You are on page 1of 20

Installation

Operation
Maintenance
ODYSSEY
Light Commercial
Split System 5-20 Tons
TWE Model 50 Hz

Air Handling Models


TWE 120 AD
TWE 180 BD
TWE 240 BD

March 2001 TWE-IOM01-EN


Model Nomenclature

Air Handling Unit


Model Nomenclature

TWE 120 A D O O B A

TTH = Cooling Only Air Handling Unit Service Digit


(Horizontal Discharge) A = First Parts list
TWE = Cooling Only and Heat Pump Minor Design Sequence
Air Handling Unit (Convertible) A = First Design Sequence
B = Second Design Sequence
Nominal Gross Cooling Capacity (MBh)
Factory Installed Options # 2
060 = 60 MBh
O = No Options
075 = 75 MBh For TTH model
A = Discharge Plenum
100 = 100 MBh
B = Return Air Grille (TWE model only)
C = Discharge Plenum and Return Air Grille
120 = 120 MBh
(TWE model only)
180 = 180 MBh For TWE model
S = Special request to be defined and approved
240 = 240 MBh
Major Design Sequence Factory Installed Options # 1
A = First Design O = No Options
B = Second Design A = 1 HP Fan Motor
B = 2 HP Fan Motor
C = 3 HP Fan Motor
D = 5 HP Fan Motor
E = 7.5 HP Fan Motor, 380/3/50
F = 7.5 HP Fan Motor, 415/3/50

Electrical Characteristics
D = 380-415/3/50

2
© American Standard Inc. 2001 TWE-IOM01-EN
Contents

Model Nomenclature 2
General Information 4
Unit Installation 5
General Data 9
Electrical Wiring 10
Dimensional Data 12
Operation and Start-up 16
Maintenance 17
Trouble Shooting 18

TWE-IOM01-EN 3
General Information

Foreword All TWE model (Both single and dual


These instructions do not attempt to circuits) have two (2) drain pans. One
cover all variations in systems, nor to for vertical and one for horizontal
provide for every possible contingency application.
to be met in connection with
installation. Should further information Note
be desired or should particular “Warnings” and “Cautions” appear at
problems arise which are not appropriate places in this manual.
sufficiently covered for the purchaser’s Your personal safety and the proper
purpose, the matter should be referred operation of this machine require
to the manufacturer. that you follow them carefully. The
manufacturer assumes no liability for
Reception installations or servicing performed by
On arrival, inspect the unit before unqualified personnel.
signing the delivery note. Specify any
damage on the delivery note, and Handling
send a registered letter of protest to The unit will be supplied with a
the last carrier of the goods within 72 shipping base and protective
hours of delivery. Notify the local packaging over the unit casing. The
Trane Sales Office at the same time. packaging should be kept on the unit
The unit should be totally inspected during handling or storage on site.
within 15 days of delivery. If any
concealed damage is discovered, stop If it is necessary to remove the
unpacking the shipment. Take photos packaging for inspection prior to
of the damage material if possible. completion of on site handling, retain
Notify the carrier immediately by packaging parts and reapply them by
phone and registered mail. Notify the tapping in position to prevent damage
local Trane Sales Office. Concealed to the casing. The unit as supplied has
damage must be reported within 15 a shipping base which is suitable for
days of delivery. Check the unit handling by a fork lift truck. If it is
nameplate to confirm that the proper necessary to sling the unit, use
unit was shipped. Available power spreader bars under the shipping
supply must be compatible with base. Ensure that ropes do not cause
electrical characteristics specified on abrasion to the surface of the unit.
component nameplates.
Warning
General Information Open and lock unit disconnect to
This manual covers the Installation, prevent injury or death from electric
Operation, and Maintenance of the shock or contact with moving parts
TWE120A single circuit air handlers, before attempting any installation or
and the TWE 180B and TWE240B maintenance.
dual circuits air handlers. These new
air handler models are completely Inspection
redesigned to incorporate a single Inspect material carefully for any
slab coil assembly, improved shipping damage. If damaged, it must
application flexibility, servicing and be reported to, and claims made
maintenance accessibility, and an against the transportation company.
improved accessory line. They are of Replace damaged parts with
the fully convertible type (vertical to authorized parts only. Check the unit
horizontal) without field removal or nameplate to confirm that the proper
re-orientation of the coil assembly. unit was shipped. Available power
(For TWE model) They are shipped supply must be compatible with
in the vertical position. electrical characteristics specified on
component nameplates.

4 TWE-IOM01-EN
Unit Installation

Table 1 - Total unit weight and corner weights (lbs) Caution


Use spreader bars to prevent straps
Shipping Net Corner Weights from damaging the unit. Install the
bars between lifting straps, both
Model Configuration Maximum Maximum #1 #2 #3 #4
underneath the unit and above the
TWE 120 A Vertical 473 419 98 108 111 102 unit. This will prevent the straps from
Horizontal 473 419 103 106 106 104 crushing the unit cabinet or damaging
the unit finish.
TWE 180 B Vertical 754 690 170 170 175 175
Horizontal 754 690 174 156 190 170 Installation Consideration
For proper installation and operation,
TWE 240 B Vertical 886 820 206 207 214 208 check each of the following before
Horizontal 886 820 210 190 230 205 mounting the units.

a. Space Requirement and


Installation, Limitation and Important Clearance
Recommendation If adding external accessories to the Allow adequate space for the unit and
The general location of the air handler unit, additional clearances must be free air or service clearance. See
is normally selected by the architect, considered for the overall space Figure 1a.
contractor, and/or buyer. For proper needed.
installation, the following items must
900 mm.
be considered. - For installation of accessories
available for this air handler, follow
a. Available power supply must agree the instructions packed with each
with electrical data on component accessory.
nameplate. 850 mm.

b. Air handler shipped wired for 380 Lifting Recommendation


volt applications. Before preparing the unit for lifting,
c. If external accessories are installed the center of gravity should be
on the unit, additional clearance determined for lifting safety. Because
must be provided. of placement of internal components,
d. All duct work should be properly the unit weight may be unevenly 850 mm.

insulated to prevent condensation distributed. Approximate total unit


and heat loss. weight and corner weights are given Figure 1a
e. Refrigerant gas piping must be in Table 1. Space requirement for TWE model
insulated. Vertical Type
Warning
Caution On site lifting equipment must be For servicing and routine
Properly insulate all refrigerant gas capable of lifting the weight of the unit maintenance, provide access to the
piping to prevent possible water with an adequate safety factor. The unit through removable panels in the
damage due to condensation and to use of under-capacity lifting devices ceiling see Figure 1b.
prevent capacity loss and possible may result in personal injury or death
compressor damage. and cause damage to the unit.

- It is recommended that the outline The crated unit can be moved using a
drawings (Pages 10 and 11) be forklift of suitable capacity. For lifting 850 mm. 850 mm.
studied and dimensions properly the unit into an elevated mounting
noted and checked against position, run lifting straps or slings
850 mm.
selected installation site. By noting under the unit and attach securely to
in advance which knockouts are the lifting device. Use spreader bars to
to be used, proper clearance protect the unit casing from damage. Figure 1b
allowances can be made for Test lift the unit to determine proper Space requirement for TWE model
installation and possible future balance and stability. Horizonal Type
service.

TWE-IOM01-EN 5
Unit Installation

b. Location, Mounting and See Figure 2b (for horizontal Note


Positioning configuration) and see Figure 2a The air handler is designed so that
Before installing any unit make sure (for vertical configuration). refrigerant piping can enter from either
proper preparation has been made at the right or left hand side. The air
each unit locating for piping and Caution handler is shipped with the intent, that
electrical connections. Before hanging the unit on suspension the refrigerant, lines will enter from the
W#4 rods, reinforce the cabinet around the left hand side. To convert to right hand
knockouts, using a large washer inside entry, unbraze the elbow on the
the cabinet. Washer should be suction line and rotate 180 degrees
W#3
between the skin of the air handler and re-braze. (See Figures 3 and 4).
and the nut on the suspension rod.
W#2
Caution
Align holes (knockouts) in the cabinet • Protect adjacent surfaces from heat
W#1 with structural supports and secure damage, when brazing in and
suspensions rods to the structure, around the air handler.
then to the air handler cabinet. If • These air handlers are shipped
knockout locations do not permit with a holding charge in the coil.
proper alignment with existing Do not bleed holding charge until
structure, it may be necessary to field refrigerant lines are ready to be
fabricate cross members on existing connected.
structural beams.
On single circuit air handlers, attached
Note to the refrigerant tube of the coil, you
When other than bottom return is to will find a cloth bag that contains two
be used, side panel removed for return (2) brass clamps (straps) and cork
duct installation, must be secured over impregnated insulation material
Figure 2a the bottom opening. approximately 9” long by 4” wide, for
attaching and insulating the expansion
W#3 Auxiliary Drain Pan valve bulb to the suction line. On dual
A field fabricated auxiliary drain pan circuits air handlers there will be two
should be installed under the unit for (2) cloth bags with like parts.
W#2 all horizontal applications, and when
W#4
air handlers are installed above Note
ceilings or in other locations where There will also be a PVC adaptor in the
W#1 condensate overflow may cause cloth bag (S), for converting, metal
damage. This drain pan will eliminate drain pan nipples to PVC.
any excess condensation that may be
due to extreme humidity or an On air handlers that will have
obstructed drain in the primary drain refrigerant lines entering the
pan. Drain lines from this pan must be cabinet from the left side, remove
installed, but should not be connected the split rubber grommet from the
to the primary drain line from the unit, knockout in the end of the air
Figure 2b
isolate the auxiliary drain pan from handler. Uncoil the cap tube with
both the air handler and the structure. the bulb attached at the expansion
Horizontal Suspension valve and place the grommet on
If the air handler will be suspended, Positioning and Installation the cap tube. With the grommet
use a suspension mounting kit to The final position must be dictated by around the tube, push the bulb
isolate the unit from the structure. required service access to unit, through the hold and position the
This is usually accomplished through weight distribution over structural grommet back into it’s original
the use of spring or rubber isolators, supports, and by the locations of position. One bulb and cap tube on
which are offered as an accessory. electrical, refrigerant and condensate single circuit units and 2 bulb (s)
Mounting rods must be field drainage connections. All refrigerant approximately 45 degrees off vertical,
supplied. Isolator selection is piping connections are made inside 10 to 12 inches outside of the air
dependent upon total unit weight, the cabinet. They may enter the handler. See Figure 3 and 4.
including accessories. Approximate cabinet through factory provided
unit weights are provided in Table 1 knockouts.

6 TWE-IOM01-EN
Unit Installation

On air handlers that will have


refrigerant lines entering the cabinet
from the right side, the bulb(s) should
be attached to the suction tube(s)
inside the cabinet, in the same manner
as above, approximately 10” from the
right end of the unit.

After attaching to the suction line(s), DRAIN


PAN
either inside or outside of the cabinet,
wrap the cork impregnated insulation
around the bulb(s) and suction tube(s).
Refrigerant piping should then be HORIZONTAL
DRAIN
insulated. CONNECTIONS
(BOTH ENDS)

Important
Ensure that the refrigerant lines DRAIN PAN
passing through the cabinet are not VERTICAL
DRAIN CONNECTIONS
resting on sharp sheet metal edges. (BOTH ENDS)

3/4" GALVANIZED
Figure 5
NIPPLE PIPE & FITTINGS

the air handler for clearance of the


Materials drain trap is recommended. For a
4" MIN.
1 Tea typical drain trap assembly, see figure
1 Plug
3 Street Ell 6a and 6b.
2-3/4"
RIGHT SIDE HOOK UP
(OPTIONAL) MIN. 1 5-1/2" Nipple
3/4
NIPPLE
2"
DIA
LEFT SIDE HOOK UP
(STANDARD) Installation, brazing, leak testing, and
DIA
evacuation of refrigerant lines are
Figure 3 Figure 6a covered in the installation instructions
packaged with the outdoor unit. Read
3/4" PVC OR COPPER
TUBING & FITTINGS
the instructions before beginning
Materials
NIPPLE 1 Tea
installation of refrigerant lines.
3 90" Ell
1 Plug
4" MIN. 1 6" Nipple
Filters
2 2" Nipple Air handlers are shipped with 1”
1 3/4" NPT to PVC washable filters installed. To replace
2-3/4" or copper adapter
RIGHT SIDE HOOK UP
MIN. filters, remove lower access panel
(OPTIONAL)

NIPPLE
3/4
DIA
LEFT SIDE HOOK UP (either end) and slide old filters
2" (STANDARD)
DIA out and replace with new ones.
Figure 4 Figure 6b See Figure 7.

Condensate Piping caps provided. They should be glued


These air handlers come standard with into place with field supplied PVC
two (2) drain pans. Drain connections cement. If the air handlers have metal
are provided on both sides of the air drain pans, the nipples will have plugs
handler for both the vertical and factory installed. When it has been
horizontal positions. See Figure 5. decided which nipple is to be used,
remove the plug from that nipple only.
When the vertical or horizontal
application has been decided, one Important REMOVE 4 SCREWS AND
ANGLE TO USE 2" FILTER

drain nipple on the bottom pan and When air handler is installed in the
both drain nipples on the upper pan vertical position and close proximity
should be sealed. If drain pans are trapping of condensate is required,
plastic there will be three (3) plastic use of a subbase accessory to raise Figure 7

TWE-IOM01-EN 7
Unit Installation

To convert from a 1” filter to a 2” filter FLANGK


Operational checks cannot be
on units so equipped, remove lower performed until the system
KNOCKOUT
access panels from both ends of the interconnection is complete.
air handler. Remove two (2) screws
and the L shaped angles from both • Verify that the unit electrical power
the top and bottom of the filter track is disconnected.
to increase the width of the filter • Inspect all field wiring connections.
opening (see figure 7). The screws All connections should be clean
and L shaped angles can be UNIT POWER ENTRY and tight.
discarded or saved for possible • Inspect unit ground connection(s).
future use. Ground must comply with all
applicable codes.
Duct Connections • Inspect unit suspension
The supply and return ducts should be arrangement (if used). Unit position
connected to the unit with flame must be secure. Remove any tools
retardant duct connectors to reduce or debris found in or near the unit.
vibration transmission. The return duct Figure 8 • Inspect duct outlets. Outlets must
should be sized to the same dimen- be open and unrestricted.
sions as the return inlet of the unit. Thermostat & Control • Inspect unit drain lines. Pipe
Connection connections must be tight and
Electrical Connections drain line unrestricted.
- Mount the thermostat in the desired
Warning • Inspect fan assembly to insure all
location.
When installing or servicing this moving parts move freely.
- Install color coded cables between
equipment, always exercise basic • If unit is horizontally mounted,
outdoor unit, indoor unit and
safety precautions to avoid the make sure secondary drain pan has
thermostat.
possibility of electric shock that could been installed.
- Connect control wiring to the
result in severe personal injury or • Inspect unit for proper filters,
terminal board located on the side
death. securely installed. All cabinet
of the fan control box.
panels must be secured.
1. All electrical lines, sizing, • Inspect owner/operator on proper
Table 2 - Recommended
protection, and grounding must system operating and
Thermostat Wire Size maintenanced procedure.
be in accordance with local codes.
2. If conduit is used, isolate whenever Maximum Wire Length
Wire Sie (Physical Distance
vibration transmission may cause a
between Unit and T-stat)
noise problem within the building
structure. 22 - gauge 30 feet
20 - gauge 50 feet
3. Ensure all connections are tight and
18 - gauge 75 feet
no wires exposed. 16 - gauge 125 feet
4. All accessories must be installed 14 - gauge 200 feet
and wired according to the
instructions packaged with that
accessory. Checkout Procedure
Complete the “Installation Checklist”
For air handler power entry only, or for at the end of this manual once
dual power entry (power entry for air installed all field wiring connections.
handler) the electrical connections are All operational checks (unit running)
made in the fan control box located in must be made after outdoor unit is
the left side of the air handler. Wiring installed and system interconnection
entrance is through holes provided in is complete.
the end of the air handler cabinet (see
Figure 8). Breaker or fuse size can be Installation Checklist
selected using the nameplates Complete this checklist once the
attached to unit. unit is installed to verify that all
recommended procedures have
Single point power entry is used, (one been accomplished before the
power entry for air handler). system is started.

8 TWE-IOM01-EN
General Data

General Data - Air Handler Units

INDOOR UNIT MODEL TWE 120 AD TWE 180 BD TWE 240 BD


POWER CONS-V/Ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50
INDOOR COIL-TYPE PLATE FIN PLATE FIN PLATE FIN
Row/FPI 3/12 3/12 3/12
Face Area (Sq.Ft.) 11.2 16.3 21.6
Tube Size inch 3/8 3/8 3/8
Refrigerant Control EXPANSION VALVE EXPANSION VALVE EXPANSION VALVE
Drain Conn. Size inch 3/4 PVC PIPE-FEMALE 1 PVC PIPE-FEMALE 1 PVC PIPE-FEMALE
No. of Refrigerant Circuit 1 2 2
INDOOR FAN-TYPE Centrifugal Type, Belt-Adjustable Drive
Dia x Width inch 15x15 15x15 15x15
No. Used 1 2 2
Nominal CFM 4,000 6,000 8,000
No. Motors-HP 1-2 1-3 1-5
Motors Speed RPM. 1,450 1,450 1,450
Volts/Ph/Hz. 380-415/3/50 380-415/3/50 380-415/3/50
F.L.Amps-L.R.Amps. 3.3-19.0 4.8-28.0 7.5-50.0
FILTER-TYPE Aluminium/Washable Filter
(No.)-Size x Thk. inch (4)-16x25x1 (8)-15x20x1 (4)-16x25x1,(4)-16x20x1
Refrigerant Factory Holding Charge
Ref. Line Connection Braze Braze Braze
Suction Line Size (each) inch 1 3/8 1 3/8 1 3/8
Liquid Line Size (each) inch 1/2 1/2 1/2
DIMENSIONS HxWxD
Crated mm 1,651x1,702x724 1,867x2,108x794 1,943x2,413x858
Uncrated mm 1,523x1,613x635 1,751x2,019x702 1,824x2,305x773
WEIGHT
Net Weight kg 190 313 372

TWE-IOM01-EN 9
Electrical Wiring

TWE120-240 (EXPORT)

10 TWE-IOM01-EN
Electrical Wiring

TWE120-240 (DOMESTIC)

TWE-IOM01-EN 11
Dimensional Data

TWE 120 AD

12 TWE-IOM01-EN
Dimensional Data

TWE 180-240 BD

TWE-IOM01-EN 13
Dimensional Data

TWE 120 AD
With Plenum (Option)

14 TWE-IOM01-EN
Dimensional Data

TWE 180-240 BD
With Plenum (Option)

TWE-IOM01-EN 15
Operation and Start-up

Preparation Start-Up Procedures


Perform the following checks and After completing all times under
inspections before operating the unit: “Pre-Start-Up”, the unit may be
started and the following checks
Inspection Checklist and adjustments performed.
• Unit is mounted securely to the
ceiling support rods (mounting a. Measure the motor voltage and
units). amps on all phases to insure proper
• Ductwork connections are operation. Compare these readings
complete. with the motor nameplate.
• Coil connections are complete and b. Disconnect load and start motor to
tight. check the direction of rotation. If
• Condensate drain pan connections the rotation need to be changed,
are complete and tight. stop the motor completely and
• Electrical connections are change the direction of rotation.
completed. Wiring is correct and c. After connecting the load, the
in accordance with the wiring motor should start quickly and run
diagram. smoothly. If it does not, the power
• Ground connection is completed. supply should be switched off at
• Check and retighten if necessary once and all connections, as well
set screws on the drive, fan pulley, as the power supply, be re-checked
fan bearings and wheel. before re-starting.
• Rotate fan by hand, to ensure that it d. In the event of excessive vibrations
runs freely and that there is no or unusual noises, the motor should
interference. be disconnected from the load and
• Check that fan is centrally located checked for poor alignment, loose
in the housing, axially and radially. mounting bolts, etc.
• Check and retighten, if necessary, e. When the motor has been operated
drive and bearing bolts, motor under load for a short period of
clamp plate bolts and isolator bolts. time, check that the operating
• Check to ensure that pulley are current totally with the nameplate
correctly aligned and that shafts current.
are parallel.
• Check belt tension as per
instruction given in the
maintenance section.

16 TWE-IOM01-EN
Maintenance

Warning To clean permanent filters, the filter


Disconnect electrical power source media and wash it in water to remove
and secure in disconnected position dust, dirt and lint, allow to dry thor-
before servicing the unit. Failure to do oughly before re-installing in the units.
so may result in personal injury or Do not rub or wring.
death from electrical shock.
Permanent filters can also be cleaned
Monthly Inspection by blowing with compressed air in
1. Check condition of air filters and opposite direction of filter airflow.
replace them if necessary.
2. Check the drain pan to be sure that Belt Maintenance
it is clean and free to carry the flow Clean fan belts and pulleys with a dry
of condensate through the drain cloth. Oil and grease must be kept off
line. belts. The use of a belt dressing is not
3. Check the coil surface for recommended. When replacing belts,
cleanliness. Clean if necessary. use a matched set.

Yearly Inspection Do not force belts onto pulleys,


1. Replace filters. but adjust motor position to allow
2. Check coil surface. Clean by mounting and then re-tighten.
vacuuming or flushing with cold
water. Do not use steam or hot
water.
3. Carry out checks as detailed in
inspection checklist in the
Operation Section.
4. Inspect the condition of the
evaporator fan belt and replace if Span
necessary. The belts fitted to TWE Force
units cannot achieve design
performance without the correct
tensioning. Deflection
5. Check condition of vibration
isolators, replace if there is any
sign of wear, loosening or material
deterioration.
6. Check fan bearings for noisy
operation and excessive lubricant Figure 9
leakage. Replace if necessary.
7. Inspect the condensate drain pan
and condensate piping to make To measure belt tension, use a belt
sure they are clear and will carry tensioner as shown in Figure 9.
away all water. Determine actual deflection by
8. Inspect the control panel wiring to depressing one belt with the belt
make sure connections are tight tensioner and then adjust the belt
and insulation is intacted. tension to the correct pounds force
and tighten all setscrews to the proper
Change/Clean Filters torques.
Change or clean air filters at least
twice a year. Filters will be required
more frequent care under high load
condition or dirty air. A clogged air
filters reduces airflow, cooling capacity
and increases energy usage.

TWE-IOM01-EN 17
Trouble Shooting

Restriction (TXV or CAP)


Check Valve (Leaking)
Excessive Evap. Load
Refrig. Undercharge
Control Transformer
High Voltage Wiring

High Indoor Airflow


Low Voltage Wiring

Low Indoor Airflow

Refrig. Overcharge

Restriction LD Coil
Low Voltage Fuse
System

Curcuit Breaker

Thermal Cutout
Capacitor (Fan)
Power Supply

Faults
Thermostat

Relay (Fan)
Refrigerant Circuit

Head Pressure Too High P

Head Pressure Too Low P P

Suction Pressure Too High P P P P

Suction Pressure Too Low P P P P

Indoor Coil Frosting P P P P

Liquid Floodback (TXV) P

Liquid Floodback (Cap. Tube) P

Electrical

I.D. Motor Won’t Start P P P P P P P P P

P Primary Causes - S Secondary Causes

18 TWE-IOM01-EN
Safety recommendations Maintenance Contract Training
To avoid accidents and damage, the It is strongly recommended that you The equipment described in this
following recommendations should be sign a maintenance contract with your manual is the result of many
observed during maintenance and local Service Agency. This contract years of research and continuous
service visits: provides regular maintenance of your development. To assist you in
1. The maximum allowable pressures installation by a specialist in our obtaining the best use of it, and
for system leak testing on low and equipment. Regular maintenance maintaining it in perfect operating
high pressure side are given in the ensures that any malfunction is condition over a long period of time,
chapter “Installation”. Always detected and corrected in good time the constructor has at your disposal
provide a pressure regulator. and minimizes the possibility that a refrigeration and air conditioning
2. Disconnect the main supply before serious damage will occur. Finally, service school. The principal aim
any servicing on the unit. regular maintenance ensures the of this is to give operators and
3. Service work on the refrigeration maximum operating life of your maintenance technicians a better
system and the electrical system equipment. We would remind you knowledge of the equipment they are
should be carried out only by that failure to respect these installation using, or that is under their charge.
qualified and experienced and maintenance instructions may Emphasis is particularly given to the
personnel. result in immediate cancellation of importance of periodic checks on the
the warranty. unit operating parameters as well as
on preventive maintenance, which
reduces the cost of owning the unit
by avoiding serious and costly
breakdown.

TWE-IOM01-EN 19
Trane Thailand Literature Order Number: TWE-IOM01-EN 0301
7th Floor, Ploenchit Center Building
Supersedes: S/S-IN-2 (EN) (TTh) TWE 0397
2 Sukhumvit Road, Klongtoey
Bangkok 10110 Stocking Location: Bangkok, Thailand
Amair Limited
35 Mu 8, Poochaosamingprai Road ∫√‘…—∑ ·Õ¡·Õ√å ®”°—¥ 35 À¡Ÿà 8 ∂.ªŸÉ‡®â“ ¡‘ßæ√“¬ µ. ”‚√ß„µâ Õ.æ√–ª√–·¥ß ®. ¡ÿ∑√ª√“°“√ 10130
Samrong Tai, Samutprakarn 10130
http://www.trane.com Since The Trane Company has a policy of continuous product and product data improvement,
An American Standard Company it reserves the right to change design and specifications without notice.

You might also like