Client: Contractor:

PT. PERTAMINA HULU ROKAN PT. EPSINDO JAYA PRATAMA

PENGADAAN 2 (DUA) UNIT POMPA INJEKSI HORIZONTAL PUMP


SYSTEM DI WIP ALUR BEMBAN FIELD RANTAU

PROJECT TITLE : PENGADAAN 2 (DUA) UNIT POMPA INJEKSI


HORIZONTAL PUMP SYSTEM
PROJECT LOCATION : WIP ALUR BEMBAN
DOCUMENT TITLE : CABLE SIZING
DOCUMENT NO. : PHR-Z1-OSF-RTU-21-NON AFE-EL-CAL-001

Attachment No.

Attachment No. of Pages

PT. EJP PT. PHR


REV DATE PURPOSE
ORIGIN CHECK APPR CHECK APPR DATE

A 08/07/2022 Issued for Review MTH SDR REI ARN/BS DN

B 05/09/2022 Issued for Approval MTH SDR REI ARN/BS DN

C 28/09/2022 Issued for Construction MTH SDR REI ARN/BS DN


Doc No. : PHR-Z1-OSF-RTU-21-NON
ELECTRICAL AFE-EL-CAL-001
Rev : C
Date : 28/ 09 / 2022
CABLE SIZING
Page : 2 of 6

TABULATION OF REVISION SHEET

REVISION REVISION
SHEET REMARKS SHEET REMARKS
A B C
1/6 x x x

2/6 x x x

3/6 x x x

4/6 x x x

5/6 x x x

6/6 x x x

ATTACHMENT
Doc No. : PHR-Z1-OSF-RTU-21-NON
ELECTRICAL AFE-EL-CAL-001
Rev : C
Date : 28/ 09 / 2022
CABLE SIZING
Page : 3 of 6

REVISION SHEET DESCRIPTION

NO PAGE SUBJECT DESCRIPTION OF CHANGE REV

1 6 Cable Sizing Revisi keterangan Cable Sizing B

2 6 Cable Sizing Revisi keterangan Cable Sizing C


Doc No. : PHR-Z1-OSF-RTU-21-NON
ELECTRICAL AFE-EL-CAL-001
Rev : C
Date : 29/ 09 / 2022
CABLE SIZING
Page : 4 of 6

COMMENTED RESPONSE SHEET

NO PAGE SUBJECT DESCRIPTION OF CHANGE REV

1 6 Cable Sizing Revisi keterangan Cable Sizing B


2 6 Cable Sizing Revisi keterangan Cable Sizing C
Doc No. : PHR-Z1-OSF-RTU-21-NON
ELECTRICAL AFE-EL-CAL-001
Rev : C
Date : 28/ 09 / 2022
CABLE SIZING
Page : 5 of 6

TABLE OF CONTENT

COVER SHEET…........................................................................................................................ 1
TABULATION OF REVISION SHEET……………….................................................................... 2
RECORD OF REVISION…........................................................................................................... 3
COMMENT RESPONSE SHEET…………………………............................................................. 4
TABLE OF CONTENT….............................................................................................................. 5
CABLE SIZING……….….………………………............................................................................. 6
Doc No. : PHR-Z1-OSF-RTU-21-NON
ELECTRICAL AFE-EL-CAL-001
Rev : C
Date : 29/ 09 / 2022
CABLE SIZING
Page : 6 of 6

CABLE SIZING

From Length Load Ib In Ca Size Cable Ig Ia Vd


ID To Device Cg It (A)
Device (M) (kW) (A) (A) 30°C Recom (A) (A) (V)
MV Panel
P-RTU- N2XSEBY
Existing WIP D&E
SWG- 85 475 54 68 1 0.7 97 3Cx1x 204 226 2.8
Cubicle RTU -SWG
18002 50 mm2
18002
MV Panel TRAFO
P-RTU- N2XSEBY
WIP D&E WIP 3
TRF- 15 475 54 68 1 0.7 97 3Cx1x 205 226 0.5
RTU -SWG - RTU-TRF-
18003 50 mm2
18002 18003
TRAFO WIP LV Panel
P-RTU- NYY 1 C x
3 WIP D & E 5x 5x
SWG- 18 475 902 1128 1 0.43 2623 5 x 240 1.0
RTU-TRF- RTU-SWG- 640 620
18003 mm2
18003 18003
Diesel LV Panel
NYY 1 C x
P-RTU-G- Generator WIP D&E 2x 2x
120 238 451 564 1 0.57 989 2 x 240 3.4
18303 RTU-G- RTU-SWG- 640 620
mm2
18303 18003
LV Panel TRAFO
P-RTU- NYY 1 C x
WIP D&E WIP D 2x 2x
TRF- 14 238 451 564 1 0.57 989 2 x 240 0.4
RTU-SWG- RTU-TRF- 640 620
18004 mm2
18003 18004
TRAFO WIP
P-RTU- NYY 1 C x
D RTU-MCC- 2x 2x
MCC- 22 238 357 446 1 0.57 783 2 x 240 0.5
RTU-TRF- 18018 640 620
18018 mm2
18004
P-RTU- NYY 1 C x
RTU-MCC- RTU-EM- 2x 2x
EM- 40 238 357 446 1 0.57 783 2 x 240 0.9
18018 18018 640 620
18018 mm2
LV Panel TRAFO
P-RTU- NYY 1 C x
WIP D&E WIP E 2x 2x
TRF- 12 238 451 564 1 0.57 989 2 x 240 0.3
RTU-SWG- RTU-TRF- 620 620
18005 mm2
18003 18005
TRAFO WIP
P-RTU- NYY 1 C x
E RTU-MCC- 2x 2x
MCC- 20 238 357 446 1 0.57 783 2 x 240 0.4
RTU-TRF- 18019 640 620
18019 mm2
18005
P-RTU- NYY 1 C x
RTU-MCC- RTU-EM- 2x 2x
EM- 50 238 357 446 1 0.57 783 2 x 240 1.1
18019 18019 640 620
18019 mm2

Notes :
Ib : Load Current It : Calculation of Current Rating
In : Safety Factor 1.25 x Ib Ig : Current Carrying Capacity @30°C in Ground
Ca : Rating Factor of Ambient Temp @ 70°C thermoplastic Ia : Current Carrying Capacity @30°C in Air
Cg : Rating Factor Cable Grouping Vd : Voltage drop