Programming & Diagnose STK2 Engels
Programming & Diagnose STK2 Engels
SETRONIK2
MA30
SETRONIK 2 DATE: 28\10\99 REL. 02
INTRODUCTION
Our compliments for choosing the SETRONIK2 controller as the controller for
your lift.
Please carefully read this booklet so that you will be able to understand all the
qualities of this device and its potential.
Warning
Since our products are in constant evolution, all information contained in this manual
can be modified by SEA SYSTEMS without notice.
Introduction -1-
SETRONIK 2 DATE: 28\10\99 REL. 02
TABLE OF CONTENTS
1. Functional Characteristics....................................................Page 03
2. Programming
2.1. Connection and Operation of the STK2-PM Programmer................. Page 04
2.2. Example of programmer use ............................................................ Page 05
2.3. Programming the secret Access Code ............................................. Page 06
2.4. Parameters storing ........................................................................... Page 07
2.5. Programming the Lift, Operation, Selector........................................ Page 08
2.6. Programming of Main Floor, Parking Floor,
Fire-men and Fire-Fighting Floor,
Vertical Rise Floor for Duplex lifts..................................................... Page 09
2.7. Operator Programming ..................................................................... Page 10
2.8. Programming the maximum number of re-levellings
and Type of position indications........................................................ Page 10
2.9. Programming of Speed and Stop Mode during maintenance,
Mobile Platform, Re-levelling at landing, Advance door opening,
Gong ................................................................................................. Page 11
2.10. Programming of Services.................................................................. Page 12
2.11. Shaft programming ........................................................................... Page 13
2.12. Timers Programming ........................................................................ Page 14
2.13. Neutral zone setting.......................................................................... Page 15
2.14. Input Programming ........................................................................... Page 16
2.15. Output Programming ........................................................................ Page 17
3. Diagnostics
3.1. .. Lift Status Display ............................................................................ Page 18
3.2. .. Runs Count and Re-levellings performed ......................................... Page 19
3.3. .. Commands for Lift Operation in the machine room ......................... Page 20
3.4. .. Display and Cancellation of Failures\Malfunctions............................ Page 21
3.5. .. Failures\Malfunctions List ................................................................. Page 22
3.6. .. Operation Indication LEDs ................................................................ Page 24
1. Functional Characteristics
1. Check that the ON\OFF switch of the Keyboard is in the OFF position.
2. Insert the connection cable in connector FC3 on the STK2-B board.
3. Bring the ON\OFF switch in the ON position.
4. All the 7 displays show the number 8 for about 2”: this function is used to check that
all displays are working correctly.
5. After the 2”, the displays show 0.00.XXXX (X indicates any number), or 0.00.0000
with the last four digits flashing. In this second case it means that an access code
has been stored and that it is therefore necessary to enter the digits of the access
code in the last 4 displays (DG3..DG6) and then press .
Programmer Operation.
1 2
4 6 5 7 3
1= Displays indicating the Parameter Code, marked as DG0, DG1 and DG2.
2= Displays indicating the Parameter Value, marked DG3, DG4, DG5, DG6.
3= DIN guide release
4= ON\OFF switch.
5= Connection cable to connector FC3 on the STK1-B board.
6= Pushbutton for displays selection.
7= Pushbuttons to modify the digits of the selected displays.
Pushbutton allows to select the display (DG0 to DG6), scrolling from left to right
whenever it is pressed. The selected display flashes.
Pushbuttons , allow to reduce and increase, respectively, the number of the
display previously selected.
(Please refer to ‘Example of programmer use’ in the following page)
3. Diagnostica -4-
SETRONIK 2 DATE: 28\10\99 REL. 02
DG0 flashes
DG0 flashes
4
1.3. Select DG1 and DG2, by pressing the pushbutton once
(DG1 and DG2 flash):
DG0 DG1 DG2 DG3 DG4 DG5 DG6
DG3..DG6 flash
4 0 2
DG3..DG6 flash
4 0 2 0 0 8 0
NOTE: The value set is operational by pressing once, but it is not stored.
For the storing please refer to paragraph ‘Parameters Storing’ (Page14)
3. Diagnostica -5-
SETRONIK 2 DATE: 28\10\99 REL. 02
0 1 0
ACCESS CODE
The old access code stored is displayed. If no code has been entered, value 0000 is
displayed.
0 1 0
ACCESS CODE
0 1 1 0 0 0 0
4. Enter the same access code entered in point 2 on displays DG3..DG6. If the code is
different, the same is not accepted, therefore the old code previously stored, if any, is
valid.
DG0 DG1 DG2 DG3 DG4 DG5 DG6
0 1 1
ACCESS CODE
5. Perform the storing. (Please refer to the following page: Parameters Storing).
3. Diagnostica -6-
SETRONIK 2 DATE: 28\10\99 REL. 02
0 1 2 0 0 0 0
0 1 2 0 0 0 0
3. Press for one second, then displays DG3..DG6 indicate the following result of
the operation:
DG0 DG1 DG2 DG3 DG4 DG5 DG6
STORING HAS CORRECTLY TAKEN
0 1 2 0 0 0 2 PLACE
Or
DG0 DG1 DG2 DG3 DG4 DG5 DG6
STORING INCORRECT.
0 1 2 0 0 0 3 Repeat the command or replace the board.
3. Diagnostica -7-
SETRONIK 2 DATE: 28\10\99 REL. 02
1 0 0
MASTER / SLAVE#1 / SLAVE #2
0= Simplex
1= Master control panel for Duplex
2= Master control panel for Triplex
3= Slave#1 control panel for Duplex or Triplex
4= Slave#2 control panel for Triplex
SELECTOR TYPE
0= Shaft with magnetic switches without safety
circuit (CS1)
1= Shaft with magnetic switches with safety circuit
(CS1)
2= Shaft with magnetic switches for multispeed
Inverter with safety circuit
3= Shaft with magnetic switches for multispeed
Inverter without safety circuit
OPERATION TYPE
0= Not enabled
1= Not enabled
2= Down collective
3= Up and down Collective
4= Not enabled
LIFT TYPE
0= 1 speed Electric lift
1= 2 speed Electric lift
2= 2 speed Electric lift with ACVV
3= Electric lift for Inverter without encoder
4= Electric lift for Inverter with encoder
5= Hydraulic lift
1 0 1
NUMBER OF SERVICES
NUMBER OF STOPS
3. Diagnostica -8-
SETRONIK 2 DATE: 28\10\99 REL. 02
1 0 2
MAIN FLOOR
1 0 3
FIRE-FIGHTING FLOOR
FIREMEN FLOOR
1 0 4
NUMBER OF DUPLEX VERTICAL RISE FLOORS
(to be programmed on the panel of the lower lift)
NOTE: Floors numbering starts from number 1 corresponding to the lower floor
3. Diagnostica -9-
SETRONIK 2 DATE: 28\10\99 REL. 02
1 0 5
B TYPE LIFT
As for lift A, but functions are combined with timer 4.05
A TYPE LIFT
00= None
01= Manual doors on landing and car
02= Manual doors on landing, not in the car, with safety photocell
03= Manual doors on landing, car automatic doors, with FCA/FCC, with control*
04= Manual doors on landing, car automatic doors, with FCA, with control*,
KCP holding during car running
05= Manual doors on landing, car automatic doors, without FCA\FCC, out of control*,
KAP o KCP holding
06..09= Not enabled
10= Automatic doors on landing and in the car, with FCA/FCC, with control*
11= Automatic doors on landing and in the car, with FCA, with control*,
KCP holding during car running
12= Automatic doors on landing and in the car, motor without FCA/FCC, without
control*, KCP or KAP holding
13= Automatic doors on landing and in the car, without FCA\FCC, without control*,
KAP o KCP holding up to the timer 4.04.
1 0 6
3. Diagnostica - 10 -
SETRONIK 2 DATE: 28\10\99 REL. 02
1 0 7
GONG ACTIVATION
0= Upon speed change only for external calls
1= On floor only for external calls
2= Upon speed change for internal or external calls
3= On floor for internal or external calls
MOVABLE PLATFORM*
0= Not enabled
1= NA contact, in APB operation and upon call
when closed it enables internal calls
2= Not enabled
3= NC contact, in APB operation and upon call
when open it enables internal calls
*MOVABLE PLATFORM:
If there isn’t the movable platform, program DG4=0.
3. Diagnostica - 11 -
SETRONIK 2 DATE: 28\10\99 REL. 02
2
TYPE OF OPENING AND
DOOR STATUS IN PARKING FOR B ACCESS:
See Type of Opening and Door Status in Parking
for A Access
B ACCESS TYPE:
See A access Type
A ACCESS TYPE:
0= There is no service
1= Simplex Access*
2= Multiplex Access**
STOP
01= Stop1
02= Stop2
03= Stop3
04= Stop4
.
.
.
32= Stop 32
*Simplex Access= This is an access whose external booking can be satisfied only by
the car with this access. For instance in case of Simplex system all
accesses are simplex accesses.
**Multiplex Access= This is an access whose external booking can be satisfied by all
cars in case of Duplex or Triplex system.
3. Diagnostica - 12 -
SETRONIK 2 DATE: 28\10\99 REL. 02
3 0 0
INTER-FLOOR TYPE
00= Normal Floors
01= Short Floors
02= Close Floors
03= Very Close Floors (second CFR bracket
required)
INTER-FLOOR SELECTION
01= Inter-floor between floor 1 and 2
02= Inter-floor between floor 2 and 3
03= Inter-floor between floor 3 and 4
04= Inter-floor between floor 4 and 5
.
.
.
31= Inter-floor between floor 31 and 32
3. Diagnostica - 13 -
SETRONIK 2 DATE: 28\10\99 REL. 02
4
TIME
Expressed in tenths of a second
(i.e. 80 = 8 seconds)
TIMER
00= high speed run time control
01= low speed time control (if TIME=0000 à the timer is not enabled)
02= floor parking (occupied)
03= parking after photocell \ door pressure switch \ doors opening pushbutton \ call
pushbutton activation
04= maximum duration of the stage side A lift doors opening/closing
05= maximum duration of the stage side B lift doors opening/closing
06= doors opening delay after stop
07= delay control at start (after the drop out of KCP, KCP1)
08= despatch to timed parking floor
09= despatch to lower outmost floor (for hydraulic lifts)
10= combinable with functions to be programmed
11= combinable with functions to be programmed
12= neutral zone setting (for levelling and advance doors opening)
13= calls cancellation control for:
- excessive floor parking with doors open due to photocell /door pressure switch/doors
opening pushbutton/call operation
- opening of contacts: AF \ MA \ ACC \ ALT
14= contactors excitation delay at start (this is used to avoid false excitations of
operating contactors due to safety contacts bouncing)
15= doors opening delay due to the activation of the safety circuit
3. Diagnostica - 14 -
SETRONIK 2 DATE: 28\10\99 REL. 02
The following procedure is used to position the magnetic brackets at the various floors
apart from setting the levelling space.
In case the levelling space adjustment is not required, please go on to points 5 and 6.
1. Position the A and B monostable at the ends of the bracket (CFR bracket).
2. Fix the CFR bracket on the car.
3. Check that timer 4.12 is on 0000 (no delay)
4. Adjust the magnetic brackets (MFR brackets) on the landings so that the car
stops aligned with the sill of the various landings when carrying out upward runs.
5. Move the bracket B monostable toward the centre of a length equal to the space
of neutral zone required.
6. Gradually increase the value of timer 4.12 so that, when upward runs are
repeated, the car stops aligned with the floor sill.
The timer value depends on the required speed and levelling space.
7. Move the bracket A monostable toward the centre so that, in coming down to the
landing, the car stops aligned with the sill.
3. Diagnostica - 15 -
SETRONIK 2 DATE: 28\10\99 REL. 02
5 0 0
INPUT FUNCTION
00 None
01 Safety photocells for lifts with no car doors
INPUTS Led Term. 02 Oil thermal sensor (NC contact)
00 Reserved 03 Low point pressure switch (NC contact)
01 Input 1 X1 X1 04 Peak point pressure switch (NC contact)
02 Input 2 X2 X2 05 Landing operation stop control (for ACVV or 3VF with
old interface
03 Input 3 X3 X3 06 1° operator contactors control
04 Input 4 X4 X4 07 2° operator contactors control
05 Input 5 X5 X5 08 Firemen operation switch contact
06 Input 6 X6 X6 09 Fire-fighting operation switch contact
07 Input 7 X7 X7 10 Preferential operation contact
08 Input 8 X8 X8 11 Safety circuit control contact (CS1)
09 Input 9 X9 J11.3 12 Additional ID magnetic switch contact for very close
landings (with CFR1 bracket)
10 Input 10 X10 J11.4 13 Additional IS magnetic switch contact for very close
landings (with CFR1 bracket)
11 Input 11 X11 J8.4 15 DS magnetic switch contact for hydraulic lifts and
extentions
12 Input 12 X12 J9.4 14 Maintenance high speed switch
13 Input 13 X13 J12.4 16 Full load contact
14 Input 14 X14 J12.3 17 Alarm with 0094 error, Out-of-service on landing
15 Input 15 X15 J12.2 18 Alarm with 0095 error, immediate out-of-service
16 Input 16 X16 J12.1 19 Alarm with 0096 error, immediate out-of-service
20 Alarm with 0097 error, Failed start (3VF)
21 Reserved operation key
22 Hong Kong\Australia Firemen operation contact
23 1° photocell for Hong Kong\Australia firemen operation
24 2° photocell for Hong Kong\Australia firemen operation
25 Out-of-service with despatch to 1st floor of programmed
parking
26 Lift operation – Insertion Key
27 Lift operation – Up button
28 Lift operation – Down button
29 Overload input (NO contact)
30 1° operator doors closing limit switch (NC contact for
lifts with motors powered during the run)
31 2° operator doors closing limit switch (NC contact for
lifts with motors powered during the run)
32 Low and peak point pressure switch (PST) (NC
contact; it can be used only on inputs X6, X9, J9.4,
J12.2)
3. Diagnostica - 16 -
SETRONIK 2 DATE: 28\10\99 REL. 02
5 0 0
NOTE: Functions 0016, 0017, 0018 are obsolete with diagrams based on Eprom 4.00 or
later types.
3. Diagnostica - 17 -
SETRONIK 2 DATE: 28\10\99 REL. 02
If the Car Position is 00 (DG5, DG6), this means that the resetting operation has not
been performed.
0 0 0
CAR POSITION
OPERATION STATUS
0= Floor parking
1= Doors closing
2= High speed motion
3= Low speed motion
4= Doors opening /Call cancellation
5= Parking off landing or Car at landing without
position
LIFT STATUS
0= Normal operation
1= Firemen operation on
2= Fire-fighting operation on
3= Preferential operation on
4= Reserved operation on
5= Safety photocell action
6= Not used
7= Out-of-service for failures at floor
8= Out-of-service for permanent failures
9= Maintenance operation on
3. Diagnostica - 18 -
SETRONIK 2 DATE: 28\10\99 REL. 02
0 0 0
NUMBER OF TENS OF RUNS
Displays DG3..DG6 show the tens of runs performed. The maximum value which can
be displayed is 9999 corresponding therefore to 99999 maximum runs.
0 0 6
RUNS NUMBER
0 0 0
NUMBER OF RELEVELLINGS
3. Diagnostica - 19 -
SETRONIK 2 DATE: 28\10\99 REL. 02
0 0 9
B OPERATOR CLOSING\OPENING OPERATION:
A=Doors opening in progress, or already open.
To perform the closing, select DG6 and press .
C=Doors closing in progress, or already closed.
To perform the opening, select DG6 and press
AUTOMATIC CALLS:
0=Function disabled. The lift works normally.
1=Calls on all floors in automatic mode, it stops if
DG3=0 or if the lift goes Out-of-service.
2=Calls on all floors in automatic mode, it stops if
DG3=0 or if any type of failure occurs.
3=It controls the car motion in low speed.
Position on DG4;
Press to go down, to go up.
(For these commands the safety devices must be
closed and the lift must not be in maintenance
condition)
3. Diagnostica - 20 -
SETRONIK 2 DATE: 28\10\99 REL. 02
0 0 1
FAILURE CODE
If the parameter value (DG3..DG6) is 0000, this means that no failure or malfunction
has occurred.
If the parameter value (DG3..DG6) is 0000, this means that no failure/malfunction has
occurred or the end of the failure codes list has been reached.
· FAILURES CANCELLATION:
1. Set ‘Parameter Code’ 0.03 on displays DG0, DG1, DG2 and press :
DG0 DG1 DG2 DG3 DG4 DG5 DG6
DG3..DG6 FLASH
0 0 3 0 0 0 0
2. Press . The parameter value (DG3..DG6) shows 0001 to indicate that failures
have been deleted:
DG0 DG1 DG2 DG3 DG4 DG5 DG6
FAILURES DELETED
0 0 3 0 0 0 1
3. Diagnostica - 21 -
SETRONIK 2 DATE: 28\10\99 REL. 02
3. Diagnostica - 22 -
SETRONIK 2 DATE: 28\10\99 REL. 02
Selector
100..123= Stop plate IS (or B if hydraulic) skipped going up (skipped floor = ‘Error code’
less 99)
124..147= Stop plate ID (or A if hydraulic) skipped going down (skipped floor = ‘Error
code’ less 123 )
148..171= Speed change plate IS (or B if hydraulic) skipped going down
(Related floor = ‘Error code’ less 147 )
172..195= Speed change plate IS (or B if hydraulic) skipped going up
(Related floor = ‘Error code’ less 171 )
196..219= Speed change plate ID (or A if hydraulic) skipped going down
(Related floor = ‘Error code’ less 195 )
220..243= Speed change plate ID (or A if hydraulic) skipped going up
(Related floor = ‘Error code’ less 219 )
244= Resetter DR open in advance of run
245= Resetter DR already open at start
246= Resetter SR open in advance of run
247= Resetter SR already open at start
248= Resetters DR and SR open simultaneously
3. Diagnostica - 23 -
SETRONIK 2 DATE: 28\10\99 REL. 02
3. Diagnostica - 24 -
SETRONIK 2 DATE: 28\10\99 REL. 02
3. Diagnostica - 25 -
SETRONIK 2 DATE: 28\10\99 REL. 02
3. Diagnostica - 26 -
SETRONIK 2 DATE: 28\10\99 REL. 02
4. DUPLEX OPERATION
Duplex operation controls two lifts, named Master and Slave, with the floor bookings
in common. The purpose of this operation is to serve all floor bookings faster than
two lifts in Simplex operation.
The assignment of the floor bookings to one or to the other car is based on the
direction, position, distance, load control, Out of order, … .
4.1. Parameter List in Duplex Operation:
DG0 DG1 DG2 DG3 DG4 DG5 DG6
1 0 0
1= Master Control Panel;
2= Slave Control Panel.
DG0 DG1 DG2 DG3 DG4 DG5 DG6
1 0 2
LOWER PARKING FLOOR
See parag.4.4.
DG0 DG1 DG2 DG3 DG4 DG5 DG6
1 0 4
FLOOR DIFFERENCE IN LEVEL NUMBER FOR
DUPLEX
(to be programmed on the panel of the lower lift;
See parag. 4.2.)
2
B ACCESS TYPE:
See A Access Type
A ACCESS TYPE:
0=There is no access
1=Simplex Access (See parag. 4.3.)
2=Multiplex Access (See parag. 4.3.)
STOP ( from 01 to 32 )
DG0 DG1 DG2 DG3 DG4 DG5 DG6
4 0 8
Delay time to despatch to the parking floor
4. Duplex Operation - 27 -
SETRONIK 2 DATE: 28\10\99 REL. 02
4. Duplex Operation - 28 -
SETRONIK 2 DATE: 28\10\99 REL. 02
4.5. Diagnosis
The Duplex operation working status can be diagnosed by the E3 Led placed on the
STK2-B board of the both control panels like it is indicated in the table below:
Duplex operation status according to the E3 Led status of the two lifts
Master E3 Status Slave#1 E3 Status Operation status
Flashing On Fixed Duplex functioning
Off On Fixed Slave#1 in Simplex
On Fixed Off Master in simplex
Off Off All out of service
The E1 Led indicates in flashing mode that the communication with the other control
panel is activated.
4. Duplex Operation - 29 -
SETRONIK 2 DATE: 28\10\99 REL. 02
5. Technical data
OPERATING TEMPERATURE 0 ¸ 40 °C
5. Technical Data - 30 -