv  Kamhv  1.016
Irefhv

Calculated LV matching factor:

Inomlv
Kamlv  Kamlv  0.572
Ireflv

1.2.3.2 Vector group matching


Vector group matching a-b: 0/11 DIFF Vector_grpendab  0
Vector group matching a-c: 0/11 DIFF Vector_grpendac  0
1.2.3.3 Zero-Sequence filtering

Rev. 00 IBT 3 1.2/3


CALCULATION NOTE 500kV MUARA ENIM S/S

Zero sequence filtering of HV winding (a) : No / Yes DIFF Zeroseq . filt.a_en=Yes


Zero sequence filtering of LV winding (a) : No / Yes DIFF Zeroseq . filt.b_en=Yes

1.2.3.4 Tripping REF 1 Characteristics


Slope 1 Calculation:
ErrHi  1  IExcERR  Rlyerr  CT errsmall ErrHi  1.14

ErrLo 
1  CTerrsmall ErrLo  0.938
1  VLTCerr
m1hv 
ErrHi  ErrLo  0.194
0.5  ErrHi  ErrLo  m1hvset  0%

Slope 2 Calculation:
ErrHi2  1  IExcErrHi  Rlyerr  CTerrlarge  1.11

ErrLo2 
1  CTerrlarge  0.938
1  VLTCerr
m2hv 
ErrHi2  ErrLo2  0.168 m2hvset  150%
0.5 ErrHi2  Err Lo2

Ihvs1 is set according to nominal current winding affected by impedance Ihvs2


winding and
is set to the rated current of the transformer
Ihvs1  Z% Irefhv Ihvs1  79.74 A

in secondary value Ihvs1


Ihvsecs1 
CT hv Ihvsecs1  0.133 A

Ihvs2  Irefhv Ihvs2  590.64 A

Ihvs2
Ihvsecs2 
CT hv Ihvsecs2  0.98 A

1.2.2.3.5 Tripping REF 2 Characteristics


Slope 1 Calculation:
ErrHi  1  IExcERR  Rlyerr  CT errsmall ErrHi  1.14

ErrLo 
1  CTerrsmall ErrLo  0.938
1  VLTCerr

Rev. 00 IBT 3 1.2/4


CALCULATION NOTE 500kV MUARA ENIM S/S

m1lv 
ErrHi  ErrLo  0.194
0.5  Err Hi  Err Lo  m1lvset  0%

Slope 2 Calculation:
ErrHi2  1  IExcErrHi  Rlyerr  CTerrlarge  1.11

ErrLo2 
1  CTerrlarge  0.938
1  VLTCerr
m2lv 
ErrHi2  ErrLo2  0.168 m2lvset  150%
0.5 Err Hi2  ErrLo2

Ilvs1 is set according to nominal current winding affected by impedance Ilvs2


winding and
is set to the rated current of the transformer
Ilvs1  Z% Ireflv Ilvs1  141.71 A

in secondary value Ilvs1


Ilvsecs1 
CTlv Ilvsecs1  0.236 A
3
Ilvs2  Ireflv Ilvs2  1.05  10 A

Rev. 00 IBT 3 1.2/5


CALCULATION NOTE 500kV MUARA ENIM S/S

Ilvs2
Ilvsecs2 
CTlv Ilvsecs2  1.75 A

Auto LowZ REF Characteristic


1

Differential Currents Is (A)


0.9

0.7

0.6
b
0.4

0.3

0.1

0
0 0.057 0.114 0.171 0.229 0.286 0.343 0.4
a

Effective Bias IR (A)

Rev. 00 IBT 3 1.2/6


CALCULATION NOTE 500kV MUARA ENIM S/S

1. 500/275/66kV 500MVA 3 BANKS POWER TRANSFORMER


1.3 DIFFERENTIAL TRANSFORMER PROTECTION MAIN 2
1.3.1 GENERAL DATA
1.3.1.1 Relay's Characteristics
Manufacturer : ABB

Type : RET670

Product Code :

Rated Current : in  1A

1.3.1.2 Enabling/disabling Differential Protection


No/Yes DIFF Enabled_USER= Yes
1.3.1.3 Transformer's Characteristic

Transformer Coupling :
YNa0  d1
HV side Voltage MAIN Vnom_primhvside  500kV

LV side Voltage MAIN Vnom_primlvside  275kV


TV side Voltage MAIN Vnom_primtvside  66kV

Z%  13.5% (Assumption)
3
Reference power :DIFF Sref  500  10 kV A
Rotary Field :MAIN Anti  Clockwise
Tap Changer position (no load)/increments MAIN tp  19 ti  0.8%
Higher Tap : Tap1  10.5%
(Assumption)
Lower Tap : TapN  15%

Inrush current/rated current


(as per manual 8 to 30 times of full load current): Kinr  10

1.3.1.4 Primary nominal currents and ratio of the main current transformers
Primary current Primary HV side 500kV : 600 / 1A Inom_CTprimhvside  600A

Primary LV side 275kV : 1200 / 1A Inom_CTprimlvside  1200A

Tertiary LV side 66kV : 2000 / 1A Inom_CTprimtvside  2000A

Rev. 00 IBT 3 1.3/1


CALCULATION NOTE 500kV MUARA ENIM S/S

Ratios Primary HV side : CThv  600

Primary LV side : CTlv  1200

Primary TV side : CTtv  2000

1.3.1.5 Errors
1.3.1.5.1 Misc Errors
Excitation Current Error : IExcERR  3%

Excitation current error are ignore, will be small compare IExcErrHi  0%


with other error at high current:

Rlyerr  5%
Relay Error
1.3.1.5.2 Current Errors
CTerrsmall  6%
CT is well out of saturation error based on CT test report,
(assumed)
CTerrlarge  6%
CT error at high current based on CT test report, (assumed)
1.3.1.5.3 Voltage Errors
Assumed VLTCerr  0.22%

1.3.2 NOMINAL RATING VALUES CALCULATION


HV mid tap voltage:
HVmid  Vnomhvside 1 
 Tap1  TapN
 2  HVmid  488.75 kV

HV full load current Sref


at mid tap voltage: Irefhv 
3  HVmid Irefhv  590.64 A

in secondary value:
Irefhv
Irefhvsec 
CT hv Irefhvsec  0.984 A

HV full load current on


Sref
Tap1  0.105 Ireftap1 

3  Vnomhvside 1  Tap1  Ireftap1  522.49 A

in secondary value:
Ireftap1
Ireftap1sec 
CThv
Ireftap1sec  0.87 A

Rev. 00 IBT 3 1.3/2


CALCULATION NOTE 500kV MUARA ENIM S/S

HV full load current on


TapN  0.15 Sref
IreftapN 

3  Vnomhvside 1  TapN  IreftapN  679.24 A

in secondary value
IreftapN
IreftapNsec  IreftapNsec  1.132 A
CT hv

LV full load current: Sref 3


Ireflv  Ireflv  1.05  10 A
3  Vnomlvside

Ireflv
Ireflvsec  Ireflvsec  0.87 A
CT lv

1.3.3 DIFFERENTIAL PROTECTION SETTING


1.3.3.1 Amplitude Matching Factors of HV and LV Windings
The matching factors must comply with the following conditions:

a. The matching factors must always be < 3

b. The ratio of the highest to the lower matching factors must be <5

c. The value of the lowest matching factors must be < 0.7


Calculated HV matching factor: Inomhv
Kamhv  Kamhv  1.016
Irefhv

Calculated LV matching factor:

Inomlv
Kamlv  Kamlv  1.143
Ireflv

1.3.3.2 Vector group matching


Vector group matching a-b: 0/11 DIFF Vector_grpendab  0
Vector group matching a-c: 0/11 DIFF Vector_grpendac  0
1.3.3.3 Zero-Sequence filtering
Zero sequence filtering of HV winding (a) : No / Yes DIFF Zeroseq . filt.a_en=Yes
Zero sequence filtering of LV winding (a) : No / Yes DIFF Zeroseq . filt.b_en=Yes

Rev. 00 IBT 3 1.3/3


CALCULATION NOTE 500kV MUARA ENIM S/S

1.3.3.4 Tripping Characteristics


1.3.3.4.1 Nominal rating HV/LV unbalanced current checking in regard with the Tap Changer
HV corrected current on tap 1:
Ishv1  Kamhv Ireftap1sec Ishv1  0.885 A

HV corrected current on tap N:


IshvN  Kamlv IreftapNsec IshvN  1.294 A

LV corrected current: Islv  Kamlv Ireflvsec Islv  1 A

Id
at tap 1 Id1  Ishv1  Islv Id1  0.115 A

Id
at tap N IdN  IshvN  Islv IdN  0.294 A

Restraining current on tap 1:


IR1 
Ishv1  Islv IR1  0.942 A
2

Restraining current on tap N:


IRN 
IshvN  Islv IRN  1.147 A
2

Slope 1 Calculation:
ErrHi  1  IExcERR  Rlyerr  CT errsmall ErrHi  1.14

ErrLo 
1  CTerrsmall
1  VLTCerr ErrLo  0.938

m1 
ErrHi  ErrLo  0.194
0.5  ErrHi  ErrLo 

Slope 2 Calculation:

ErrHi2  1  IExcErrHi  Rlyerr  CTerrlarge  1.11

ErrLo2 
1  CTerrlarge  0.938
1  VLTCerr
m2 
ErrHi2  ErrLo2  0.168
0.5 ErrHi2  Err Lo2

Rev. 00 IBT 3 1.3/4


CALCULATION NOTE 500kV MUARA ENIM S/S

Idiff1  0.2 pu
Basic threshold value Idiff>
Setting defining the second knee of tripping characteristic IRm2  1 pu

Gradient of the tripping characteristic of differential protection


in the range 0.5Idiff1  IR  IRm2
m1  0.19
Recommendation m1 set:
m1set  0.3

Gradient of the tripping characteristic of the differential protection


in the range IR  IRm2
m2  0.168
Recommendation m2 set
m2set  0.8

Operating current at tap 1: Iop1  m1set IR1  0.283 A

Operating current at tap N:


   
Iop2  m1set IRm2a  m2set IRN  IRm2a   0.418 A

MICOM P643 tripping characteristics:

1
0.9
0.8
Differential Current

0.7
0.6
y 0.5
0.4
0.3
0.2
0.1
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
x

Restraint Current
We can check that there is enough stability with Idiff1  0.2 m1set  0.3 m2set  0.8

Rev. 00 IBT 3 1.3/5


CALCULATION NOTE 500kV MUARA ENIM S/S

1.3.3.5 Rapid (high set) differential protection


function
1.3.3.5.1 Inrush stabilization (harmonic restraint)
The fundamental wave I(fo) and second harmonic components I(2*fo) of the differential current
are determined. if the ratio I(2*fo)/I(fo) exceedss a specific adjustable value in at least one
measuring system, tripping is blocked optionally (Without/Phase Selective/Not Phase Selective).

Operating mode of the inrush stabilization function


Without / Phase-Selective / Not Phase-Selective DIFF Op.mode_harm=Phase-Selective
Operate value of the inrush stabilization function (from a harmonic analysis of a typical
magnetizing-inrush current)
10 / 50 % DIFF RushI2fo_Ifo  20%

1.3.3.5.2 Overfluxing Restraint


The differential current is filtered and fundamental I(fo) and fifth harmonic components I(5*fo)
are determined. if the ratio I(5*fo)/I(fo) exceeds the set value over I(5fo)/I(fo) in at least one
measuring system, and if the restraining current is smaller than 4. Iref, then tripping is blocked
selectively
Operating mode of the overfluxing restraint function: No / Yes DIFF Overflux . bl. en: Yes
Operate value of the overfluxing restraint function : 10 / 80 % DIFF OverI5fo_Ifo  35%
1.3.3.5.3 Adjustable High Set Threshold Idiff>>
Maximum primary current: Ifo  IreftapN

Maximum fault current:


IreftapN
Ir  Ir  5031.37 A
Z%

In secondary value: Ir
ir  ir  8.386 A
CT hv

Correct value for deactivation of harmonic restraint and overfluxing ir Kamhv  8.519 A
restraint functions (refered to relevant reference current):
Chosen setting: 5 / 30 Iref DIFF Idiff2  10 pu

Rev. 00 IBT 3 1.3/6


CALCULATION NOTE 500kV MUARA ENIM S/S

1.4 RESTRICTED EARTH FAULT IBT 500/275/66 kV PROTECTION MAIN 2


1.4.1 GENERAL DATA
1.4.1.1 Relay's Characteristics
Manufacturer : ABB

Type : RET670

Product Code :

Rated Current : in  1A

1.4.1.2 Enabling/disabling REF Protection


No/YEs REF Enabled_USER= Yes

1.4.1.3 Transformer's Characteristic

Transformer Coupling : YNa0  d1


Vnom_primhvside  500kV
HV side Voltage MAIN
Vnom_primlvside  275kV
LV side Voltage MAIN
Vnom_primtvside  66kV
TV side Voltage MAIN

Z%  13.5% (Assumption)
3
Reference power :DIFF Sref  500  10 kV A
Rotary Field :MAIN Anti  Clockwise
Tap Changer position (no load)/increments MAIN tp  19 ti  0.8%
Higher Tap : Tap1  10.5%
(Assumption)
Lower Tap : TapN  15%

Inrush current/rated current


(as per manual 8 to 30 times of full load current): Kinr  10

1.4.1.4 Primary nominal Diff. currents and ratio of the main current transformers
Primary current Primary HV side 500kV : 600 / 1A Inom_CTprimrhvside  600A

Primary LV side 275kV : 1200 / 1A Inom_CTprimrlvside  1200A

Tertiary LV side 66 kV : 2000 / 1A Inom_CTprimrtvside  2000A

Rev. 00 IBT 3 1.4/1


CALCULATION NOTE 500kV MUARA ENIM S/S

1.4.1.5 Primary nominal neutral currents and ratio of the main current transformers
Primary current Primary REF HV side 500kV : 600/1A Inom_CTprimhvside  600A

Primary REF LV side 275kV : 600/1A Inom_CTprimlvside  600A

Ratios NCT NCT HV side (Common) : CThv  600

NCT LV side (Common) : CTlv  600

NCT Star Connection side : CTtv  600

1.4.1.6 Errors
1.4.1.6.1 Misc Errors
Excitation Current Error : IExcERR  3%

Excitation current error are ignore, will be small compare IExcErrHi  0%


with other error at high current:

Rlyerr  5%
Relay Error
1.4.1.6.2 Current Errors
CTerrsmall  6%
CT is well out of saturation error based on CT test report,
(assumed)
CTerrlarge  6%
CT error at high current based on CT test report, (assumed)
1.4.1.6.3 Voltage Errors
Assumed VLTCerr  0.22%

1.4.2 NOMINAL RATING VALUES CALCULATION


HV mid tap voltage:
HVmid  Vnomhvside 1 
 Tap1  TapN
 2  HVmid  488.75 kV

HV full load current Sref


at mid tap voltage: Irefhv 
3  HVmid Irefhv  590.64 A

in secondary value:
Irefhv
Irefhvsec 
CT hv Irefhvsec  0.984 A

HV full load current on


Sref
Tap1  0.105 Ireftap1 

3  Vnomhvside 1  Tap1  Ireftap1  522.49 A

Rev. 00 IBT 3 1.4/2


CALCULATION NOTE 500kV MUARA ENIM S/S

in secondary value:
Ireftap1
Ireftap1sec 
CThv Ireftap1sec  0.87 A
HV full load current on
TapN  0.15 Sref
IreftapN 
 
3  Vnomhvside 1  TapN IreftapN  679.24 A

in secondary value
IreftapN
IreftapNsec  IreftapNsec  1.132 A
CT hv

LV full load current: Sref 3


Ireflv  Ireflv  1.05  10 A
3  Vnomlvside

Ireflv
Ireflvsec  Ireflvsec  1.75 A
CT lv

1.4.3 REF PROTECTION SETTING


1.4.3.1 Amplitude Matching Factors of HV and LV Windings
Inomhv  Inom_CTprimhvside

Inomlv  Inom_CTprimlvside

Calculated HV matching factor: Inomhv


Kamhv  Kamhv  1.016
Irefhv

Calculated LV matching factor:

Inomlv
Kamlv  Kamlv  0.572
Ireflv

1.4.3.2 Vector group matching


Vector group matching a-b: 0/11 DIFF Vector_grpendab  0
Vector group matching a-c: 0/11 DIFF Vector_grpendac  0
1.4.3.3 Zero-Sequence filtering

Rev. 00 IBT 3 1.4/3


CALCULATION NOTE 500kV MUARA ENIM S/S

Zero sequence filtering of HV winding (a) : No / Yes DIFF Zeroseq . filt.a_en=Yes


Zero sequence filtering of LV winding (a) : No / Yes DIFF Zeroseq . filt.b_en=Yes

1.4.3.4 Tripping REF 1 Characteristics


Slope 1 Calculation:
ErrHi  1  IExcERR  Rlyerr  CT errsmall ErrHi  1.14

ErrLo 
1  CTerrsmall ErrLo  0.938
1  VLTCerr
m1hv 
ErrHi  ErrLo  0.194
0.5  ErrHi  ErrLo  m1hvset  0%

Slope 2 Calculation:
ErrHi2  1  IExcErrHi  Rlyerr  CTerrlarge  1.11

ErrLo2 
1  CTerrlarge  0.938
1  VLTCerr
m2hv 
ErrHi2  ErrLo2  0.168 m2hvset  150%
0.5 ErrHi2  Err Lo2

Ihvs1 is set according to nominal current winding affected by impedance Ihvs2


winding and
is set to the rated current of the transformer
Ihvs1  Z% Irefhv Ihvs1  79.74 A

in secondary value Ihvs1


Ihvsecs1 
CT hv Ihvsecs1  0.133 A

Ihvs2  Irefhv Ihvs2  590.64 A

Ihvs2
Ihvsecs2 
CT hv Ihvsecs2  0.98 A

1.4.2.3.5 Tripping REF 2 Characteristics


Slope 1 Calculation:
ErrHi  1  IExcERR  Rlyerr  CT errsmall ErrHi  1.14

ErrLo 
1  CTerrsmall ErrLo  0.938
1  VLTCerr

Rev. 00 IBT 3 1.4/4


CALCULATION NOTE 500kV MUARA ENIM S/S

m1lv 
ErrHi  ErrLo  0.194
0.5  Err Hi  Err Lo  m1lvset  0%

Slope 2 Calculation:
ErrHi2  1  IExcErrHi  Rlyerr  CTerrlarge  1.11

ErrLo2 
1  CTerrlarge  0.938
1  VLTCerr
m2lv 
ErrHi2  ErrLo2  0.168 m2lvset  150%
0.5 Err Hi2  ErrLo2

Ilvs1 is set according to nominal current winding affected by impedance Ilvs2


winding and
is set to the rated current of the transformer
Ilvs1  Z% Ireflv Ilvs1  141.71 A

in secondary value Ilvs1


Ilvsecs1 
CTlv Ilvsecs1  0.236 A
3
Ilvs2  Ireflv Ilvs2  1.05  10 A

Rev. 00 IBT 3 1.4/5


CALCULATION NOTE 500kV MUARA ENIM S/S

Ilvs2
Ilvsecs2 
CTlv Ilvsecs2  1.75 A

AutoREF LowZ Characteristic


1

Differential Currents Is (A)


0.9

0.7

0.6
b
0.4

0.3

0.1

0
0 0.057 0.114 0.171 0.229 0.286 0.343 0.4
a

Effective Bias IR (A)

Rev. 00 IBT 3 1.4/6


CALCULATION NOTE 500kV MUARA ENIM S/S

1.5 F51PH+N1 500kV OVERCURRENT IBT 3 PROTECTION


1.5.1 GENERAL DATA
1.5.1.1 Relay's Characteristics
Manufacturer : General Electric

Type : MICOM P14D

Product Code : P14DL26A6C0560A

Rated Current : in  1A
1.5.1.2 Enabling/disabling Overcurrent Protection
No/Yes OCR Enabled_USER = Yes
No/Yes OCR I>1_en = Yes
No/Yes EF IN>1_en = Yes

1.5.1.3 Transformer's Characteristic

Transformer Coupling : YNa0  d

HV side Voltage MAIN Vnom_primhvside  500kV

LV side Voltage MAIN Vnom_primlvside  275kV


Z%  13.5%
3
Reference power : Sref  500  10 kV A
Rotary Field :MAIN Anti  Clockwise
1.5.2 Overcurrent Operation Setting
1.5.2.1 Selection of Current Threshold "I>1 Current Set"
CT Ratio : 600 / 1A Inom_CTprim  600A
CTprim  600
Phase current factor : Ri  1.5

Required setting : Iocr  Ifl Ri Iocr  866.03 A

in secondary value Iocr


IOCR 
CTprim IOCR  1.44 A

Rev. 00 IBT 3 1.5/1


CALCULATION NOTE 500kV MUARA ENIM S/S

1.5.2.2 Selection of Time Characteristic "I>1


Function"There is four type of time characteristic using IEC Curve, the general mathematic expression is:

top  TMS L  C


k
α 
  Ii  
  I   1
  set  
top is the operating time

L is a constant (usually only used for ANSI/IEEE curves)


TMS is time multiplier setting
α is a constant, which can be shosen to satisfy the required curve characteristic
k is a constant, which can be shosen to satisfy the required curve characteristic
C is a constant for adding definite time ( Definite Time Adder)

Curve k α L
IEC Standard Inverse 0.14 0.02 0
IEC Very Inverse 13.5 1 0
IEC Extremely Inverse 80 2 0
UK LTI 120 1 0

1.3.1 Curve Characteristic


Curve Characteristic : Standard Inverse
Short circuit current on HV side :
Ifl
Isc 
Z%

Minimum Short Circuit current on HV side : Iscmin  0.88 Isc

Tripping time requirement : top  0.1 s

TMS requirement : TMS  0.021


1.5.2.3 Selection of Timer Hold Facility "I>1 tRESET"
Setting range from 0.04 s to 100 s in 0.01 steps Selection : treset  0 s

1.5.3 Earth Fault Operation Setting

Rev. 00 IBT 3 1.5/2


CALCULATION NOTE 500kV MUARA ENIM S/S

1.5.2.1 Selection of Current Threshold "I>1 Current Set"


CT Ratio : 600 / 1A Inom_CTprim  600A
CTprim  600

Earth fault Range : 0.5 Ifl  Ief  0.8Ifl Ref  0.5

Required setting : Ief  Ifl Ref Ief  288.68 A

in secondary value Ief


IEF 
CTprim IEF  0.48 A

1.5.2.2 Selection of Time Characteristic "I>1 Function"


There is four type of time characteristic using IEC Curve, the general mathematic expression is:

top  TMS L  C


k
α 
  Ii  
  I   1
  set  
top is the operating time

L is a constant (usually only used for ANSI/IEEE curves)


TMS is time multiplier setting
α is a constant, which can be shosen to satisfy the required curve characteristic
k is a constant, which can be shosen to satisfy the required curve characteristic
C is a constant for adding definite time ( Definite Time Adder)

Curve k α L
IEC Standard Inverse 0.14 0.02 0
IEC Very Inverse 13.5 1 0
IEC Extremely Inverse 80 2 0
UK LTI 120 1 0

1.3.1 Curve Characteristic

Rev. 00 IBT 3 1.5/3


CALCULATION NOTE 500kV MUARA ENIM S/S

Curve Characteristic : Standard Inverse


Short circuit current on HV side : Ifl
Isc 
Z%

Minimum Short Circuit current on HV side : Iscmin  0.88 Isc

Tripping time requirement : topef  0.3 s

TMS requirement : TMSef  0.421


1.5.2.3 Selection of Timer Hold Facility "I>1 tRESET"
Setting range from 0.04 s to 100 s in 0.01 steps Selection : treset  0 s

Rev. 00 IBT 3 1.5/4


CALCULATION NOTE 500kV MUARA ENIM S/S

1.6 F51PH+N2 275KV OVERCURRENT IBT 3 PROTECTION


1.6.1 GENERAL DATA
1.6.1.1 Relay's Characteristics
Manufacturer : General Electric

Type : MICOM P14D

Product Code : P14DL26A6C0560A

Rated Current : in  1A
1.6.1.2 Enabling/disabling Overcurrent Protection
No/Yes OCR Enabled_USER = Yes
No/Yes OCR I>1_en = Yes
No/Yes EF IN>1_en = Yes

1.6.1.3 Transformer's Characteristic

Transformer Coupling : YNa0  d

HV side Voltage MAIN Vnom_primhvside  275kV

LV side Voltage MAIN Vnom_primlvside  500kV


Z%  13.5%
3
Reference power : Sref  500  10 kV A
Rotary Field :MAIN Anti  Clockwise
1.6.2 Overcurrent Operation Setting
1.6.2.1 Selection of Current Threshold "I>1 Current Set"
CT Ratio : 1200 / 1A Inom_CTprim  1200A
CTprim  1200
Phase current factor : Ri  1.5
3
Required setting : Iocr  Ifl Ri Iocr  1.57  10 A

in secondary value Iocr


IOCR 
CTprim IOCR  1.31 A

Rev. 00 IBT 3 1.6/1


CALCULATION NOTE 500kV MUARA ENIM S/S

1.6.2.2 Selection of Time Characteristic "I>1 Function"


There is four type of time characteristic using IEC Curve, the general mathematic expression is:

top  TMS L  C


k
α 
  Ii  
  I   1
  set  
top is the operating time

L is a constant (usually only used for ANSI/IEEE curves)


TMS is time multiplier setting
α is a constant, which can be shosen to satisfy the required curve characteristic
k is a constant, which can be shosen to satisfy the required curve characteristic
C is a constant for adding definite time ( Definite Time Adder)

Curve k α L
IEC Standard Inverse 0.14 0.02 0
IEC Very Inverse 13.5 1 0
IEC Extremely Inverse 80 2 0
UK LTI 120 1 0

1.3.1 Curve Characteristic


Curve Characteristic : Standard Inverse
Short circuit current on HV side :
Ifl
Isc 
Z%

Minimum Short Circuit current on HV side : Iscmin  0.88 Isc

Tripping time requirement : top  0.1 s

TMS requirement : TMS  0.021


1.6.2.3 Selection of Timer Hold Facility "I>1 tRESET"
Setting range from 0.04 s to 100 s in 0.01 steps Selection : treset  0 s

Rev. 00 IBT 3 1.6/2


CALCULATION NOTE 500kV MUARA ENIM S/S

1.6.3 Earth Fault Operation Setting


1.6.2.1 Selection of Current Threshold "I>1 Current Set"
CT Ratio : 600 / 1A Inom_CTprim  600A
CTprim  1200

Earth fault Range : 0.5 Ifl  Ief  0.8Ifl Ref  0.5

Required setting : Ief  Ifl Ref Ief  524.86 A

in secondary value Ief


IEF 
CTprim IEF  0.44 A

1.6.2.2 Selection of Time Characteristic "I>1 Function"


There is four type of time characteristic using IEC Curve, the general mathematic expression is:

top  TMS L  C


k
α 
  Ii  
  I   1
  set  
top is the operating time

L is a constant (usually only used for ANSI/IEEE curves)


TMS is time multiplier setting
α is a constant, which can be shosen to satisfy the required curve characteristic
k is a constant, which can be shosen to satisfy the required curve characteristic
C is a constant for adding definite time ( Definite Time Adder)

Curve k α L
IEC Standard Inverse 0.14 0.02 0
IEC Very Inverse 13.5 1 0
IEC Extremely Inverse 80 2 0
UK LTI 120 1 0

1.3.1 Curve Characteristic

Rev. 00 IBT 3 1.6/3


CALCULATION NOTE 500kV MUARA ENIM S/S

Curve Characteristic : Standard Inverse


Short circuit current on HV side : Ifl
Isc 
Z%

Minimum Short Circuit current on HV side : Iscmin  0.88 Isc

Tripping time requirement : topef  0.3 s

TMS requirement : TMSef  0.457


1.6.2.3 Selection of Timer Hold Facility "I>1 tRESET"
Setting range from 0.04 s to 100 s in 0.01 steps Selection : treset  0 s

Rev. 00 IBT 3 1.6/4


CALCULATION SETTING 500kV MUARA ENIM S/S

1.7 F51PH+N 70kV IBT 3 NEUTRAL VOLTAGE DISPLACEMENT (NVD)


TRANSFORMER PROTECTION RELAY
1.7.1 GENERAL DATA
1.7.1.1 Relay's Characteristics
Manufacturer : General Electric

Type : MICOM P14D

Product Code : P14DL26A6C0560A

Rated Current : in  1A
1.7.1.2 Enabling/disabling Residual Overvoltage Protection
No/Yes Residual O/V NVDEnabled_USER = Yes
No/Yes NVD VN>1_en = Yes

1.7.1.3 Transformer's Characteristic YNynD11

Transformer Coupling : Vnom_primhvside  500kV

HV side Voltage MAIN Vnom_primlvside  275kV

LV side Voltage MAIN Vnom_primtvside  66kV

Vnom_sec hvside  100V

Vnom_sec lvside  100V

Vnom_sec tvside  100V

3
Reference power : Sref  500  10 kV A
Rotary Field :MAIN Anti  Clockwise

Rev. 00 IBT 3 1.7.1/1


CALCULATION NOTE 500kV MUARA ENIM S/S

2. 500kV CIRCULATING CURRENT PROTECTION DIAMETER 7


2.1 CIRCULATING CURRENT PROTECTION MAIN 1
2.1.1 GENERAL DATA
2.1.1.1 Relay's Characteristics
Manufacturer : General Electric

Type : MICOM P643

Product Code : P64391TF6S0910M

Rated Current : in  1A

Rated Voltage : u n  100V


2.1.1.2 Enabling/disabling Differential Protection
No/Yes DIFF Enabled_USER= Yes
2.1.1.3 CT's & VT's Characteristic

Rated Voltage : Ur  500kV

Rated Current : Ir  4kA

In  1A

Rlead : Rlead  6.37Ω

RCTsec : RCTsec  5Ω

Usat : Usat  4kV


CTerror is well out of saturation error
CT err  2% based on CT test report,
(assumed)

2.1.1.4 Relay Electrical Data


Rrelay :
Rrelay  0.1 Ω
Relay Error: Rlyerr  2%

2.1.1.5 Errors
2.1.1.5.1 Misc Errors

Excitation Current Error : IExcERR  3%

Excitation current error are ignore, will be small compare IExcErrHi  0%


with other error at high current:

Rlyerr  2%
Relay Error
2.1.1.5.2 Current Errors
CT errsmall  6%
CT is well out of saturation error based on CT test report,
(assumed)
CT errlarge  6%
CT error at high current based on CT test report, (assumed)
2.1.1.5.3 Voltage Errors
Assumed VLTCerr  0.22%

Rev. 00 DIAMETER 7 2/1


CALCULATION NOTE 500kV MUARA ENIM S/S

2.1.2 CALCULATION SETTING


2.1.2.1 DIFFERENTIAL PROTECTION SETTING
2.1.2.1.1 Amplitude Matching Factors of HV and LV Windings
The matching factors must comply with the following conditions:

a. The matching factors must always be < 3

b. The ratio of the highest to the lower matching factors must be <5

c. The value of the lowest matching factors must be < 0.7


in circulating current protection usually used same CT ration in each winding.
Calculated matching factor: Ir
Kn 
Iref Kn  3.464

2.1.2.1.2 Tripping Characteristics


2.1.2.1.2.1 Nominal rating HV/LV unbalanced current checking in regard with the Tap
Changer
corrected current:
I1  Kn  Iref I1  4000 A

I2  Kn  Iref I2  4000 A
I3  I2 I3  4000 A
Id1
Id1  I1  I2 Id1  0 A

Restraining current : I1  I2


IR1  IR1  4000 A
2
Slope 1 Calculation:
Err Hi  1  IExcERR  Rlyerr  CTerrsmall Err Hi  1.11

1  CTerrsmall
Err Lo 
1  VLTCerr Err Lo  0.938

ErrHi  ErrLo
m1   0.168
0.5  Err Hi  Err Lo 

Slope 2 Calculation:

Err Hi2  1  IExcErrHi  Rlyerr  CT errlarge  1.08

1  CTerrlarge
Err Lo2   0.938
1  VLTCerr
ErrHi2  ErrLo2
m2   0.141
0.5 Err Hi2  ErrLo2

Rev. 00 DIAMETER 7 2/2


CALCULATION NOTE 500kV MUARA ENIM S/S

Idiff1  0.2 pu
Basic threshold value Idiff>
Setting defining the second knee of tripping characteristic Is2  1 pu

Gradient of the tripping characteristic of differential protection


in the range 0.5Idiff1  IR  IRm2
m1  0.17
Recommendation m1 set:
m1set  0.3
Gradient of the tripping characteristic of the differential protection
in the range IR  IRm2
m2  0.141
Recommendation m2 set
m2set  0.8

MICOM P643 tripping characteristics:

1
0.9
0.8
Differential Current

0.7
0.6
y 0.5
0.4
0.3
0.2
0.1
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
x

Restraint Current
We can check that there is enough stability with Idiff1  0.2 m1set  0.3 m2set  0.8 Is2  1 pu

Rev. 00 DIAMETER 7 2/3


CALCULATION NOTE 500kV MUARA ENIM S/S

2. 500kV CIRCULATING CURRENT PROTECTION DIAMETER 7


2.2 CIRCULATING CURRENT PROTECTION MAIN 2
2.2.1 GENERAL DATA
2.2.1.1 Relay's Characteristics
Manufacturer : ABB

Type : REB670

Product Code :

Rated Current : in  1A

Rated Voltage : u n  100V


2.2.1.2 Enabling/disabling Differential Protection
No/Yes DIFF Enabled_USER= Yes
2.2.1.3 CT's & VT's Characteristic

Rated Voltage : Ur  500kV

Rated Current : Ir  4kA

In  1A

Rlead : Rlead  6.37Ω

RCTsec : RCTsec  5Ω

Usat : Usat  4kV


CTerror is well out of saturation error
CT err  2% based on CT test report,
(assumed)

2.2.1.4 Relay Electrical Data


Rrelay :
Rrelay  0.1 Ω
Relay Error: Rlyerr  2%

2.2.1.5 Errors
2.2.1.5.1 Misc Errors

Excitation Current Error : IExcERR  3%

Excitation current error are ignore, will be small compare IExcErrHi  0%


with other error at high current:

Rlyerr  2%
Relay Error
2.2.1.5.2 Current Errors
CT errsmall  6%
CT is well out of saturation error based on CT test report,
(assumed)
CT errlarge  6%
CT error at high current based on CT test report, (assumed)
2.2.1.5.3 Voltage Errors
Assumed VLTCerr  0.22%

Rev. 00 IBT 3 2.2/1


CALCULATION NOTE 500kV MUARA ENIM S/S

2.2.2 CALCULATION SETTING


2.2.2.1 DIFFERENTIAL PROTECTION SETTING
2.2.2.1.1 Amplitude Matching Factors of HV and LV Windings
The matching factors must comply with the following conditions:

a. The matching factors must always be < 3

b. The ratio of the highest to the lower matching factors must be <5

c. The value of the lowest matching factors must be < 0.7


in circulating current protection usually used same CT ration in each winding.
Calculated matching factor: Ir
Kn 
Iref Kn  3.464

2.2.2.1.2 Tripping Characteristics


2.2.2.1.2.1 Nominal rating HV/LV unbalanced current checking in regard with the Tap
Changer
corrected current:
I1  Kn  Iref I1  4000 A

I2  Kn  Iref I2  4000 A
I3  I2 I3  4000 A
Id1
Id1  I1  I2 Id1  0 A

Restraining current : I1  I2


IR1  IR1  4000 A
2
Slope 1 Calculation:
Err Hi  1  IExcERR  Rlyerr  CTerrsmall Err Hi  1.11

1  CTerrsmall
Err Lo 
1  VLTCerr Err Lo  0.938

ErrHi  ErrLo
m1   0.168
0.5  Err Hi  Err Lo 

Slope 2 Calculation:

Err Hi2  1  IExcErrHi  Rlyerr  CT errlarge  1.08

1  CTerrlarge
Err Lo2   0.938
1  VLTCerr
ErrHi2  ErrLo2
m2   0.141
0.5 Err Hi2  ErrLo2

Rev. 00 IBT 3 2.2/2


CALCULATION NOTE 500kV MUARA ENIM S/S

Idiff1  0.2 pu
Basic threshold value Idiff>
Setting defining the second knee of tripping characteristic Is2  1 pu

Gradient of the tripping characteristic of differential protection


in the range 0.5Idiff1  IR  IRm2
m1  0.17
Recommendation m1 set:
m1set  0.3
Gradient of the tripping characteristic of the differential protection
in the range IR  IRm2
m2  0.141
Recommendation m2 set
m2set  0.8

MICOM P643 tripping characteristics:

1
0.9
0.8
Differential Current

0.7
0.6
y 0.5
0.4
0.3
0.2
0.1
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
x

Restraint Current
We can check that there is enough stability with Idiff1  0.2 m1set  0.3 m2set  0.8 Is2  1 pu

Rev. 00 IBT 3 2.2/3


CALCULATION NOTE MUARA ENIM 500kV S/S

3.1 BREAKER FAILURE & SZP PROTECTION DIAMETER 7


3.1.1 GENERAL DATA
3.1.1.1 Relay's Characteristics
Manufacturer : GE

Type : MiCOM P14D

Cortec : P14DL26A6C0560A

Rated Current :
in  1A
Maximum fault current :
if  50kA
Fault withstanding duration :
twithstand  1s

3.1.1.2 CT's characteristics


Rated voltage : Ur  71.5kV

Rated current : Ir  2000A

3.1.2 CALCULATION SETTING


3.1.2.1 Circuit Breaker Failure
Operation Scheme
when a fault occurs, one or more protection devices will operate and issue a trip command to the
relevant circuit breakers. operation of the circuit breaker is essential to isolate the fault and
prevent, or at least limit, damage to the power system. If the fault current has not been interrupted
a set time delay from circuit breaker trip initiation, the CBF protection will operate, whreby the
upstream circuit breakers are back triped to ensure that the fault is isolated.
CBFail 1 Status: Enabled
CBFail 1 Timer: 0.15s
CBFail 2 Status: Enabled
CBFail 2 Timer: 0.25s
Volt Prot Reset: I  Only
Ext Prot Reset: I  Only

I< Current Set: Iuc  20%  in Iuc  0.2 A

ISEF< Current Set: Isef  50%  in Isef  0.5 A

REV. 00 IBT 3 3.1/1


CALCULATION NOTE MUARA ENIM 500kV S/S

3.1.2.2 Short Zone Protection


Operation Scheme
SZP principle bay be extended by setting fast-acting overcurrent elements on the incoming
feeders to a substation, which are then arranged to be blocked by start contacts from the devices
protecting the putgoing feeders. This allowed to trip for a fault condition on the busbar, but is
stable for external faults due to the blocking signal.
I >1 Status: Enabled

I>1 Function: DT

I>1 Directional: NonDirectional


I>1 Current Set:
1A
I>1 Time Delay:
70ms
I>1 Treset: 0s

I >2 Status: Enabled

I>2 Function: DT

I>2 Directional: NonDirectional


I>2 Current Set:
1A
I>2 Time Delay:
150ms
I>2 Treset: 0s

REV. 00 IBT 3 3.1/2


CALCULATION NOTE 500kV MUARA ENIM S/S

3.2 F90 AUTOMATIC VOLTAGE REGULATION (AVR) TAP CONTROLLER


3.2.1 GENERAL DATA
3.3.1.1 Relay's Characteristic
Manufacturer : MR TAPCON

Type : TAPCON BPL


AVR for 3 Banks
(R, S, T)
Product Code :

Leaflet :

Rated Current : in  1A
3.3.2 Operation Setting
3.3.2.1 Basic Values
Bandwidth :  Xw2  0.6ΔVtap  Xw2  0.49

Time Program : Linear

Set Point1 : 100%

Select Index 1 : 275kV


CTnomval  1A
CT Ratio :
CTkni  1200

VT Ratio : VTconf  2750


VTknu  2000

3.3.2.2 Parameters
Vuv  10%( blocking )
Undervoltage :

Overvoltage : Vov  10% ( blocking )

Overcurrent : Iocr  120% ( blocking )

Rev. 00 IBT 3 3.2/1


CALCULATION NOTE 500kV MUARA ENIM S/S

2.25
ΔVtap 
275
3
ΔVtap  8.182  10

Xw2  0.6 ΔVtap 100

Rev. 00 IBT 3 3.2/2


DIAMETER 4 PLTU DIAMETER 3 PLTU DIAMETER 2 NEW DIAMETER 1 NEW
DIAMETER 7 +BWT03 DIAMETER 6 +BWT02 DIAMETER 5 +BWT01 SUMSEL 8-1 SUMSEL 8-2 AUR DURI 2 AUR DURI 1
=B04 =B03 =B02 =B01
=B07 IBT 3 BAY =B06 IBT 2 BAY =B05 IBT 1 BAY

TO 275 KV INCOMING FEEDER IBT 3 BAY TO 275 KV INCOMING FEEDER IBT 2 BAY TO 275 KV INCOMING FEEDER IBT 1 BAY

TO 400/230 VAC DISTRIBUTION BOARD TO 400/230 VAC DISTRIBUTION BOARD

ACSR/AS 2X450 mm2


This document is the property of PT. WIJATI AJI, Copyright to be observed

BUSBAR B , 500KV, 4000A, 50KA/1s, BIL 1550KV, 50HZ TAL 2X850 mm2

TAL 2X850 mm2

TAL 2X850 mm2

TAL 2X850 mm2

BUSBAR A , 500KV, 4000A, 50KA/1s, BIL 1550KV, 50HZ (EXISTING) TAL 2X850 mm2

FUTURE BAY FUTURE BAY

PT. PLN (PERSERO)


UNIT INDUK PEMBANGUNAN SUMATRA BAGIAN SELATAN

CONTRACT No. : 0015.PJ/DAN.01.03/UIP SUMBAGSEL/2020. TANGGAL 16 DESEMBER 2020

PEMBANGUNAN EXTENSION IBT-3


GITET 500/275 kV MUARA ENIM
(PAKET ENIM 3)
KONSORSIUM
WIJATI - HASTA

SINGLE LINE DIAGRAM


GITET 500 kV MUARA ENIM

0015PJ-03ME-E/L-51-S7-401
1 2 3 4 5 6 7 8

A A
©2016 Grid Solution proprietary and confidential information. All rights Reserved. This document is the property of Grid Solu tion and may not be reproduced,
transmitted, stored or copied in whole or in part, or used to furnish information to others, without the prior written permission of Grid Solution

B B

AE TR
01 AS MANUFACTURE AM
12/1/2021 12/1/2021

AE TR
00 ORIGINAL ISSUE FA
4/23/2021 4/23/2021
DRAWN BY : CHECKED BY :
NO REVISION STATUS
DATE : DATE :

C OWNER C
PT PLN ( PERSERO )
UNIT INDUK PEMBANGUNAN SUMATERA BAGIAN SELATAN
Jl. Residen A. Rozak No. 2180, Sekojo Palembang 30118

CONTRACTOR
KONSORSIUM WIJATI-HASTA
Jl. Let Jend S Parman No. 52 Semarang 50232
Telp. 024 8441546 ( Hunting 7 Lines ) Fax. 024 8315360
D PROJECT D

PEMBANGUNAN EXTENSION IBT 3 GITET 500/275 KV MUARA ENIM ( PAKET ENIM 3 )

CONTRACT No : 0015.PJ/DAN.01.03/UIP SUMBAGSEL/2020, DATE : 16 DESEMBER 2020

DRAWING TITTLE

E BLOCK DIAGRAM - DIAMETER 7 & IBT3 E


GITET 500kV MUARA ENIM

SHEET : DESIGN BY DRAWN DESIGNED CHECKED APPROVED


/A1 12/1/2021 4/23/2021 12/1/2021 12/1/2021

SCALE :

NTS
AE DKP TR AN
F PAPER SIZE : DRAWING NO : F
REVISION NO :
A4 0015PJ-03ME-E/L-55-S7-801 01
1 2 3 4 5 6 7 8
Revision Drawn by Checked by Approved by
Modification
Drawn Date Checked Date Approved Date

00 ARIF TEDDY AUFAR ORIGINAL ISSUE


4/23/2021 4/23/2021 4/23/2021
©2016 GE Grid Solutions proprietary and confidential information. All Rights Reserved. This document is the property of GE Grid Solutions and may not be reproduced,

01 ARIF TEDDY AUFAR AS MANUFACTURE


12/1/2021 12/1/2021 12/1/2021
transmitted, stored,or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solutions.

Project Title
DRAWING REVISION
Revision 01
GE Energy Connections Grid Solutions 500/275kV MUARA ENIM
Drawing No. Sheet Nxt Sht
IBT 3 SUBSTATION
0015PJ-03ME-E/L-55-S7-801 /AA1 /AB
Designation Title line 1 Title line 2 Title line 3 Title line 4 R1 R2 R3 R4 R5 R6 R7 R8
/A1 COVER SHEET 00 01
/AA1 DRAWING REVISION 00 01
/AB DRAWING CONTENT 00 01
/BB0 BLOCK DIAGRAM 500kV DIAMETER 7 CUTOFF B 00 01
/BB1 BLOCK DIAGRAM 500kV DIAMETER 7 CUTOFF AB 00 01
©2016 GE Grid Solutions proprietary and confidential information. All Rights Reserved. This document is the property of GE Grid Solutions and may not be reproduced,
transmitted, stored,or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solutions.

Project Title
DRAWING CONTENT
Revision 01
GE Energy Connections Grid Solutions 500/275kV MUARA ENIM
Drawing No. Report
IBT 3 SUBSTATION /AB 1 of 1
0015PJ-03ME-E/L-55-S7-801
1 2 3 4 5 6 7 8
DIAMETER 7
INCOMING 275kV +EW1173 +ES1170
500kV MARSHALLING KIOSK DIAMETER 7
IBT-3 -A30B
DIAMETER-7 CUT OFF B 500kV CONTROL
A 3 X SURGE ARRESTER -F2 SEE WG. 0015PJ-03ME-E/ SEE DWG. 0015PJ-03ME-E/L-55-S7-701-01 -X30B
A
Ur 240kV 20kA -XC43
L55-S7-701-07
CURRENT TRANSFORMER

P1
3 x 1 PHASE CT -X2101 MICOM C264
-XV6423 -X30B
600-1200/1A, CL. TPX -T5.101 FROM CVT-M BUSBAR B (CVT-T6.423)
-X2102 -XV6673 -X30B
600-1200/1A, CL. TPX -T5.102 FROM CVT-M TEE OFF 2 (CVT-T6.673)
-X2103 CVTM-T6.673
600-1200/1A, CL. 5P20
-T5.103 //BB1.5A
20VA @600A, 40VA @1200A
©2016 GE Grid Solutions proprietary and confidential information. All Rights Reserved. This document is the property of GE Grid Solutions and may not be reproduced,

-X2104
2000-4000/1A, CL. TPX -T5.104 +EF1170 +EF11751
-X2105 TO 275kV DIAMETER 7 500/275kV IBT 3 DIAMETER 7 (MAIN 1)
2000-4000/1A, CL. TPX -T5.105 500kV BREAKER FAILURE PROTECTION 500kV PROTECTION PANEL
-T6.71 SEE DWG. 0015PJ-03ME-E/L-55-S7-701-02 SEE DWG. 0015PJ-03ME-E/L-55-S7-701-03
transmitted, stored, or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solutions.

P2
3 CT
-T10 -T5.8n -K863M1 -F87T1 (TRANSF. DIFF. PROT. M1 OPERATE)
AUTO TRANSFORMER 2000/1A, 3 PHASE CVT -F87T1 (REF1)
(OUT OF SCOPE) MVAJ105
CL.TPX 70kV;√3/0,1;√3/0,1; √3kV -F50BFB -F51PH+N.1 (O/C PROT. 500kV OPERATE)
3X1 PHASE -X50BFB -F871CL (275kV CCP LINE M1 OPERATE)
500/275/66kV -T10 W1 : 30VA, CL.3P -XC33 -K863CC1 [-K94RC1] 275kV PROT. M1 OPERATE
500MVA (OUT OF SCOPE) -T5.8n W2 : 30VA, CL.0.2 MVAJ105 -F873 (CCP PROT. M1 OPERATE)
B B

-T6.712

-T6.711
3 PHASE CT -XV6422 -X50BFB MICOM P14D -K863TE
-T5.761 -X17111 FROM CVT-P BUSBAR B
MVAJ105 TRANSF. ELECTROMECHANICAL TRIP
(CVT-T6.422)
600-1200/1A, CL.TPX -K863BBB1
-T5.762 -T5.761-T5.762 -T5.771-T5.772 -X2772 -XV6672 -X50BFB MVAJ105 -F87BBB1 (BUSBAR B PROT. M1 OPERATE)
FROM VT-P TEE OFF (-T6.672)
600-1200/1A, CL.TPX
P1 P2 P1 P2 -X2771
1 PHASE NEUTRAL (500kV) -XV6672
-T5.771 CVTP-T6.672 -K86BF3 [-K94B] -F50BFB, OC,U/O VOLTAGE (-Q53)
//BB1.5B
600-1200/1A, CL.TPX -X2911 MVAJ105
[-K94B1] 50BF FROM ADJACENT
(CB BUS B FROM OTHER DIAMETER), -F50BFB
-T5.772 (50BF (-Q53))
600-1200/1A, CL.TPX -X2761 -F7411...3B [-K94AB] -F50BFAB, 50BF/SZP/OC (-Q52)
P2

CURRENT TRANSFORMER -X2745 -F50BFB (RETRIP FROM 50BF CB -Q53)


3 x 1 PHASE CT
-T5.745 -F87T1 (TRANSF. DIFF. PROT. M1 OPERATE) +EF11752
-X2744 VDF-10
2000-4000/1A, CL.TPX -F873 (CCP PROT. M1 OPERATE) 500/275kV IBT 3 DIAMETER 7 (MAIN 2)
-T5.744 -F7421...3B
2000-4000/1A, CL.TPX -X2743
-F871CL (275kV CCP LINE M1 OPERATE) 500kV PROTECTION PANEL
-T5.743 -F87T2 (TRANSF. DIFF. PROT. M2 OPERATE) SEE DWG. 0015PJ-03ME-E/L-55-S7-701-04
600-1200/1A, CL.5P20
-X2742 -F874 (CCP PROT. M4 OPERATE) -F87T2 (TRANSF. DIFF. PROT. M2 OPERATE)

C 600-1200/1A, CL.TPX -T5.742 VDF-10 -F872CL (275kV CCP LINE M2 OPERATE) -K863M2 -F87T2 (REF2)
C
-F51PH+N.2 (O/C PROT. 275kV OPERATE)
-X2741 MVAJ105 -F51PH+N.3 (NVD PROT. 70kV OPERATE)
600-1200/1A, CL.TPX -T5.741 -F872CL (275kV CCP LINE M2 OPERATE)
P1

-K863CC2 [-K94RC2] 275kV PROT. M2 OPERATE


MVAJ105 -F874 (CCP PROT. M2 OPERATE)
-F1 -Q3771
3 X SURGE ARRESTER M -K863BBB2
Ur 444kV, 20kA, Class 4 7B7-3E MVAJ105 -F87BBB2 (BUSBAR B PROT. M2 OPERATE)
3 POLE
+EF1102
DISCONNECTING SWITCH WITH EARTHING -Q2771 500kV BUSBAR PROTECTION PANEL
550kV, 4000A, 50kA/1s 7B7-3 BUSBAR B (MAIN 1 & 2) +ES1117
M SEE DWG. PI058-MEN-500-SAS-2561-ED- 500/275kV IBT 3 DIAMETER 7
S3110 500kV AVR PANEL
BUSBAR B SEE DWG. 0015PJ-03ME-E/L-55-S7-701-05
500kV, 4000A, 50KA/1s, BIL 1550kV -X270 -X87BB21.7 F87BB21 -A300
3 POLES -XC03 -X90 -F90 -X300
DISCONNECTOR SWITCH -Q2671 -X271 -X87BB22.7 U><
7B7-2 F87BB22
PANTOGRAPH TYPE FROM 275kV CVT -XV6112 -X90 MICOM C264
550kV, 4000A,50kA/1s M (-T6112, CL. 0.2)
D CURRENT TRANSFORMER
-X300 D
P2

3 x 1 PHASE CT -X2735
2000-4000/1A, CL. TPX -T5.735
-X2734 +EF11752
2000-4000/1A, CL. TPX -T5.734
500/275kV IBT 3 DIAMETER 7 (MAIN 2)
2000-4000/1A, CL. 5P20 -X2733 +EF11751 500kV PROTECTION PANEL
-T5.733 500/275kV IBT 3 DIAMETER 7 (MAIN 1)
20VA @2000A, 40VA @4000A
500kV PROTECTION PANEL SEE DWG. 0015PJ-03ME-E/L-55-S7-701-04
-X2732 SEE DWG. 0015PJ-03ME-E/L-55-S7-701-03 CT-T5.34
2000-4000/1A, CL. TPX -T5.732 //BB1.7C
CT-T5.35 CT-T5.44
-X2731 //BB1.5C //BB1.7C
2000-4000/1A, CL. TPX -T5.731 CT-T5.45 CVTP-T6.711
//BB1.5C //BB1.7E
P1

CVTP-T6.672
//BB1.5E -F87T2
3 POLE -Q5371 CT-T5.43 -X87T2A
CIRCUIT BREAKER 7B7 //BB1.5E -XC42
TRIP COIL 1
3 OPERATING MECHANISM
M TRIP COIL 2
-XC41 -X87T1A -F87T1 -XC911 -X87T2A
550kV, 4000A, 50kA/1s
E -Q2571
E
-XC61 -X87T1A -XC72 -X87T2B
DISCONNECTOR SWITCH 7B7-1
550kV, 4000A, 50kA/1s M -XC71 -X87T1B -XC02 -X87T2B
RET670
-T6.67
3 PHASE CVT -XC01 -X87T1B
MICOM P643
500;√3/0,1;√3/0,1; √3kV -F51PH+N.2
W1 : 15VA, CL.3P
W2 : 15VA, CL.3P
-F51PH+N.1 -XC03 -T71.1 -X51PH+N.2A
W3 : 15VA, CL.0.2 -XC43 -T71.1 -X51PH+N.1A ICT
TO CUTOFF AB 1/1A-10VA
-T6.671

-T6.673

ICT MICOM P14D


-X16733 1/1A-10VA CL.0.2
-T6.672

-XV6672 MICOM P14D


CL.0.2 -X51PH+N.1A FROM 275kV CVT -XV6111 -X51PH+N.2A
-X16722 (-T6111, CL. 3P)

Project Title BLOCK DIAGRAM =S01=D07 Revision 01


500kV DIAMETER 7
F GE Energy Connections Grid Solutions 500/275kV MUARA ENIM
CUTOFF B Drawing No. Sheet Nxt Sht
F
IBT 3 SUBSTATION
0015PJ-03ME-E/L-55-S7-801 /BB0 /BB1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+EW1172 +ES1170 -A30AB


500kV MARSHALLING KIOSK DIAMETER 7
A DIAMETER-7 CUT OFF A/AB 500kV CONTROL -XC23 -X30AB A
SEE DWG. 0015PJ-03ME-E/L55- SEE DWG. 0015PJ-03ME-E/L-55-S7-701-01
S7-701-06 MICOM C264
CVTM-T6.673 -XV6673 FROM CVT-M TEE OFF 2 (CVT-T6.673) -X30AB
//BB0.6A
TO CUTOFF B
-XV6413 FROM CVT-M BUSBAR A (CVT-T6.413) -X30AB
FROM CVT-M BUSBAR A
(CVT-T6.413)
©2016 GE Grid Solutions proprietary and confidential information. All Rights Reserved. This document is the property of GE Grid Solutions and may not be reproduced,

+EF1170

-XC23
DIAMETER 7
500kV BREAKER FAILURE PROTECTION
SEE DWG. 0015PJ-03ME-E/L-55-S7-701-02 -F50BFAB
transmitted, stored, or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solutions.

ICT
1/1A-10VA -X50BFAB
-Q2471 -XC23 CL.0.2 -T71.1
3 POLE 7AB7-2
MICOM P14D
DISCONNECTOR SWITCH
M CVTP-T6.672 -XV6672 FROM CVT-P TEE OFF (-T6.672) -X50BFAB
550kV, 4000A, 50kA/1s //BB0.6B
B B
-XV6412 FROM CVT-P BUSBAR A (CVT-T6.412) -X50BFAB
FROM CVT-P BUSBAR A
(CVT-T6.412)
-F50BFAB (RETRIP FROM 50BF CB -Q52)
-F87T1 (TRANSF. DIFF. PROT. M1 OPERATE)
-F873 (CCP PROT. M1 OPERATE)
CURRENT TRANSFORMER
-F7411...3AB -F7421...3AB

P2
-F871CL (275kV CCP LINE M1 OPERATE)
3 x 1 PHASE CT
2000-4000/1A, CL. TPX
-X2725
-T5.725 -F87T2 (TRANSF. DIFF. PROT. M2 OPERATE)
-F874 (CCP PROT. M2 OPERATE)
2000-4000/1A, CL. TPX -X2724 VDF-10 VDF-10 -F872CL (275kV CCP LINE M2 OPERATE)
-T5.724
[-K94AB] -F50BFAB, OC,U/O VOLTAGE (-Q52)
-K86BF2
2000-4000/1A, CL. 5P20 -X2723 MVAJ105
[-K94A1] 50BF FROM ADJACENT
-T5.723 (CB BUS A FROM OTHER DIAMETER), -F50BFAB (50BF
20VA @2000A, 40VA @4000A
(-Q52))
[-K94B] -F50BFB, 50BF/SZP/OC (-Q53)
2000-4000/1A, CL. TPX -X2722
-T5.722
2000-4000/1A, CL. TPX -X2721 +EF11751 +EF11752
-T5.721 500/275kV IBT 3 DIAMETER 7 (MAIN 1) 500/275kV IBT 3 DIAMETER 7 (MAIN 2)
C 500kV PROTECTION PANEL 500kV PROTECTION PANEL C
P1

SEE DWG. 0015PJ-03ME-E/L-55-S7-701-03 SEE DWG. 0015PJ-03ME-E/L-55-S7-701-04


-F873 -F874
3 POLE -Q5271 CT-T5.35 -XC35 -X873A CT-T5.34 -XC34 -X874A
CIRCUIT BREAKER 7AB7 TRIP COIL 1 //BB0.6E //BB0.7E
3 OPERATING MECHANISM
M TRIP COIL 2 CT-T5.45 -XC45 -X873A CT-T5.44 -XC44 -X874A
550kV, 4000A, 50kA/1s //BB0.6E //BB0.7E
-XC21 -X873B -XC22 -X874B

MICOM P643 REB670


3 POLE
DISCONNECTOR SWITCH -Q2371 -F87T2 (TRANSF. DIFF. PROT. M2 OPERATE)
550kV, 4000A, 50kA/1s 7AB7-1 -F87T2 (REF2)
-F87T1 (TRANSF. DIFF. PROT. M1 OPERATE) -K862M22
M -K862M12 -F87T1 (REF1) MVAJ105
-F51PH+N.2 (O/C PROT. 275kV OPERATE)
-F51PH+N.3 (NVD PROT. 70kV OPERATE)
MVAJ105 -F51PH+N.1 (O/C PROT. 500kV OPERATE) -F872CL (275kV CCP LINE M2 OPERATE)
-F871CL (275kV CCP LINE M1 OPERATE)
-K862CC12 [-K94RC1] 275kV PROT. M1 OPERATE -K862CC22 [-K94RC2] 275kV PROT. M2 OPERATE
MVAJ105 MVAJ105
D -F873 (CCP PROT. M1 OPERATE) -F874 (CCP PROT. M2 OPERATE)
D
-K862TE -K861BBA2
MVAJ105 TRANSF. ELECTROMECHANICAL TRIP MVAJ105 -F87BBA2 (BUSBAR A PROT. M2 OPERATE)
-K861BBA1 -F51PH+N.3
MVAJ105 -F87BBA1 (BUSBAR A PROT. M1 OPERATE)

MICOM P14D
+EF11751 CVTP-T6.711 -XV6711 -X51PH+N.3A
500/275kV IBT 3 DIAMETER 7 (MAIN 1) //BB0.7E
500kV PROTECTION PANEL
3 POLES SEE DWG. 0015PJ-03ME-E/L-55-S7-701-03
DISCONNECTOR SWITCH -Q2171
PANTOGRAPH TYPE 7A7-1 -XC43
550kV, 4000A, 50kA/1s CT-T5.43
M //BB0.6E
CVTP-T6.672 -XV6672
//BB0.6E +EA1102
500kV FAULT RECORDER PANEL
E SEE DWG. 0015PJ 03ME E/L 60 S7 605 E
+EF1101
BUSBAR A 500kV BUSBAR PROTECTION PANEL
BUSBAR A (MAIN 1 & 2)
SEE DWG. PI058-MEN-500-SAS-2561-ED-
S3110

-X270 -X87BB11.7 TP14-S


F87BB11 FR

-X271 -X87BB12.7 TP13


F87BB12

Project Title BLOCK DIAGRAM =S01=D07 Revision 01


500kV DIAMETER 7
F GE Energy Connections Grid Solutions 500/275kV MUARA ENIM
CUTOFF AB Drawing No. Sheet Nxt Sht
F
IBT 3 SUBSTATION
0015PJ-03ME-E/L-55-S7-801 /BB1 ---
1 2 3 4 5 6 7 8
This document is the exclusive property of GE Grid Solutions and shall not be used, copied or communicated to third parties without prior authorization

SSH TR
00 ORIGINAL ISSUE FA
30 NOV 2021 30 NOV 2021
DRAWN BY : CHECKED BY :
NO REVISION STATUS
DATE : DATE :

OWNER
PT PLN ( PERSERO )
UNIT INDUK PEMBANGUNAN SUMATERA BAGIAN SELATAN
Jl. Residen A. Rozak No. 2180, Sekojo Palembang 30118

CONTRACTOR
KONSORSIUM WIJATI-HASTA
Jl. Let Jend S Parman No. 52 Semarang 50232
Telp. 024 8441546 ( Hunting 7 Lines ) Fax. 024 8315360

PROJECT

PEMBANGUNAN EXTENSION IBT 3 GITET 500/275 KV MUARA ENIM ( PAKET ENIM 3 )

CONTRACT No : 0015.PJ/DAN.01.03/UIP SUMBAGSEL/2020, DATE : 16 DESEMBER 2020

DRAWING TITTLE

PROPOSAL PROTECTION RELAY SETTING


GITET 275 KV MUARA ENIM

SHEET : DESIGN BY DRAWN DESIGNED CHECKED APPROVED


30 NOV 2021 30 NOV 2021 30 NOV 2021 30 NOV 2021
1
SCALE :

NA SSH SSH TR AN

PAPER SIZE : DRAWING NO : REVISION NO :

A4 0015PJ-03ME-E/L-02-S6-206 00
CALCULATION NOTE 275kV MUARA ENIM S/S

1. 275kV CIRCULATING CURRENT PROTECTION LINE IBT 3


1.1 CIRCULATING CURRENT PROTECTION MAIN 1
1.1.1 GENERAL DATA
1.1.1.1 Relay's Characteristics
Manufacturer : General Electric

Type : MICOM P643

Product Code : P64391TF6S0910M

Rated Current : in  1A

Rated Voltage : u n  100V


1.1.1.2 Enabling/disabling Differential Protection
No/Yes DIFF Enabled_USER= Yes
1.1.1.3 CT's & VT's Characteristic

Rated Voltage : Ur  275kV

Rated Current : Ir  4kA

In  1A

Rlead : Rlead  6.37Ω

RCTsec : RCTsec  5Ω

Usat : Usat  4kV


CTerror is well out of saturation error
CT err  2% based on CT test report,
(assumed)

1.1.1.4 Relay Electrical Data


Rrelay :
Rrelay  0.1 Ω
Relay Error: Rlyerr  2%

1.1.1.5 Errors
1.1.1.5.1 Misc Errors

Excitation Current Error : IExcERR  3%

Excitation current error are ignore, will be small compare IExcErrHi  0%


with other error at high current:

Rlyerr  2%
Relay Error
1.1.1.5.2 Current Errors
CT errsmall  6%
CT is well out of saturation error based on CT test report,
(assumed)
CT errlarge  6%
CT error at high current based on CT test report, (assumed)
1.1.1.5.3 Voltage Errors
Assumed VLTCerr  0.22%

Rev. 00 DIAMETER 1 1/1


CALCULATION NOTE 275kV MUARA ENIM S/S

1.1.2 CALCULATION SETTING


1.1.2.1 DIFFERENTIAL PROTECTION SETTING
1.1.2.1.1 Amplitude Matching Factors of HV and LV Windings
The matching factors must comply with the following conditions:

a. The matching factors must always be < 3

b. The ratio of the highest to the lower matching factors must be <5

c. The value of the lowest matching factors must be < 0.7


in circulating current protection usually used same CT ration in each winding.
Calculated matching factor: Ir
Kn 
Iref Kn  1.905

1.1.2.1.2 Tripping Characteristics


1.1.2.1.2.1 Nominal rating HV/LV unbalanced current checking in regard with the Tap
Changer
corrected current:
I1  Kn  Iref I1  4000 A

I2  Kn  Iref I2  4000 A
I3  I2 I3  4000 A
Id1
Id1  I1  I2 Id1  0 A

Restraining current : I1  I2


IR1  IR1  4000 A
2
Slope 1 Calculation:
Err Hi  1  IExcERR  Rlyerr  CTerrsmall Err Hi  1.11

1  CTerrsmall
Err Lo 
1  VLTCerr Err Lo  0.938

ErrHi  ErrLo
m1   0.168
0.5  Err Hi  Err Lo 

Slope 2 Calculation:

Err Hi2  1  IExcErrHi  Rlyerr  CT errlarge  1.08

1  CTerrlarge
Err Lo2   0.938
1  VLTCerr
ErrHi2  ErrLo2
m2   0.141
0.5 Err Hi2  ErrLo2

Rev. 00 DIAMETER 1 1/2


CALCULATION NOTE 275kV MUARA ENIM S/S

Idiff1  0.2 pu
Basic threshold value Idiff>
Setting defining the second knee of tripping characteristic Is2  1 pu

Gradient of the tripping characteristic of differential protection


in the range 0.5Idiff1  IR  IRm2
m1  0.17
Recommendation m1 set:
m1set  0.3
Gradient of the tripping characteristic of the differential protection
in the range IR  IRm2
m2  0.141
Recommendation m2 set
m2set  0.8

MICOM P643 tripping characteristics:

1
0.9
0.8
Differential Current

0.7
0.6
y 0.5
0.4
0.3
0.2
0.1
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
x

Restraint Current
We can check that there is enough stability with Idiff1  0.2 m1set  0.3 m2set  0.8 Is2  1 pu

Rev. 00 DIAMETER 1 1/3


CALCULATION NOTE 275kV MUARA ENIM S/S

1. 275kV CIRCULATING CURRENT PROTECTION LINE IBT 3


1.2 CIRCULATING CURRENT PROTECTION MAIN 2
1.2.1 GENERAL DATA
1.2.1.1 Relay's Characteristics
Manufacturer : SIEMENS

Type : 7UT86

Product Code :

Rated Current : in  1A

Rated Voltage : u n  100V


1.2.1.2 Enabling/disabling Differential Protection
No/Yes DIFF Enabled_USER= Yes
1.2.1.3 CT's & VT's Characteristic

Rated Voltage : Ur  275kV

Rated Current : Ir  4kA

In  1A

Rlead : Rlead  6.37Ω

RCTsec : RCTsec  5Ω

Usat : Usat  4kV


CTerror is well out of saturation error
CT err  2% based on CT test report,
(assumed)

1.2.1.4 Relay Electrical Data


Rrelay :
Rrelay  0.1 Ω
Relay Error: Rlyerr  2%

1.2.1.5 Errors
1.2.1.5.1 Misc Errors

Excitation Current Error : IExcERR  3%

Excitation current error are ignore, will be small compare IExcErrHi  0%


with other error at high current:

Rlyerr  2%
Relay Error
1.2.1.5.2 Current Errors
CT errsmall  6%
CT is well out of saturation error based on CT test report,
(assumed)
CT errlarge  6%
CT error at high current based on CT test report, (assumed)
1.2.1.5.3 Voltage Errors
Assumed VLTCerr  0.22%

Rev. 00 IBT 3 1.2/1


CALCULATION NOTE 275kV MUARA ENIM S/S

1.2.2 CALCULATION SETTING


1.2.2.1 DIFFERENTIAL PROTECTION SETTING
1.2.2.1.1 Amplitude Matching Factors of HV and LV Windings
The matching factors must comply with the following conditions:

a. The matching factors must always be < 3

b. The ratio of the highest to the lower matching factors must be <5

c. The value of the lowest matching factors must be < 0.7


in circulating current protection usually used same CT ration in each winding.
Calculated matching factor: Ir
Kn 
Iref Kn  1.905

1.2.2.1.2 Tripping Characteristics


1.2.2.1.2.1 Nominal rating HV/LV unbalanced current checking in regard with the Tap
Changer
corrected current:
I1  Kn  Iref I1  4000 A

I2  Kn  Iref I2  4000 A
I3  I2 I3  4000 A
Id1
Id1  I1  I2 Id1  0 A

Restraining current : I1  I2


IR1  IR1  4000 A
2
Slope 1 Calculation:
Err Hi  1  IExcERR  Rlyerr  CTerrsmall Err Hi  1.11

1  CTerrsmall
Err Lo 
1  VLTCerr Err Lo  0.938

ErrHi  ErrLo
m1   0.168
0.5  Err Hi  Err Lo 

Slope 2 Calculation:

Err Hi2  1  IExcErrHi  Rlyerr  CT errlarge  1.08

1  CTerrlarge
Err Lo2   0.938
1  VLTCerr
ErrHi2  ErrLo2
m2   0.141
0.5 Err Hi2  ErrLo2

Rev. 00 IBT 3 1.2/2


CALCULATION NOTE 275kV MUARA ENIM S/S

Idiff1  0.2 pu
Basic threshold value Idiff>
Setting defining the second knee of tripping characteristic Is2  1 pu

Gradient of the tripping characteristic of differential protection


in the range 0.5Idiff1  IR  IRm2
m1  0.17
Recommendation m1 set:
m1set  0.3
Gradient of the tripping characteristic of the differential protection
in the range IR  IRm2
m2  0.141
Recommendation m2 set
m2set  0.8

MICOM P643 tripping characteristics:

1
0.9
0.8
Differential Current

0.7
0.6
y 0.5
0.4
0.3
0.2
0.1
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
x

Restraint Current
We can check that there is enough stability with Idiff1  0.2 m1set  0.3 m2set  0.8 Is2  1 pu

Rev. 00 IBT 3 1.2/3


CALCULATION NOTE 275kV MUARA ENIM S/S

2. 275kV CIRCULATING CURRENT PROTECTION DIAMETER 1


2.1 CIRCULATING CURRENT PROTECTION MAIN 1
2.1.1 GENERAL DATA
2.1.1.1 Relay's Characteristics
Manufacturer : General Electric

Type : MICOM P643

Product Code : P64391TF6S0910M

Rated Current : in  1A

Rated Voltage : u n  100V


2.1.1.2 Enabling/disabling Differential Protection
No/Yes DIFF Enabled_USER= Yes
2.1.1.3 CT's & VT's Characteristic

Rated Voltage : Ur  275kV

Rated Current : Ir  4kA

In  1A

Rlead : Rlead  6.37Ω

RCTsec : RCTsec  5Ω

Usat : Usat  4kV


CTerror is well out of saturation error
CT err  2% based on CT test report,
(assumed)

2.1.1.4 Relay Electrical Data


Rrelay :
Rrelay  0.1 Ω
Relay Error: Rlyerr  2%

2.1.1.5 Errors
2.1.1.5.1 Misc Errors

Excitation Current Error : IExcERR  3%

Excitation current error are ignore, will be small compare IExcErrHi  0%


with other error at high current:

Rlyerr  2%
Relay Error
2.1.1.5.2 Current Errors
CT errsmall  6%
CT is well out of saturation error based on CT test report,
(assumed)
CT errlarge  6%
CT error at high current based on CT test report, (assumed)
2.1.1.5.3 Voltage Errors
Assumed VLTCerr  0.22%

Rev. 00 DIAMETER 1 2/1


CALCULATION NOTE 275kV MUARA ENIM S/S

2.1.2 CALCULATION SETTING


2.1.2.1 DIFFERENTIAL PROTECTION SETTING
2.1.2.1.1 Amplitude Matching Factors of HV and LV Windings
The matching factors must comply with the following conditions:

a. The matching factors must always be < 3

b. The ratio of the highest to the lower matching factors must be <5

c. The value of the lowest matching factors must be < 0.7


in circulating current protection usually used same CT ration in each winding.
Calculated matching factor: Ir
Kn 
Iref Kn  1.905

2.1.2.1.2 Tripping Characteristics


2.1.2.1.2.1 Nominal rating HV/LV unbalanced current checking in regard with the Tap
Changer
corrected current:
I1  Kn  Iref I1  4000 A

I2  Kn  Iref I2  4000 A
I3  I2 I3  4000 A
Id1
Id1  I1  I2 Id1  0 A

Restraining current : I1  I2


IR1  IR1  4000 A
2
Slope 1 Calculation:
Err Hi  1  IExcERR  Rlyerr  CTerrsmall Err Hi  1.11

1  CTerrsmall
Err Lo 
1  VLTCerr Err Lo  0.938

ErrHi  ErrLo
m1   0.168
0.5  Err Hi  Err Lo 

Slope 2 Calculation:

Err Hi2  1  IExcErrHi  Rlyerr  CT errlarge  1.08

1  CTerrlarge
Err Lo2   0.938
1  VLTCerr
ErrHi2  ErrLo2
m2   0.141
0.5 Err Hi2  ErrLo2

Rev. 00 DIAMETER 1 2/2


CALCULATION NOTE 275kV MUARA ENIM S/S

Idiff1  0.2 pu
Basic threshold value Idiff>
Setting defining the second knee of tripping characteristic Is2  1 pu

Gradient of the tripping characteristic of differential protection


in the range 0.5Idiff1  IR  IRm2
m1  0.17
Recommendation m1 set:
m1set  0.3
Gradient of the tripping characteristic of the differential protection
in the range IR  IRm2
m2  0.141
Recommendation m2 set
m2set  0.8

MICOM P643 tripping characteristics:

1
0.9
0.8
Differential Current

0.7
0.6
y 0.5
0.4
0.3
0.2
0.1
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
x

Restraint Current
We can check that there is enough stability with Idiff1  0.2 m1set  0.3 m2set  0.8 Is2  1 pu

Rev. 00 DIAMETER 1 2/3


CALCULATION NOTE 275kV MUARA ENIM S/S

2. 275kV CIRCULATING CURRENT PROTECTION DIAMETER 1


2.2 CIRCULATING CURRENT PROTECTION MAIN 2
2.2.1 GENERAL DATA
2.2.1.1 Relay's Characteristics
Manufacturer : SIEMENS

Type : 7UT86

Product Code :

Rated Current : in  1A

Rated Voltage : u n  100V


2.2.1.2 Enabling/disabling Differential Protection
No/Yes DIFF Enabled_USER= Yes
2.2.1.3 CT's & VT's Characteristic

Rated Voltage : Ur  275kV

Rated Current : Ir  4kA

In  1A

Rlead : Rlead  6.37Ω

RCTsec : RCTsec  5Ω

Usat : Usat  4kV


CTerror is well out of saturation error
CT err  2% based on CT test report,
(assumed)

2.2.1.4 Relay Electrical Data


Rrelay :
Rrelay  0.1 Ω
Relay Error: Rlyerr  2%

2.2.1.5 Errors
2.2.1.5.1 Misc Errors

Excitation Current Error : IExcERR  3%

Excitation current error are ignore, will be small compare IExcErrHi  0%


with other error at high current:

Rlyerr  2%
Relay Error
2.2.1.5.2 Current Errors
CT errsmall  6%
CT is well out of saturation error based on CT test report,
(assumed)
CT errlarge  6%
CT error at high current based on CT test report, (assumed)
2.2.1.5.3 Voltage Errors
Assumed VLTCerr  0.22%

Rev. 00 IBT 3 2.2/1


CALCULATION NOTE 275kV MUARA ENIM S/S

2.2.2 CALCULATION SETTING


2.2.2.1 DIFFERENTIAL PROTECTION SETTING
2.2.2.1.1 Amplitude Matching Factors of HV and LV Windings
The matching factors must comply with the following conditions:

a. The matching factors must always be < 3

b. The ratio of the highest to the lower matching factors must be <5

c. The value of the lowest matching factors must be < 0.7


in circulating current protection usually used same CT ration in each winding.
Calculated matching factor: Ir
Kn 
Iref Kn  1.905

2.2.2.1.2 Tripping Characteristics


2.2.2.1.2.1 Nominal rating HV/LV unbalanced current checking in regard with the Tap
Changer
corrected current:
I1  Kn  Iref I1  4000 A

I2  Kn  Iref I2  4000 A
I3  I2 I3  4000 A
Id1
Id1  I1  I2 Id1  0 A

Restraining current : I1  I2


IR1  IR1  4000 A
2
Slope 1 Calculation:
Err Hi  1  IExcERR  Rlyerr  CTerrsmall Err Hi  1.11

1  CTerrsmall
Err Lo 
1  VLTCerr Err Lo  0.938

ErrHi  ErrLo
m1   0.168
0.5  Err Hi  Err Lo 

Slope 2 Calculation:

Err Hi2  1  IExcErrHi  Rlyerr  CT errlarge  1.08

1  CTerrlarge
Err Lo2   0.938
1  VLTCerr
ErrHi2  ErrLo2
m2   0.141
0.5 Err Hi2  ErrLo2

Rev. 00 IBT 3 2.2/2


CALCULATION NOTE 275kV MUARA ENIM S/S

Idiff1  0.2 pu
Basic threshold value Idiff>
Setting defining the second knee of tripping characteristic Is2  1 pu

Gradient of the tripping characteristic of differential protection


in the range 0.5Idiff1  IR  IRm2
m1  0.17
Recommendation m1 set:
m1set  0.3
Gradient of the tripping characteristic of the differential protection
in the range IR  IRm2
m2  0.141
Recommendation m2 set
m2set  0.8

MICOM P643 tripping characteristics:

1
0.9
0.8
Differential Current

0.7
0.6
y 0.5
0.4
0.3
0.2
0.1
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
x

Restraint Current
We can check that there is enough stability with Idiff1  0.2 m1set  0.3 m2set  0.8 Is2  1 pu

Rev. 00 IBT 3 2.2/3


CALCULATION NOTE MUARA ENIM 275kV S/S

3.1 BREAKER FAILURE & SZP PROTECTION DIAMETER 1


3.1.1 GENERAL DATA
3.1.1.1 Relay's Characteristics
Manufacturer : GE

Type : MiCOM P14D

Cortec : P14DL26A6C0560A

Rated Current :
in  1A
Maximum fault current :
if  50kA
Fault withstanding duration :
twithstand  1s

3.1.1.2 CT's characteristics


Rated voltage : Ur  71.5kV

Rated current : Ir  2000A

3.1.2 CALCULATION SETTING


3.1.2.1 Circuit Breaker Failure
Operation Scheme
when a fault occurs, one or more protection devices will operate and issue a trip command to the
relevant circuit breakers. operation of the circuit breaker is essential to isolate the fault and
prevent, or at least limit, damage to the power system. If the fault current has not been interrupted
a set time delay from circuit breaker trip initiation, the CBF protection will operate, whreby the
upstream circuit breakers are back triped to ensure that the fault is isolated.
CBFail 1 Status: Enabled
CBFail 1 Timer: 0.15s
CBFail 2 Status: Enabled
CBFail 2 Timer: 0.25s
Volt Prot Reset: I  Only
Ext Prot Reset: I  Only

I< Current Set: Iuc  20%  in Iuc  0.2 A

ISEF< Current Set: Isef  50%  in Isef  0.5 A

REV. 00 IBT 3 3.1/1


CALCULATION NOTE MUARA ENIM 275kV S/S

3.1.2.2 Short Zone Protection


Operation Scheme
SZP principle bay be extended by setting fast-acting overcurrent elements on the incoming
feeders to a substation, which are then arranged to be blocked by start contacts from the devices
protecting the putgoing feeders. This allowed to trip for a fault condition on the busbar, but is
stable for external faults due to the blocking signal.
I >1 Status: Enabled

I>1 Function: DT

I>1 Directional: NonDirectional


I>1 Current Set:
1A
I>1 Time Delay:
70ms
I>1 Treset: 0s

I >2 Status: Enabled

I>2 Function: DT

I>2 Directional: NonDirectional


I>2 Current Set:
1A
I>2 Time Delay:
150ms
I>2 Treset: 0s

REV. 00 IBT 3 3.1/2


+DWT03
DIAMETER 5 DIAMETER 4 +DWT01 +DWT02 IBT 3
+DWL01 +DWL02 DIAMETER 3 DIAMETER 2 DIAMETER 1
IBT 1 IBT 2 INCOMING FEEDER IBT 3 BAY
=D05 LUMUT BALAI LINE 1 =D04 LUMUT BALAI LINE 2 =D03 =D02 =D01

FROM 500 / 275 / 67 KV IBT 1 FROM 500 / 275 / 67 KV IBT 2 FROM 500 / 275 / 67 KV IBT 3

ACSR/AS 2X450 mm2

BUSBAR A , TAL 2X660 mm2 275 KV, 40KA/1s, BIL 1050KV, 50HZ

TAL 2X510 mm2 TAL 2X510 mm2 TAL 2X510 mm2 TAL 2X510 mm2 TAL 2X510 mm2

TAL 2X510 mm2 TAL 2X510 mm2 TAL 2X510 mm2


This document is the property of PT. WIJATI AJI, Copyright to be observed

TAL 2X510 mm2

TAL 2X510 mm2 TAL 2X510 mm2

BUSBAR B , TAL 2X660 mm2 275 KV, 40KA/1s, BIL 1050KV, 50HZ

GUMAWANG LINE 1 GUMAWANG LINE 2 FUTURE LINE BAY FUTURE LINE BAY FUTURE LINE BAY
+DWL03 +DWL04 +DWL0# +DWL0# +DWL0#

PT. PLN (PERSERO)


UNIT INDUK PEMBANGUNAN SUMATRA BAGIAN SELATAN

CONTRACT No. : 0015.PJ/DAN.01.03/UIP SUMBAGSEL/2020. TANGGAL 16 DESEMBER 2020

PEMBANGUNAN EXTENSION IBT-3


GITET 500/275 kV MUARA ENIM
(PAKET ENIM 3)
KONSORSIUM
WIJATI - HASTA

SINGLE LINE DIAGRAM


GITET 275 kV MUARA ENIM

0015PJ-03ME-E/L-51-S6-401
1 2 3 4 5 6 7 8

A A
©2016 Grid Solution proprietary and confidential information. All rights Reserved. This document is the property of Grid Solu tion and may not be reproduced,
transmitted, stored or copied in whole or in part, or used to furnish information to others, without the prior written permission of Grid Solution

B B

AE TR
01 AS MANUFACTURE AM
12/1/2021 12/1/2021

AE TR
00 ORIGINAL ISSUE FA
4/23/2021 4/23/2021
DRAWN BY : CHECKED BY :
NO REVISION STATUS
DATE : DATE :

C OWNER C
PT PLN ( PERSERO )
UNIT INDUK PEMBANGUNAN SUMATERA BAGIAN SELATAN
Jl. Residen A. Rozak No. 2180, Sekojo Palembang 30118

CONTRACTOR
KONSORSIUM WIJATI-HASTA
Jl. Let Jend S Parman No. 52 Semarang 50232
Telp. 024 8441546 ( Hunting 7 Lines ) Fax. 024 8315360
D PROJECT D

PEMBANGUNAN EXTENSION IBT 3 GITET 500/275 KV MUARA ENIM ( PAKET ENIM 3 )

CONTRACT No : 0015.PJ/DAN.01.03/UIP SUMBAGSEL/2020, DATE : 16 DESEMBER 2020

DRAWING TITTLE

E BLOCK DIAGRAM - DIAMETER 1 & CONNECTION 500/275 KV E


GITET 275kV MUARA ENIM

SHEET : DESIGN BY DRAWN DESIGNED CHECKED APPROVED


/A1 12/1/2021 4/23/2021 12/1/2021 12/1/2021

SCALE :

NTS
AE DKP TR AN
F PAPER SIZE : DRAWING NO : F
REVISION NO :
A4 0015PJ-03ME-E/L-55-S6-801 01
1 2 3 4 5 6 7 8
Revision Drawn by Checked by Approved by
Modification
Drawn Date Checked Date Approved Date

00 ARIF TEDDY AUFAR ORIGINAL ISSUE


4/23/2021 4/23/2021 4/23/2021
©2016 GE Grid Solutions proprietary and confidential information. All Rights Reserved. This document is the property of GE Grid Solutions and may not be reproduced,

01 ARIF TEDDY AUFAR AS MANUFACTURE


12/1/2021 12/1/2021 12/1/2021
transmitted, stored,or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solutions.

Project Title
DRAWING REVISION
Revision 01
GE Energy Connections Grid Solutions 500/275kV MUARA ENIM
Drawing No. Sheet Nxt Sht
IBT 3 SUBSTATION
0015PJ-03ME-E/L-55-S6-801 /AA1 /AB
Designation Title line 1 Title line 2 Title line 3 Title line 4 R1 R2 R3 R4 R5 R6 R7 R8
/A1 COVER SHEET 00 01
/AA1 DRAWING REVISION 00 01
/AB DRAWING CONTENT 00 01
/BB0 BLOCK DIAGRAM 275kV DIAMETER 1 CUTOFF A 00 01
/BB1 BLOCK DIAGRAM 275kV DIAMETER 1 CUTOFF AB 00 01
©2016 GE Grid Solutions proprietary and confidential information. All Rights Reserved. This document is the property of GE Grid Solutions and may not be reproduced,
transmitted, stored,or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solutions.

Project Title
DRAWING CONTENT
Revision 01
GE Energy Connections Grid Solutions 500/275kV MUARA ENIM
Drawing No. Report
IBT 3 SUBSTATION /AB 1 of 1
0015PJ-03ME-E/L-55-S6-801
1 2 3 4 5 6 7 8
+EW1111 =D01+W1
275kV MARSHALLING KIOSK DIAMETER 1
DIAMETER-1 CUT OFF A 275kV CONTROL
A SEE DWG. 0015PJ-03ME-E/EL- SEE DWG. 0015PJ-03ME-E/L-55-S6-701-01 A
55-S6-701-05 -A30A
-XC43 -X30A

MICOM C264
-XV6012 -X30A
FROM CVT-M BUSBAR A (CVT-T6.012)

FROM 500/275/67kV IBT3 -XV6112 FROM CVT-M TEE OFF (CVT-T6.112) -X30A
©2016 GE Grid Solutions proprietary and confidential information. All Rights Reserved. This document is the property of GE Grid Solutions and may not be reproduced,

TO AVR -XV6112 CVTM-T6.112


IN 500kV PANEL //BB1.5A
SURGE ARRESTER (3P) -F2
240kV 20kA
transmitted, stored, or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solutions.

=D01+R5 =D01+R1
DIAMETER 1 INCOMING IBT 3 DIAMETER 1
CURRENT TRANSFORMER

P2
3 x 1 PHASE CT -X2145 275kV BREAKER FAILURE PROTECTION 275kV PROTECTION PANEL MAIN 1
-T5.145 SEE DWG. 0015PJ-03ME-E/L-55-S6-701-02 SEE DWG. 0015PJ-03ME-E/L-55-S6-701-03
B 2000-4000/1A, CL. TPX B
-X2144 -F50BFA -K861M1 -F871CL (CCP PROT. FOR LINE M1 OPERATE)
2000-4000/1A, CL. TPX -T5.144 -XC33 -X50BFA
MVAJ105 [-K94RC1] (500kV PROTECTION OPERATE)
2000-4000/1A, CL. 0.2s
-X2143
-T5.143 FROM CVT-M BUSBAR A -XV6011 -X50BFA MICOM P14D -K861CC1
20(@2000A)/40(@4000A)VA
-X2142 (CVT-T6.011 MVAJ105 -F871 (CCP PROT. M1 OPERATE)
2000-4000/1A, CL. TPX -T5.142 -X50BFA
FROM CVT-P TEE OFF (-T6.111) -XV6111 -K861BBA1
-X2141 MVAJ105 -F87BBA1 (BUSBAR A PROT. M1 OPERATE)
2000-4000/1A, CL. TPX -T5.141 CVTP-T6.111
P1

//BB1.5B
TO -F51PH+N.2 -XV6111
-Q38 (OCR 275kV PROT. RELAY MICOM P14D) -F7411...3A
M IN 500kV PANEL [-K94A] -F50BFA, OC,U/O VOLTAGE (-Q51)
6A1-3E -K86BF1
[-K94A1] 50BF FROM ADJACENT
MVAJ105 (CB BUS A FROM OTHER DIAMETER), -F50BFA (50BF
3 POLE DS WITH EARTHING
(-Q51))
300kV, 3150A, 40kA/1s -Q28 VDF-10
[-K94AB] -F50BFAB, 50BF/SZP/OC (-Q52)
6A1-3 M -F7421...3A
C C
=D01+R2
VDF-10
INCOMING IBT 3 DIAMETER 1
-F50BFA (RETRIP FROM 50BF CB -Q51) 275kV PROTECTION PANEL MAIN 2
-F871CL (CCP PROT. FOR LINE M1 OPERATE)
-F871 (CCP PROT. M1 OPERATE)
SEE DWG. 0015PJ-03ME-E/L-55-S6-701-04
-K861BBA1 ((BUSBAR A PROT. M1 OPERATE)) -K861M2
BUSBAR A MVAJ105 -F872CL (CCP PROT. FOR LINE M1 OPERATE)

[-K94RC2] (500kV PROTECTION OPERATE)


-K861CC2
DISCONNECTOR SWITCH -Q20
MVAJ105
300kV, 3150A, 40kA 6A1-1 -F872CL (CCP PROT. FOR LINE M2 OPERATE) -F872 (CCP PROT. M2 OPERATE)
-F872 (CCP PROT. M2 OPERATE)
M
-K861BBA2 ((BUSBAR A PROT. M2 OPERATE))
-K861BBA2
CURRENT TRANSFORMER MVAJ105 -F87BBA2 (BUSBAR A PROT. M2 OPERATE)
P2

3 x 1 PHASE CT -X2115
2000-4000/1A, CL. TPX -T5.115 CT-T5.44
//BB1.7D
-X2114 CT-T5.14
D 2000-4000/1A, CL. TPX -T5.114 //BB1.7D D
-X2113 -F872CL
2000-4000/1A, CL. 5P20 =D01+R1
-T5.113 -XC04 -X872CLA
20(@2000A)/40(@4000A)VA INCOMING IBT 3 DIAMETER 1
-X2112 275kV PROTECTION PANEL MAIN 1
2000-4000/1A, CL. TPX -T5.112 -X872CLA
SEE DWG. 0015PJ-03ME-E/L-55-S6-701-03 -XC42
-X2111 CT-T5.45 7UT86
2000-4000/1A, CL. TPX -T5.111 //BB1.5D
P1

CT-T5.15
//BB1.5D
CIRCUIT BREAKER -Q51 -F871CL
3 POLE OPERATED FROM CT 275kV (-T5.104)
6A1 TRIP COIL 1
-XC05 -X871CLA
300kV, 4000A, 50kA FROM CT 275kV (-T5.105) (SEE BLOCK DIAGRAM 500kV)
M TRIP COIL 2
(SEE BLOCK DIAGRAM 500kV)
DISCONNECTOR SWITCH -Q21 -XC41 -X871CLA
300kV, 3150A, 40kA 6A1-2 =D00+R1
MICOM P643
M -XC41 275kV BUSBAR A PROTECTION PANEL (EXISTING)
-T6.11 SEE DWG. (3)G73011-E3234-S110001
E E
3 PHASE CVT
275;√3/0,1;√3/0,1; √3kV =D00+DX5
W1 : 30VA, CL.3P DIGITAL FAULT RECORDER PANEL 5
W2 : 30VA, CL.0.2 SEE DWG. 0015PJ-03ME-E/L-60-S6-605
TO CUTOFF AB
X8715
-T6.111

-T6.112

TP12-S F87BA.M1
-X16112 FR

-X16111 TP11 X8725


F87BA.M2

Project Title BLOCK DIAGRAM =S01=D01 Revision 01


275kV DIAMETER 1
F GE Energy Connections Grid Solutions 500/275kV MUARA ENIM
CUTOFF A Drawing No. Sheet Nxt Sht
F
IBT 3 SUBSTATION
0015PJ-03ME-E/L-55-S6-801 /BB0 /BB1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+EW1112 =D01+W1 -A30AB


275kV MARSHALLING KIOSK DIAMETER 1
A DIAMETER-1 CUT OFF AB 275kV CONTROL -XC23 -X30AB A
SEE DWG. 0015PJ-03ME-E/EL-55- SEE DWG. 0015PJ-03ME-E/L-55-S6-701-01
S6-701-06 MICOM C264
CVTM-T6.112 -XV6112 FROM CVT-M TEE OFF (-T6.112) -X30AB
//BB0.6B
TO CUTOFF A
-XV6022 FROM CVT-M BUSBAR B (CVT-T6.022) -X30AB
FROM CVT-M BUSBAR B
(CVT-T6.022)
©2016 GE Grid Solutions proprietary and confidential information. All Rights Reserved. This document is the property of GE Grid Solutions and may not be reproduced,

=D01+R5

-XC23
DIAMETER 1
275kV BREAKER FAILURE PROTECTION -F50BFAB
transmitted, stored, or copied in whole or in part, or used to furnish information to others, without the prior written permission of GE Grid Solutions.

SEE DWG. 0015PJ-03ME-E/L-55-S6-701-02 ICT


1/1A-10VA -X50BFAB
-Q22 -XC23 CL.0.2 -T71.1
DISCONNECTOR SWITCH 6AB1-1
MICOM P14D
300kV, 3150A, 40kA
M CVTP-T6.111 -XV6111 FROM CVT-P TEE OFF (-T6.111) -X50BFAB
//BB0.6C
B B
-XV6021 FROM CVT-M BUSBAR B (CVT-T6.021) -X50BFAB
FROM CVT-M BUSBAR B
(CVT-T6.021)

-F7411...3AB -F7421...3AB
CURRENT TRANSFORMER

P2
3 x 1 PHASE CT
2000-4000/1A, CL. TPX
-X2125
-T5.125 VDF-10 VDF-10
[-K94AB] -F50BFAB, OC,U/O VOLTAGE (-Q52)
2000-4000/1A, CL. TPX -X2124 -K86BF2
-T5.124 [-K94B1] 50BF FROM ADJACENT
MVAJ105 (CB BUS B FROM OTHER DIAMETER), -F50BFAB (50BF
2000-4000/1A, CL. 5P20 -X2123 (-Q52))
20(@2000A)/40(@4000A)VA -T5.123 -K863BBB1
[-K94A] -F50BFA, 50BF/SZP/OC (-Q51)
-F872CL (CCP PROT. FOR LINE M2 OPERATE)
2000-4000/1A, CL. TPX -X2122 -F872 (CCP PROT. M2 OPERATE)
MVAJ105 -F87BBB1 (BUSBAR B PROT. M1 OPERATE)
-T5.122 -K863BBB2 ((BUSBAR B PROT. M2 OPERATE)) -K863BBB2
2000-4000/1A, CL. TPX -X2121 -F50BFAB (RETRIP FROM 50BF CB -Q52)
MVAJ105 -F87BBB2 (BUSBAR B PROT. M2 OPERATE)
-T5.121 -F871CL (CCP PROT. FOR LINE M1 OPERATE)
C C
P1

-F871 (CCP PROT. M1 OPERATE)


-K863BBB1 ((BUSBAR B PROT. M1 OPERATE))

CIRCUIT BREAKER -Q52


3 POLE OPERATED 6AB1 TRIP COIL 1
=D01+R1 =D01+R2
300kV, 4000A, 50kA TRIP COIL 2 INCOMING IBT 3 DIAMETER 1 INCOMING IBT 3 DIAMETER 1
M
275kV PROTECTION PANEL MAIN 1 275kV PROTECTION PANEL MAIN 2
SEE DWG. 0015PJ-03ME-E/L-55-S6-701-03 SEE DWG. 0015PJ-03ME-E/L-55-S6-701-04
-F871 -F872
DISCONNECTOR SWITCH
CT-T5.45 -XC45 -X871A CT-T5.44 -XC44 -X872A
300kV, 3150A, 40kA -Q23 //BB0.5D //BB0.7D
6AB1-2
M CT-T5.15 -XC15 -X871A CT-T5.14 -XC14 -X872A
//BB0.5E //BB0.7D
-XC21 -X871B -XC22 -X872B
D MICOM P643 7UT86 D

-F872CL (CCP PROT. FOR LINE M2 OPERATE)


-K862M11 -F871CL (CCP PROT. FOR LINE M1 OPERATE) -K862M21
MVAJ105 [-K94RC1] (500kV PROTECTION OPERATE) MVAJ105 [-K94RC2] (500kV PROTECTION OPERATE)

-K862CC11 -K862CC21
MVAJ105 -F871 (CCP PROT. M1 OPERATE)
MVAJ105 -F872 (CCP PROT. M2 OPERATE)

E =D00+R2 E
275kV BUSBAR B PROTECTION PANEL (EXISTING)
SEE DWG. (3)G73011-E3234-S110002
BUSBAR B

X8715
F87BB.M1

X8725
F87BB.M2

Project Title BLOCK DIAGRAM =S01=D01 Revision 01


275kV DIAMETER 1
F GE Energy Connections Grid Solutions 500/275kV MUARA ENIM
CUTOFF AB Drawing No. Sheet Nxt Sht
F
IBT 3 SUBSTATION
0015PJ-03ME-E/L-55-S6-801 /BB1 ---
1 2 3 4 5 6 7 8