Professional Documents
Culture Documents
ABB RCCB RCBO Connections Configuration 2CSC420005B0201
ABB RCCB RCBO Connections Configuration 2CSC420005B0201
FAQ no. 1
Which is the working voltage range of an RCD?
FAQ no. 2
Is it possible to use a F204 RCCB in a 3 phase system
without neutral?
FAQ no. 3
Which are the possible wiring configurations for a 4P RCCB
of the F200 range?
FAQ no. 4
Which is the difference between AC, A and B type RCDs and
which are typical applications for different type of RCDs?
FAQ no. 5
Considering an RCBO, which is the right tripping curve to be
selected depending on the application?
FAQ no. 6
Which is the difference between direct contacts and indirect
contacts?
FAQ no. 7
Why 30mA is the preferred value for Idn?
FAQ no. 8
How to coordinate MCBs and RCDs speaking about short
circuit?
FAQ no. 9
Which is the difference between UL Listed (UL) and UL
recognized (UR) products? F200 is UL or UR certified?
FAQ no. 1 FAQ no. 2
Which is the working voltage range of an RCD? Is it possible to use a F204 RCCB in a 3 phase system without
neutral?
According to the product standards for RCDs, these devices Maximum and minimum operating voltage of F 200 RCCB The internal circuit of test button of the RCCB F204 is wired The value of the external resistance (Ω) depends on the I∆n of
have to be equipped with a test device to simulate the standard test button inside the device between terminals 5/6 and 7/8/N as shown the selected RCCB, as shown in the table:
passing through the detecting device of a residual current in in the picture and has been sized for an operating voltage
I∆n [A] Rest [Ω]
order to allow a periodic testing of the ability of the residual between 110 and 254 V.
F 200 standard F 204 standard F 204 standard 0.03 3300
current device to operate.
In = ≤ 100 A In = ≤ 100 A In = ≤ 125 A
The operating voltage of the test button identifies the working If the circuit is supplied with a concatenate voltage higher 0.1 1000
Ut = < 110-254 V Ut = < 110-254 V Ut = < 185-440 V
voltage of the RCD: Ut range is the real operating range of than 254 V, as in the typical case of 3 phase network with 0.3 330
an RCD because the device has to be installed in way it’s 1/2 3/4 1/2 3/4 5/6 7/8/N 1/2 3/4 5/6 7/8/N concatenate voltage (phase-phase) of 400 V, it is not possible 0.5 200
possible to test it using test push button. to use these RCDs wiring only the phases because the circuit
In order to properly evaluate the functioning of the test circuit, of the test button will not be supplied.
Another solution for a 3P system without neutral is to use the
it must be considered the wiring of internal test circuit.
1/2 3/4 5/6 7/8/N F204 with neutral on the left side.
In the technical catalogue, for each RCD range you can find
In this case the test circuit is wired between terminals 3/4
the Ut voltage range and the position of the internal test
and 5/6 and it is possible to connect the three phases
circuit; here follow an example for F200 RCCB range.
on terminals 1/2, 3/4 and 5/6 without the need to add an
external resistance:
254 (440 for 125 A); 2/1 4/3 2/1 4/3 6/5 8/7/N 2/1 4/3 6/5 8/7/N
Max. operating voltage of circuit test 2/1 4/3 6/5 8/7/N
440 for F 200 left neutral N 1/2 3/4 5/6
110 (185 for 125 A);
Min. operating voltage of circuit test
195 for F 200 left neutral
With this information, referring to the F202 standard it is clear Also it is not possible to use the RCCBs shifting the cables of
indicated that the device will properly work if it is supplied one pole (phases on terminals 3/4 - 5/6 and 7/8/N) because
between 110 and 254V. the circuit of the test button will be supplied at 400 V and it
Considering an F204 standard (≤ 100A) the device will will give a not exact information about functionality. N 2/1 4/3 6/5
R S T
7/8/N 1/2 3/4 5/6
Rest
2 3
FAQ no. 3 FAQ no. 5
Which are the possible wiring configurations for a 4P RCCB Considering an RCBO, which is the right tripping curve to be
of the F200 range? selected depending on the application?
F204 with neutral on the right side F204 with neutral on the left side According Tripping Thermal release Electromagnetic release Typical application
to characteristic (overload tripping) (short-circuit tripping)
L1-L2-L3-N L1-N L1-L2 L1-L2-L3-N L1-N Non Tripping Tripping Tripping Hold Tripping Tripping Tripping
230V AC between L1-N 230V AC 230V AC 230V AC between L1-N; 230V AC tripping time current time current time current time
400V AC between L2-L3 current
IEC/EN B 1.13 I n >1h 1.45 In <1h 3 In >0.1s 5 In <0.1s Protection of long line cables,
L1 L2 L3 N L1 N L1 L2 N L1 L2 L3 L1 N
(inductive loads)
L1-L2-L3 L1-L2 L1-L2-L3 L1-L2 L1-L2-L3 IEC/EN K 1.05 I n >1h 1.2 In <1h 10 I n >0.2s 14 I n <0.2s Protection of cables supplying
230V AC between L2-L3 400V AC 400V AC between L1-L2 230V-400V AC L2-L3 230V-400V AC 60947-2 1.5 In <2min motors
(with an external resistance*) (with an external resistance*) 6.0 In >2 s
L1 L2 L1 L2 L3
L1 L2 L3 L1 L2 L1 L2 L3
1/2 3/4 5/6 7/8/N 1/2 3/4 5/6 7/8/N
1/2 3/4 5/6 7/8/N N 1/2 3/4 5/6 N 1/2 3/4 5/6
FAQ no. 6
R (Ω) R (Ω)
I∆n [A]
0.03
Rest [Ω]
3300
Which is the difference between direct contacts and indirect
0.1
0.3
1000
330
contacts?
0.5 200
FAQ no. 4
Which is the difference between AC, A and B type RCDs and
which are typical applications for different type of RCDs?
A direct contact refers to a person coming into contact An indirect contact refers to a person coming into contact
with live parts or conductors that are normally live: the main with an exposed conductive part which is not normally alive,
RCD type Type of residual current Typical application protection against direct contacts is the physical prevention but has become alive accidentally (due to insulation failure or
detected of contact with live parts by means of barriers, insulation, some other cause). The protection against indirect contacts is
AC type Sinusoidal alternating Networks at 50-60 Hz. inaccessibility, etc. mainly realized by disconnection of the supply, by means of a
Basic loads (e.g. standard oven
with electrical resistance). residual current device.
A type Sinusoidal alternating and Networks at 50-60 Hz. RCDs of high sensitivity (IΔn ≤ 30mA) are able to provide both
direct pulsating Loads with electronic protection against indirect contact hazards and the additional
components (e.g. air protection against the dangers of direct contact.
conditioning).
B type Sinusoidal alternating, Networks with variable
direct pulsating and frequence (e.g. supplied by a
pulsating or smooth DC frequency converter).
Three phase loads that require
variable frequence (e.g. motor
which needs speed regulation)
4 5
FAQ no. 7
Why 30mA is the preferred value for Idn?
The IEC publication 60479-1”Basic safety publication on the The more dangerous area is the AC-4 where physical It‘s a common statement that in order to protect people from
effects of current on human beings and livestock” provides damages could occur to human body. direct contact an high sensitive RCD is strictly recommended.
basic guidance on the effects of shock current on human When a current higher than 30 mA passes through a part of a According to IEC publication 60364-4-41 (Low-voltage
beings and livestock, for use in the establishment of electrical human body, there is serious danger for people if the current electrical installations – Part 4-41: Protection for safety
safety requirements. is not interrupted in a very short time: – Protection against electric shock) an RCD suitable for
For a given current path through the human body, the danger protection against Direct Contact has to have its trip threshold
to persons depends mainly on the magnitude and duration of set at 30 mA for AC current.
the current flow. ms
These devices, used to disconnect the power supply
10000
a b c1 c2 c3 automatically, operate as fast to prevent injury to, or death by
5000
electrocution, of a normally healthy human.
50
20
10
0.1 0.2 0.5 1 2 5 10 20 50 100 200 500 1000 2000 5000 10000
Body current IB
This publication defines 4 zones considering the hazards Zones Boundaries Physiological effects
mA
of electric shock on human body depending on current- AC-1 Up to 0,5 mA Perception possible but usually no 'startled'
magnitude/time duration. curve a reaction
AC-2 0,5 mA up to Perception and involuntary muscular
curve b contractions likely but usually no harmful
ms electrical physiological effects
10000
a b c1 c2 c3 AC-3 Curve b and Strong involuntary muscular contractions.
5000 above Difficulty in breathing. Reversible
disturbances of heart function. lmmobilization
Duration of current flow t
AC-4.1
2000 AC-4.2 may occur. Effects increasing
AC-4.3 with current magnitude. Usually no organic
1000
damage to be expected
500
AC-4 1) Above curve Patho-physiological effects may occur such as
AC-1 AC-2 AC-3 AC-4
c1 cardiac arrest, breathing arrest,
200
and burns or other cellular damage. Probability
of ventricular fibrillation increasing with current
magnitude and time
50
c 1- c 2 AC-4.1 Probability of ventricular fibrillation
increasing up to about 5%
20
c 2- c 3 AC-4.2 Probability of ventricular fibrillation up
10
to about 50%
0.1 0.2 0.5 1 2 5 10 20 50 100 200 500 1000 2000 5000 10000
Body current IB mA Beyond curve AC-4.3 Probability of ventricular fibrillation
c3 above 50%
6 7
FAQ no. 8
How to coordinate MCBs and RCDs speaking about short
circuit?
Rated making and breaking capacity (Im) is the capacity of The product standard IEC/EN 61008 provides some tests to
the RCCB to make, to carry for a specified time and to break verify the behaviour of RCCB in short-circuit conditions
short-circuit currents. The values of Inc and I∆c have to be related to the type of
Rated residual making and breaking capacity (I∆m) is the SCPD to prove these values and its rated current: RCCBs
capacity of the RCCB to make, to carry for a specified time F200 series have been tested with an SCPD (a fuse) with
and to break residual short-circuit currents. rated current 100A (Inc=10kA) and this indication is in front of
These values are laser printed in front of the RCCB and the F200.
written in the technical catalogue.
If you are using an RCCB you must verify that the Short Circuit Protection Device (SCPD) protects
it from the effects of high current that arise under short-circuit conditions. The IEC/EN 61008
RCDs
pro M compact Coordination tables: F 200 RCCBs
provides some tests to verify the behaviour of RCCB in short-circuit conditions. The tables below
provide the maximum withstanding short-circuit current expressed in eff. kA for which the RCCBs
F 202
SN201/S201 Na 6 6
Max. operating voltage of circuit test IEC V 254 (440 for 125 A); 440 for F 200 left neutral 254 254 SN201M/S201M Na
S202L
S202
10
10
20
10
10
20 20
S202M 25 25 25
S202P 40 25 25
UL/CSA V 277 (up to 63 A); 480 for F 200 left neutral - S292
S802N
S802S
25
36
50
25
36
50
25
36
50
25
36
50
25
36
50
25
36
50
Coordination tables between Short Circuit Protection Devices (SCPD) and F 200
Fuse 25 gG 100
Min. operating voltage of circuit test V 110 (185 for 125 A); 195 for F 200 left neutral 110 110
Fuse 40 gG 60 60
Fuse 63 gG 20 20 20
Fuse 100 gG 10 10 10 10 10
RCCBs
Fuse 125 gG 10
If you are using an RCCB you must verify that the Short Circuit Protection Device (SCPD) protects
SN201N/SN201/SN201M 3 3
Rated conditional short-circuit current Inc=IDc SCPD - fuse kA 10 (for 125 A fuse is gG 125 A) S201L/S201L Na/S202L
S201/S201 Na/S202
4.5
6
4.5
6 6
it from the effects of high current that arise under short-circuit conditions. The IEC/EN 61008
S201M/S201M Na/S202M 10 10 10
gG 100 A
S201P/S201P Na/S202P 25 15 15
S291/S292 10 10 10 10 10 10
S801N/S802N 20 20 20 20 20 20
provides some tests to verify the behaviour of RCCB in short-circuit conditions. The tables below
S801S/S802S 25 25 25 25 25 25
provide the maximum withstanding short-circuit current expressed in eff. kA for which the RCCBs
Three-phases circuits with neutral (y/Δ) 230-240 V/400-415 V*
25 A 40 A 63 A 80 A 100 A 125 A
SN201L/S201L/S201LNa* 4.5 4.5
11
Rated impulse withstand voltage (1.2/50) Uimp kV 4 SN201/S201/S201Na* 6 6
are protected thanks to the coordination with the SCPD installed upstream or downstream. The
SN201M/S201M/S201MNa* 10 10
S202L* 10 10
S202* 20 20 20
Surge current resistance (wave 8/20) A 250 3000 5000 250 250
Fuse 125 gG 10
F 202
* The switches are considered between phase and neutral (230/240V)
ABB 11/91
F 202
400-415 V circuits with isolated neutral (IT) under double faults
25 A 40 A 63 A 80 A 100 A 125 A
8 9
SN201N/SN201/SN201M 3 3
S201L/S201L Na/S202L 4.5 4.5
FAQ no. 9 For your notes
Which is the difference between UL Listed (UL) and UL
Recognized (UR) products? F200 is UL or UR certified?
10 11
Contact us
ABB SACE The data and illustrations are not binding. We reserve
2CSC420005B0201 - 01/2013
the right to modify the contents of this document on the
A division of ABB S.p.A. basis of technical development of the products, without
Line Protection Devices prior notice.
www.abb.com