Professional Documents
Culture Documents
EDJ22403
POWER SYSTEM I
EXPERIMENT 4 (Part A)
The selection of switch gear, conductor size, relay setting, determining the rating requirements of
additional power equipment, and validating system stability all require information from a fault
analysis of a power system. An abnormality is a power system problem. Condition that jeopardises
the system's stability. The balanced 3-phase a.c. operating mode of a power system depicts its
steady state. Nevertheless, this situation is troubled by sudden alterations to the system from the
outside or the inside. When one or more points on the system's insulation fail or when a conducting
object comes into contact with a live point, a short circuit or fault occurs. In this experiment,
students describe the value of a three-phase fault that occurred at bus 3 and had a fault impedance
of j0.16 p.u. This experiment aims to pinpoint a bus-to-bus problem.
B) BACKGROUND OF STUDY
In the fault analysis, there are two methods for calculating fault outcomes. The first approach
involves calculating the fault current at many chosen locations to provide an overall summary of
various faults. Calculating the precise fault outcomes and fault current flows for a particular fault
point is required for the second method. Through this simulation, the fault impedance value, which,
in this instance, is supplied as 0.16, will change the scaled magnitude and angle values. The value
of the sub transient phase current in p.u. and degree units will also change. Additionally,
symmetrical faults only yield positive sequence values and do not lead to zero or negative sequence
components because they are perfectly balanced. Unsymmetrical faults include single line to
ground faults, double line-to-line faults, and line-to-line faults. While symmetrical and
unsymmetrical faults typically occur at the generator's terminal, open circuit and short circuit faults
occur on the transmission line.
C) METHODOLOGY
The diagram is simulated using PowerWorld software as part of the study and evaluation
procedures. The conductors of the various phases are connected to one another by the bus,
transmission line, load, and generator. In this lab, buses 2 and 3 are PV and PQ buses, however
bus 1 is slack. At buses 1 and 2, generators are present. The base MVA is 100 and the base voltage
is 11kV. Bus 1-2's limit A was set to 1000 MVA, and its impedance Zik was set at j0.02 p.u.
Additionally, buses 1-3 and 2-3 employ an impedance zik of 0.40 p.u. and a limit A of 1000 MVA.
After being created on the software, the circuit needs compute to find the fault currents and
voltages.
D) SIMULATION RESULTS DISCUSSION
Result
PART A
Question 1
Question 2
Question 3
Question 5
BUS 1
BUS 2
BUS 3
Question 6
Line to Line
Fault An alysis
Faultlmpedance
5 (5) [750 kV] R : 0.00000
6 (6) [750 kV] B 3.699 -146. 90
7 (7) [0. l2 kV] X : 0.00000 If Angle: 95.60 deg.
Units C 5. 254 56. 96
MW Mvar
hus Spccilicd
” Voltage Scl›cJulc Min Max . MW
M n Max
at bus 1?
5. lVhat is the result for Q1, Q2 and Q3 if the fault is a bolted fault? State your
understanding and observation.
(3 marks)
Single Line-To-Ground
Line-To-Line
3 Phase Balanced
Double Line-To-Ground
Discussion
On bus 3, a fault current of 2.348 -69.97 occurs. Subtranscient phase current is calculated as 2.348-
69.97 for A, 2.348-170.03 for B, and 2.348-50.03 for C. The outcome is shown in the software's
table. Values are given in p.u. A three phase fault occurs when the A, B, and C phases short to one
another without the ground being involved. The theory and outcomes are related. The outcomes
are connected to faults in balanced or symmetrical three-phase circuits. The third bus is now the
subject of this section. Impedance X on bus 3 is j0.16 in value. Additionally, the degree of the
substracient phase is different although the value in p.u. is the same. At buses 1 and 2, the new
value generator is 100 MW/55 Mvar. The fault currents caused by short circuits are controlled by
the system impedance between the generating voltages and the fault, and they can be several orders
of magnitude bigger than the ordinary operating currents.
E) CONCLUSION
The software for fault analysis were able to produce accurate findings thanks to the notion of
symmetrical components' input data. It was found that symmetrical fault analysis may display the
post fault bus voltages, however unbalanced fault analysis can only present findings for total fault
current, bus voltages, and line currents during the failure. The initiative could be viewed as a
success as a result. Finally, the learner is familiar with the many types of power system faults or
issues. Students are also able to determine the size of short circuit fault currents and use
PowerWorld as a fault analysis tool. Short circuits can cause currents that are several orders of
magnitude bigger than those in regular operation.
EMJ32304 OEL
Rubric Guidelines
CRITERIA Marks
5 4 3 2 1-0
A. Introduction (10%)
UniMAP, 1
EMJ32304 OEL
C. Methodology (40%)
UniMAP, 2
EMJ32304 OEL
F. Conclusion (5%)
UniMAP, 8