FUNCTIONAL LOGIC DIAGRAM
LEGENDS
TRANSFER
INDICATOR OF
13-LAL- 13-LAL- DCS ALARM
SIGNALS TO
AND LOGIC 10022 10022
& ANOTHER
FUNCTION SHEET 13-LAL-10022
SHEET :001 SHEET :008
t1____0
ON DELAY
TIMER
HW 13-LT-10022 H> PHYSICAL
t = xx sec
OR LOGIC A TMRxx
I Diff level INPUT
FUNCTION IPS Transmitter
PULSE TIMER
T= xx sec
13-KMXZ-13103 SL
S
O
OUTPUT
TRIP LO/WO F
COOLER FAN K- SERIAL LINK
GREATER T
THAN OR 13103 MOTOR IPS
>= EQUAL TO
LOGIC
FUNCTION
SL S 13-EMRN-10031C
O INPUT
F LO/WO COOLER FAN SERIAL LINK
IPS T RUNNING FB
S c
FCS TAGS IPS TAGS
RS RS FLIP FLOP NORMAL = 0 NORMAL = 1
LOGIC Note-1 ALARM = 0
ALARM = 1
R1 FUNCTION
d
SHEET NO :00
_
INPUT OUTPUT
FCS/FIELD
FCS LUBE OIL SYSTEM ANALOG INPUTS FOR WIP – P-151001 ALARM FIELD
15-TAH- 15-TAH-
HW 15-TT-10046 H 10046 10046 Refer Note 1
A 27 OC 15-TAH-10046
I P-151001 LUBE OIL SHEET :010 SHEET :015
FCS TEMPERATURE L
20 OC 15-TAL- 15-TAL-
10046 10046
15-TAL-10046
SHEET :010 SHEET :015
SHEET :027
HW 15-PT-100181
A
I P-151001 LUBE OIL
FCS PRESS BEFORE L 120 kPag 15-PAL-10181
COOLER
15-PAH- 15-PAH-
HW 15-PT-10182 H 10182 10182
A 220 kPag 15-PAH-10182
I P-151001 LUBE OIL SHEET :010 SHEET :013
FCS OUTLET PRESSURE L
120 kPag 15-PAL- 15-PAL-
10182 10182
15-PAL-10182
SHEET :010 SHEET :013
SHEET :027
HW 15-LT-10069 SHEET: 028
H
A 67.1 %
I P-151001 LUBE OIL 15-LAH-10069
FCS TANK LEVEL L
41.6 % 15-LAL- 15-LAL-
10069 10069
15-LAL-10069
SHEET :010 SHEET :013
SHEET :015
HW 15-PDT-10188 H
A
I P-151001 L.O.
FCS FILTER DIFF. PRESS 150 kPa 15-PDAH-10188
HW 13-TT-10045 H
A 80 OC
P-151001 LUBE OIL 15-TAH-10045
I
FCS TEMP AFTER L
COOLER 43 OC
15-TAL-10045
Note-1 FCS TAGS
NORMAL = 0 SHEET NO :010
ALARM = 1
INPUT OUTPUT
FCS/FIELD
FCS SEAL SYSTEM ANALOG INPUTS FOR WIP – P-151001 ALARM FIELD
HW 15-TT-10043 70 OC
H
A
15-TAH-10043
I P-151001 SEAL
SYSTEM TEMP
FCS (NDE SEAL)
HW 15-PMRN-1003
D
LO PUMP RUNNING RUNNING =1
FCS I FB NOT RUNNING =0
&
HW 15-PMAV-1003
D
LO PUMP AVAIABLE AVAILABLE=1
I
FCS FB
NOT AVAILABLE =0 START 15-PMST-1003 V HW
& S c P151003
LO PUMP START W MCC
RS
R1
SK S 15-HS-10267 d STOP 15-PMSP-1003 V HW
A P151003
O
F AUTO /MANUAL AUTO=1 LO PUMP STOP W MCC
FCS
SELECTION FROM M
T GRAPHICS MANUAL =0
t=1sec
&
SK S 15-HS-10268
O
F MANUAL START
FCS T FROM GRAPHICS ST
SK S 15-HS-10269
O 1
&
F MANUAL STOP
SP t=1sec
FCS T FROM GRAPHICS
AUTO AUTO
START START INTER INTER SHEET NO :012
SHEET :012 LOCK LOCK
SHEET :013
SHEET :013 SHEET :012
INPUT OUTPUT
FCS/FIELD
AUX LO PUMP P-151003 ALARM FIELD
t1____0
15-PAL- 15-PAL-
10182 10182
t = 15 sec
HW 15-PMRN-1003 SHEET :010 SHEET :013 TMR28
D
& AUTO AUTO
LO PUMP RUNNING RUNNING =1 START START
I
FCS FB NOT RUNNING =0
SHEET :013 SHEET :012
Ref note 1
ST_SEQ ST_SEQ
ST-1 ST-21 SP_SEQ SP_SEQ
SHEET :027 SHEET :013 ST-1 ST-1
SHEET :035 SHEET: 013
15-PAH- 13-PAH-
10182 10182 INTER INTER
LOCK LOCK
SHEET :010 SHEET :013
SHEET :013 SHEET :012
SP_SEQ SP_SEQ
ST-4 ST-4
SHEET :036 SHEET: 013
HW 15-EMRN-10017
D
LO HEATER RUNNING =1
FCS I RUNNING FB NOT RUNNING =0
&
15-EMAV-10017
HW D
LO HEATER AVAILABLE=1
FCS I AVAILABLE FB
NOT AVAILABLE =0 HW
START 15-EMST-10017 V
& S c
LO HEATER
START W MCC
RS
R1
HW
SK S 15-HS-10273 d STOP 15-EMSP-10017 V
A
O LO HEATER
F AUTO /MANUAL AUTO=1 STOP W MCC
FCS
SELECTION FROM M
T GRAPHICS MANUAL =0
t=1sec
&
SK S 15-HS-10274
O
F MANUAL START
FCS T FROM GRAPHICS ST
HW 15-PMRN-1001
D
MAIN PUMP P-151001 RUNNING =1
FCS I RUNNING FB NOT RUNNING =0
SK S 15-HS-10275
O 1
&
F MANUAL STOP t=1sec
SP
FCS T FROM GRAPHICS
15-LAL- 15-LAL-
10069 10069
ST_SEQ ST_SEQ
ST-1 ST-1
SHEET :021 SHEET :015
15-LAL- 15-LAL-
10069 10069
SHEET :010 SHEET :015
t1____0
TRP SEQ TRP SEQ
END END t = 60 sec
SHEET :040 SHEET :015 TMR30
SHEET NO :015
INPUT OUTPUT
FCS/FIELD
LUBE OIL FAN COOLER E-151015 ALARM FIELD
HW 15-EMRN-1005
D
LO FAN COOLER RUNNING =1
FCS I RUNNING FB NOT RUNNING =0
&
HW 15-EMAV-1005
D
LO FAN COOLER AVAILABLE=1
I
FCS AVAILABLE FB
NOT AVAILABLE =0 HW
START 15-EMST-1005 V
S c
& LO FAN COOLER
START W MCC
SR
R1
d HW
SK S 15-HS-10270 STOP 15-EMSP-1005 V
A
O LO FAN COLLER
F AUTO /MANUAL AUTO=1 STOP W MCC
FCS
SELECTION FROM M
T GRAPHICS MANUAL =0
t=1sec
SK S 15-HS-10271
O &
F MANUAL START
FCS ST
T FROM GRAPHICS
HW 15-PMRN-1001
D
MAIN PUMP P-151001 RUNNING =1
I
FCS RUNNING FB NOT RUNNING =0
SK S 15-HS-10272 &
O 1
F MANUAL STOP t=1sec
SP
FCS T FROM GRAPHICS
AUTO AUTO
START START INTER INTER
SHEET :017 SHEET :016 LOCK LOCK
SHEET :017 SHEET :016 SHEET NO :016
INPUT OUTPUT
FCS/FIELD
LUBE OIL FAN COOLER E-151015 ALARM FIELD
SP_SEQ SP_SEQ
ST-4 ST-4 INTER INTER
SHEET :036 LOCK LOCK
SHEET: 017
SHEET :017 SHEET :016
TRP SEQ TRP SEQ
ST-3 ST-3
SHEET :040 SHEET: 017
SHEET NO :017
INPUT OUTPUT
FCS/FIELD
SEAL SYSTEM PUMP – P151004/P151005 –DUTY / STANDBY SELECTION ALARM FIELD
1 P151005 P151005
STANDBY STANDBY
SK S 15-HS-10262
O P151004 P151004
P151004/P151005
F STANDBY STANDBY
STANDY S
FCS T ST
SELECTION FROM
SHEET :018 SHEET :019
GRAPHICS
1 P151005 P151005
DUTY DUTY
13-PMAV-10005
HW D
P151004 AVAILABLE=1
FCS I
PUMP AVAIABLE NOT AVAILABLE =0 START START
& P151004 P151004
& STANDBY STANDBY
P151005 P151005
FAILED FAILED SHEET :018 SHEET :019
PRES PRES
SHEET :022 SHEET :018
13-PMAV-10004
HW D
P151005 AVAILABLE=1
FCS I
PUMP AVAIABLE NOT AVAILABLE =0 START START
& P151005 P151005
& STANDBY STANDBY
P151004 P151004
FAILED FAILED SHEET :018 SHEET :020
PRES PRES
SHEET :021 SHEET :018
SHEET NO :018
INPUT OUTPUT
FCS/FIELD
SEAL SYSTEM PUMP – P151004 ALARM FIELD
P151004 P151004
DUTY DUTY
HW 13-PMRN-10004
D SHEET :018 SHEET :019
RUNNING =1
FCS I PUMP RUNNING FB
NOT RUNNING =0
&
13-PMAV-10004
HW D
START START
1
P151004 P151004
STANDBY STANDBY t=1sec
SK S 13-PMST-10004
O
F MANUAL START
FCS T FROM GRAPHICS ST
SK S 13-PMSP-10004
O 1
&
F MANUAL STOP t=1sec
SP
FCS T FROM GRAPHICS
&
13-PMAV-10005
HW D
START START
P151005 P151005 1
STANDBY STANDBY t=1sec
AND
SHEET :018 SHEET :020
SK S 13-PMST-10005
O
F MANUAL START
FCS T FROM GRAPHICS ST
P151005 P151005
&
STANDBY STANDBY
ST_SEQ ST_SEQ
ST-3 ST-3
SHEET :028 SHEET :021
15-LAL- 15-LAL-
10068 10068 .
15-PAL- 15-PAL-
10183 10183
SHEET :011 SHEET :021
ST_SEQ ST_SEQ
ST-3 ST-3
SHEET :028 SHEET :022
15-PAL- 15-PAL-
10183 10183
SHEET :011 SHEET :022 OR
15-PAL- 15-PAL-
NOTE : 1
10184 10184
t1____0
SHEET :011 SHEET :022 P151005 P151005 P151005 FAIL TO BUILD
HW 13-PMRN-10005 t = 10sec & FAILED FAILED UP PRESSURE
D
PRES PRES
P-151005 PUMP RUNNING =1
FCS I SHEET :022 SHEET :018
RUNNING FB NOT RUNNING =0
HW 15-EMRN-10016
D
RUNNING =1
FCS I RUNNING FB
NOT RUNNING =0
&
13-EMAV-10001
HW D
t=1sec
&
SK S 15-EMST-10264
O
F MANUAL START
FCS T FROM GRAPHICS ST
HW 15-PMRN-1001
D
MAIN PUMP P-151001 RUNNING =1
FCS I RUNNING FB NOT RUNNING =0
SK S 15-EMSP-10265
1
O
&
F MANUAL STOP t=1sec
SP
FCS T FROM GRAPHICS
AUTO AUTO
START INTER INTER
START LOCK LOCK SHEET NO :023
SHEET :024 SHEET :023 SHEET :024 SHEET :023
INPUT OUTPUT
FCS/FIELD
SEAL SYSTEM COOLER FAN E-151016 ALARM FIELD
INTER INTER
LOCK LOCK
SHEET :024 SHEET :023
SP_SEQ SP_SEQ
ST-4 ST-4
SHEET :036 SHEET: 024
SHEET NO :024
INPUT OUTPUT
IPS/FCS / FIELD
STARTUP PERMISSIVE WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
15-FCS-DS-IPS-003
RESET RESET ON S SL
15-HS-10004 O
SEQ SEQ F
SEQUENCE REST T
SHEET :025 ` SH-025 TO SH -003
SHEET :026 IPS
1
S c STARTUP STARTUP
t=2sec PERM PERM
RS
SHEET :025 SHEET :026
R1
SL S 15-IPS-DS-FCS-003 d
O HW 15-PMAV-1003
D
F 15-PMXZ-1001 TRIP
IPS T SH-004 TO SH -025 I
LO PUMP AVAIABLE
FCS FB
15-EMAV-10017
SL S 15-IPS-DS-FCS-004 HW D
O 15-GBSC-10002
LO HEATER
F CLOSE FB FCS I AVAILABLE FB
IPS T SH-005 TO SH -025
HW 15-EMAV-1005
SL S 15-IPS-DS-FCS-005 D
O 15-GBSC-10001 LO FAN COOLER
F CLOSE FB I
FCS AVAILABLE FB
IPS T SH-005 TO SH -025 & &
13-EMAV-10001
HW 15-PMAV-1001 HW D
D
SEAL COOLER FAN
MAIN PUMP DCS I AVAIABLE FB
FCS I AVAILABLE FB
13-PMAV-10004 S 15-IPS-DS-FCS-005
HW D SL
O
SEAL PUMP 151004 F 15-PZI-10003
FCS I IPS
AVAIABLE FB T SUCTION PRESSURE
13-PMAV-10005
HW D
SEAL PUMP 151005
FCS I AVAIABLE FB SHEET NO :025
INPUT OUTPUT
FCS / FIELD
START SEQUENCE – WI PUMP P-151001 ALARM FIELD
SK S 15-HS-10006
O START
F START SEQ FROM SEQ
FCS T GRAPHICS ST
START SEQ
SK S 15-ABORT-10006
O ABORT ABORT
F ABORT SEQ FROM
SP
FCS T GRAPHICS ABORT ABORT SHEET :026 SHEET :027,028,029,030, ABORT SEQ
SEQ SEQ 031,032
SHEET :026,028,030, SHEET :026
030/1,031
SK S 15-HS-10004 RESET RESET
O SEQ SEQ
F SEQUENCE RESET
FCS ST SHEET :026 SHEET :025 RESET SEQ
T FROM GRAPHICS
SHEET :032
START
SEQ
SEQUENCE START
& ACTIVATED
ABORT ABORT
t1____0
HW 15-EMRN-10017 ST_SEQ ST_SEQ
D ST-2 ST-2
t = 15sec
LO HEATER RUNNING =1 TMR28 SHEET :027 SHEET :028
I
FCS RUNNING FB NOT RUNNING =0
HW 15-PMRN-1003
D &
LO PUMP RUNNING RUNNING =1
I
FCS FB NOT RUNNING =0
ST_SEQ ST_SEQ
ST-1 ST-1
SHEET :021 SHEET: 027
15-TAL- 15-TAL-
10046 10046
15-PAL- 15-PAL- t1____0
SHEET :010 SHEET :027 10182 10182
t = 15sec
SHEET :010 SHEET :027 TMR22 SHEET NO :027
INPUT OUTPUT
FCS / FIELD
START SEQUENCE –WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
STEP 2--LO PUMP PRESSURE CHECK , SUCTION INLET PRESSURE,START SEAL SYSTEM AND SEAL
SYSTEM COOLER RUNNING FB
ST_SEQ ST_SEQ
ST-1 ST-1
SHEET :027 SHEET :028
HW 13-PMRN-1003 t1____0
D
LO PUMP RUNNING RUNNING =1 & t = 15sec LO HEADER
I
FCS FB NOT RUNNING =0 TMR22 PRESSURE NOT
15-PAL-100182 HEALTHY
13-PAL- 15-PAL-
100182 100182
SHEET :012 SHEET :028
ST_SEQ ST_SEQ
ST-2 ST-2
ST_SEQ ST_SEQ
SHEET :027 SHEET :028 S c ST-3 ST-3
RS SHEET :028 SHEET :021
HW 13-PMRN-10001
D SHEET :022
R1 d SHEET :024
AUX LO PUMP RUNNING =1
I ST_SEQ ST_SEQ
FCS RUNNING FB NOT RUNNING =0
END END
&
SHEET :032 SHEET :028 OR
13-PAL- 15-PAL-
100182 100182 ABORT
ABORT
SHEET :012 SHEET :028
SUCTION
t1____0 PRESSURE NOT
SK S 15-IPS-DS-FCS-007 HEALTHY
O 15-PZI-10003
F SUCTION PRESSURE t = 30sec ABORT ABORT
IPS
LOW LOW TMR08 SEQ SEQ 15-PALL-10003
T SH-005 TO SH-028
SHEET NO :028
SHEET :028 SHEET :26
INPUT OUTPUT
FCS / FIELD
START SEQUENCE –WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
ST_SEQ ST_SEQ
ST-3 ST-3
SHEET :028 SHEET :029
HW 13-PMRN-10001
D
AUX LO PUMP RUNNING =1
FCS I RUNNING FB NOT RUNNING =0
ST_SEQ ST_SEQ
S c ST-4 ST-4
15-PAL- 15-PAL- RS
10083 10083 SHEET :029 SHEET :030
SHEET :011 SHEET :029 R1 d
15-PAL- ST_SEQ ST_SEQ
15-PAL-
10084 & END END
10084
SHEET :011 SHEET :029 SHEET :032 SHEET :029
HW 15-EMRN-10016
D
SEAL COOLER RUNNING =1 ABORT ABORT
I
FCS RUNNING FB NOT RUNNING =0
SHEET :026 SHEET :029
HW 15-PMRN-10004
D
SEAL PUMP 10004 RUNNING =1
FCS I
RUNNING FB NOT RUNNING =0 OR
HW 15-PMRN-10005
D
SEAL PUMP 10005 RUNNING =1
FCS I
RUNNING FB NOT RUNNING =0
15-PAL- 15-PAL-
10083 10083
t1____0 SEAL SYSTEM
SHEET :011 SHEET :029 & HEADER
t = 15sec PRESSURE NOT
15-PAL- 15-PAL- ABORT ABORT HEALTHY
TMR09 15-PAL-
10084 10084 SEQ SEQ
100183/100184
SHEET :011 SHEET :029 SHEET :029 SHEET :026
SHEET NO :029
INPUT OUTPUT
FCS / FIELD
START SEQUENCE –WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
ST_SEQ ST_SEQ
ST-4 ST-4
SHEET :029 SHEET :030 S c ST_SEQ
ST-4A
RS
`` O 15-KSV-10007 HW
ST_SEQ ST_SEQ VENT VALVE - V
R1 d C SOV W DCS
END END
SHEET :032 SHEET :030
ABORT ABORT
ST_SEQ
ST-4B
ST_SEQ t1____0
ST-4A 15-FIC-10001B HW
HW 15-GBSO-10007 & ST_SEQ MIINIMUM BY-PASS A
D t = 300sec LINE
TMR11 ST-4B
CASING VENT SET 80% AND IN O
I FCS
FCS VALVE OPEN FB MANUAL MODE
t1____0
& ABORT ABORT CASING VENT
t = 5sec SEQ SEQ VALVE OPEN
TMR10 FB NOT
ST_SEQ SHEET :030 SHEET :026 AVAILABLE
ST-4B 15-GBSO-10007
S c
SR
ST_SEQ ST_SEQ
ST-5A ST-5A R1 d
SHEET :031 SHEET: 030 ST_SEQ ST_SEQ
ST-5 ST-5
ABORT ABORT
SHEET :030 SHEET :031
CASING VENT
SHEET :026 SHEET :030 VALVE CLOSE
t1____0 FB NOT
HW 15-GBSC-10007 ST_SEQ ABORT ABORT AVAILABLE
D ST-4B SEQ SEQ
& t = 5sec 15-GBSC-10007
I
CASING VENT TMR11 SHEET NO :030
DCS VALVE CLOSE FB SHEET :030/1 SHEET :026
INPUT OUTPUT
FCS / FIELD
START SEQUENCE –WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
HW 15-GBSC-10007
D ST_SEQ
S ST_SEQ
c
CASING VENT ST-5A ST-5A
I RS
FCS VALVE CLOSE FB
SHEET :031 SHEET :030
& SHEET :017
R1 d SHEET :034
ST_SEQ ST_SEQ ST_SEQ ST_SEQ
ST-5 ST-5 END END
SHEET :030 SHEET :031 SHEET :032 SHEET :031
ABORT SIGNAL
ABORT
TRANSFER FROM
SHEET :026 SHEET :031 FCS TO IPS FOR
START SEQ STEP 6
HW 15-PMRN-10001
D
15-FCS-DS-IPS-001
MAIN PUMP RUNNING =1 t1____0 ON S SL
FCS I RUNNING FB ST_SEQ ST_SEQ O
NOT RUNNING =0
& t = 20sec ST-6 ST-6 START-SEQ STEP-6 F
T
TMR14 SH-031 TO SH -003 IPS
HW 15-EMRN-1005 SHEET :031 SHEET :003
D
LO FAN COOLER
I
FCS RUNNING FB ST_SEQ
ST-5A MAIN PUMP
RUNNING FB
t1____0 NOT
& ABORT ABORT
15-PMRN-10001 AVAILABLE
t = 5sec SEQ SEQ
TMR13 SHEET :031 SHEET :026
LO FAN
t1____0 COOLER
& STOP STOP RUNNING FB
15-EMRN-10005
t = 30sec SEQ SEQ NOT
TMR25 AVAILABLE
SHEET :031 SHEET :035
SHEET NO :031
INPUT OUTPUT
FCS / FIELD
START SEQUENCE –WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
STEP 8— LO PUMP STOP AND START SEQUENCE END
SL S 15-IPS-DS-FCS-001 ON 15-FIC-10001B HW
O t1____0 A
F START SEQ STEP-8 MIINIMUM BY-PASS
IPS T SH-003 TO SH -032 LINE
T = 360 sec IN AUTO MODE O FCS
TMR23
S ST_SEQ ST_SEQ
SL S 15-IPS-DS-FCS-001 ON c ST-8 ST-8
&
O
F 15-GBSC-10002 RS SHEET :032 SHEET :013
IPS T SH-005 TO SH -032 R1
d
SL S 15-IPS-DS-FCS-001 ON
O
F 15-GBSO-10001 ST_SEQ ST_SEQ
IPS T SH-005 TO SH -032 END END
SHEET :032 SHEET :032
ABORT ABORT
RESET RESET
SEQ SEQ
SHEET :026 SHEET :032
SHEET NO :032
INPUT OUTPUT
FCS/FIELD
MANI PUMP -P-131001 ALARM FIELD
HW 15-PMRN-1001
D
MAIN PUMP RUNNING =1
FCS I RUNNING FB NOT RUNNING =0
&
HW 15-PMAV-1001
D
MAIN PUMP AVAILABLE=1
I
FCS AVAILABLE FB
NOT AVAILABLE =0 START 15-PMST-1001 V
& S c MAIN PUMP HW
START W MCC
RS
R1
SK S MAIN PUMP d STOP 15-PMSP-1001 V
A
O MAIN PUMP HW
F AUTO /MANUAL AUTO=1 STOP W MCC
SELECTION FROM M
FCS T GRAPHICS MANUAL =0
t=1sec
&
SK S MAIN PUMP
O
F MANUAL START
FCS T FROM GRAPHICS ST
SK S MAIN PUMP
1
O
&
F MANUAL STOP t=1sec
SP
FCS T FROM GRAPHICS
HW 15-PMRN-1001
D ON 15-FCS-DS-IPS-004 S SL
MAIN PUMP O
MAIN PUMP RUNNING =1 F
FCS I RUNNING FB RUNNING FB
NOT RUNNING =0 T
SH-034 TO SH -009 IPS
SHEET NO :034
INPUT OUTPUT
FCS / FIELD
STOP SEQUENCE – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
SL S 15-IPS-DS-FCS-002
ON
O
F STOP SEQ – B6
IPS T SH-003 TO SH -035 STOP STOP
SEQ-B7 SEQ-B7
SHEET :031 SHEET :035
STOP
SEQ
SP_SEQ SP_SEQ
HW 15-PMRN-1001 & ST-1 ST-1
D
MAIN PUMP RUNNING =1 SHEET :035 SHEET: 013
FCS I RUNNING FB NOT RUNNING =0
SP_SEQ SP_SEQ
ST-1 ST-1
SHEET :035 SHEET: 035
&
HW 15-PMRN-1003
D
LO PUMP RUNNING RUNNING =1 S c SP_SEQ SP_SEQ
I
FCS FB NOT RUNNING =0 ST-2 ST-2
RS SHEET :035 SHEET: 034
R1 SHEET: 035
SP_SEQ SP_SEQ
END d
END
SHEET :037 SHEET :035
RESET RESET
SEQ SEQ
SHEET :026 SHEET :035
SHEET NO :035
INPUT OUTPUT
FCS / FIELD
STOP SEQUENCE – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
SP_SEQ SP_SEQ
ST-2 ST-2
SP_SEQ SP_SEQ
SHEET :035 SHEET: 036 ST-3 ST-3
HW 15-PMRN-1001
D
SHEET :036 SHEET: 016
MAIN PUMP RUNNING =1 & SHEET: 018
FCS I RUNNING FB NOT RUNNING =0 SHEET: 024
HW 15-PMRN-1003
D
LO PUMP RUNNING RUNNING =1
I
FCS FB NOT RUNNING =0
STOP – LO PUMP
SP_SEQ SP_SEQ
ST-4 ST-4
t1____0 SHEET :036 SHEET: 037
SP_SEQ SP_SEQ
ST-3 ST-3 S c SHEET: 013 15-FCS-DS-IPS-002 S SL
t = 20sec
TMR15 O
SHEET :036 SHEET: 036 RS STOP-SEQ STEP-3 F
R1 SH-036 TO SH -003 T IPS
SP_SEQ SP SEQ
END END d
RESET RESET
SEQ SEQ
SHEET :026 SHEET :036
SHEET NO :036
INPUT OUTPUT
FCS / FIELD
STOP SEQUENCE – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
HW 15-EMRN-1005
D
LO FAN COOLER RUNNING =1
FCS I RUNNING FB NOT RUNNING =0 SP_SEQ SP SEQ
END END
SK S 15-IPS-DS-FCS-004
O 15-FCS-DS-IPS-001 SL
F 15-GBSC-10002 ENABLE OVERRIDE S
IPS T SH-005 TO SH -037 & 15-FZI-10003,15-PZI- O
10185,15-PZI- F
SK S 15-IPS-DS-FCS-005 10186,15-PZI-10187 T IPS
O SH-37 TO SH-009
F 15-GBSC-10001
IPS T SH-005 TO SH -037
HW 15-EMRN-10016
D
SEAL COOLER RUNNING =1
FCS I RUNNING FB NOT RUNNING =0
HW 13-PMRN-10004
D
SEAL PUMP RUNNING =1
DCS I RUNNING FB NOT RUNNING =0
HW 13-PMRN-10005
D
SEAL PUMP RUNNING =1
I
DCS RUNNING FB NOT RUNNING =0
SHEET NO :037
INPUT OUTPUT
FCS / FIELD
TRIP CONDITION – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
TRIP CONDITION
1 13- 13-
RESET RESET S c PMXZ- PMXZ-
SEQ SEQ t=2sec
10001 10001
SHEET :026 SHEET :038 RS SHEET :038 SHEET :039
R1
SL S 15-IPS-DS-FCS-003 d
O
F 15-PMXZ-1001 TRIP
IPS T SH-004 TO SH -025
&
S 15-IPS-DS-FCS-005
SL
O
15-PZI-10003
F
IPS SUCTION PRESSURE
T SH-005 TO SH-038
SHEET NO :038
INPUT OUTPUT
FCS / FIELD
TRIP SEQUENCE – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
13- 13-
PMXZ- PMXZ-
10001 10001
SHEET :038 SHEET :392 & S c TRP SEQ TRP SEQ
ST-1 ST-1
HW 15-PMRN-1001 RS
D SHEET: 039
SHEET :039
MAIN PUMP RUNNING =1 R1
FCS I RUNNING FB d
NOT RUNNING =0
RESET RESET
SEQ SEQ
SHEET :026 SHEET :039
RESET RESET
SEQ SEQ
SHEET :026 SHEET :039 SHEET NO :039
INPUT OUTPUT
FCS / FIELD
TRIP SEQUENCE – WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
HW 15-PMRN-1001
D
&
MAIN PUMP RUNNING =1 S c TRP SEQ TRP SEQ
FCS I RUNNING FB ST-3 ST-3
NOT RUNNING =0
RS SHEET :040 SHEET: 014
SK S 15-IPS-DS-FCS-005 R1 SHEET: 016
O SHEET: 018
d
F 15-GBSC-10001 SHEET :025
IPS T SH-005 TO SH -040 SHEET: 041
RESET RESET
SEQ SEQ
SHEET :026 SHEET :040
SHEET NO :040
INPUT OUTPUT
FCS / FIELD
TRIP SEQUENCE– WI PUMP P-151001 CONTROL LOGIC ALARM FIELD
HW 13-PMRN-10004
D
SEAL PUMP RUNNING =1
I
FCS RUNNING FB NOT RUNNING =0
HW 13-PMRN-10005
D
SEAL PUMP RUNNING =1
I
FCS RUNNING FB NOT RUNNING =0
SHEET NO :041