Professional Documents
Culture Documents
Table of Contents
Table of Contents........................................................................................... 2
2. Recommendations .................................................................................... 7
2.1 Recommendations for Great Falls G.S. Generator Re- runner and Re-wind
...................................................................................................................... 7
2.2 Recommendations for Great Falls G.S. Generator Excitation Systems ....... 7
2.3 Recommendations for McArthur Falls G.S. Excitation Systems................... 9
2.4 Recommendations for Slave Falls G.S. Generator Re-runner and Re-wind
.................................................................................................................... 11
2.5 Recommendations for Slave Falls G.S. Excitation Systems ...................... 11
2.6 Recommendations for Great Falls G.S., McArthur Falls G.S. and Slave
Falls G.S. Proposed Digital Speed Governors ............................................ 13
2.7 Recommendations for Great Falls G.S., McArthur Falls G.S. and Slave
Falls G.S. Mathematical Computer Models ................................................. 14
3. Introduction ............................................................................................... 14
3.1 Considerations at Great Falls G.S. ............................................................ 15
3.2 Considerations at McArthur Falls G.S. ....................................................... 15
3.3 Considerations at Slave Falls G.S. ............................................................ 15
3.4 Deliverables ............................................................................................... 16
Page 2
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 3
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
1. Executive Summary
This Interconnection Evaluation Study (IES) report summarizes a joint
Winnipeg River study which addresses separate interconnection requests
from the Generation Maintenance Engineering Department, Generation
South, for proposed generator uprate along with substantial modifications
to the excitation systems and speed governing systems at Great Falls
G.S., McArthur Falls G.S. and Slave Falls G.S.. As the system effects of
upgrades at any one location could impact the proposed upgrades at the
others it was decided that a joint Winnipeg River study was necessary.
Page 4
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
6. Considering existing fault levels at Great Falls and Slave Falls and the
recent replacement of all 115 kV breakers with ones having
significantly higher maximum short circuit interrupting ratings, the
increase in MW output at these two stations is not expected to pose
any concern.
1. Existing AVRs and rotating main exciters shall be replaced by full high
initial response static exciters on all units at McArthur Falls G.S. and
Slave Falls G.S.. Due to the age and vintage of existing rotating main
exciters at these two stations, and the potential impact of power
system stabilizers at these locations, static pilot exciters which provide
voltage regulation via existing rotating main exciters, are not
recommended for these two stations.
2. Existing AVRs and rotating main exciters shall be replaced by full high
initial response static exciters on the remaining units (1,2,4-6) at Great
Falls G.S.. These exciters shall be of similar functionality to the existing
exciter on Great Falls Unit 3 which was commissioned in August 2003.
3. The new high initial response exciters shall come equipped with
modern dual input power system stabilizers along with line drop
compensators.
Page 5
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
As per the IES agreements, all funding for the substantial modifications at
Great Falls, McArthur Falls and Slave Falls shall come from the Power
Supply Division.
Page 6
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
2. Recommendations
The recommendations from this IES are provided below for each station
studied as per the IES agreements. As per the IES agreements, all
funding for the substantial modifications at Great Falls, McArthur Falls and
Slave Falls shall be come from the Power Supply Division.
Based on the results and discussions above and work already performed
on Great Falls Unit 3, the following are recommended for Great Falls Units
1,2,4,5 and 6 excitation system upgrades:
Fast, bus fed, high initial response full static exciters with continuous
acting voltage regulators; the exciters will be required to circulate
positive field current only;
The time for the excitation voltage to reach 95% of the difference
between ceiling voltage and rated load field voltage shall be 25
milliseconds or less after a sudden sustained 5% step change in
generator terminal voltage;
Exciter field forcing voltage limits Efdmax and Efdmin shall be specified
as +6.0 pu and –5.0 pu, respectively. In this case, 1 pu field voltage
shall be defined as the generator field voltage required to produce 1
pu terminal (stator) voltage on the open circuit air-gap line. Rotor
insulation shall be specified to accommodate these limits.
Page 7
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 8
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Fast, bus fed, high initial response full static exciters with continuous
acting voltage regulators; the exciters will be required to circulate
positive field current only;
Due to the age and vintage of existing rotating main exciters at this
station, and the potential impact of power system stabilizers, static pilot
exciters which provide voltage regulation via existing rotating main
exciters, are not recommended.
The time for the excitation voltage to reach 95% of the difference
between ceiling voltage and rated load field voltage shall be 25
milliseconds or less after a sudden sustained 5% step change in
generator terminal voltage;
Exciter field forcing voltage limits Efdmax and Efdmin shall be specified
as +6.0 pu and –5.0 pu, respectively. In this case, 1 pu field voltage
shall be defined as the generator field voltage required to produce 1 pu
terminal (stator) voltage on the open circuit air-gap line. If the rotors of
these units are not sufficiently insulated to accommodate these limits
then the highest field forcing limits allowable shall be used.
Page 9
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
0.0 Ks 2 5.0
Tw12H
Ks2 Signal transducer gain in Power 0.5814
path
Page 10
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Fast, bus fed, high initial response static exciters with continuous
acting voltage regulators; the exciters will be required to circulate
positive field current only;
Due to the age and vintage of existing rotating main exciters at this
station, and the potential impact of power system stabilizers, static pilot
exciters which provide voltage regulation via existing rotating main
exciters, are not recommended.
The time for the excitation voltage to reach 95% of the difference
between ceiling voltage and rated load field voltage shall be 25
milliseconds or less after a sudden sustained 5% step change in
generator terminal voltage;
Exciter field forcing voltage limits Efdmax and Efdmin shall be specified
as +6.0 pu and –5.0 pu, respectively. In this case, 1 pu field voltage
shall be defined as the generator field voltage required to produce 1 pu
terminal (stator) voltage on the open circuit air-gap line. Rotor
insulation shall be specified to accommodate these limits.
Page 11
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 12
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
General Governor Specifications for Great Falls, McArthur Falls and Slave Falls
Parameter Suggested Range Study
Value
Permanent Adjustable from 0 to 10% in 4%
Droop/Speed steps of 1%
Regulation
Dead Band Should not exceed 0.036 Hz 0.0
Dead Time For step load change of more than 0.0 sec.
10% of capacity of turbine, dead
time shall not exceed 0.2 seconds
Temporary Speed This parameter shall be 6.1 sec.
Droop Time continuously adjustable from 0 to
Constant 30 seconds.
Temporary Speed Shall be continuously adjustable 36.0 %
Droop from 0 to 150 %.
Proportional Gain Shall be continuously adjustable 1.0 pu
from 0 to 20
Derivative Gain Shall be continuously adjustable 0.0 sec.
from 0 to 5 seconds
Page 13
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
3. Introduction
According to the terms and conditions of the Manitoba Hydro Open Access
Interconnection Tariff, the Manitoba Hydro Power Supply Business Unit,
referred to as The Generator, submitted three separate interconnection
requests for Manitoba Hydro to prepare Interconnection Evaluation Study
(IES) reports. The Generator requested that Manitoba Hydro assess the
impact on steady-state, transient and small signal stability of the power
system as well as short circuit levels, due to the proposed generator
uprating and substantial modifications to excitation systems and to governor
systems at Great Falls G.S., McArthur Falls G.S. and Slave Falls G.S..
Details on the substantial modifications proposed for the three plants can be
found in the attached Interconnection Evaluation Study Agreements in
Appendix A. Brief summaries, as they apply to each plant, are provided
below. As the system effects of substantial modifications at any one
location could impact proposed upgrades and generator control parameter
recommendations at others, including plants in the vicinity which are not
included in the upgrade projects, it was decided that a joint Winnipeg River
study was necessary.
Page 14
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Great Falls G.S. is located on the Winnipeg River and currently has six units
with an overall plant rating of 151.3 MVA. As part of the Great Falls Unit 3
and 4 re-runnering projects, Great Falls Unit 3 was re-runnered, rewound
and equipped with a new full static exciter, complete with a dual input power
system stabilizer and commissioned in August 2003, see references [2, 3, 4,
and 5] for details. The additional generation approved for this project,
based on the IFS report of July 14, 2003 [1] was 8 MW.
This IES will evaluate the impact of the generation increase of an additional
3 MW of Network Resource Interconnection Service. The additional 3 MW
of generation output at Great Falls exceeds the approved facility generation
level of 139.6 MW of Network Resource Interconnection service associated
with the Unit 3 and 4 re-runnering project.
This IES will also consider the replacement of existing Automatic Voltage
Regulators (AVRs) and rotating main exciters with full static exciters and
existing electro-mechanical governors with digital governors on the
remaining 5 units. The projected in-service date is 2009.
McArthur Falls G.S. in located on the Winnipeg River and currently has
eight units with an overall plant rating of 68 MVA. The IES will evaluate the
impact of replacing existing rotating main exciters and AVRs on each unit
with either full static exciters or static pilot exciters. If full static exciters are
recommended the AVR as well as the rotating main exciter on each unit will
be replaced with a full static exciter. Should static pilot exciters be
recommended, these will replace the AVR on each unit and will provide
regulation of the generator field voltage through the existing main exciter.
The IES will also evaluate the impact of replacing existing electro-
mechanical governors on each of the eight units with digital governors. The
projected in-service date is 2011.
Slave Falls G.S. is located on the Winnipeg River and currently has eight
units with an overall plant rating of 80 MVA (72 MW @ 0.9 pf lagging). The
IES will evaluate the impact of re-runnering and re-winding these units in
order to obtain an additional 28 MW of additional generation at this location.
The IES will also evaluate the impact of substantial modifications to the
excitation systems and speed governors associated with these units. The
proposed work involves replacing existing rotating main exciters and AVRs
on each unit with either full static exciters or static pilot exciters. If full static
Page 15
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
exciters are recommended the AVR as well as the rotating main exciter on
each unit will be replaced with a full static exciter. Should static pilot
exciters be recommended, these will replace the AVR on each unit and will
provide regulation of the generator field voltage through the existing main
exciter.
The IES will also evaluate the impact of replacing existing electro-
mechanical governors on each of the eight units with digital governors. The
projected in-service date is 2009.
3.4 Deliverables
This joint IES will consider the steady-state, transient and small signal
stability effects along with impacts on fault levels in the area due to the
generation increase along with proposed substantial modifications to
existing excitation and speed governing systems at these three plants. The
study will evaluate the impact on the Manitoba Hydro system as well as the
surrounding interconnected power system. Short Circuit Analysis is
required to assess any increased short circuit levels on proposed new
breaker layout and proposed increased generator output at Great Falls and
Slave Falls. Studies will be conducted under several simulated system
scenarios, generator loading and seasonal conditions.
Page 16
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
- The northern ac group of generators in the queue, that is, the firming of
Kelsey, Kettle on ac, Jenpeg and Wuskwatim will not impact the results
of this study and therefore were not considered.
- The proposed 300 MW wind plant was not included in this study based
on anticipated minimal impact to the study results.
- The new plant at Pointe du Bois may have some impact on the study
results but because the final transmission plan was unknown at the
time of this study none was assumed. This will require further analysis
at the IFS stage.
- The IFS will also cover the full range of firm import/export capability.
The new 115 kV breakers which were installed in the 115 kV Winnipeg
River power system have a minimum of around 40 - 50 kA maximum short
circuit interrupting rating. The 3 MW generation increase at Great Falls and
28 MW generation increase at Slave Falls is expected to have minimal
effects on the short circuit levels and hence will not affect circuit breaker
requirements.
6. ACCC Analysis
In order to evaluate the proposed facility upgrades at Great Falls, McArthur
Falls and Slave Falls generating stations, load flow analysis which included
single and multi-element contingencies were performed using the AC
Contingency Calculation (ACCC) in PSS/E. AC single contingency analysis,
Page 17
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
similar to that which was performed for facility upgrades at Pine Falls G.S.
(see reference [6]), was performed here.
Due to time constraints, the ACCC analysis was limited to futuristic, high
loading, high generation and high power transfer system conditions with the
Manitoba Hydro power system operating highly stressed. A modified 2014
winter peak case which included increased generation at Pine Falls, Great
Falls and Slave Falls was used in this analysis. Some results from the
ACCC line flow analysis report are shown in Table 1 below.
Results from the ACCC analysis show no major violations in flow and voltage of
concern in the area due to the contingency analysis. As seen in both Tables 1
and 2, some values were marginal in the stressed case prior to the contingency
analysis.
Therefore the proposed uprating of Great Falls units 1,2,4,5 and 6 to obtain an
additional 3 MW above the 8 MW already approved, will not have any significant
negative impact on the power system and may go forward. Similarly, based on
ACCC results, the proposed 28 MW uprating of the Slave Falls units may also
proceed. Should this project proceed to the IFS stage, further ACCC analysis is
recommended.
This section of the study was completed in order to evaluate the impact of the
proposed substantial modifications to the excitation systems and speed
governor controls for the Great Falls, McArthur Falls and Slave Falls
generating stations. In the following sections the impact of these proposed
changes on the stations themselves as well as the surrounding power system
will be evaluated separately for each station.
For these studies Great Falls Units 1, 2, 4, 5 and 6 are netted and modelled
as one generator, similar to what was done in references [1], [2],and [5].
Simulations were conducted with existing exciter models on this unit
representing the existing arrangement of an AVR regulating a rotating main
exciter which is used to regulate the field voltage of the unit. To represent the
Page 19
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
proposed fast, high initial response full static exciters, models similar to those
of the refurbished Great Falls Unit 3 was used (see reference [5]). The Power
System Stabilizer transfer function for Unit 3 was also modeled on the netted
unit to represent future dual input PSS2A or PSS2B type PSSs on each unit.
Figure 1 shows the rotor angle of the generator which represents Units
1,2,4,5 and 6 following a three phase, five cycle fault on the Great Falls 115
kV bus (see single line diagram in Appendix C). A 3-5 cycle fault clearing
time is typical for faults in the Manitoba Hydro’s 115 kV system. Figure 2
shows a “zoomed in” version of the same waveform.
Results show that the proposed faster full static exciter will significantly
increase the speed of response of the unit to voltage changes and improve
the steady state voltage regulation. Results also demonstrate that the
transient response of the units at Great Falls will also improve following a
close-in bus fault, by lowering the “first swing” transient rotor angle deviation.
In reference [5] the addition of a line drop compensator to Great Falls Unit 3
was discussed in detail as well as the future benefits of having line drop
compensators installed on all six units at Great Falls. Results showed small
improvements in the voltage recovery levels on the Great Falls 115 kV bus
following disturbances in the vicinity of the station when line drop
compensation was modeled on Unit 3.
Figure 1 Rotor angles of Great Falls Units 1,2,4,5 & 6 with fast and existing
exciters for a 3 ph., 5 cy. Fault on great Falls 115 kV bus.
Page 20
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Figure 1: Great Falls Units 1,2,4,5 & 6 response to a 5 cy., 3 ph. Fault on Great
Falls 115 kV Bus with Existing and Proposed Exciters
Page 21
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
1.101
1.1005
1.1
1.0995
1.099
1.0985
1.098
1.0975
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
T im e in se co n d s
U3 LDC @ 0% U3 LDC @ 30% U3 LDC @ 60%
1.11
1.105
1.1
1.095
1.09
1.085
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
Tim e in se
Grt. Falls. Bus Vlt. (no LDC) Grt.conds
Falls. Bus Vlt. (60% LDC on all units)
Page 22
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Based on the results and discussions above and work already performed on
Great Falls Unit 3, the following are recommended for Great Falls units
1,2,4,5 and 6 excitation system upgrades:
Fast, bus fed, high initial response static exciters with continuous acting
voltage regulators; the exciters will be required to circulate positive field
current only;
The time for the excitation voltage to reach 95% of the difference
between ceiling voltage and rated load field voltage shall be 25
milliseconds or less after a sudden sustained 5% step change in
generator terminal voltage;
Exciter field forcing voltage limits Efdmax and Efdmin shall be specified as
+6.0 pu and –5.0 pu, respectively. In this case, 1 pu field voltage shall
be defined as the generator field voltage required to produce 1 pu
terminal (stator) voltage on the open circuit air-gap line. Rotor insulation
shall be specified to accommodate these limits.
Page 23
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 24
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Results confirm that the faster exciter will improve the speed of the steady
state voltage regulation on the McArthur falls bus. Results also confirm that
the faster exciter improves the “first swing” stability but degrades the local
oscillatory mode. Simulations with a modified version of the Great Falls U3
PSS shows significant improvement in the damping provided to the local
mode. For additional reasons discussed above, the McArthur Falls new
excitation system should also come equipped with dual input PSS2A or
PSS2B type stabilizers. Similar to Great Falls G.S., studies to date have not
identified a need for contribution to inter-area mode damping from McArthur
Falls..
Page 25
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Figure 5: McArthur Falls Rotor Angle Following a 3ph, 5cy. Bus fault on the
McArthur Falls 115 kV bus
One of the options to be considered for this station in the IES was the
installation of static pilot exciters to replace the existing AVRs and to provide
voltage regulation via the existing rotating main exciter. Considering the
vintage of the existing McArthur Falls rotating exciters and the relative
participation of these generators in the local oscillatory mode (see Small
Signal Stability studies), it is recommended that this option not be
considered.
Static pilot exciters may provide less excitation to local modes of oscillation
following a disturbance but they also inhibit the effectiveness of PSSs in
damping local modes in the vicinity due to the increased time lag introduced
into the stabilizing loop because the PSS has to provide field modulation of
the generator through the slower rotating main exciter. There are cases
where PSSs have been added to static pilot exciters but with limited
success.
Based on the above, the following are recommended for the McArthur Falls
G.S. excitation systems for the eight units:
Fast, bus fed, high initial response static exciters with continuous acting
voltage regulators; the exciters will be required to circulate positive field
current only;
The time for the excitation voltage to reach 95% of the difference
between ceiling voltage and rated load field voltage shall be 25
milliseconds or less after a sudden sustained 5% step change in
generator terminal voltage;
Exciter field forcing voltage limits Efdmax and Efdmin shall be specified as
+6.0 pu and –5.0 pu, respectively. In this case, 1 pu field voltage shall
be defined as the generator field voltage required to produce 1 pu
terminal (stator) voltage on the open circuit air-gap line. If the rotors of
these units are not sufficiently insulated to accommodate these limits
then the highest field forcing limits allowable shall be used.
Page 26
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 27
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Similar to the other two plants, high speed initial response exciters and
PSSs were simulated on the eight units at Slave Falls using models of Great
Falls commissioned Unit 3. Figure 6 shows the rotor angles of the Slave
Falls units following a three phase, five cycle clearing bus fault on the 115
kV bus.
Page 28
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Figure 6: Slave Falls Rotor Angle Following a 3ph, 5cy. Bus Fault on the Slave
Falls 115 kV bus
Results show some reduction in rotor angle “first swing” with the faster exciter
modelled. In this case both exciters seem to excite the local oscillatory mode.
Again a PSS installed at this location provides very good damping to the local
mode.
According to the IES Slave Falls G.S., was to receive consideration for a
static pilot exciter installation. Similar arguments apply here which are further
strengthened by the small signal study results below which shows that Slave
Falls is the number one relative participant in the local oscillatory mode.
Therefore full static exciters which enhance the effectiveness of PSSs
installed at this location are recommended.
Based on the Great Falls studies and the overall plan by Power Supply to
enable LDCs on the Winnipeg River when the opportunity arises, LDCs are
recommended for the Slave Falls units.
Based on the above, the following are recommended for the Slave Falls G.S.
excitation systems for the eight units:
Fast, bus fed, high initial response static exciters with continuous acting
voltage regulators; the exciters will be required to circulate positive field
current only;
The time for the excitation voltage to reach 95% of the difference
between ceiling voltage and rated load field voltage shall be 25
milliseconds or less after a sudden sustained 5% step change in
generator terminal voltage;
Exciter field forcing voltage limits Efdmax and Efdmin shall be specified as
+6.0 pu and –5.0 pu, respectively. In this case, 1 pu field voltage shall
be defined as the generator field voltage required to produce 1 pu
terminal (stator) voltage on the open circuit air-gap line. Rotor insulation
shall be specified to accommodate these limits.
Page 29
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 30
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
In this section of the IES, results from small signal stability studies conducted
using eigenvalue analysis in SSAT are presented. Details on eigenvalue
analysis can be found in references [8, 9, 10, 11, 12 and 13] and will not be
reproduced here.
Briefly the state of the power system is analyzed in the frequency domain and
the eigenvalues associated with various modes of oscillations identified.
Further analysis is performed to determine the level of participation of each
generator in a particular oscillatory mode by identifying and using the left and
right eigenvectors associated with the eigenvalues of the mode. The results
are usually normalized to the generator with the largest participation thereby
assigning this generator a relative participation factor of 1.
Page 31
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
River area power system. These modes are summarized in Table 6 and are
classified based on the dominant plants in the mode shape.
Results show that none of these local oscillatory modes are in violation of the
Manitoba Hydro damping criteria under steady state, system intact conditions.
Figures 7 to 11 show details on other plants which form part of the mode
shape and participate in the identified modes.
(a) (b)
Page 32
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Figure 7: (a) Mode Shape and (b) Participating Generators in 1.635 Hz (Mode 1)
(a) (b)
Figure 8: (a) Mode Shape and (b) Participating Generators in 1.773 Hz (Mode 2)
(a) (b)
Page 33
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Figure 9: (a) Mode Shape and (b) Participating Generators in 1.517 Hz (Mode 3)
(a)
(b)
Figure 10: (a) Mode Shape and (b) Participating Generators in 2.139 Hz (Mode
4)
(a) (b)
Page 34
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Figure 11 :(a) Mode Shape and (b) Participating Generators in 1.813 Hz (Mode
5)
Using the PSS parameters proposed in Section 7 for the generators at Great
Falls, McArthur Falls and Slave Fall, the effects of these PSSs on the
damping of local Modes 1 to 5 was assessed.
With all other Winnipeg River PSSs out of service, the PSSs on the Great
Falls units were enabled and their gains collectively adjusted. The PSSs at
Great Falls had negligible effects on the damping of Modes 1, 2, 3 and 4.
Figure 12 shows a root locus of the eigenvalues associated with Mode 5, the
1.813 Hz mode as the gains on the Great Falls PSSs are collectively
adjusted. Since the Great Falls generators showed significantly higher
relative participation in this mode than other Winnipeg River plants the effect
of its PSSs on the damping of this mode is not surprising.
Similarly with all other PSSs disabled (gains set to 0) the gain on the Slave
Falls PSS was adjusted from 0 to 6. The effect on modes other than Mode 3,
the 1.52 Hz mode, is negligible. A root locus plot is shown in Figure 13.
Again due to the fact that the Slave Falls units are top participants in this
mode the results are consistent with expectations. Based on the relatively
high participation of Pointe du Bois as well as Seven Sisters units in this local
oscillatory mode, it is conceivable that PSSs at these locations will also
positively affect the damping on this mode. IES reports, references [15] and
[16] document stability studies pertaining to the refurbishment of Pointe du
Bois G.S..
Page 35
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
12
Eige nv a lue Im a gina ry (ra d/s e c ) K=0
f =1.813Hz
ζ =19.35 %
K=0.5
f =1.72Hz
10 ζ =26.53 %
K=6
f =1.42 Hz
ζ =40.57 %
8
-4.5 -4 -3.5 -3 -2.5 -2 -1.5
Eigenvalue Real (rad/sec)
Figure 11: Root Locus of 1.812 Hz mode (Mode 5) due to Great Falls PSS gain
12
Eige nv a lue Im a gina ry (ra d/s e c )
K=2
f =1.47 Hz
ζ =16.47 %
10 K=0
f =1.52 Hz
ζ =10.44 %
K=6
f =1.3 Hz
8
ζ =31.6 %
6
-3 -2.5 -2 -1.5 -1 -0.5
Eigenvalue Real (rad/sec)
Figure 12: Root Locus of 1.517 Hz mode (Mode 3) due to Slave Falls PSS gain
With other PSSs disabled the gain on the McArthur PSS was adjusted from 0
to 6. The effect on modes other than Mode 4, the 2.14 Hz mode, is
negligible. A root locus plot is shown in Figure 14. Results are consistent
Page 36
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
with the relative participation factors and mode shape results shown in Figure
10 for Mode 4. Small gain adjustments results in significant improvements in
damping on this mode.
14
E ig en valu e Im ag in ary (rad /sec)
K=0
f =2.14 Hz
12 ζ =9.66 %
K=2
f =1.96 Hz
ζ =24.58 %
10
K=6
f =1.56 Hz
ζ =37.66 %
8
-4.5 -4 -3.5 -3 -2.5 -2 -1.5 -1 -0.5
Eigenvalue Real (rad/sec)
Figure 14: Root Locus of 2.14 Hz mode (Mode 4) due to McArthur Falls PSS
gain
Results from the small signal stability study are consistent with those from the
transient stability study showing that high speed full static exciters are
desirable for Great Falls, McArthur Falls and Slave Falls generating stations.
Even though the damping on local modes in the area is not a concern based
on Manitoba Hydro’s damping criteria, the relatively low costs associated with
adding PSSs to a full static exciter package suggests that PSSs should be
included in the full static exciter packages. Based on simulation results,
these PSSs will add significant damping to the Manitoba Hydro southern
system. PSSs are not required to provide damping to inter-area modes since
studies do not show any significant participation of the plants in inter-area
modes.
Page 37
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Part of this IES for Great Falls, McArthur Falls and Slave Falls was to
determine if there are any system benefits to be derived from replacing
existing electro-mechanical governors at these three plants with digital
governors.
Existing governor models at the three plants were replaced with models of
digital governors similar to those at Limestone G.S. and full load rejections
simulated. Results are shown in Figures 15, 16 and 17.
Figure 15: Simulated full load rejection at Great Falls with existing and digital
governor models
Page 38
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Figure 16: Simulated full load rejection at McArthur Falls with existing and digital
governor models
Page 39
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Figure 17: Simulated full load rejection at Slave Falls with existing and digital
governor models
Page 40
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 41
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
(ii) The governor supports continuous, stable and reliable operation of the
generating unit for fundamental frequency variations of 60 ± 0.5 Hz
[14];
(iii) The governor supports continuous, stable and reliable operation of the
generating unit for system frequency variations between 58 and 63.5
Hz which lasts for less than or equal to 30 seconds [7, 14];
(iv) Simulation of a load rejection between zero and any load within the
capability of the turbine shall show that speed will be returned to the
speed reference with no more than one under-speed deviation not to
exceed 5% and one overspeed deviation not to exceed 5% after the
initial overspeed deviation [19];
(v) Simulation of an on-line speed reference step change not less than 5%
with demonstrated stable governor response [18].
(vi) Stability studies shall cover the operating range between maximum
and minimum net heads with the discharge corresponding to full load
under each respective net head [7, 14];
(vii) Following stability studies the supplier shall indicate the actual setting
as well as setting ranges of the governor parameters for which the
control circuit remains stable after any disturbance [7, 14].
Page 42
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
(e) Clear indication of all limits along with adjustable limit ranges.
It is anticipated that these models will be used in system studies and for
Midwest Reliability Organization (MRO) and North American Electric
Reliability Council (NERC) equipment verification tests. The models shall be
compatible with PSS/E V29 or later and PSCAD/EMTDC V4.2.1 or later.
These models will be used for interconnection type studies in which model
information may be freely shared with other internal and external
stakeholders.
Page 43
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
11. References
[1] Manitoba Hydro Report, “Great Falls Accreditation Studies”, submitted
to MAPP Design Review Subcommittee, 2003 07 14.
[2] B.A. Archer, “Great Falls Unit 3 Static Exciter and Power System
Stabilizer”, System Planning Interoffice Memorandum to J.B. Davies,
TM 01/2, 2001 03 28.
[4] M.S. Abdel-Hadi, “Great Falls Unit #3 AVR and PSS Settings”, System
Performance Interoffice Memorandum to J.B. Davies, 2003 08 06.
[5] B.A. Archer, “Great Falls Unit 3 Stability Models”, System Planning
Interoffice Memorandum to J.B. Davies, TM 03/22, 2003 09 05.
[10] Prabha Kundur, “Power System Stability and Control”, McGraw Hill
Inc., 1994.
[11] P. Kundur, G.J. Rogers, D.Y. Wong, L. Wang and M.G. Lauby, “A
Comprehensive Computer Program Package for Small Signal stability
Analysis of Power Systems”, IEEE Transactions on Power Systems,
Vol. 5, No. 4, November 1990.
[12] D.C. Lee, P. Kundur, “Advanced Excitation Controls For Power System
Stability Enhancement”, Proceedings of CIGRE International
Conference on Large High Voltage Electric Systems, Paris, 1986.
Page 44
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
[18] MRO Generator Testing Review Task Force, “MRO Generator Testing
Guidelines”, Approved by the MRO Board of Directors, March 2007.
[20] IEEE Working Group on Prime Mover and Energy Supply Models for
System Dynamic Performance Studies, “Hydraulic Turbine and Turbine
Control Models for System Dynamic Studies”, IEEE Transactions on
Power Systems, Vol. 7, No. 1, February 1992.
Page 45
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 46
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
ATTACHMENT 2
THIS AGREEMENT is made and entered into this 23 day of May, 2008 by
and between Manitoba Hydro (Power Supply Business Unit), a corporation
incorporated pursuant to the provisions of The Manitoba Hydro Act, R.S.M. 1987,
c.H190, [corporate description of Generator] existing under the laws of the
Province of Manitoba, sometimes hereinafter referred to as "Generator," and
Manitoba Hydro, a corporation incorporated pursuant to the provisions of The
Manitoba Hydro Act, C.C.S.M. c.H190. Generator and Manitoba Hydro each
may be referred to as a "Party," or collectively as the "Parties."
RECITALS
1.0 The terms used in this Agreement shall have the meanings specified in the
Manitoba Hydro Open Access Interconnection Tariff.
Page 47
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
7.0 Generator shall make an initial payment of the estimated cost for
performance of the Study and preparation of Study Report in the
Page 48
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
11.0 This Agreement shall not be assigned without the prior written
consent of the other Party.
Page 49
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
18.0 All products of, or resulting from, the performance of the Study and
preparation of the Study Report by Manitoba Hydro in the course of
performing this Agreement, including but not limited to, all
information, drawings, Reports, records, documents, research
notes, data, photographs, maps, materials, drafts, working drafts,
documents or tangible assets and any intellectual property therein,
including patent, trademark, copyrights, design and trade secrets
(hereinafter collectively referred to as “Service Product”) shall
become the exclusive property of Manitoba Hydro immediately
upon creation or assembly, notwithstanding the fact that all or a
portion of the data provided by Generator may be incorporated
within the Service Product. The Generator shall have no right to
copy, modify, amend, alter, sell, lend or dispense of any such
Service Products in any manner for any reason.
19.0 The Generator shall have no right to use the Service Products
except for the purpose of determining whether the Generator shall
proceed with having Manitoba Hydro perform an Interconnection
Facilities Study.
Page 50
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
20.2 If there is a Force Majeure event that has affected a Party’s ability
to perform its obligations under this Agreement the Party shall
forthwith (and in any event no later than the end of the next
business day after it first becomes aware that an occurrence
constitutes a Force Majeure event) notify the other Party in writing
of the reasons why it believes the occurrence constitutes a Force
Majeure event, identifying the nature of the event, its expected
duration, and the particulars of the obligations affected by the
event, and furnish to the other Party reports with respect to the
Force Majeure event at such intervals as the other Party may
reasonably request during the continuance of the Force Majeure
event.
Page 51
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 52
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 53
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
EXHIBIT A
to
Interconnection Evaluation Study Agreement For
Great Falls Generating Facility
(i) In one phase the upgrades to unit excitation and governors will be studied
in conjunction with Pine Falls G.S.(units 1-6), Great Falls G.S.(units 1,2,5
& 6), Slave Falls G.S.(units 1-6) and McArthur Falls G.S (units 1-8) based
upon the following:
a. Existing Automatic Voltage Regulators (AVRs) and rotating main
exciters replaced with full static exciters and;
b. Existing electro mechanical governors replaced with digital governors.
c. The study will investigate options at McArthur Falls G.S in order to
recommend either full static excitation systems or static pilot exciters to
function with existing rotating main exciters.
The study will assume that Great Falls units 3 & 4 are already equipped
with full static exciters and that all proposed full static exciters for the
generating stations under consideration will be of similar type (functionality
and speed of response) to the ABB full static excitation systems with
modern power system stabilizers, recently installed on Great Falls units 3
& 4. Studies will be performed with the assumption of Pointe du Bois G.S.
as it exists today and with some anticipated features of the proposed
redevelopment.
The study will consider steady state, transient and small signal stability
effects of the new excitation and digital governors systems versus existing
ones from a system perspective (Manitoba Hydro as well as the
surrounding MRO interconnected system). Studies will be conducted
under several simulated system scenarios, generator loading and
seasonal conditions.
Page 54
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
(ii) The second phase of the Interconnection Evaluation Study will investigate
the possible generation increase of an additional 3 MW of Network
Resource Interconnection Service. The second phase of the
Interconnection Evaluation /study will be based upon the following
assumptions:
Study Models
Page 55
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 56
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
ATTACHMENT 2
THIS AGREEMENT is made and entered into this 23 day of May, 2008 by
and between Manitoba Hydro (Power Supply Business Unit), a corporation
incorporated pursuant to the provisions of The Manitoba Hydro Act, R.S.M. 1987,
c.H190, [corporate description of Generator] existing under the laws of the
Province of Manitoba, sometimes hereinafter referred to as "Generator," and
Manitoba Hydro, a corporation incorporated pursuant to the provisions of The
Manitoba Hydro Act, C.C.S.M. c.H190. Generator and Manitoba Hydro each
may be referred to as a "Party," or collectively as the "Parties."
RECITALS
1.0 The terms used in this Agreement shall have the meanings specified in the
Manitoba Hydro Open Access Interconnection Tariff.
Page 57
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
7.0 Generator shall make an initial payment of the estimated cost for
performance of the Study and preparation of Study Report in the
amount of $10,000.00 minus the $10,000 deposit = $0.00 at the
time of delivering the executed Agreement to Manitoba Hydro.
Manitoba Hydro shall charge and Generator shall pay for all actual
costs of the Study and Study Report (including the provision of
supporting documentation) in excess of the deposit paid by
Generator (at the time of submitting its Interconnection Request)
Page 58
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
20.0 This Agreement shall not be assigned without the prior written
consent of the other Party.
Page 59
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
18.0 All products of, or resulting from, the performance of the Study and
preparation of the Study Report by Manitoba Hydro in the course of
performing this Agreement, including but not limited to, all
information, drawings, Reports, records, documents, research
notes, data, photographs, maps, materials, drafts, working drafts,
documents or tangible assets and any intellectual property therein,
including patent, trademark, copyrights, design and trade secrets
(hereinafter collectively referred to as “Service Product”) shall
become the exclusive property of Manitoba Hydro immediately
upon creation or assembly, notwithstanding the fact that all or a
portion of the data provided by Generator may be incorporated
within the Service Product. The Generator shall have no right to
copy, modify, amend, alter, sell, lend or dispense of any such
Service Products in any manner for any reason.
19.0 The Generator shall have no right to use the Service Products
except for the purpose of determining whether the Generator shall
proceed with having Manitoba Hydro perform an Interconnection
Facilities Study.
Page 60
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
20.2 If there is a Force Majeure event that has affected a Party’s ability
to perform its obligations under this Agreement the Party shall
forthwith (and in any event no later than the end of the next
business day after it first becomes aware that an occurrence
constitutes a Force Majeure event) notify the other Party in writing
of the reasons why it believes the occurrence constitutes a Force
Majeure event, identifying the nature of the event, its expected
duration, and the particulars of the obligations affected by the
event, and furnish to the other Party reports with respect to the
Force Majeure event at such intervals as the other Party may
reasonably request during the continuance of the Force Majeure
event.
Page 61
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 62
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
EXHIBIT A
to
Interconnection Evaluation Study Agreement For
McArthur Falls Generating Facility
(iii) In one phase the upgrades to unit excitation and governors will be studied
in conjunction with Pine Falls G.S.(units 1-6), Great Falls G.S.(units 1,2,5
& 6), Slave Falls G.S.(units 1-6) and McArthur Falls G.S (units 1-8) based
upon the following:
a. Existing Automatic Voltage Regulators (AVRs) and rotating main
exciters replaced with full static exciters and;
b. Existing electro mechanical governors replaced with digital governors.
c. The study will investigate options at McArthur Falls G.S in order to
recommend either full static excitation systems or static pilot exciters to
function with existing rotating main exciters.
The study will assume that Great Falls units 3 & 4 are already equipped
with full static exciters and that all proposed full static exciters for the
generating stations under consideration will be of similar type (functionality
and speed of response) to the ABB full static excitation systems with
modern power system stabilizers, recently installed on Great Falls units 3
& 4. Studies will be performed with the assumption of Pointe du Bois G.S.
as it exists today and with some anticipated features of the proposed
redevelopment.
The study will consider steady state, transient and small signal stability
effects of the new excitation and digital governors systems versus existing
ones from a system perspective (Manitoba Hydro as well as the
surrounding MRO interconnected system). Studies will be conducted
under several simulated system scenarios, generator loading and
seasonal conditions.
Page 63
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
The estimated cost for the McArthur Falls Generating Station portion of
the study is $10,000.00.
Page 64
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
ATTACHMENT 2
THIS AGREEMENT is made and entered into this 23 day of May, 2008 by
and between Manitoba Hydro (Power Supply Business Unit), a corporation
incorporated pursuant to the provisions of The Manitoba Hydro Act, R.S.M. 1987,
c.H190, [corporate description of Generator] existing under the laws of the
Province of Manitoba, sometimes hereinafter referred to as "Generator," and
Manitoba Hydro, a corporation incorporated pursuant to the provisions of The
Manitoba Hydro Act, C.C.S.M. c.H190. Generator and Manitoba Hydro each
may be referred to as a "Party," or collectively as the "Parties."
RECITALS
1.0 The terms used in this Agreement shall have the meanings specified in the
Manitoba Hydro Open Access Interconnection Tariff.
Page 65
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
7.0 Generator shall make an initial payment of the estimated cost for
performance of the Study and preparation of Study Report in the
amount of $43,000.00 minus the $10,000 deposit = $33,000.00 at
the time of delivering the executed Agreement to Manitoba Hydro.
Manitoba Hydro shall charge and Generator shall pay for all actual
costs of the Study and Study Report (including the provision of
supporting documentation) in excess of the deposit paid by
Generator (at the time of submitting its Interconnection Request)
Page 66
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
29.0 This Agreement shall not be assigned without the prior written
consent of the other Party.
Page 67
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
18.0 All products of, or resulting from, the performance of the Study and
preparation of the Study Report by Manitoba Hydro in the course of
performing this Agreement, including but not limited to, all
information, drawings, Reports, records, documents, research
notes, data, photographs, maps, materials, drafts, working drafts,
documents or tangible assets and any intellectual property therein,
including patent, trademark, copyrights, design and trade secrets
(hereinafter collectively referred to as “Service Product”) shall
become the exclusive property of Manitoba Hydro immediately
upon creation or assembly, notwithstanding the fact that all or a
portion of the data provided by Generator may be incorporated
within the Service Product. The Generator shall have no right to
copy, modify, amend, alter, sell, lend or dispense of any such
Service Products in any manner for any reason.
19.0 The Generator shall have no right to use the Service Products
except for the purpose of determining whether the Generator shall
proceed with having Manitoba Hydro perform an Interconnection
Facilities Study.
Page 68
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
20.2 If there is a Force Majeure event that has affected a Party’s ability
to perform its obligations under this Agreement the Party shall
forthwith (and in any event no later than the end of the next
business day after it first becomes aware that an occurrence
constitutes a Force Majeure event) notify the other Party in writing
of the reasons why it believes the occurrence constitutes a Force
Majeure event, identifying the nature of the event, its expected
duration, and the particulars of the obligations affected by the
event, and furnish to the other Party reports with respect to the
Force Majeure event at such intervals as the other Party may
reasonably request during the continuance of the Force Majeure
event.
Page 69
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 70
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
EXHIBIT A
to
Interconnection Evaluation Study Agreement For
Slave Falls Generating Facility
(iv) In one phase the upgrades to unit excitation and governors will be studied
in conjunction with Pine Falls G.S.(units 1-6), Great Falls G.S.(units 1,2,5
& 6), Slave Falls G.S.(units 1-6) and McArthur Falls G.S (units 1-8) based
upon the following:
a. Existing Automatic Voltage Regulators (AVRs) and rotating main
exciters replaced with full static exciters and;
b. Existing electro mechanical governors replaced with digital governors.
c. The study will investigate options at McArthur Falls G.S in order to
recommend either full static excitation systems or static pilot exciters to
function with existing rotating main exciters.
The study will assume that Great Falls units 3 & 4 are already equipped
with full static exciters and that all proposed full static exciters for the
generating stations under consideration will be of similar type (functionality
and speed of response) to the ABB full static excitation systems with
modern power system stabilizers, recently installed on Great Falls units 3
& 4. Studies will be performed with the assumption of Pointe du Bois G.S.
as it exists today and with some anticipated features of the proposed
redevelopment.
The study will consider steady state, transient and small signal stability
effects of the new excitation and digital governors systems versus existing
ones from a system perspective (Manitoba Hydro as well as the
surrounding MRO interconnected system). Studies will be conducted
under several simulated system scenarios, generator loading and
seasonal conditions.
Page 71
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
(v) The second phase of the Interconnection Evaluation Study will investigate
the possible generation increase of an additional 30 MW of Network
Resource Interconnection Service. The second phase of the
Interconnection Evaluation Study will be based upon the following
assumptions:
Study Models
Page 72
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 73
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
APPENDIX B: Correspondence
Page 74
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
APPENDIX C :
MRO Model Single Line
Page 75
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 76
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 77
Great Falls, McArthur Falls and Slave Falls Generator Uprate and Excitation and Governor
Systems Upgrade Interconnection Evaluation Study
Page 78