OPERATE
(Setting X0 to the table center)
What value you add to one of two measuring systems, the same value you will
subtract from the second measuring system to keep their difference constant!!!
Which direction is for the motor to plus for the linear scale is to minus.
Find parameters:
34090[0] absolute motor measuring system offset
34090[1] linear scale offset
Old values you write down just to be sure!!!!!!
Example: (notice-values here are not the same like actual values on your machine)
You need move support about 0.1mm to right
34090[0] $MA_REFP_MOVE_DIST_CORR = 21475.815 + 0.1=
34090[1] $MA_REFP_MOVE_DIST_CORR = 799.152 - 0.1=
Notice:
If value in 34090[1] be increased than axis move to minus direction!!
After the setting of measuring systems has to be each other max difference for both
measuring systems less than 0.1mm (0.0039inch) - this default tolerance value is
defined in MD 36500 for scale synchronization (referencing of scale).
If is not in the range you can adjust only one measuring system offset parameter to
approximately equal both measuring systems.
Way to this menu: Diagnostic- I>I –Axis diag.- Service axis – X axis
Motor Max
measuring difference of
system both
measuring
Linear scale systems
measuring define
system
MD36500