TRANSFORMER COSERVATOR
TYPE
Document No. : Rev. A
DED EXPANSION NICKEL HEAP
Page :
BMR-ELC-DTS-ST-0013 LEACH 5,000 T/Y
1 of 3
DOCUMENT NO. Rev. A
DED EXPANSION NICKEL HEAP LEACH 5,000 T/Y PAGE :
BMR‐ELC‐DTS‐ST‐0013
2 of 3
TABLE OF CONTENT
REVISION
PAGE TITLE REMARK
A B C 0
1 of 3 COVER SHEET X
2 of 3 TABLE OF CONTENT X
3 of 3 DATA SHEET FOR TRANSFORMER COSERVATOR TYPE X
DATA SHEET FOR TRANSFORMER
COSERVATOR TYPE
DOCUMENT NO. Rev. A
DED EXPANSION NICKEL HEAP LEACH 5,000 T/Y PAGE :
BMR‐ELC‐DTS‐ST‐0013
3 of 3
1 GENERAL
2 Equipment No: 00‐TR‐01 Manufacturer : ‐
3 RFQ / PO No. : ‐ Order No : ‐
4 Total Quantity: 1 Unit Serial No. : ‐
5 Spec. No. : BMR‐ELC‐SPE‐ST‐0003‐RB Standard : IEC60076
6 Transformer type: Conservator
7 EVIRONMENTAL DATA
8 Maximum temperature : 45 oC Location Indoor Outdoor
9 Minimum temperature : 21 oC Area Classification Hazardous Non Hazardous
:
10 Design temperature : 38 oC Zone 0 1
11 Humidity at Design Tem: 100% saturation at all temperature Class 1 2
12 Atmosphere : Heavy Dust, Corrosive Insulation Class : A
13 Altitude : Less than 1000 m Enclosure Degree of Protect: IP 55
14 Max. Sound level : 65 dB
15
16 ELECTRICAL CHARACTERISTIC
17 Rated Capacity : 17500 kVA No‐load loss at nominal voltage : NOTE‐1 W
18 Rated Voltage : 1'ry 11 kV 2'ry 20 kV Load losses (at 75 oC) : NOTE‐1 W
19 Winding connection : 1'ry Wye 2'ry Delta Impedance : NOTE‐1 %
20 Vector Group (connectio: YNd‐5 Design life : 20 year
21 Frequency : 50Hz ± 5% Temperature Rise ‐ Oil : NOTE‐1 oC
22 Number of Phase : 3 Phase ‐ Winding : NOTE‐1 oC
23 Insulation Class of the Windings Primary Secondary COOLING REQUIREMENTS
24 Insulation Class NOTE‐1 kV NOTE‐1 kV Cooling Class ONAN ONAF ……….
25 Basic Impulse Level (BIL) 75 kV 125 kV Oil Specification MINERAL SYNTHETIC
26 Applied Voltage Test During 1 Minute 28 kV 50 kV Grade : ‐ Type : ‐
27 Tapping On Load LV Winding Motorized Remote Control Pnl Radiator Required Not-Required
28 Off Load HV Winding Manual with external handle Oil Volume : NOTE‐1
29 Tapping Range: ± 5% Tapping Step : ± 2.5%
30 Tapping Volt : 19.0 19.50 20.50 21.0 kV
31 ACCESSORIES Alarm Trip Indication Quantity Range Units Model Remarks
32 Magnetic Oil Level (Tap Changer) 1
33 Magnetic Oil Level Conservator 1
34 Dial Thermometer 1
35 Winding thermometer 1
36 Bucholz Relay 1
37 Pressure Relief Device 1
38 AC Power Supply Failled 1
39 Upper Fill/Oil Filter Valve 1 Noted‐1 (Type)
40 Radiator Isolation Valve (Inlet/Outlet) : (supplier to state quantity) 1
41 Conservator c/w Sampling Valve 1
42 Drain Valve c/w sampling point 1 Noted‐1 (Type)
43 Shock Indicator 1
44 Neutral CT N/A
45 HV/LV Junction Box/Terminal Control Box 1/‐/1
46 Others Noted‐1
47 PHYSICAL ARRANGEMENT
48 Height Width Depth Weight Mounting Skid/Pad Other
Mechanical Data Standard Other
49 mm mm mm kg Protective Coating
50 Radiators NOTE 1 NOTE 1 NOTE 1 NOTE 1 Tropicalization Required Not-Required
51 Core & Winding NOTE 1 NOTE 1 NOTE 1 NOTE 1 Tank Enclosure Sealed Breathing
52 Tank & Fittings NOTE 1 NOTE 1 NOTE 1 NOTE 1 Testing Routine Type Special
53 Total (Overall) NOTE 1 NOTE 1 NOTE 1 NOTE 1 Colour Light Grey Dark Grey Other
54
55
NOTE :
1. Filled by vendor
2. Vendor shall be provided the data of: - Calculation and Damage Curve
- Inrush Current Calculation
-