You are on page 1of 8

DATA SHEET FOR

HV SWITCHGEAR 20kV

Document No. : Rev. A


DED EXPANSION NICKEL HEAP LEACH
Page :
BMR-ELC-DTS-ST-0003 5,000 T/Y
1 of 8

CLIENT : PT. BUKIT MAKMUR RESOURCES


VENDOR : PT. SIKO TECHNO
PROJECT NAME : DED EXPANSION NICKEL HEAP LEACH 5,000 T/Y
LOCATION : KABAENA ISLAND - SOUTH-EAST SULAWESI
CONTRACT NO. : BMR/PRC/2022/VI/048/SKLR

A 11-Dec-2022 Issued For Review GTP NIC YYT


PREPARED BY CHECKED BY REVIEWED BY APPROVED BY

Rev DATE DESCRIPTION PT. BUKIT MAKMUR


PT. SIKO TECHNO
RESOURCES
DATA SHEET FOR 
HV SWITCHGEAR 20kV
DOCUMENT NO. Rev. A
DED EXPANSION NICKEL HEAP LEACH 5,000 T/Y PAGE :
BMR‐ELC‐DTS‐ST‐0003
2 of 8
TABLE OF CONTENT
REVISION
PAGE TITLE REMARK
A B C 0
1 of 8 COVER SHEET X
2 of 8 TABLE OF CONTENT X
3 of 8 DATASHEET FOR MEDIUM VOLTAGE SWITCHGEAR UPSTREAM X
4 of 8 DATASHEET FOR MEDIUM VOLTAGE SWITCHGEAR DOWNSTREAM X
5 of 8 DATASHEET FOR MEDIUM VOLTAGE SWITCHGEAR DESALINASI X
6 of 8 DATASHEET FOR MEDIUM VOLTAGE SWITCHGEAR KOLAM CADANGAN AIR SUNGAI X
7 of 8 DATASHEET FOR MEDIUM VOLTAGE SWITCHGEAR CAMP X
8 of 8 DATASHEET FOR MEDIUM VOLTAGE SWITCHGEAR JETTY FACILITIES X
DATA SHEET FOR 
HV SWITCHGEAR 20kV
DOCUMENT NO. Rev. A
DED EXPANSION NICKEL HEAP LEACH 5,000 T/Y PAGE :
BMR‐ELC‐DTS‐ST‐0003
3 of 8

1 GENERAL
2 Equipment No. : 01‐SWGR‐01, 01‐SWGR‐02 Manufacturer : Note 1
3 Location :  Upstream 1 & 2 Area
4 RFQ / PO No. : Vendor :  Note 1
5 Total Quantity : 2 Unit Model No. :  Note 1
6 Spec. No. : BMR‐ELC‐SPE‐ST‐0004‐RB Ref. SLD :  BMR‐ELC‐SLD‐ST‐0003‐RC
7  
8 EVIRONMENTAL DATA
9 Maximum temperature :
o
45 C Location : Indoor Outdoor
10 Minimum temperature :
o
21 C Area Classification : Hazardous Non Hazardous

11 Design temperature : 40 C
o
Zone : 0 1
12 Humidity at Design Temp.  : 85.2% saturation at all temperature Class : 1 2
13 Atmosphere : Heavy Dust Temperature Class : Note 1
14 Corrosive Non Corrosive Gas Group : Note 1
15 Altitude : Less than 1000m Standard : IEC 
16
17 ELECTRICAL CHARACTERISTIC
18 Rated Voltage 24 kV Frequency 50 Hz Enclosure
19 Nominal Current 630 A Number of Phase 3 ph Protection Degree : IP 3X
20 Continuous Bus Rating Note 1 A Cubicle type : Metal Clad Metal Enclosed
21 Short‐time withstand current 16.0 kA for 1 sec Cubicle Colour : Note 1
22 Rated Lightning Impulse (1.2/50ms) 125 kV Plate thickness
23 Busbar system Copper, Silver coated on connection surface ‐ Door : 3.2 mm Frame mm
24 Busbar insulation Heat Shrink Insulated ‐ Side/Top plate : 2.3 mm
25 Earth Fault Current Note 1 A ‐ Cover Plate : 3.0 mm (Aluminum)
26 Earth Location NER Size mm2
27 Cable Entry
28 LBS type Vacuum Air Break Others ‐ Incoming : Top Bottom
29 Breaker type Vacuum Air Break Others ‐ Outgoing : Top Bottom
30 Operating Mechanism Solenoid valve Storage energy ‐ Cover Plate : With Without
31 Nominal 3phase interrupting capacity Note 1 kA Space Heater : Required Not required
32 Spring Charging motor ‐ Thermostat : Required Not required
33 Relay Coordination responsibility Vendor Purchaser ‐ Control voltage : 220 VAC 500 Watt
34
35 Control Voltage ‐ Closing : 110 ‐ 120 VAC Back Access  : Required No required
Not
36 Control Voltage ‐ Tripping : 110 ‐ 120 VAC Clearence : Note 1 mm
37 Control Voltage ‐ Contactor : 110 ‐ 120 VAC
38 Control Voltage ‐ Indication : 110 ‐ 120 VAC Supply of Heat termination kit Yes No
39 DC Supply for Switchgear : 110 ‐ 120 VAC
40
41 METERING, PROTECTION AND INSTRUMENTS
42 As Per Single Line Diagram (Vendor to specify in Tender)
43
44
45
46 PHYSICAL ARRANGEMENT TESTING
47 Height Width Depth Weight Testing Routine Type Special
Mechanical Data
48 mm mm mm kg
49 Switchgear Note 1 Note 1 Note 1 Note 1
50 Freight Note 1 Note 1 Note 1 Note 1
Note :
1 Vendor to fill in all information required to complete data sheet
DATA SHEET FOR 
HV SWITCHGEAR 20kV
DOCUMENT NO. Rev. A
DED EXPANSION NICKEL HEAP LEACH 5,000 T/Y PAGE :
BMR‐ELC‐DTS‐ST‐0003
4 of 8

1 GENERAL
2 Equipment No. : 02‐SWGR‐01, 02‐SWGR‐02 Manufacturer : Note 1
3 Location :  Downstream 1 & 2 Area
4 RFQ / PO No. : Vendor :  Note 1
5 Total Quantity : 2 Unit Model No. :  Note 1
6 Spec. No. : BMR‐ELC‐SPE‐ST‐0004‐RB Ref. SLD :  BMR‐ELC‐SLD‐ST‐0003‐RC
7  
8 EVIRONMENTAL DATA
9 Maximum temperature :
o
45 C Location : Indoor Outdoor
10 Minimum temperature :
o
21 C Area Classification : Hazardous Non Hazardous

11 Design temperature : 40 C
o
Zone : 0 1
12 Humidity at Design Temp.  : 85.2% saturation at all temperature Class : 1 2
13 Atmosphere : Heavy Dust Temperature Class : Note 1
14 Corrosive Non Corrosive Gas Group : Note 1
15 Altitude : Less than 1000m Standard : IEC 
16
17 ELECTRICAL CHARACTERISTIC
18 Rated Voltage 24 kV Frequency 50 Hz Enclosure
19 Nominal Current 630 A Number of Phase 3 ph Protection Degree : IP 3X
20 Continuous Bus Rating Note 1 A Cubicle type : Metal Clad Metal Enclosed
21 Short‐time withstand current 16.0 kA for 1 sec Cubicle Colour : Note 1
22 Rated Lightning Impulse (1.2/50ms) 125 kV Plate thickness
23 Busbar system Copper, Silver coated on connection surface ‐ Door : 3.2 mm Frame mm
24 Busbar insulation Heat Shrink Insulated ‐ Side/Top plate : 2.3 mm
25 Earth Fault Current Note 1 A ‐ Cover Plate : 3.0 mm (Aluminum)
26 Earth Location NER Size mm2
27 Cable Entry
28 LBS type Vacuum Air Break Others ‐ Incoming : Top Bottom
29 Breaker type Vacuum Air Break Others ‐ Outgoing : Top Bottom
30 Operating Mechanism Solenoid valve Storage energy ‐ Cover Plate : With Without
31 Nominal 3phase interrupting capacity Note 1 kA Space Heater : Required Not required
32 Spring Charging motor ‐ Thermostat : Required Not required
33 Relay Coordination responsibility Vendor Purchaser ‐ Control voltage : 220 VAC 500 Watt
34
35 Control Voltage ‐ Closing : 110 ‐ 120 VAC Back Access  : Required No required
Not
36 Control Voltage ‐ Tripping : 110 ‐ 120 VAC Clearence : Note 1 mm
37 Control Voltage ‐ Contactor : 110 ‐ 120 VAC
38 Control Voltage ‐ Indication : 110 ‐ 120 VAC Supply of Heat termination kit Yes No
39 DC Supply for Switchgear : 110 ‐ 120 VAC
40
41 METERING, PROTECTION AND INSTRUMENTS
42 As Per Single Line Diagram (Vendor to specify in Tender)
43
44
45
46 PHYSICAL ARRANGEMENT TESTING
47 Height Width Depth Weight Testing Routine Type Special
Mechanical Data
48 mm mm mm kg
49 Switchgear Note 1 Note 1 Note 1 Note 1
50 Freight Note 1 Note 1 Note 1 Note 1
Note :
1 Vendor to fill in all information required to complete data sheet
DATA SHEET FOR 
HV SWITCHGEAR 20kV
DOCUMENT NO. Rev. A
DED EXPANSION NICKEL HEAP LEACH 5,000 T/Y PAGE :
BMR‐ELC‐DTS‐ST‐0003
5 of 8

1 GENERAL
2 Equipment No. : 00‐SWGR‐03 Manufacturer : Note 1
3 Location :  Desalinasi Area
4 RFQ / PO No. : Vendor :  Note 1
5 Total Quantity : 1 Unit Model No. :  Note 1
6 Spec. No. : BMR‐ELC‐SPE‐ST‐0004‐RB Ref. SLD :  BMR‐ELC‐SLD‐ST‐0003‐RC
7  
8 EVIRONMENTAL DATA
9 Maximum temperature :
o
45 C Location : Indoor Outdoor
10 Minimum temperature :
o
21 C Area Classification : Hazardous Non Hazardous

11 Design temperature : 40 C
o
Zone : 0 1
12 Humidity at Design Temp.  : 85.2% saturation at all temperature Class : 1 2
13 Atmosphere : Heavy Dust Temperature Class : Note 1
14 Corrosive Non Corrosive Gas Group : Note 1
15 Altitude : Less than 1000m Standard : IEC 
16
17 ELECTRICAL CHARACTERISTIC
18 Rated Voltage 24 kV Frequency 50 Hz Enclosure
19 Nominal Current 630 A Number of Phase 3 ph Protection Degree : IP 3X
20 Continuous Bus Rating Note 1 A Cubicle type : Metal Clad Metal Enclosed
21 Short‐time withstand current 16.0 kA for 1 sec Cubicle Colour : Note 1
22 Rated Lightning Impulse (1.2/50ms) 125 kV Plate thickness
23 Busbar system Copper, Silver coated on connection surface ‐ Door : 3.2 mm Frame mm
24 Busbar insulation Heat Shrink Insulated ‐ Side/Top plate : 2.3 mm
25 Earth Fault Current Note 1 A ‐ Cover Plate : 3.0 mm (Aluminum)
26 Earth Location NER Size mm2
27 Cable Entry
28 LBS type Vacuum Air Break Others ‐ Incoming : Top Bottom
29 Breaker type Vacuum Air Break Others ‐ Outgoing : Top Bottom
30 Operating Mechanism Solenoid valve Storage energy ‐ Cover Plate : With Without
31 Nominal 3phase interrupting capacity Note 1 kA Space Heater : Required Not required
32 Spring Charging motor ‐ Thermostat : Required Not required
33 Relay Coordination responsibility Vendor Purchaser ‐ Control voltage : 220 VAC 500 Watt
34
35 Control Voltage ‐ Closing : 110 ‐ 120 VAC Back Access  : Required No required
Not
36 Control Voltage ‐ Tripping : 110 ‐ 120 VAC Clearence : Note 1 mm
37 Control Voltage ‐ Contactor : 110 ‐ 120 VAC
38 Control Voltage ‐ Indication : 110 ‐ 120 VAC Supply of Heat termination kit Yes No
39 DC Supply for Switchgear : 110 ‐ 120 VAC
40
41 METERING, PROTECTION AND INSTRUMENTS
42 As Per Single Line Diagram (Vendor to specify in Tender)
43
44
45
46 PHYSICAL ARRANGEMENT TESTING
47 Height Width Depth Weight Testing Routine Type Special
Mechanical Data
48 mm mm mm kg
49 Switchgear Note 1 Note 1 Note 1 Note 1
50 Freight Note 1 Note 1 Note 1 Note 1
Note :
1 Vendor to fill in all information required to complete data sheet
DATA SHEET FOR 
HV SWITCHGEAR 20kV
DOCUMENT NO. Rev. A
DED EXPANSION NICKEL HEAP LEACH 5,000 T/Y PAGE :
BMR‐ELC‐DTS‐ST‐0003
6 of 8

1 GENERAL
2 Equipment No. : 00‐SWGR‐04 Manufacturer : Note 1
3 Location :  Kolam Cadangan Air Sungai
4 RFQ / PO No. : Vendor :  Note 1
5 Total Quantity : 1 Unit Model No. :  Note 1
6 Spec. No. : BMR‐ELC‐SPE‐ST‐0004‐RB Ref. SLD :  BMR‐ELC‐SLD‐ST‐0003‐RC
7  
8 EVIRONMENTAL DATA
9 Maximum temperature :
o
45 C Location : Indoor Outdoor
10 Minimum temperature :
o
21 C Area Classification : Hazardous Non Hazardous

11 Design temperature : 40 C
o
Zone : 0 1
12 Humidity at Design Temp.  : 85.2% saturation at all temperature Class : 1 2
13 Atmosphere : Heavy Dust Temperature Class : Note 1
14 Corrosive Non Corrosive Gas Group : Note 1
15 Altitude : Less than 1000m Standard : IEC 
16
17 ELECTRICAL CHARACTERISTIC
18 Rated Voltage 24 kV Frequency 50 Hz Enclosure
19 Nominal Current 630 A Number of Phase 3 ph Protection Degree : IP 3X
20 Continuous Bus Rating Note 1 A Cubicle type : Metal Clad Metal Enclosed
21 Short‐time withstand current 16.0 kA for 1 sec Cubicle Colour : Note 1
22 Rated Lightning Impulse (1.2/50ms) 125 kV Plate thickness
23 Busbar system Copper, Silver coated on connection surface ‐ Door : 3.2 mm Frame mm
24 Busbar insulation Heat Shrink Insulated ‐ Side/Top plate : 2.3 mm
25 Earth Fault Current Note 1 A ‐ Cover Plate : 3.0 mm (Aluminum)
26 Earth Location NER Size mm2
27 Cable Entry
28 LBS type Vacuum Air Break Others ‐ Incoming : Top Bottom
29 Breaker type Vacuum Air Break Others ‐ Outgoing : Top Bottom
30 Operating Mechanism Solenoid valve Storage energy ‐ Cover Plate : With Without
31 Nominal 3phase interrupting capacity Note 1 kA Space Heater : Required Not required
32 Spring Charging motor ‐ Thermostat : Required Not required
33 Relay Coordination responsibility Vendor Purchaser ‐ Control voltage : 220 VAC 500 Watt
34
35 Control Voltage ‐ Closing : 110 ‐ 120 VAC Back Access  : Required No required
Not
36 Control Voltage ‐ Tripping : 110 ‐ 120 VAC Clearence : Note 1 mm
37 Control Voltage ‐ Contactor : 110 ‐ 120 VAC
38 Control Voltage ‐ Indication : 110 ‐ 120 VAC Supply of Heat termination kit Yes No
39 DC Supply for Switchgear : 110 ‐ 120 VAC
40
41 METERING, PROTECTION AND INSTRUMENTS
42 As Per Single Line Diagram (Vendor to specify in Tender)
43
44
45
46 PHYSICAL ARRANGEMENT TESTING
47 Height Width Depth Weight Testing Routine Type Special
Mechanical Data
48 mm mm mm kg
49 Switchgear Note 1 Note 1 Note 1 Note 1
50 Freight Note 1 Note 1 Note 1 Note 1
Note :
1 Vendor to fill in all information required to complete data sheet
DATA SHEET FOR 
HV SWITCHGEAR 20kV
DOCUMENT NO. Rev. A
DED EXPANSION NICKEL HEAP LEACH 5,000 T/Y PAGE :
BMR‐ELC‐DTS‐ST‐0003
7 of 8

1 GENERAL
2 Equipment No. : 00‐SWGR‐05 Manufacturer : Note 1
3 Location :  Camp Area
4 RFQ / PO No. : Vendor :  Note 1
5 Total Quantity : 1 Unit Model No. :  Note 1
6 Spec. No. : BMR‐ELC‐SPE‐ST‐0004‐RB Ref. SLD :  BMR‐ELC‐SLD‐ST‐0003‐RC
7  
8 EVIRONMENTAL DATA
9 Maximum temperature :
o
45 C Location : Indoor Outdoor
10 Minimum temperature :
o
21 C Area Classification : Hazardous Non Hazardous

11 Design temperature : 40 C
o
Zone : 0 1
12 Humidity at Design Temp.  : 85.2% saturation at all temperature Class : 1 2
13 Atmosphere : Heavy Dust Temperature Class : Note 1
14 Corrosive Non Corrosive Gas Group : Note 1
15 Altitude : Less than 1000m Standard : IEC 
16
17 ELECTRICAL CHARACTERISTIC
18 Rated Voltage 24 kV Frequency 50 Hz Enclosure
19 Nominal Current 630 A Number of Phase 3 ph Protection Degree : IP 3X
20 Continuous Bus Rating Note 1 A Cubicle type : Metal Clad Metal Enclosed
21 Short‐time withstand current 16.0 kA for 1 sec Cubicle Colour : Note 1
22 Rated Lightning Impulse (1.2/50ms) 125 kV Plate thickness
23 Busbar system Copper, Silver coated on connection surface ‐ Door : 3.2 mm Frame mm
24 Busbar insulation Heat Shrink Insulated ‐ Side/Top plate : 2.3 mm
25 Earth Fault Current Note 1 A ‐ Cover Plate : 3.0 mm (Aluminum)
26 Earth Location NER Size mm2
27 Cable Entry
28 LBS type Vacuum Air Break Others ‐ Incoming : Top Bottom
29 Breaker type Vacuum Air Break Others ‐ Outgoing : Top Bottom
30 Operating Mechanism Solenoid valve Storage energy ‐ Cover Plate : With Without
31 Nominal 3phase interrupting capacity Note 1 kA Space Heater : Required Not required
32 Spring Charging motor ‐ Thermostat : Required Not required
33 Relay Coordination responsibility Vendor Purchaser ‐ Control voltage : 220 VAC 500 Watt
34
35 Control Voltage ‐ Closing : 110 ‐ 120 VAC Back Access  : Required No required
Not
36 Control Voltage ‐ Tripping : 110 ‐ 120 VAC Clearence : Note 1 mm
37 Control Voltage ‐ Contactor : 110 ‐ 120 VAC
38 Control Voltage ‐ Indication : 110 ‐ 120 VAC Supply of Heat termination kit Yes No
39 DC Supply for Switchgear : 110 ‐ 120 VAC
40
41 METERING, PROTECTION AND INSTRUMENTS
42 As Per Single Line Diagram (Vendor to specify in Tender)
43
44
45
46 PHYSICAL ARRANGEMENT TESTING
47 Height Width Depth Weight Testing Routine Type Special
Mechanical Data
48 mm mm mm kg
49 Switchgear Note 1 Note 1 Note 1 Note 1
50 Freight Note 1 Note 1 Note 1 Note 1
Note :
1 Vendor to fill in all information required to complete data sheet
DATA SHEET FOR 
HV SWITCHGEAR 20kV
DOCUMENT NO. Rev. A
DED EXPANSION NICKEL HEAP LEACH 5,000 T/Y PAGE :
BMR‐ELC‐DTS‐ST‐0003
8 of 8

1 GENERAL
2 Equipment No. : 00‐SWGR‐06 Manufacturer : Note 1
3 Location :  Jetty Facilities
4 RFQ / PO No. : Vendor :  Note 1
5 Total Quantity : 1 Unit Model No. :  Note 1
6 Spec. No. : BMR‐ELC‐SPE‐ST‐0004‐RB Ref. SLD :  BMR‐ELC‐SLD‐ST‐0003‐RC
7  
8 EVIRONMENTAL DATA
9 Maximum temperature :
o
45 C Location : Indoor Outdoor
10 Minimum temperature :
o
21 C Area Classification : Hazardous Non Hazardous

11 Design temperature : 40 C
o
Zone : 0 1
12 Humidity at Design Temp.  : 85.2% saturation at all temperature Class : 1 2
13 Atmosphere : Heavy Dust Temperature Class : Note 1
14 Corrosive Non Corrosive Gas Group : Note 1
15 Altitude : Less than 1000m Standard : IEC 
16
17 ELECTRICAL CHARACTERISTIC
18 Rated Voltage 24 kV Frequency 50 Hz Enclosure
19 Nominal Current 630 A Number of Phase 3 ph Protection Degree : IP 3X
20 Continuous Bus Rating Note 1 A Cubicle type : Metal Clad Metal Enclosed
21 Short‐time withstand current 16.0 kA for 1 sec Cubicle Colour : Note 1
22 Rated Lightning Impulse (1.2/50ms) 125 kV Plate thickness
23 Busbar system Copper, Silver coated on connection surface ‐ Door : 3.2 mm Frame mm
24 Busbar insulation Heat Shrink Insulated ‐ Side/Top plate : 2.3 mm
25 Earth Fault Current Note 1 A ‐ Cover Plate : 3.0 mm (Aluminum)
26 Earth Location NER Size mm2
27 Cable Entry
28 LBS type Vacuum Air Break Others ‐ Incoming : Top Bottom
29 Breaker type Vacuum Air Break Others ‐ Outgoing : Top Bottom
30 Operating Mechanism Solenoid valve Storage energy ‐ Cover Plate : With Without
31 Nominal 3phase interrupting capacity Note 1 kA Space Heater : Required Not required
32 Spring Charging motor ‐ Thermostat : Required Not required
33 Relay Coordination responsibility Vendor Purchaser ‐ Control voltage : 220 VAC 500 Watt
34
35 Control Voltage ‐ Closing : 110 ‐ 120 VAC Back Access  : Required No required
Not
36 Control Voltage ‐ Tripping : 110 ‐ 120 VAC Clearence : Note 1 mm
37 Control Voltage ‐ Contactor : 110 ‐ 120 VAC
38 Control Voltage ‐ Indication : 110 ‐ 120 VAC Supply of Heat termination kit Yes No
39 DC Supply for Switchgear : 110 ‐ 120 VAC
40
41 METERING, PROTECTION AND INSTRUMENTS
42 As Per Single Line Diagram (Vendor to specify in Tender)
43
44
45
46 PHYSICAL ARRANGEMENT TESTING
47 Height Width Depth Weight Testing Routine Type Special
Mechanical Data
48 mm mm mm kg
49 Switchgear Note 1 Note 1 Note 1 Note 1
50 Freight Note 1 Note 1 Note 1 Note 1
Note :