W N E
BU-800 HIGH
PRESSURE WI
GENERAL NOTES :
1. DO NOT SCALE THIS DRAWING.
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
UNLESS OTHERWISE NOTED.
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
DRAWING TITLE :
COVER SHEET
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/CS 04
shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
installed as per approved Shop drawing. 09.08.2023 N.T.S
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
10)
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
W N E
400000
ASPHALT ROAD TO BUHASA
11599.4321
4981
X
20000
X
PP01
15000
PP04 B
R7000
28000 4000 6000 4000 10000 28000 10000 4000 10000 28000 R7000 15000
22 21 20
PP04C
PP04 D
10000
PP05
PP06
PP04 A
PP02
10600
X
8500 4 4 8500
4 8500
X
5 5 5 30 30
GENERAL NOTES :
14000 14000
2400
2400 33 2400
X
2400
2400 30
1. DO NOT SCALE THIS DRAWING.
X
6000 6000
8500 4 4 8500 4 8500
34
X
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
UNLESS OTHERWISE NOTED.
X
6000 6000 6000 HDD AREA
5 14000 5 5 14000
73.0x70.0M
6000
X
8500 4 4 8500 4 8500 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
X
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
X
30 2400
60,000 GAL.
10000
X
4 4 4
30,000 GAL.
30,000 GAL.
8500 8500 8500
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
X
10000
5 14000
5 5 14000
X
13000
PATH WAY
BREECHING
X
4 4 4 17
INLET
PATH WAY
PATH WAY
FIRE
8500
X
3000
6000 28000
6000
WATER TANK
WATER TANK
WATER TANK
WATER TANK
X
POTABLE
POTABLE
POTABLE
POTABLE
302400 30
8 NOS.15000 GAL.
10400
4 4 4
X
8500 8500 8500 2000
X
WASHING
WATER TANK
WATER TANK
WATER TANK
WATER TANK
POTABLE
POTABLE
POTABLE
POTABLE
6000 AREA 6000
WASHING AREA 10400
X
10000
10000
X
8500 8500 8500
6000 4000
6000
HYDRO TESTING AREA
X
MRJ
10000
6000
2400
5 14000
5 6000 5 14000
6000 6626 73.0x70.0M 03 FOR APPROVAL 07.08.2023 KKI
30
X
2400
10001
DIESEL GENERATOR
02 FOR APPROVAL 28.07.2023 KKI MRJ
8500 4 4 8500 4 8500
6000
X
5400
6000 6000
01 FOR APPROVAL 24.07.2023 KKI MRJ
X
2400
X
5 14000 5 4A 5 14000 21300
16 21300
8500 4 8500 4 8500 QUANTITY AREA OF
REV. NO. DESCRIPTION DATE DRAWN CHKD
X
R7000 CABIN TYPE OF TOTAL AREA TYPE OF TYPE OF FIRE
4B R7000 NAME OF UNIT USAGE OF UNIT / BUILDING (m²)
(m²)
9991 10000 No. UNIT PROTECTION ALARM SYSTEM
SLOPE 8% SLOPE 8% SLOPE 8% SLOPE 8%
X
R7000
4000 10000 28000 R7000 R15000
2500
CLIENT:
2500 2500
1 SENIOR STAFF ACCOMMODATION BLOCK - 1 ACCOMMODATION 4 86.40 m² 345.60 m² FHR + EXTINGUISHER
6
X
6000 6000 5061
X X X
6 2 STAFF ACCOMMODATION TYPE -1 BLOCK - 2 ACCOMMODATION 35 86.40 m² 3024.00 m² FHR + EXTINGUISHER
2500
8000 R7000
300000 7500 2600 11600 15205 13146 2601 3 STAFF ACCOMMODATION TYPE - 2 BLOCK - 3 ACCOMMODATION 1 86.40 m² 86.40 m² FHR + EXTINGUISHER
ROBT STONE (ME)LLC
GATE
6390 39900
LPG STORAGE 10000 10000 4 WORKERS ACCOMMODATION TYPE - 1 BLOCK - 4 ACCOMMODATION 26 238.00 m² 6188.00 m² FHR + EXTINGUISHER
TANK 5400
16 R7000
R7000 4A WORKERS ACCOMMODATION TYPE - 2 BLOCK - 4A ACCOMMODATION 1 119.00 m² 119.00 m² FHR + EXTINGUISHER
P.O. Box. 39588
8463 21300
R10000
X X X X X X X X X X X
X X X X X X X X 25000
2400
4B WORKERS ACCOMMODATION TYPE - 3 BLOCK - 4B ACCOMMODATION 1 119.00 m² 119.00 m² FHR + EXTINGUISHER Abu Dhabi, U.A.E
23000 2500 20000
11322
15 14 23770 18000 2500 6 5 WORKERS TOILET BLOCK - 5 TOILET 18 56.00 m² 1008.00m² EXTINGUISHER
X
20000 14000 30
X
2400
X
6 6.25m² 25.00 m² EXTINGUISHER
R15000
6000
X
TRUCK PARKING 6000
X
X
PARKING
3600
6000
CLINIC BLOCK - 7 CLINIC 1 86.40 m² EXTINGUISHER
Gatch Road
FIRE ALARM SYSTEM &
X
7200 7A MEDICAL WASTE ROOM BLOCK - 7A WASTE ROOM 1 4.00 m² 4.00 m² EXTINGUISHER CONSULTANT :
X
5869
11 45150
X
14400 2900
31 TENNIS COURT VOLLEY BALL
COURT
FOOT BALL
COURT
FIRE DETECTION SYSTEM
6000
7 12000 18 30000 8 CAMP OFFICE & CAMP STORE BLOCK - 8 OFFICE & STORE 1 108.00 m² 108.00 m² FHR + EXTINGUISHER
X
3400
X X X X X X X X X
7230
X
DIESEL
X
GENERATOR 12200
9 STAFF GYM & RECREATION BLOCK - 9 GYM & RECREATION 1 172.80 m² 172.80 m² FHR + EXTINGUISHER
AREA FOR
X
AIR PUMP &
X
X
2900 6000 2000
7A
10 11
X
WORKERS RECREATION BLOCK - 11 RECREATION 1 172.80 m² 172.80 m² EXTINGUISHER
2000
2900
32 18000
13
X
6000
X
E 8%
OP
SL
10800
6500
2400 30 12 LAUNDRY BLOCK - 12 LAUNDRY 1 129.60 m² 129.60 m² EXTINGUISHER
X X X X X X X X
X
9
20000
X
2400
12 12000
14400 16400
10000
X
X
7082
3000 12000 6000 12000 6000 12000 Gatch Road SPRINKLER + FHR +
8000 10800 12000 14 WORKERS DINING HALL BLOCK - 14 DINING HALL 951.85 m² 951.85 m²
23 23 23
X
3600 1 EXTINGUISHER
X
X
R7000
6000
BASKET BALL
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 SPRINKLER + FHR +
15 GENERAL KITCHEN BLOCK - 15 KITCHEN 1 798.00 m² 798.00 m²
X
6000 COURT
FIRE CONTRACTOR
X
X
EXTINGUISHER
H
R7000 24000 6000 24000 6000 24000 6000 24000 6000 24000
23 23 23 16 SUBSTATION BLOCK - 16 SUBSTATION 2 115.02 m² 230.04 m² EXTINGUISHER
X
1 1 2 3 2
X
17 FIRE PUMP ROOM BLOCK - 17 FIRE PUMP ROOM 1 84.50 m² 84.50 m² EXTINGUISHER
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
3600
3600 3600
6000 6000
X
12000
X
6000 6000 6000
23 23 23 3600
X
6000 8000
19 SUPER MARKET BLOCK - 19 SUPER MARKET 1 269.28 m² 269.28 m² EXTINGUISHER
1 1 2 2 2 P.O. Box: 91962, Mussafah 14, Abu Dhabi
X
3600 3600 3600 12000
29 2400
2X2 ROAD
6000 20 STORE SHED -1 (OPEN SHED) BLOCK - 20 STORE SHED 1 600.00 m² 600.00 m² EXTINGUISHER
X
2400
2400 6000 30 T: +971 25535167, F: +971 25535159
BARRIER
CRASH
X
BLOCK - 21 STORE SHED 1 450.00 m² 450.00 m² EXTINGUISHER
24000 2400 30 23 23 23 3600 10000
X
30 2400
3600
24000
24 ADNOC STAFF GYM BLOCK - 24 GYM 1 120.00 m² 120.00 m² EXTINGUISHER FIRE ALARM SYSTEM &
X
20000
2400
6000 6000 6000 8000 26 ADNOC STAFF LAUNDRY BLOCK -26 LAUNDRY 1 43.20 m² 43.20 m² EXTINGUISHER
23 23 23
TEMPORARY CAMP ACCOMMODATION
3600 3600
2400
9600 30
X
6000
27 ADNOC STAFF DINING HALL BLOCK - 27 219.98 m² EXTINGUISHER
X
2400
26194
6000 6000
30 2400
24000
6000
23 23 23 3600
27 13500 DIESEL DISPENSER PETROL DISPENSER
29 ADNOC STAFF MOSQUE BLOCK - 29 PRAYER ROOM 1 80.00 m² 80.00 m² EXTINGUISHER
X
3600 2 2 2 3600
2 2 3600
6000 6000
30 ELECTRICAL ROOM TYPE -1 BLOCK - 30 SMDB ROOM 20 5.76 m² 115.20 m² EXTINGUISHER
R7000 30
X
31 ELECTRICAL ROOM TYPE -2 BLOCK - 31 SMDB ROOM 2 9.86 m² 19.72 m² EXTINGUISHER ZONE :
X
R7000 3400
2400
23 23 23
MADINAT ZAYED
3600 10000
6000
2400
6000 6000 312900 32 ELECTRICAL ROOM TYPE -3 BLOCK - 32 SMDB ROOM 2 8.41 m² 16.82 m² EXTINGUISHER
X
2400 30
X
2400 6000
30 33 AIR BLOWER & PUMP ROOM BLOCK - 33 PUMP ROOM 1 72.25 m² 72.25 m² EXTINGUISHER
24 37056
X
7000
12000
X
3600 2 2 2 2 2 23 23 23 3600
28 36 36 19 35 SECTOR NO : PLOT NO :
X
6000 6000
6000 2900
2500 2900 36 DIESEL TANK WITH SHED-1 BLOCK - 36 DIESEL TANK WITH SHED 1 97.00 m² 97.00 m² EXTINGUISHER
HABSHAN T1019
X
32
X
2 2 2 2 2 23 23 23
SLOPE 8%
3600
3600 3600 DIESEL TANK WITH SHED - PETROL TANK WITH SHED - 21600 37 PETROL TANK WITH SHED-2 BLOCK - 36 PETROL TANK WITH SHED 1 58.91 m² 58.91 m² EXTINGUISHER
2500
6 26 3600
8000
10,000 GALLON -2 NOS. 10,000 GALLON
X
7000
X
24000 6000 24000 6000 24000 6000 24000 6000 24000 12000 6000 12000 6000 12000 17075
4500 4000 3000 TOTAL UNITS 173 TOTAL AREA 19,411.80m²
8000 6372 12000
PROJECT DESCRIPTION :
PLOT LIMIT GATE PLOT LIMIT
BU HASA ACCOMMODATION (RSME AND ADNOC) PLAN LABOUR CAMP @ BUHASA
DRAWING TITLE :
SITE PLAN
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future
SFS/RS/BUH/SP 04
shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
installed as per approved Shop drawing. 09.08.2023 1:1000
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
10)
BU HASA ROAD 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
TOWARDS CICPA GATE NFPA 101) KKI MRJ
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
2400
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
W N E
BU-800 HIGH
PRESSURE WI
GENERAL NOTES :
PLOT LIMIT 400000 PLOT LIMIT
1530
GATE
LEGENDS 1. DO NOT SCALE THIS DRAWING.
2477
2496
6000
3964
15000 30000 40000
3000
4981
X
FHC
4965
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
6000
20000
X
FHD-10
DESCRIPTION MAKE
PP01
FHC 15000
SYMBOL
PP04 B
R7000 Ø180 UG HDPE PIPE Ø180 UG HDPE PIPE Ø180 UG HDPE PIPE 20
3961
28000 4000 6000 4000 10000 28000 10000 4000 10000 28000 R7000 15000
22 21
PP04C
PP04 D
10000
PP05
PP06
FHR FHR FHR
PP04 A
PP02
10600
X
FHC-01 FHC-11 FHC-21
10620
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
HDPE PIPE
HDPE PIPE
4 4 4 RECESSED PENDENT SPRINKLER, 69°, CHROME
FHC
8500 8500
Ø75 UG
Ø90 UG
6000 FHC-74 FHC-73
8500
BRISTOL
X
1005 3616
5 14000
5 5 14000
X
2400
Ø50UG HDPE PIPE BRISTOL ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
X
HDPE PIPE
6000 6000 48304 26718
HDPE PIPE
HDPE PIPE
4 4 4
Ø50UG
8500 8500 8500
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
Ø63UG
Ø63UG
34
X
120 MTS DISTANCE F
ZONE CONTROL VALVE ASSEMBLY BRISTOL
FHD
X
6000 6000 6000 HDD AREA
FHR 5 14000 5 FHR 5 14000
FHR
73.0x70.0M
Ø160 UG HDPE PIPE FHD-09
FHC
FHC-03 FHC-13 FHC-23 6000
X
HDPE PIPE
HDPE PIPE
4 4 4 A
AIR RELEASE VALVE
Ø50UG
Ø63UG
8500 8500 8500 BRISTOL
X
6000 WASHING
X
30 Ø50UG HDPE PIPE BRISTOL
10000
FHR
10000 10000
FHR
FABRICATION AND MATERIAL STORAGE AREA ALARM CHECK VALVE
HDPE PIPE
HDPE PIPE
Ø50UG
Ø50UG
30,000 GAL.
30,000 GAL.
8500 8500 8500
FIRE FIGHTING PUMP SET HORIZONTAL END
X
10000
5 14000
5 5 14000
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED).
DIESEL
6000 6000 6000
X
FHR FHR FHR 13000
FIRE & POTABLE PUMP ROOM 1.NO ELECTRIC PUMP (DUTY) BRISTOL
Ø180 UG HDPE PIPE
PATH WAY
PATH WAY
04 FOR APPROVAL 09.08.2023 KKI MRJ
J
1.NO DIESEL PUMP (STAND BY)
X
4 4 4 17
PATH WAY
PATH WAY
X
2400 2400
3000
6000 28000
6000
WATER TANK
WATER TANK
WATER TANK
WATER TANK
X
POTABLE
POTABLE
POTABLE
POTABLE
30 30
8 NOS.15000 GAL.
FHC-06 FHC-16 FHC-26 10400
HDPE PIPE
4 4 4
HDPE PIPE
HDPE PIPE
X
2000
Ø50UG
106138
8500 8500 8500
Ø50UG
Ø50UG
FIRE HOSE REEL - SINGLE CABINET, FULL M.S RED 01 FOR APPROVAL 24.07.2023 KKI MRJ
X
WASHING
WATER TANK
WATER TANK
WATER TANK
WATER TANK
POWDER COATED, (SURFACE MOUNTED)
POTABLE
POTABLE
POTABLE
POTABLE
6000
WASHING AREA AREA 6000
00 FOR APPROVAL 28.03.2023 KKI MRJ
10400
FHR
X
FHR FHR FHR
FHC-07
10000
X
Ø63UG
4000
6000
6000 * 1 " PRESSURE REDUCING VALVE
HYDRO TESTING AREA
X
CLIENT:
10000
6000
2400
5 14000
5 6000 5 14000
6000 6626 73.0x70.0M
FHR 30 FHR FHR
2 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK
X
2400
HDPE PIPE
6000
4 4 4
Ø75UG
Ø63UG
Ø50UG
X
5400
FHD-02
6000 6000
FIREX/ ROBT STONE (ME)LLC
FHC
X
FIRE GUARD
P.O. Box. 39588
2400
FHD
FHR
X
5 5 5 Abu Dhabi, U.A.E
HDPE PIPE
HDPE PIPE
FHC-09 14000
4A
FHC-19 14000 FHC-29
16 21300
Ø63 UG
Ø90 UG
21300
X
R7000
FHC-10 9991 10000
4B FHC-20 FHD-12 FHC-30
R7000
3922
X
R7000 R15000
FHD
X
6000 6000 5061 FHC
120 MTS DISTANCE FHD-07
6
6461
X X X Ø160 UG HDPE PIPE Ø160 UG HDPE PIPE CONSULTANT :
FHC
FHD
FHD
Ø80 PIPE TO DELUGE VALVE
FHD-08 2500
4546
300000 8000
7500 11600 15205 13146 2601 Ø 150MM WET TYPE FIRE HYDRANT-Ø 65MM
9216
GATE
FHC-38 FHD
17166
6390 39900 BRISTOL
FHC-39
OUTLET, 2 NO'S
FHR
FHR
6120
25000
X X X X X X X X
8463 21300 SPRINKLER SYSTEM 23000 X X X X X X X X X X X
2500 FIRE BREECHING2400
INLET 20000
X
120 MTS DISTANCE
20000 14000 30
X
2400
X
Ø180 UG HDPE PIPE
R15000
10674 12000
R15000
FHR
6000
X
Ø160UG HDPE PIPE FOR TRUCK PARKING 6000
X
X
3600 FHC-72
SPRINKLER SYSTEM PARKING 6000
Gatch Road
FHC-33 FHC-36
X
7200
X
FHR
5869
11 45150
X
2900 FHR
35944
TENNIS COURT
COURT COURT
6000 Ø160 UG HDPE PIPE
7 12000 18 30000
X
3400
X X X X X X X X X
7230
X
X
Ø50 UG HDPE PIPE
GENERATOR
Ø160 UG HDPE PIPE
12200
AREA FOR
X
AIR PUMP &
X
X
2900 6000 2000
7A
10 SPEED FIRE & SAFETY EQUIPMENT L.L.C.
X
2000
2900
32 18000
13
X
6000
X
E 8%
OP
SL
FHC-71
10800
FHC-31 6500
2400 30 X X X X X X X X Ø50 UG HDPE PIPE FHR
X
9
20000
FHR
Ø160 UG
X
2400
12 14400 FHC-35
P.O. Box: 91962, Mussafah 14, Abu Dhabi
HDPE PIPE
10000
FHR
FHR 24000
X
X
FHC-40 X
T: +971 25535167, F: +971 25535159
3174
7949
FHC-32 Ø63 UG 7082 Ø50 UG 3000 12000 6000 12000 6000 12000 Gatch Road
8000 10800 FHR
12000 HDPE PIPE HDPE PIPE Ø160 UG HDPE PIPE Ø50 UG
23 23 23
X
3600
X
X
X
X
H
FHR
SLOPE 8% SLOPE 8%
PROJECT NAME
Ø50 UG
1 1 2 3 2
X
3600
9000
X
Ø50 UG HDPE
6000 PIPE Ø50 UG HDPE PIPE Ø63 UG HDPE PIPE
6000 Ø50 UG Ø50 UG HDPE PIPE 6000 75022
23 23 23 3600
X
X
@ BUHASA
3600 3600 3600 12000
HDPE PIPE
29 2400 FHR
2X2 ROAD
FHC-62 6000
Ø75 UG
2400
120 MTS DISTANCE
73711
FHR
2400 30
BARRIER
CRASH
X
24000 2400 30 23 23 23 3600 10000
X
HDPE PIPE
X
FHC-42 FHC-45 FHC-48 FHC-51 FHC-54 2400 6000
25
X
11657
FHD-03
FHR 30
Ø50 UG HDPE PIPE
2400
FHR
Ø50 UG HDPE PIPE
FHR
Ø63 UG HDPE PIPE
FHR
Ø50 UG HDPE PIPE
FHR 14500
ZONE :
MADINAT ZAYED
6000 Ø50 UG 6000
Ø50 UG HDPE PIPE
23 23 23
X
FHD
24000 3600
HDPE PIPE
X
1000 2992
2 3600 2 2 3600 2 2 3600 FHC-67
HDPE PIPE
6000
6005 6000 FHC-63 FHR
Ø90 UG
2400
FHR 20000
6000 6000 6000 8000
154010
3600
23 3600
23 23
HDPE PIPE
30
9600
SECTOR NO : PLOT NO :
Ø63 UG
X
6000
X
16000
2 FHC-43
3600 2 FHC-46 2 FHC-49
3600 2 FHC-52 2 FHC-55
3600
6000 38425
FHR FHR FHR FHR FHR
HABSHAN T1019
X
2400
FHC-68 26194
6000 Ø50 UG HDPE PIPE Ø50 UG HDPE PIPE Ø63 UG HDPE PIPE Ø50 UG Ø50 UG HDPE PIPE 6000
30 6000
23 23 23 3600
27
FHR
24000 13500
HDPE PIPE DIESEL DISPENSER
2400
6000FHC-64 6000 Ø180 UG HDPE PIPE Ø160 UG HDPE PIPE PROJECT DESCRIPTION :
3422
R7000 30 FHC
X
FHR
HDPE PIPE
R7000 3400
2400
23 23 23 3600
Ø63 UG
FHD
6000 10000
SPRINKLER SYSTEM
2400
FHD-04
6000
FHC
7000
10000
2 2 2 2500 2500
2 2 23 23 23 3600
Ø50 UG
3600
FHC-56 FHC-57 FHC-58 FHC-59 FHC-60
28 FHC-69
19
X
6000 Ø50 UG HDPE PIPE Ø50 UG HDPE PIPE Ø63 UG HDPE PIPE Ø50 UG HDPE PIPE
6000
Ø75 UG
1248 32
DRAWING TITLE :
X
2 2 2 2 2 23 23 23
SLOPE 8%
6000 3600
3600 3600 DIESEL TANK WITH SHED - PETROL TANK WITH SHED - 21600
2500
6 26 3600
4023
7000
Ø180 UG HDPE PIPE Ø180
6000 UG 12000
HDPE PIPE
X
24000 6000 24000 6000 24000 6000 24000 6000 24000 12000 6000 12000
4000 3000
10960
Ø180 UG HDPE PIPE
8000
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future
SFS/RS/BUH/FP/01 04
shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
installed as per approved Shop drawing. 09.08.2023 1:1000
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
10)
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
BU HASA ROAD in this building in accordance to the relevant NFPA code and standards.
TOWARDS CICPA GATE 11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
28000
1 2 3 4 5 6 7
14000
14000 N
W N E
A
BED ROOM - 12 BED ROOM - 11 BED ROOM - 10 BED ROOM - 9 BED ROOM - 8 BED ROOM - 7
ASPHALT ROAD TO BUHASA
BU-800 HIGH
PRESSURE WI
8500
RECESSED PENDENT SPRINKLER, 69°, CHROME
FINISH,STANDARD RESPONSE.
BRISTOL UNLESS OTHERWISE NOTED.
BED ROOM - 1 BED ROOM - 2 BED ROOM - 3 BED ROOM - 4 BED ROOM - 5 BED ROOM - 6 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
UPRIGHT SPRINKLER, 79°,STANDARD RESPONSE. BRISTOL
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
F
ZONE CONTROL VALVE ASSEMBLY BRISTOL ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
A
AIR RELEASE VALVE BRISTOL
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED).
DIESEL
1.NO ELECTRIC PUMP (DUTY) BRISTOL
J
1.NO DIESEL PUMP (STAND BY)
B 1.NO JOCKEY PUMP
FHR Ø 150MM X 4 WAY BREECHING INLET-FLANGED INLET BRISTOL
04 FOR APPROVAL 09.08.2023 KKI MRJ
· FIRE EXTINGUISHERS ARE NOT PROVIDED IN ALL CARAVANS. 03 FOR APPROVAL 07.08.2023 KKI MRJ
· FOR LOCATION REFER: SFS/RS/BHS/FP/SP. FIRE HOSE REEL - SINGLE CABINET, FULL M.S RED
02 FOR APPROVAL 28.07.2023 KKI MRJ
POWDER COATED, (SURFACE MOUNTED)
BLOCK-4 WORKERS ACCOMMODATION TYPE-1 FHR * 1" X 30 METER HOSE REEL DRUM WITH
· FIRE HOSE REEL CABINET SHALL NOT PROVIDED IN ALL CARAVANS. BRISTOL 01 FOR APPROVAL 24.07.2023 KKI MRJ
NUMBER OF BLOCKS: 26 NOZZLE .
Ø50 U.G HDPE PIPE · FOR LOCATION REFER: SFS/RS/BHS/FP/SP. * 1 " PRESSURE REDUCING VALVE 00 FOR APPROVAL 28.03.2023 KKI MRJ
· TOTAL LENGTH OF THE HOSE REEL - 30 METERS.
2 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK REV. NO. DESCRIPTION DATE DRAWN CHKD
CLIENT:
FIREX/
4 KG DCP EXTINGUISHER LPCB/BSI KITEMARK FIRE GUARD
FHD
Ø 150MM WET TYPE FIRE HYDRANT-Ø 65MM
OUTLET, 2 NO'S BRISTOL
CONSULTANT :
1 2 3 4 5
24000 1 2 3 4 5
4900 7100 6900 5100
24000
A 12000 12000
BED ROOM - 1 TOILET BED ROOM - 2 BED ROOM - 3 TOILET BED ROOM - 4
A FIRE CONTRACTOR
BED ROOM - 1 TOILET TOILET BED ROOM - 2 BED ROOM - 3 TOILET TOILET BED ROOM - 4
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
3600
3600
TOILET TOILET T: +971 25535167, F: +971 25535159
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
PROJECT NAME
B
TEMPORARY CAMP ACCOMMODATION
FHR B @ BUHASA
BLOCK-2 STAFF ACCOMMODATION TYPE-1
· FIRE EXTINGUISHERS ARE NOT PROVIDED IN ALL CARAVANS.
· FOR LOCATION REFER: SFS/RS/BHS/FP/SP. SLOPE 8%
FHR SLOPE 8% ZONE :
NUMBER OF BLOCKS: 35 MADINAT ZAYED
· FIRE HOSE REEL CABINET SHALL NOT PROVIDED IN ALL CARAVANS.
Ø50 U.G HDPE PIPE · FOR LOCATION REFER: SFS/RS/BHS/FP/SP.
BLOCK-3 STAFF ACCOMMODATION TYPE-2 · FIRE EXTINGUISHERS ARE NOT PROVIDED IN ALL CARAVANS.
SECTOR NO : PLOT NO :
· TOTAL LENGTH OF THE HOSE REEL - 30 METERS. · FOR LOCATION REFER: SFS/RS/BHS/FP/SP.
NUMBER OF BLOCKS: 01 Ø50 U.G HDPE PIPE HABSHAN T1019
· FIRE HOSE REEL CABINET SHALL NOT PROVIDED IN ALL CARAVANS.
· FOR LOCATION REFER: SFS/RS/BHS/FP/SP. PROJECT DESCRIPTION :
· TOTAL LENGTH OF THE HOSE REEL - 30 METERS.
LABOUR CAMP @ BUHASA
1 2 3 4 5 DRAWING TITLE :
24000
12000 12000 FIRE PROTECTION SYSTEM LAYOUT
FOR BLOCK-1,2,3 &4
A
BED ROOM - 1 TOILET BED ROOM - 2 BED ROOM - 3 TOILET BED ROOM - 4 ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future
SFS/RS/BUH/FP/02 04
3600
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
W N E
28000
1 2 3 4 5 6 7 ASPHALT ROAD TO BUHASA
A
BED ROOM - 1 BED ROOM - 2 BED ROOM - 3 BED ROOM - 4 BED ROOM - 5 BED ROOM - 6 BU-800 HIGH
PRESSURE WI
4250
1. DO NOT SCALE THIS DRAWING.
SYMBOL DESCRIPTION MAKE
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
RECESSED PENDENT SPRINKLER, 69°, CHROME
FINISH,STANDARD RESPONSE.
BRISTOL UNLESS OTHERWISE NOTED.
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
UPRIGHT SPRINKLER, 79°,STANDARD RESPONSE. BRISTOL
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
B F
ZONE CONTROL VALVE ASSEMBLY BRISTOL ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
FHR A
AIR RELEASE VALVE BRISTOL
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
· FIRE HOSE REEL CABINET SHALL NOT PROVIDED IN ALL CARAVANS. FIRE FIGHTING PUMP SET HORIZONTAL END
Ø50 U.G HDPE PIPE · FOR LOCATION REFER: SFS/RS/BHS/FP/SP.
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED).
DIESEL
· TOTAL LENGTH OF THE HOSE REEL - 30 METERS. 1.NO ELECTRIC PUMP (DUTY) BRISTOL
J
1.NO DIESEL PUMP (STAND BY)
BLOCK-4A WORKERS ACCOMMODATION TYPE-2 1.NO JOCKEY PUMP
04 FOR APPROVAL 09.08.2023 KKI MRJ
NUMBER OF BLOCKS: 01 Ø 150MM X 4 WAY BREECHING INLET-FLANGED INLET BRISTOL
03 FOR APPROVAL 07.08.2023 KKI MRJ
FIRE HOSE REEL - SINGLE CABINET, FULL M.S RED
02 FOR APPROVAL 28.07.2023 KKI MRJ
POWDER COATED, (SURFACE MOUNTED)
FHR * 1" X 30 METER HOSE REEL DRUM WITH BRISTOL 01 FOR APPROVAL 24.07.2023 KKI MRJ
NOZZLE .
* 1 " PRESSURE REDUCING VALVE 00 FOR APPROVAL 28.03.2023 KKI MRJ
2 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK REV. NO. DESCRIPTION DATE DRAWN CHKD
28000 CLIENT:
FIREX/
4 KG DCP EXTINGUISHER LPCB/BSI KITEMARK FIRE GUARD
1 2 3 4 5
7000 7000 7000 7000
10 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK
ROBT STONE (ME)LLC
P.O. Box. 39588
A Abu Dhabi, U.A.E
50 LITRE FOAM TROLLEY FIRE EXTINGUISHER NAFFCO
FIRE CONTRACTOR
B
SLOPE 8% SLOPE 8%
FHR SLOPE 8% SLOPE 8% SPEED FIRE & SAFETY EQUIPMENT L.L.C.
EXIT-1 EXIT-2 EXIT-3 EXIT-4 P.O. Box: 91962, Mussafah 14, Abu Dhabi
T: +971 25535167, F: +971 25535159
· FIRE EXTINGUISHERS ARE NOT PROVIDED IN ALL CARAVANS. E-mail: speedfse@eim.ae, www.speedsafetyuae.com
· FOR LOCATION REFER: SFS/RS/BHS/FP/SP.
BLOCK-4B WORKERS ACCOMMODATION TYPE-3 Ø50 U.G HDPE PIPE
NUMBER OF BLOCKS: 01 · FIRE HOSE REEL CABINET SHALL NOT PROVIDED IN ALL CARAVANS. PROJECT NAME
· FOR LOCATION REFER: SFS/RS/BHS/FP/SP.
· TOTAL LENGTH OF THE HOSE REEL - 30 METERS. TEMPORARY CAMP ACCOMMODATION
@ BUHASA
ZONE :
MADINAT ZAYED
SECTOR NO : PLOT NO :
1 2
HABSHAN T1019
12000
A PROJECT DESCRIPTION :
OBSERVATION WARD
LABOUR CAMP @ BUHASA
3600
DRAWING TITLE :
1 2
2500
A FIRE PROTECTION SYSTEM LAYOUT
FOR BLOCK-4A, 4B, 6 &7
7200
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
WAITING AREA TOILET CONSULTING ROOM
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2500
2. Any architectural changes like addition, deletion, modification during construction or in future
SFS/RS/BUH/FP/03 04
shall be submitted to ADCD for both architectural and shop approvals.
SUBMISSION DATE : SCALE :
3600
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
installed as per approved Shop drawing. 09.08.2023 1:75
900
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
B3N-2022-000555-CD-SHD-02 A1
B 5.
10)
All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA
SHELTER 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
B NFPA 101) KKI MRJ
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
BLOCK-6 GUARD ROOM by voice announcement system according to (NFPA 72).
NUMBER OF BLOCKS: 04 FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
BLOCK-7 CLINIC EXIT-1 SHELTER (NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
NUMBER OF BLOCKS: 01 10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
1 2
14400
EXIT-4 EXIT-3
10000 SHELTER
SHELTER SHELTER W N E
1 2 3 A
STAFF GYM RECREATION
A ASPHALT ROAD TO BUHASA
STORE
FHR
BU-800 HIGH
PRESSURE WI
DISTANCE: 16 METERS
1. DO NOT SCALE THIS DRAWING.
SYMBOL DESCRIPTION MAKE
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
7148
DIS
RS
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
UPRIGHT SPRINKLER, 79°,STANDARD RESPONSE.
TE
BRISTOL
TA
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
12000
ME
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
NC
F
ZONE CONTROL VALVE ASSEMBLY BRISTOL ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
E: 2
0
10800
E: 2
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
0
A
NC
ME
AIR RELEASE VALVE BRISTOL
TA
TE
DIS
ALARM CHECK VALVE BRISTOL
RS
FIRE FIGHTING PUMP SET HORIZONTAL END
B
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED).
DIESEL
1.NO ELECTRIC PUMP (DUTY) BRISTOL
TOILET
J
1.NO DIESEL PUMP (STAND BY)
1.NO JOCKEY PUMP
04 FOR APPROVAL 09.08.2023 KKI MRJ
Ø 150MM X 4 WAY BREECHING INLET-FLANGED INLET BRISTOL
3652
EXIT-1
FHR EXIT-2
4 KG DCP EXTINGUISHER LPCB/BSI KITEMARK
FIREX/
FIRE GUARD
SHELTER
10 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK
ROBT STONE (ME)LLC
SHELTER SHELTER P.O. Box. 39588
BLOCK-8 CAMP OFFICE & CAMP STORE Abu Dhabi, U.A.E
NUMBER OF BLOCKS: 01 Ø50 U.G HDPE PIPE 50 LITRE FOAM TROLLEY FIRE EXTINGUISHER NAFFCO
FHD
Ø 150MM WET TYPE FIRE HYDRANT-Ø 65MM
BRISTOL
BLOCK-9 STAFF GYM & RECREATION OUTLET, 2 NO'S
CONSULTANT :
NUMBER OF BLOCKS: 01
16400
1 14400 2
1 2 1200 1200
SHELTER FIRE CONTRACTOR
1200
1200
SHELTER
P.O. Box: 91962, Mussafah 14, Abu Dhabi
A A
T: +971 25535167, F: +971 25535159
WORKERS WORKERS E-mail: speedfse@eim.ae, www.speedsafetyuae.com
RECREATION-1 RECREATION-2
PROJECT NAME
ZONE :
MADINAT ZAYED
SECTOR NO : PLOT NO :
HABSHAN T1019
DIS
RS
S
TE
PROJECT DESCRIPTION :
TA
ER
ME
NC
ET
B
12000
12200
E:
: 20
20
:1
CE
CE
ME
N
AN
DRAWING TITLE :
TA
TE
ST
DIS
RS
DI
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future
SFS/RS/BUH/FP/04 04
shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
installed as per approved Shop drawing. 09.08.2023 1:75
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
C B 10)
DRAWN BY : CHECKED BY :
FHR 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and
2000
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
SLOPE 8% 8. All portions of these building shall be fully protected by automatic sprinklers system according to
FOR CIVIL DEFENSE APPROVAL :
Ø50 U.G HDPE PIPE SHELTER SHELTER SHELTER
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
2000 Ø50 U.G HDPE PIPE 2000
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
BLOCK-10 MOSQUE in this building in accordance to the relevant NFPA code and standards.
BLOCK-11 WORKERS RECREATION
NUMBER OF BLOCKS: 01 11. All fire door and windows shall be according to (NFPA 80).
NUMBER OF BLOCKS: 01 12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
W N E
BU-800 HIGH
PRESSURE WI
11700 5255 1736 8114 13196 2600 1. DO NOT SCALE THIS DRAWING.
SYMBOL DESCRIPTION MAKE
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
1 2 3 4 5 6 7 8 RECESSED PENDENT SPRINKLER, 69°, CHROME
2500 2500
FINISH,STANDARD RESPONSE.
BRISTOL UNLESS OTHERWISE NOTED.
SHELTER
SHELTER
1 1
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
2
Ø50 U.G HDPE PIPE Ø50 U.G HDPE PIPE 2
1500 UPRIGHT SPRINKLER, 79°,STANDARD RESPONSE. BRISTOL
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
3 3
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
A F
1500
ZONE CONTROL VALVE ASSEMBLY BRISTOL ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
DISH WASH ROOM
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
COLLECTION AREA
1700
1077 3000 1077
2000
FHR
A
AIR RELEASE VALVE BRISTOL
HAND WASH AREA 1014 3000 3000 1000 HAND WASH AREA
WATER DRINKING
3634
FHR
Ø25
Ø25
FIRE FIGHTING PUMP SET HORIZONTAL END
2800
Ø25
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED).
DIESEL
Ø50 U.G HDPE PIPE
B 1.NO ELECTRIC PUMP (DUTY) BRISTOL
800
J
6265 1.NO DIESEL PUMP (STAND BY)
1000 4000 4000 4000 4000 4000 4000 4000 4000 4000 2950 1000 1.NO JOCKEY PUMP
(TYP) (TYP) (TYP) (TYP) (TYP) (TYP) (TYP) (TYP) (TYP) (TYP) (TYP)
(TYP) 04 FOR APPROVAL 09.08.2023 KKI MRJ
Ø 150MM X 4 WAY BREECHING INLET-FLANGED INLET BRISTOL
(TYP)
2000
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø32
Ø32
03 FOR APPROVAL 07.08.2023 KKI MRJ
FIRE HOSE REEL - SINGLE CABINET, FULL M.S RED
02 FOR APPROVAL 28.07.2023 KKI MRJ
POWDER COATED, (SURFACE MOUNTED)
FHR * 1" X 30 METER HOSE REEL DRUM WITH BRISTOL 01 FOR APPROVAL 24.07.2023 KKI MRJ
NOZZLE .
* 1 " PRESSURE REDUCING VALVE 00 FOR APPROVAL 28.03.2023 KKI MRJ
(TYP)
DRAWN CHKD
3000
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø40
Ø32
Ø40
2 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK REV. NO. DESCRIPTION DATE
9442
CLIENT:
FIREX/
4 KG DCP EXTINGUISHER LPCB/BSI KITEMARK FIRE GUARD
Ø40
Ø40
Ø40
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
50 LITRE FOAM TROLLEY FIRE EXTINGUISHER
(TYP)
3000
NAFFCO
23000
FHD
Ø 150MM WET TYPE FIRE HYDRANT-Ø 65MM
OUTLET, 2 NO'S BRISTOL
CONSULTANT :
Ø40
Ø40
Ø40
Ø40
Ø50
Ø40
Ø50
Ø40
Ø40
Ø40
Ø40
Ø40
Ø50 Ø65 Ø80 Ø80 Ø80 Ø100 Ø100 Ø100 Ø100 Ø100 Ø100 F
Ø110 UG HDPE PIPE FOR
(TYP)
SPRINKLER SYSTEM
3000
Ø100 ZCV
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
3000
FIRE CONTRACTOR
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
(TYP)
3000
PROJECT NAME
6924
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
(TYP)
3000
C 3 SECTOR NO : PLOT NO :
SHELTER
HABSHAN T1019
2 2
1200 1 SHELTER 1 1200
DRAWING TITLE :
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future
SFS/RS/BUH/FP/05 04
2000
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
39900
1500
N
1200
W N E
SHELTER S
SHELTER
A
GARBAGE
2650
RECEIVING AREA
ROOM
SALAD ROOM LEGENDS
ASPHALT ROAD TO BUHASA
PROTEIN FREEZER
VEG FREEZER
FISH FREEZER
RECESSED PENDENT SPRINKLER, 69°, CHROME
VEG CHILLER
B BRISTOL BU-800 HIGH
FINISH,STANDARD RESPONSE. PRESSURE WI
PRE WASH AREA
PACKING ROOM
CHAPATTI ROOM
UPRIGHT SPRINKLER, 79°,STANDARD RESPONSE. BRISTOL
F
ZONE CONTROL VALVE ASSEMBLY BRISTOL
A
1. DO NOT SCALE THIS DRAWING.
AIR RELEASE VALVE BRISTOL
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
ALARM CHECK VALVE BRISTOL UNLESS OTHERWISE NOTED.
C
FIRE FIGHTING PUMP SET HORIZONTAL END
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
PVC CURTAIN
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED).
DIESEL
MEAT ROOM MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
1.NO ELECTRIC PUMP (DUTY) BRISTOL
3200
FD 60
J
1.NO DIESEL PUMP (STAND BY)
1.NO JOCKEY PUMP CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
HOT KITCHEN
Ø 150MM X 4 WAY BREECHING INLET-FLANGED INLET BRISTOL
SHADED
RECEIVING OFFICE 4000 4000 4000 4000 4000 4000 4000 4000 4000 2000
D
20000
FD 60
STAFF ENTRANCE Ø25 Ø25 Ø32 Ø40 Ø40 Ø40 Ø32 Ø25 Ø25 FIRE HOSE REEL - SINGLE CABINET, FULL M.S RED
POWDER COATED, (SURFACE MOUNTED)
1200
FHR * 1" X 30 METER HOSE REEL DRUM WITH
DEFROST CHILLER
BRISTOL
FISH DE-CHILLER
CHICKEN ROOM NOZZLE .
EGG CHILLER
DAIRY CHILLER
Ø50
2 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK
5200
TOILET
LOCKERS
PVC CURTAIN
TOILET 10 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK 02 FOR APPROVAL 28.07.2023 KKI MRJ
FISH ROOM
01 FOR APPROVAL 24.07.2023 KKI MRJ
50 LITRE FOAM TROLLEY FIRE EXTINGUISHER NAFFCO
E KKI MRJ
00 FOR APPROVAL 28.03.2023
Ø 150MM WET TYPE FIRE HYDRANT-Ø 65MM
GARBAGE ROOM
FHD
OUTLET, 2 NO'S BRISTOL REV. NO. DESCRIPTION DATE DRAWN CHKD
1500
ROBT STONE (ME)LLC
5250
1200
Ø50
P.O. Box. 39588
DISPOSABLE DRY STORE CHEMICAL STORAGE
STORE Abu Dhabi, U.A.E
FD 60
1500
Ø50 G.I TO SPRINKLERS
IN ABOVE VOID LEVEL
CONSULTANT :
F 1200
1200
SHELTER
SHELTER
FHR P.O. Box: 91962, Mussafah 14, Abu Dhabi
A
T: +971 25535167, F: +971 25535159
600
GARBAGE
(TYP)
1074
1150
1150
1100 3500 1700 1950 E-mail: speedfse@eim.ae, www.speedsafetyuae.com
PROTEIN FREEZER
3500
FISH FREEZER
(TYP)
B
3000
3000
Ø25
(TYP)
3500
@ BUHASA
Ø40
Ø25
PRE WASH AREA
PACKING ROOM
CHAPATTI ROOM
Ø32
Ø25
Ø25 Ø32 Ø25 MADINAT ZAYED
Ø40
SECTOR NO : PLOT NO :
Ø25 Ø25 Ø32
(TYP)
3000
3000
Ø50
Ø50
HABSHAN T1019
3500
C
3500
Ø50
PROJECT DESCRIPTION :
1760
PVC CURTAIN
1800
Ø25
2000 3500 3500 1900 MEAT ROOM
Ø25 Ø25
LABOUR CAMP @ BUHASA
(TYP)
3200
1150
1150
1600
FD 60
DRAWING TITLE :
SHADED
RECEIVING OFFICE 2000 4000 1800 1000 4000
3500
D
FD 60
(TYP)
3500
3500
STAFF ENTRANCE
Ø50
Ø65
1200
FIRE PROTECTION SYSTEM LAYOUT
DEFROST CHILLER
FISH DE-CHILLER
CHICKEN ROOM
EGG CHILLER
1600
DAIRY CHILLER
TOILET 1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
LOCKERS
drawings.
SFS/RS/BUH/FP/06 04
3500
Ø65
Ø25 Ø25 1800 2. Any architectural changes like addition, deletion, modification during construction or in future
1950
(TYP)
3500
3500
PVC CURTAIN
Ø60
TOILET
FISH ROOM 3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
1100
1:75
1900
Ø25
1500
1250 3000 1250 4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
E 2000 3500 3500 1900 Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
(TYP) (TYP) (TYP) (TYP) Approval Department.
975
850
Ø25
10)
Ø65
1500
Ø25 1800 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
3500
KKI MRJ
(TYP)
3026
3000
NFPA 101)
1075
Ø40
2575
Ø25
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
5250
2500
STORE
1500FD 60
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
Ø50
1075
900
850
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
1500
1200
SHELTER
BLOCK-15 GENERAL KITCHEN (BELOW CEILING LEVEL) PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
1425 Ø25 this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
2000
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
NUMBER OF BLOCKS: 01 Ø160 UG HDPE PIPE FOR
SPRINKLER SYSTEM
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
Ø100
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
3000
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
Ø100 G.I PIPE FOR SPRINKLER NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
SYSTEM TO BLOCK-13 and tested in accordance with (UAE fire and life safety code and other relevant international standards).
Ø25 18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
1 2 3 21300 4 5
1 1200 2
10800 4300 3350 3350 10300
EXIT-3
A N
1200
W N E
SHELTER
A
SHELTER
STORE
2000 TRF1 TRF2 BUS
ASPHALT ROAD TO BUHASA
COUPLER
MDB-1 MDB-2
5400
BU-800 HIGH
PRESSURE WI
2000
QRM ROOM
TRANSFORMER ROOM CB-1 CB-2
SHELTER
WASHING AREA
LEGENDS GENERAL NOTES :
1. DO NOT SCALE THIS DRAWING.
SYMBOL DESCRIPTION MAKE
ERS
6.5 MET 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
:2 RECESSED PENDENT SPRINKLER, 69°, CHROME
NCE B BRISTOL UNLESS OTHERWISE NOTED.
D ISTA FINISH,STANDARD RESPONSE.
IRON PRESSING
1600 3400 2650 2650 7338 3662 F
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
12000
ZONE CONTROL VALVE ASSEMBLY BRISTOL ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
BLOCK-16 SUB-STATION A
AIR RELEASE VALVE BRISTOL
NUMBER OF BLOCKS: 02
ALARM CHECK VALVE BRISTOL
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED).
DIESEL
1.NO ELECTRIC PUMP (DUTY) BRISTOL
J
1.NO DIESEL PUMP (STAND BY)
LINE SORTING 1.NO JOCKEY PUMP
04 FOR APPROVAL 09.08.2023 KKI MRJ
1 6 Ø 150MM X 4 WAY BREECHING INLET-FLANGED INLET BRISTOL
2 3 4 5
03 FOR APPROVAL 07.08.2023 KKI MRJ
30000 FIRE HOSE REEL - SINGLE CABINET, FULL M.S RED
02 FOR APPROVAL 28.07.2023 KKI MRJ
1400 1400 1400 1400 1400 2500 5000 1500 7500 6500 POWDER COATED, (SURFACE MOUNTED)
FHR * 1" X 30 METER HOSE REEL DRUM WITH BRISTOL 01 FOR APPROVAL 24.07.2023 KKI MRJ
NOZZLE .
1200
SHELTER
* 1 " PRESSURE REDUCING VALVE 00 FOR APPROVAL 28.03.2023 KKI MRJ
A DRAWN CHKD
DOCUMENT CONTROL ROOM QA/QC ROOM 2 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK REV. NO. DESCRIPTION DATE
WC WC WC WC WC PANTRY STORE ROOM
CLIENT:
B
2350
2550
FIREX/
4 KG DCP EXTINGUISHER LPCB/BSI KITEMARK
FHR SHELTER
FIRE GUARD
1200
4000
10 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK
ROBT STONE (ME)LLC
BLOCK-12 LAUNDRY
P.O. Box. 39588
Abu Dhabi, U.A.E
NUMBER OF BLOCKS: 01 1200 50 LITRE FOAM TROLLEY FIRE EXTINGUISHER NAFFCO
2450 HAND WASH AREA
3500
2050
DISTANCE: 30 METERS
FHR
1 2
6500 PRINTER
FIRE CONTRACTOR
2000
A WORK STATION WORK STATION
20000
MANAGER OFFICE-6
T: +971 25535167, F: +971 25535159
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
4600
PROJECT NAME
Ø50 U.G HDPE PIPE
DISTANCE: 30 METERS
ZONE :
ADMINISTRATION MADINAT ZAYED
13000
OFFICE
SECTOR NO : PLOT NO :
C HABSHAN T1019
MANAGER OFFICE -1 MANAGER OFFICE -2 MANAGER OFFICE -3 MANAGER OFFICE -4 RECEIPTION MANAGER OFFICE -5
5800
PROJECT DESCRIPTION :
FHR
B 4050 4550 3600 3600 3600 4292 3600 2706
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
30000 1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
BLOCK-17 FIRE PUMP ROOM drawings.
NUMBER OF BLOCKS: 01
BLOCK-18 ROBT STONE OFFICE SFS/RS/BUH/FP/07 04
1500
NUMBER OF BLOCKS: 01 SHELTER 2. Any architectural changes like addition, deletion, modification during construction or in future
BLOCK-18 shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
ROBT STONE OFFICE 2000 installed as per approved Shop drawing. 09.08.2023 1:75
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
1 2 3 5 10)
DRAWN BY : CHECKED BY :
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and
NFPA 101) KKI MRJ
12000 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
4150 1750 1750 4350 8. All portions of these building shall be fully protected by automatic sprinklers system according to
FOR CIVIL DEFENSE APPROVAL :
(NFPA 13).
A 9. Standpipe system shall be provided in these building according to (NFPA 14).
LIVING ROOM PANTRY TOILET BED ROOM 10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
3600
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
B NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
AIR LOCK
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
BLOCK-23 ADNOC STAFF ACCOMMODATION NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
NUMBER OF BLOCKS: 30 safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
1 2
40000
A
N
W N E
BU-800 HIGH
PRESSURE WI
15000
DI S
ST
AN ER 1. DO NOT SCALE THIS DRAWING.
CE ET SYMBOL DESCRIPTION MAKE
M
:2 5
3. 3. 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
5 E :2 RECESSED PENDENT SPRINKLER, 69°, CHROME
M
ET
A NC FINISH,STANDARD RESPONSE.
BRISTOL UNLESS OTHERWISE NOTED.
ER
ST
S DI 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
UPRIGHT SPRINKLER, 79°,STANDARD RESPONSE. BRISTOL
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
F
ZONE CONTROL VALVE ASSEMBLY BRISTOL ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
A
AIR RELEASE VALVE BRISTOL
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED).
DIESEL
1.NO ELECTRIC PUMP (DUTY) BRISTOL
J
1.NO DIESEL PUMP (STAND BY)
1.NO JOCKEY PUMP
FHD
Ø 150MM WET TYPE FIRE HYDRANT-Ø 65MM
OUTLET, 2 NO'S BRISTOL
CONSULTANT :
15000
15000
DI
ST
FIRE CONTRACTOR
AN
S
ER
ET
C
E:
M
30
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
20
C E:
.0
AN
0
T
DIS
M
PROJECT NAME
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
EXIT-3
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
installed as per approved Shop drawing. 09.08.2023 1:100
(TYP)
3000
Ø25
Ø25
Ø25
Ø25
Ø25
Ø25
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
S Approval Department.
14250
ER 5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
ET
M 10)
5 DRAWN BY : CHECKED BY :
26. 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and
CE: NFPA 101) KKI MRJ
Ø32
Ø32
Ø32
Ø32
Ø32
Ø32
TAN 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
18000
D
3000
Ø40 Ø65 Ø65 Ø80 Ø80 Ø80 FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
Ø25
Ø50
Ø25
Ø25
Ø50
Ø25
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(TYP)
2500
Ø50
Ø50
Ø25
Ø25
Ø25
Ø25
SHELTER
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
1500 PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ
(TYP)
EXIT-2
1150
1800
and NFPA 101).
Ø50
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
B standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379
COLLECTION AREA
HAND WASH ROOM DISH WASH ROOM 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
Ø50
code (including local power authority standards) and the relevant NFPA codes and standards.
1765
1765
WC 19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
WC under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
A safety code.
FHR 21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
1 2 3 EXIT -1 4 5 NFPA-110 especially sprinkler system.
BLOCK-13 STAFF DINNING HALL
22. Air condition equipment's is not allowed inside a protected staircase.
NUMBER OF BLOCKS: 01 SHELTER
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
Ø50 U.G HDPE PIPE
2650 5500 5200 10650 NFPA-101 requirement was missed during plan review.
1 2 KEY PLAN :
13500
Ø50 U.G HDPE PIPE
SHELTER
SHELTER
N
FHR
W N E
AIR LOCK A
FOR LADIES
1400 3500 3500 3500 1400
(Typ) (Typ) (Typ) (Typ) (Typ)
ASPHALT ROAD TO BUHASA
SHELTER
3705
C
BU-800 HIGH
PRESSURE WI
STORE
(Typ)
3500
DISTANCE: 30 METERS
Ø25
Ø25
Ø25
Ø25
CASH COUNTER
MOBILE COUNTER GENERAL NOTES :
S
ER
ET
1. DO NOT SCALE THIS DRAWING.
SUPER MARKET HALL
2M
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
:2
6250
UNLESS OTHERWISE NOTED.
CE
SHELF SHELF SHELF
AN
OFFICE 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
ST
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
DI
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
(Typ)
3500
Ø32
Ø25
Ø25
Ø25
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
Ø25
Ø25
Ø50 Ø50 Ø65 Ø65 Ø65
12200
16000
FROM BLOCK-28
B
9165
Ø32
Ø40
Ø40
Ø25
SALOON STAFFS KITCHEN
SHELTER
3500
(Typ)
Ø32
Ø32
Ø25
Ø25
03 FOR APPROVAL 07.08.2023 KKI MRJ
CHILLER
5950
IS
TA
01 FOR APPROVAL 24.07.2023 KKI MRJ
N
SHELF SHELF SHELF SHELF
C
00 FOR APPROVAL 28.03.2023 KKI MRJ
E:
SHELTER
29
STORE REV. NO. DESCRIPTION DATE DRAWN CHKD
(Typ)
ET
1185
DISTANCE: 24 METERS CLIENT:
ER
Ø25
Ø25
S
ROBT STONE (ME)LLC
Ø25
COLD&FOOD ITEMS CLOTHES CLOTHES WALL SHELF WALL SHELF Ø25 P.O. Box. 39588
2000
Abu Dhabi, U.A.E
A
STORE
2830
16150 5450
1066 1140 LEGENDS
2000
21600
1424
1415
SYMBOL DESCRIPTION MAKE CONSULTANT :
TOILET TOILET TOILET TOILET
BLOCK-19 SUPER MARKET
3 2 1
RECESSED PENDENT SPRINKLER, 69°, CHROME
BRISTOL
Ø25
NUMBER OF BLOCKS: 01 FINISH,STANDARD RESPONSE.
B
6022 2280 UPRIGHT SPRINKLER, 79°,STANDARD RESPONSE. BRISTOL
FHR
ZONE CONTROL VALVE ASSEMBLY BRISTOL
SHELTER
ALARM CHECK VALVE BRISTOL
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
FIRE FIGHTING PUMP SET HORIZONTAL END P.O. Box: 91962, Mussafah 14, Abu Dhabi
Ø50 U.G HDPE PIPE
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED). T: +971 25535167, F: +971 25535159
DIESEL
1.NO ELECTRIC PUMP (DUTY) BRISTOL
1 2 E-mail: speedfse@eim.ae, www.speedsafetyuae.com
J
1.NO DIESEL PUMP (STAND BY)
20000 1.NO JOCKEY PUMP
· NEARBY FIRE HOSE REEL IS PLACED WITH IN 30 METERS OF COVERAGE AREA PROJECT NAME
· FOR LOCATION REFER: SFS/RS/BHS/FP/SP. Ø 150MM X 4 WAY BREECHING INLET-FLANGED INLET BRISTOL
15795 3905
FIRE HOSE REEL - SINGLE CABINET, FULL M.S RED
TEMPORARY CAMP ACCOMMODATION
A FHR POWDER COATED, (SURFACE MOUNTED) @ BUHASA
LOUNGE-1 LOUNGE-2 FHR * 1" X 30 METER HOSE REEL DRUM WITH BRISTOL
3000 NOZZLE .
* 1 " PRESSURE REDUCING VALVE ZONE :
SHELTER MADINAT ZAYED
2 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK
A B
1900
FIREX/
SECTOR NO : PLOT NO :
4 KG DCP EXTINGUISHER LPCB/BSI KITEMARK FIRE GUARD
HABSHAN T1019
2
LOCKER / STORE TOILET
10 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK PROJECT DESCRIPTION :
DIS ROOM
6400
TAN
CE: 3
0 ME TOILET 50 LITRE FOAM TROLLEY FIRE EXTINGUISHER NAFFCO
LABOUR CAMP @ BUHASA
TER
S FHD
Ø 150MM WET TYPE FIRE HYDRANT-Ø 65MM
OUTLET, 2 NO'S BRISTOL
DRAWING TITLE :
DIS
TA
B ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
N
12000
RECREATION AREA
CE
14500
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
:3
drawings.
SFS/RS/BUH/FP/09 04
0M
2. Any architectural changes like addition, deletion, modification during construction or in future
ET
shall be submitted to ADCD for both architectural and shop approvals.
ER
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
S
installed as per approved Shop drawing. 09.08.2023 1:75
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
10)
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
KKI MRJ
7800
NFPA 101)
REFRESHMENT
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
TOILET by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
1
BLOCK-25 ADNOC STAFF RECREATION 18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NUMBER OF BLOCKS: 01 NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
A B
1
12000
2 A B 3400
W
N
S
E
2400
1
SLOPE 8% 1 SUB ELECTRICAL
SUB ELECTRICAL ASPHALT ROAD TO BUHASA
A ROOM ROOM
STORE
(DRY AREA) BU-800 HIGH
WASHING WASHING PRESSURE WI
2400
DRYER MACHINE
2900
MACHINE MACHINE
LAUNDRY
(WET AREA)
3600
LEGENDS GENERAL NOTES :
1. DO NOT SCALE THIS DRAWING.
SYMBOL DESCRIPTION MAKE
2 RECESSED PENDENT SPRINKLER, 69°, CHROME
BRISTOL
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
UNLESS OTHERWISE NOTED.
IRONING
TABLE
B
2 FINISH,STANDARD RESPONSE.
NUMBER OF BLOCKS: 01
FIRE FIGHTING PUMP SET HORIZONTAL END
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED).
DIESEL
1.NO ELECTRIC PUMP (DUTY) BRISTOL
J
1.NO DIESEL PUMP (STAND BY)
1 10000 2 1.NO JOCKEY PUMP
04 FOR APPROVAL 09.08.2023 KKI MRJ
Ø 150MM X 4 WAY BREECHING INLET-FLANGED INLET BRISTOL
03 FOR APPROVAL 07.08.2023 KKI MRJ
3450 1200 5350
FIRE HOSE REEL - SINGLE CABINET, FULL M.S RED
02 FOR APPROVAL 28.07.2023 KKI MRJ
POWDER COATED, (SURFACE MOUNTED)
CHEMICAL STORAGE DETAILS A FHR * 1" X 30 METER HOSE REEL DRUM WITH BRISTOL 01 FOR APPROVAL 24.07.2023 KKI MRJ
NOZZLE .
1. DISH WASHING LIQUID 18225 * 1 " PRESSURE REDUCING VALVE 00 FOR APPROVAL 28.03.2023 KKI MRJ
REV. NO. DESCRIPTION DATE DRAWN CHKD
2. ALL PURPOSE CLEANER 1 2 3 4 5 6 2 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK
2550 3550 1450 5050 5625 CLIENT:
3. FLOOR CLEANER ETC.. FIREX/
Ø50 U.G HDPE PIPE 4 KG DCP EXTINGUISHER LPCB/BSI KITEMARK FIRE GUARD
SHELTER RS ROBT STONE (ME)LLC
FHR ETE 10 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK
A 8M P.O. Box. 39588
:2 Abu Dhabi, U.A.E
CHEMICAL BAKERY CHEFROOM
875
DAILYSTORAGE DRY STORE CE
AN
1138
1388
STORE ST
1500
3000 1160 D I
2543
2000
1675 1165
8000
FHD
Ø 150MM WET TYPE FIRE HYDRANT-Ø 65MM
OUTLET, 2 NO'S BRISTOL
1125 Ø25 Ø32 Ø25 CONSULTANT :
Ø25
Ø25
3000 1000
Ø25
B 850
DISH WASH B
ABLUTION TOILET
AREA
Ø40
1425
1750
CONTAINED)
2
EXIT-2
Ø25 Ø32 Ø25 Ø25
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
C P.O. Box: 91962, Mussafah 14, Abu Dhabi
1450
Ø65
Ø80 Ø80 Ø80 Ø50 @ BUHASA
17075
TO BLOCK-27 STAFF D FHR
Ø100
MADINAT ZAYED
Ø40
925 ROOM 925 · NEARBY FIRE HOSE REEL IS PLACED WITH IN 30 METERS OF COVERAGE AREA
1500
3500
Ø65
Ø25
HABSHAN T1019
Packing Tables
TO SPRINKLERS IN
Ø25
Ø100 ZCV
Ø32 Ø50 Ø50 Ø32
Ø25 ROOM
3000
Ø25
Ø25
A B LABOUR CAMP @ BUHASA
3000
Ø40
CHILLER 2900
DRAWING TITLE :
Ø25
Ø25
Ø25
(INSULATED COLD
E
FISH PREPARATION
CONTAINED)
1
Ø110 UG HDPE PIPE FOR
ROOM
1375
Ø32
3000
Ø25
Ø25 Ø25 ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
2900
1025
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
RECIVING AREA PRE1700
WASH GARBAGE SFS/RS/BUH/FP/10 04
ELECTRICKITCHEN TOILET 3000 ROOM
2. Any architectural changes like addition, deletion, modification during construction or in future
1175 AREA 1283 shall be submitted to ADCD for both architectural and shop approvals.
Ø25 Ø25 3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
1418
1:75
860
09.08.2023
825
10)
NUMBER OF BLOCKS: 01 SHELTER DRAWN BY : CHECKED BY :
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and
NFPA 101) KKI MRJ
BLOCK-32 ELECTRICAL ROOM TYPE-3 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
NUMBER OF BLOCKS: 02 8. All portions of these building shall be fully protected by automatic sprinklers system according to
FOR CIVIL DEFENSE APPROVAL :
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
SHELTER in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
10000
1 2 N
W N E
360
BUND WALL
B-42/O-1/T-1 ASPHALT ROAD TO BUHASA
2860
1 2 364
1 2
1008
8500
BU-800 HIGH
PRESSURE WI
A
FLAMMABLE LIQUID
3222
10000
FINISH,STANDARD RESPONSE.
9706
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
UPRIGHT SPRINKLER, 79°,STANDARD RESPONSE. BRISTOL
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
F
1430 6191 1430 ZONE CONTROL VALVE ASSEMBLY BRISTOL ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
4500
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
8500
A
AIR RELEASE VALVE BRISTOL
ROLLING SHUTTER
B-42/O-1/T-2
2860
ALARM CHECK VALVE BRISTOL
RAMP
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED).
DIESEL
FLAMMABLE LIQUID
J
1.NO DIESEL PUMP (STAND BY)
1.NO JOCKEY PUMP
KKI MRJ
360
04 FOR APPROVAL 09.08.2023
Ø 150MM X 4 WAY BREECHING INLET-FLANGED INLET BRISTOL
756
756
FIRE HOSE REEL - SINGLE CABINET, FULL M.S RED
02 FOR APPROVAL 28.07.2023 KKI MRJ
POWDER COATED, (SURFACE MOUNTED)
B 4500 1261
FHR * 1" X 30 METER HOSE REEL DRUM WITH
NOZZLE .
BRISTOL 01 FOR APPROVAL 24.07.2023 KKI MRJ
* 1 " PRESSURE REDUCING VALVE 00 FOR APPROVAL 28.03.2023 KKI MRJ
BLOCK-33 AIR BLOWER & PUMP ROOM
BLOCK-34 BOOSTER PUMP ROOM BLOCK-36 REV. NO. DESCRIPTION DATE DRAWN CHKD
2 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK
NUMBER OF BLOCKS: 01 NUMBER OF BLOCKS: 01 DIESEL TANK WITH SHED-2 CLIENT:
FIREX/
4 KG DCP EXTINGUISHER LPCB/BSI KITEMARK FIRE GUARD
FHD
Ø 150MM WET TYPE FIRE HYDRANT-Ø 65MM
OUTLET, 2 NO'S BRISTOL
CONSULTANT :
1 2
12000 18225
A
1 2 3 4 5 6
2550 3550 1450 5050 5625
SHELTER
A
CHEMICAL BAKERY CHEFROOM DAILYSTORAGE DRY STORE FIRE CONTRACTOR
STORE
2543
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
1500.0000
P.O. Box: 91962, Mussafah 14, Abu Dhabi
B T: +971 25535167, F: +971 25535159
DISH WASH E-mail: speedfse@eim.ae, www.speedsafetyuae.com
AREA VEGETABLE&SALAD FREEZER
PREPARATIONROOM
9000
4207
TEMPORARY CAMP ACCOMMODATION
@ BUHASA
FREEZER ZONE :
C
1875 3500 3500 3500 3500 2000
MADINAT ZAYED
Ø40 Ø40 Ø32 Ø25 Ø25
SECTOR NO : PLOT NO :
HABSHAN T1019
17075
D
POTSTORE CHICKENPREPARATION
Ø40
B TAPPING FROM
LABOUR CAMP @ BUHASA
PackingTables
BELOW CEILING LEVEL
BLOCK-35 MAJLIS MEATPREPARATION
NUMBER OF BLOCKS: 01 ROOM DRAWING TITLE :
CHILLER
E FIRE PROTECTION SYSTEM LAYOUT
FISH PREPARATION
ROOM
FOR BLOCK- 28,31, 32, 33,34 & 35
2920
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future
SFS/RS/BUH/FP/11 04
RECIVING AREA PRE WASH GARBAGE
ELECTRICKITCHEN TOILET ROOM shall be submitted to ADCD for both architectural and shop approvals.
AREA
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
1418
LOCK
AIR
SHELTER 5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA
A NUMBER OF BLOCKS: 01 10)
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
1420
2860
365 11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
FLAMMABLE LIQUID
3 PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
1255 STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
1385
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
753
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
B STAMP: STAMP:
NFPA-14 SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
753
753
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
1255 NFPA-20 STAMP: safety code and NFPA 101 and 5000).
BLOCK-36 19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72
PETROL TANK WITH SHED-1 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
W N E
A
DIESEL PUMP 6 BAR MANUAL KKI MRJ
01 FOR APPROVAL 24.07.2023
DIESEL TANK
LEVEL INDICATOR
1
REV. NO. DESCRIPTION DATE DRAWN CHKD
CLIENT:
DIESEL OUT
DIESEL IN
Ø 180mm UNDER GROUND HDPE PIPE
monitoring or secured in open position by a padlock or riveted strap unless otherwise specified and approved by the Civil
DIESEL PUMP
2. DIESEL PUMP SUCTION LINE OS & Y GATE VALVE Ø 200MM 1 NO.
TO PIPING NETWORK
6500
Ø 100 PRV
not be subject to excessive temperature, vibration, mechanical injury, or flooding with water and Current-carrying parts
FIRE PUMP ROOM Ø 150 NRV
Ø 150 OS&Y VALVE
Ø 65 GV 5. DIESEL PUMP DISCHARGE LINE OS & Y GATE VALVE Ø 150MM 1 NO.
shall not be less than 12 in. (305 mm) above the floor level. As per NPFA 20
6. ELECTRIC PUMP DISCHARGE LINE OS & Y GATE VALVE Ø 150MM 1 NO. 4- the diesel engine exhaust system shall be install according the NFPA 20, in terms of muffler , exhaust pipe ; type of pipes ,
JOCKEY PUMP Ø 200 GV size , insulation , dimensions , clearance , flipper
7. JOCKEY PUMP DISCHARGE LINE OS & Y GATE VALVE Ø 65MM 1 NO. , and installation . As per NPFA 20
FIRE CONTRACTOR
ELECTRICAL PUMP
5- All Foundation dimensions for all fire pumps on the pump room shall be provided according to NFPA 20 requirements.
8. CONCENTRIC REDUCER Ø 150 X Ø 100 4 NO. 6- Fire contractor shall be provide the operation chart (operation logic table) for the fire pump set in terms of pump capacity,
working pressure and cut-in & cut-off pressure for each pump. SPEED FIRE & SAFETY EQUIPMENT L.L.C.
9. TEST LINE GATE VALVE Ø 150MM 2 NO. 7- Fire contractor shall be provide the approved riser diagram layout at the fire pump room.
P.O. Box: 91962, Mussafah 14, Abu Dhabi
8- Fuel tank for the diesel fire pump shall be install according the NFPA 20, in terms of labeling, capacity, connection,
10. FLOW METER Ø 150MM 1 NO. Masonry reservoir, etc. T: +971 25535167, F: +971 25535159
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
BREECHING INLET
1 9- The fire water tanks shall be provided with drain arrangement, overflow connection, access manhole, ladders, level
6" x 4 WAY FIRE
2" PSL 11. PRESSURE RELIEF VALVE Ø 100MM 1 NO. indicators, low level switch, etc.
1 1 10- Flow meter arrangement on the test and drain line shall be according the manufacture requirement and NFPA 20
2" PSL 2" PSL
12. MAIN DELIVERY LINE ISOLATION VALVE Ø 150MM 1 NO. PROJECT NAME
11- The pressure sensing line connected from the fire pump to control panels shall be install accordance to according the
EP JP DP Ø 150mm DELIVERY LINE NFPA 20 in term of material, dimensions, check valves, pressure transducer, etc.
12- Fire pump controllers shall be listed and approved by international testing laboratories, certified by international
TEMPORARY CAMP ACCOMMODATION
@ BUHASA
2
conformity certification bodies and listed by Civil Defence
13- Elbows and tees with a centerline plane parallel to a horizontal split-case pump shaft shall only be permitted in the
suction line where the distance between the flanges of the pump suction intake and the elbow and tee is greater than 10
ZONE :
Ø 150 NRV
times the suction pipe diameter.
14- The vertical turbine pumps distance between the bottom of the strainer and the bottom of the water tank should be
MADINAT ZAYED
PROPOSED FIRE PUMP: one-half of the pump bowl diameter but not less than 12 in. (305 mm).
Ø 180mm UNDERGROUND HDPE PIPE LINE HORIZONTAL END SUCTION FIRE PUMP SET: 15-The components and dimensions of all piping and valves size inside this fire pump room shall be according to NFPA 20 SECTOR NO : PLOT NO :
requirements.
DIESEL ENGINE - 1000 GPM @ 10 BAR 16-Distance between all firefighting device and other components on the building shall according to UAE fire and lift safety
HABSHAN T1019
code and relevant NFPA standards.
ELECTRICAL PUMP-1000 GPM @ 10 BAR 17- All details of hungers, supports, pipes and fitting on all firefighting system components and fire pump room shall be
PROJECT DESCRIPTION :
JOCKEY PUMP - 10 GPM @ 10 BAR installed and provided on this building according to UAE fire life safety code other relevant NFPA standards.
LABOUR CAMP @ BUHASA
DRAWING TITLE :
IN TE 09
E R
VALVE
Ø 12.5MM
12 05 NR
V
08 TE (and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
NRV
M GA E OS Ø 15
TE 0M Ø 15 &Y V Ø 20 &Y 0M
GA E OS VAL
M E
&Y L V
OS VA Ø1
50
MM
Ø 15 0M
M
DE
LIV
ER
0M
M
SU
CT
IO
VA GA
LV TE
E
MT
ES
TL
IN
E
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
50M LIN NR YL NL this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
Ø 1 ERY V IN
E
NE
IV
L EY
DE CK 14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
Ø 15
JO
0M
M
DE
L IV 03
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
ER
Ø 12.5MM
OS & Y GATE
Y LIN 15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
NRV
E
VALVE
(FR Ø
DIE OM 150 TE standards.
SE V GA E
PA L PU
NE MP
BR MM
EA LIN
CH
IN E 07 Ø 50
MM
NR Ø 15
0M
M
DE
&Y LV
OS VA
E
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
G IN LIV
L LE ER
YL ST
LIN
T) IN
E 08 M
TE code (including local power authority standards) and the relevant NFPA codes and standards.
JO
PA CKEY M
(FR Ø
OM 150
08 PU
MP Ø 15
0M
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
.5M BR MM RIC
NE 12
Ø NRV EA LIN CT and tested in accordance with (UAE fire and life safety code and other relevant international standards).
L CH
IN E
G IN ELE E
LIN
OS & Y GATE
EL LE ST 18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
EC T) TE
STAMP:
VALVE
M
TR
PROPOSED FIRE PUMP: PA IC P 06 V 150M
NFPA-20
Ø 12.5MM
NE UM 2.5 Ø 15
0M
L P Ø 1 NRV
HORIZONTAL END SUCTION FIRE PUMP SET: 19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
DIESEL ENGINE - 1000 GPM @ 10 BAR NFPA-72
BR 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
ELECTRICAL PUMP-1000 GPM @ 10 BAR EA
INL CHIN safety code.
JOCKEY PUMP - 10 GPM @ 10 BAR ET G
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
ISOMETRIC VIEW 23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
SCALE - NTS
NFPA-101 requirement was missed during plan review.
KEY PLAN :
LEGENDS
SYMBOL DESCRIPTION MAKE
RECESSED PENDENT SPRINKLER, 69°, CHROME
BRISTOL
FINISH,STANDARD RESPONSE.
F
ZONE CONTROL VALVE ASSEMBLY BRISTOL
A
AIR RELEASE VALVE BRISTOL
ELECTRIC
SUCTION 1000 GPM @ 10 BAR (UL LISTED).
DIESEL
1.NO ELECTRIC PUMP (DUTY) BRISTOL
GENERAL NOTES :
J
1.NO DIESEL PUMP (STAND BY)
1.NO JOCKEY PUMP
1. DO NOT SCALE THIS DRAWING.
Ø 150MM X 4 WAY BREECHING INLET-FLANGED INLET BRISTOL 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
UNLESS OTHERWISE NOTED.
FIRE HOSE REEL - SINGLE CABINET, FULL M.S RED
POWDER COATED, (SURFACE MOUNTED) 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
FHR * 1" X 30 METER HOSE REEL DRUM WITH BRISTOL RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
NOZZLE .
* 1 " PRESSURE REDUCING VALVE MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
2 KG CO2 EXTINGUISHER LPCB/BSI KITEMARK CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
FIREX/
4 KG DCP EXTINGUISHER LPCB/BSI KITEMARK FIRE GUARD
NEPO ESOLC NEPO ESOLC NEPO ESOLC CLOSE NEPO ESOLC NEPO ESOLC NEPO ESOLC
OPEN
CLOSE OPEN
HDPE PIPE
DESCRIPTION DRAWN CHKD
Ø160 U.G
REV. NO. DATE
HDPE PIPE
Ø50 U.G HDPE PIPE TO SPRINKLER
FHC-62 CLIENT:
Ø50 U.G
CLOSE ESOLC ESOLC ESOLC CLOSE ESOLC NEPO ESOLC NEPO ESOLC
OPEN NEPO NEPO NEPO OPEN NEPO
F
Ø50 U.G Ø50 U.G Ø50 U.G
HDPE PIPE HDPE PIPE HDPE PIPE ROBT STONE (ME)LLC
HDPE PIPE
Ø160 U.G
TO SPRINKLER
SYSTEM IN BLOCK-13 FHC-56 FHC-63 TO DRAIN NEARBY
FHC-13 FHC-23 FHC-03 FHC-08 FHC-18 FHC-28 FHC-34 FHC-41 FHC-44 FHC-47 FHC-50 FHC-53
ALARM
P.O. Box. 39588
CHECK VALVE
Ø50 U.G HDPE PIPE Ø50 U.G Ø50 U.G Ø50 U.G
TO DRAIN NEARBY BLOCK- 18 20, 21 & 22
HDPE PIPE HDPE PIPE HDPE PIPE
FHC-42 CLOSE OPEN CLOSE OPEN CLOSE OPEN NEPO ESOLC NEPO ESOLC NEPO ESOLC NEPO ESOLC NEPO ESOLC NEPO ESOLC NEPO ESOLC
FOR NEPO ESOLC NEPO ESOLC
Ø50 U.G Ø50 U.G Ø50 U.G Ø25 Ø25 RING DETECTION
BLOCK- 19 CONSULTANT :
RING
HDPE PIPE
Ø25
HDPE PIPE HDPE PIPE
Ø80
Ø50 U.G HDPE PIPE Ø50 U.G HDPE PIPE PRESSURE Ø50 U.G PIPE Ø50 U.G PIPE
FHC-58 FHC-59 FHC-65 FHC-68 FHC-67 FHC-70 FHC-71 FHC-74
Ø80
Ø90 U.G HDPE PIPE
Ø180 UNDER GROUND MAIN RING HDPE PIPE Ø180 UNDER GROUND MAIN RING HDPE PIPE Ø180 UNDER GROUND MAIN RING HDPE PIPE Ø180 UNDER GROUND MAIN RING HDPE PIPE
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
P.O. Box: 91962, Mussafah 14, Abu Dhabi
T: +971 25535167, F: +971 25535159
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
FHD-11 FHD-01 FHD-02 FHD-03 FHD-04 FHD-05 FHD-06 FHD-07 FHD-08 FHD-09 FHD-10
FHD
FHD
FHD
FHD
FHD
FHD
FHD
FHD
FHD
FHD
FHD
TEMPORARY CAMP ACCOMMODATION
@ BUHASA
Ø180 UNDER GROUND MAIN RING HDPE PIPE Ø180 UNDER GROUND MAIN RING HDPE PIPE Ø180 UNDER GROUND MAIN RING HDPE PIPE Ø180 UNDER GROUND MAIN RING HDPE PIPE
ZONE :
MADINAT ZAYED
SECTOR NO : PLOT NO :
HABSHAN T1019
Ø150 flow meter
300 MM
(2* DIA MIN)
750 MM
(5* DIA MIN)
PROJECT DESCRIPTION :
Ø150 test line
M
Ø150 GV
Ø150 GV
Ø150 BREECHING INLET PIPE
Ø150 PRV Discharge line
LABOUR CAMP @ BUHASA
Ø100 PRV P P
Ø150 GV Ø200 GV
DIESEL PUMP D
CONTROL PANEL Ø150 NRV 30,000 X 2 US GALLONS WATER TANKS
PUMP ROOM
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future
SFS/RS/BUH/FP/13 04
PROPOSED FIRE PUMP:
shall be submitted to ADCD for both architectural and shop approvals.
HORIZONTAL END SUCTION FIRE PUMP SET:
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
DIESEL ENGINE - 1000 GPM @ 10 BAR
ELECTRICAL PUMP-1000 GPM @ 10 BAR installed as per approved Shop drawing. 09.08.2023 N.T.S
JOCKEY PUMP - 10 GPM @ 10 BAR 4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
10)
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
750
TOTAL NO. OF Q.B DETECTOR FOR LPG GAS TANK BODY 4 Nos. 1. DO NOT SCALE THIS DRAWING.
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
NO. OF RING 2
UNLESS OTHERWISE NOTED.
WATER SPRAY NOZZLE K-FACTOR K-18
Ø25 DETECTION PIPE 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
MINIMUM PRESSURE REQUIRED AT REMOTEST NOZZLE 3.5 BAR RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
FROM DELUGE VALVE MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
MINIMUM DISCHARGE THROUGH EACH NOZZLE @ 3.5 BAR (LPM) K-FACTOR 18 - 33.7 LPM ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
Ø80 GATE VALVE CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
500 1740 500 TOTAL WATER REQUIREMENT (AS PER CALCULATION) FOR
690
63.00 LPM
LPG GAS TANK
Ø80 PIPE FROM DELUGE VALVE
63.00 x 1.10 (10%) = 69.3 LITER
200
ADD 10% FOR HYDRAULIC IMBALANCE
69.3 LPM (18.30 GPM)
269.6 LPM
PROPOSED TOTAL FLOW
71.20 GPM
04 FOR APPROVAL 09.08.2023 KKI MRJ
03 FOR APPROVAL 07.08.2023 KKI MRJ
02 FOR APPROVAL 28.07.2023 KKI MRJ
WATER SPRAY NOZZLE SPRAY PATTERN 01 FOR APPROVAL 24.07.2023 KKI MRJ
00 FOR APPROVAL 28.03.2023 KKI MRJ
REV. NO. DESCRIPTION DATE DRAWN CHKD
Ø80 FIRE PROTECTION PIPE CLIENT:
Ø25
Ø80 DELUGE VALVE & ASSEMBLY
Ø80
PRESSURE
Ø25 FIRE DETECTION RING
GAUGE Ø65 RING BOTTOM
Ø65 RING RING FIRE CONTRACTOR
SOLENOID
Ø25 RING VALVE SPEED FIRE & SAFETY EQUIPMENT L.L.C.
1190 P.O. Box: 91962, Mussafah 14, Abu Dhabi
Ø80
T: +971 25535167, F: +971 25535159
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
MANUAL
RELEASE LEGENDS PROJECT NAME
DRAWING TITLE :
MEDIUM VELOCITY WATER SPRAY PIPING DETAILS 1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
FOR LPG TANK 2. Any architectural changes like addition, deletion, modification during construction or in future
SFS/RS/BUH/FP/14 04
REDUCER shall be submitted to ADCD for both architectural and shop approvals.
SUBMISSION DATE : SCALE :
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
installed as per approved Shop drawing. 09.08.2023 1:50
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Ø80 DELUGE VALVE Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
10)
SPRAY 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
SPRAY KKI MRJ
NOZZLE 120° NFPA 101)
NOZZLE 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
MEDIUM VELOCITY SPRAY NOZZLE DETAILS in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
80Ø
N1LP N1LP N2HP N2HP N2HP N2HP N1LP N2HP N2HP N2HP
201 E
N1LP N1LP N1HP N1LP N1LP N1LP N1HP N1LP N1LP N1HP
Hood 02
GENERAL KITCHEN
FD 60
BFR BFR BFR BFR
10 10 10 10
5
BFR
10 ROBT STONE (ME)LLC
CHAPATTI ROOM P.O. Box. 39588
ASH AREA Abu Dhabi, U.A.E
WASHROOM POT
ADNOC KITCHEN
SEQUENCE OF OPERATION
PVC CURTAIN
6
N1HP N1LP N1LP N1HP N1LP
AL SHAHBA
PACKING ROOM ENG. SAFETY & SECURITY CO. L.L.C.
P.O. Box: 26146,
SHARJAH ,UAE
TEL : 06 5341777
P.O. Box: 231775,
DUBAI,UAE
TEL : 04 2677955
FAX : 06 5342666 FAX : 04 2677956
email : sessco@emirates.net.ae
www.sesscofire.com
GARBAGE ROOM
POT STORE
ACTUATION CARTRIDGE
MADINAT ZAYED T1019
HABSHAN
PIPING VOLUME CHART DESIGN FLOW CALCULATION DESIGN FLOW CALCULATION
PROPOSED WET CHEMICAL FIRE SUPPRESSION
SYSTEM IN LAYOUT & CALCULATIONS IN
GENERAL KITCHEN
CYLINDER CAPACITY
SESSCO/J19563/KHS-01/03
PARTY CONSULTANT MAIN CONTRACTOR FIRE CONTRACTOR APPROVED INSTALLER
MAXIMUM PIPING per CYLINDER SIZE
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ Engr.NAME: RAKESH
NFPA-20 STAMP:
NFPA-72
FIRE SUPPRESSION SYSTEM LAYOUT
SCALE 1:50MTRS NFPA-110
NFPA-101
SEQUENCE OF OPERATION ABU DHABI CIVIL DEFENSE GENERAL NOTES LEGEND
Hood 01
BU
CK FIR
E
EQ
EY
UIP
ME
NT E
ACTUATION CARTRIDGE
CYLINDER CAPACITY
FIR
E
EY
E
FIR
E
E YE FIR
E
E YE FIR
E
E YE
C K CK CK CK
BU U BU BU
NT NT NT NT
ME ME ME ME
EQ
UIP
B EQ
UIP
EQ
UIP
EQ
UIP
AL SHAHBA
ENG. SAFETY & SECURITY CO. L.L.C.
P.O. Box: 26146, P.O. Box: 231775,
SHARJAH ,UAE DUBAI,UAE
TEL : 06 5341777 TEL : 04 2677955
FAX : 06 5342666 FAX : 04 2677956
email : sessco@emirates.net.ae
www.sesscofire.com
NFPA-20 STAMP:
NFPA-72
NFPA-110
NFPA-101
ABU DHABI CIVIL DEFENSE GENERAL NOTES LEGEND
SEQUENCE OF OPERATION
BFR
201 E
05
BFR
10 ACTUATION CARTRIDGE
Hood 01
FRYER BRATT PAN COMBI OVEN PIPING VOLUME CHART
N1LP N1LP
N1HP N1HP
N1LP N1LP N1LP DESIGN FLOW CALCULATION
ROBT STONE (ME)LLC
P.O. Box. 39588
Abu Dhabi, U.A.E
PROPOSED
FIRE SUPPRESSION SYSTEM LAYOUT
SCALE 1:50MTRS
GENERAL NOTES
BUCKEYE FIRE EQUIPMENT
SYSTEM VOLUME CALCULATIONS for HOOD 01 P.O. Box 428, 110 Kings Road, Kings Mountain
North Carolina 28086
Tel. No. 704 739 7415 Fax No. 704 739 7418
www.buckeyef.com
Hood 01
AL SHAHBA
ENG. SAFETY & SECURITY CO. L.L.C.
P.O. Box: 26146, P.O. Box: 231775,
SHARJAH ,UAE DUBAI,UAE
TEL : 06 5341777 TEL : 04 2677955
FAX : 06 5342666 FAX : 04 2677956
email : sessco@emirates.net.ae
www.sesscofire.com
FIRE EY
E
FIR
E
EY
E TEMPORARY CAMP ACCOMMODATION
CK CK @ BUHASA
BU BU
T T
EN EN
PM PM
UI UI
EQ EQ
SESSCO/J19563/KHS-01/03
PARTY CONSULTANT MAIN CONTRACTOR FIRE CONTRACTOR APPROVED INSTALLER
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ Engr.NAME: RAKESH
NFPA-20 STAMP:
NFPA-72
SRM BOX
FIRE FIRE
E YE EYE
BUCK EQUIPMENT
BUCK EQUIPMENT
FRONT VIEW REAR VIEW LEFT SIDE VIEW RIGHT SIDE VIEW FRONT VIEW REAR VIEW LEFT SIDE VIEW RIGHT SIDE VIEW
RIGHT SIDE VIEW LEFT SIDE VIEW RIGHT SIDE VIEW LEFT SIDE VIEW
C
BU BACK VIEW BU BACK VIEW
E NT E NT
U IPM U IPM
EQ ER EQ ER
IST M IST M
N MSTE N MSTE
HE SY HE SY
ITCIRE ITCIRE
E KT F E KT F
EY AN EY AN
CK UR CK UR
BUSTA : 231
775
E BUSTA : 231
775
E
RE . Box I, UA 5
BA 795 6
P.O DU 267 795
RE . Box I, UA 5
BA 795 6
P.O DU 267 795
: 04 267 : 04 267
TEL : 04t.ae TEL : 04t.ae
FAX ne FAX ne
es. es.
46, rat m 46, rat m
: 261 E mi .co : 261 E mi .co
UA 7 @e ire UA 7 @e ire
. Box , 177 6 sco cof . Box , 177 6 sco cof
P.OARJAH534 266: ses ess P.OARJAH 534 266: ses ess
SHL : 06 534 ail ww
w.s SHL : 06 534 ail ww
w.s
TE : 06 em TE : 06 em
FAX FAX
ISOMETRIC ISOMETRIC
DETAILS of DETAILS of
BUCKEYE MAIN CYLINDER CABINET with SRM BUCKEYE SLAVE CYLINDER CABINET
ROBT STONE (ME)LLC
P.O. Box. 39588
Abu Dhabi, U.A.E
IN CASE OF
FIRE
PULL HANDLE HARD CYLINDER INSTALLATION DETAILS
TO ACTUATE
FIRE SUPPRESSION SYSTEM
FIRE
EYE
BUCK EQUIPMENT
RPS-M
NOTE.
2
2 4
4
AL SHAHBA
ENG. SAFETY & SECURITY CO. L.L.C.
P.O. Box: 26146, P.O. Box: 231775,
1 3
1
3 SHARJAH ,UAE DUBAI,UAE
TEL : 06 5341777 TEL : 04 2677955
SYSTEM RELEASING MODULE IN-SET POSITION DETAILS FAX : 06 5342666 FAX : 04 2677956
email : sessco@emirates.net.ae
www.sesscofire.com
S FIGURE A
R
M
SRM WIRING DETAILS
TEMPORARY CAMP ACCOMMODATION
FIRE
EYE
@ BUHASA
BUCK EQUIPMENT
MADINAT ZAYED
AUTHORIZED DEALER
SESSCO/J19563/KHS-03/03
PARTY CONSULTANT MAIN CONTRACTOR FIRE CONTRACTOR APPROVED INSTALLER
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ Engr.NAME: RAKESH
NFPA-20 STAMP:
NFPA-72
NFPA-110
NFPA-101
KEY PLAN :
4 5 6 7
ECOLOGY UNIT
ROOF FLOOR
W N E
400x350mm
SALAD ROOM 400x300mm EXHAUST AIR DUCT INTERFACED WITH
FIRE ALARM SYSTEM
HOOD-01
4000 X 1200 mm BU-800 HIGH
PRESSURE WI
300
300
PACKING ROOM
85% OF TOTAL EXTRACT
CHAPATTI ROOM
900x600mm
EXHAUST AIR DUCT
800x600mm 1.5mm CS Fire Rated
FLOURECENT LAMP
300
300
300
300
250 300 300 250 KITCHEN EXHAUST DUCT UNLESS OTHERWISE NOTED.
KED (1.5mm CARBON STEEL FIRE RATED DUCT)
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
KITCHEN MAKE UP AIR DUCT RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
KMAD (1.5mm CARBON STEEL FIRE RATED DUCT) ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
MEAT ROOM
KMAF FRESH AIR HANDLING UNIT
FD 60
ACCESS DOOR
HOOD-02 KEF RETURN AIR ECOLOGY UNIT WITH FAN
10000 X 2800 mm GROUND FLOOR
EXTRACT AIR : 8900 L/S
HOT KITCHEN
MOTORIZED SMOKE DAMPER
SHADED
MAKE UP AIR : 7565 L/S
85% OF TOTAL EXTRACT SECTION FOR EXTRACT DUCT
FD 60
MOTORIZED SMOKE FIRE DAMPER
04 FOR APPROVAL 09.08.2023 KKI MRJ
CHICKEN ROOM 03 FOR APPROVAL 07.08.2023 KKI MRJ
02 FOR APPROVAL 28.07.2023 KKI MRJ
WASHROOM POT POT STORE INTERFACED WITH 01 FOR APPROVAL 24.07.2023 KKI MRJ
300x300mm FIRE ALARM SYSTEM
PVC CURTAIN
FISH ROOM ROBT STONE (ME)LLC
1 HR FIRE P.O. Box. 39588
RATED DUCT Abu Dhabi, U.A.E
GARBAGE ROOM
CONSULTANT :
1500
FLOURECENT LAMP
ACCESS DOOR
FRESH
(OR) S/S BAFFLE TYPE AIR OUTLET
GREASE FILTER
IF SIZE NOT POSSIBLE, SMALL
ACCESS DOOR EVERY 3.7m
1200 OIL
COLLECTOR
CHEMICAL STORAGE
FD 60
FIRE CONTRACTOR
1500
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
AIR FLOW-7565 L/S
FRESH AIR FAN-2(KMAF) P.O. Box: 91962, Mussafah 14, Abu Dhabi
1200 T: +971 25535167, F: +971 25535159
MSD MSFDAIR FLOW-1275 L/S MSD MSFD
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
FRESH AIR FAN-1 (KMAF)
1200
SHELTER GROUND FLOOR
AIR FLOW-8900 L/S AIR FLOW-1500 L/S PROJECT NAME
ECOLOGY UNIT-2 (KEF) ECOLOGY UNIT-1(KEF)
2000
SECTION FOR MAKE UP & EXTRACT DUCT TEMPORARY CAMP ACCOMMODATION
@ BUHASA
BELL MOUTH WITH WIRE MESH
EXHAUST AIR LOUVER ZONE :
SEQUENCE OF OPERATION IN THE EVENT
1500 x 1500mm OF GENERAL FIRE:-
MADINAT ZAYED
13
MS PLATFORM INTAKE AIR LOUVER 5000 1. Fire alarm system is interfaced with gas panel
WITH SAND TRAP AND SECTOR NO : PLOT NO :
INTAKE AIR LOUVER WITH SAND 2. In the event of fire FACP will provide signal to gas
TRAP AND INSECT SCREEN
INSECT SCREEN
panel which enable to gas panel to shut down the HABSHAN T1019
1500 x 600mm
3000 x 2000mm gas valve serving.
KMAF-AIR FLOW-1275 L/S PROJECT DESCRIPTION :
KMAF-AIR FLOW-7565 L/S FRESH AIR FAN-1 (KMAF) 3.The kitchen hood fan shall be shut down in the
FRESH AIR FAN-2 event of general fire
5076 LABOUR CAMP @ BUHASA
SEQUENCE OF OPERATION IN THE EVENT OF
KITCHEN HOOD SYSTEM ACTIVATION (HOOD FIRE):-
BELL MOUTH WITH WIRE MESH DRAWING TITLE :
1. Kitchen hood system is connected to LPG panel
EXHAUST AIR LOUVER through FACP.
2600 x 1500mm 2. In the event of activation of kitchen hood system
KEF-AIR FLOW 8900 L/S
by a hood fire , the FACP will provide signal to gas VENTILATION SYSTEM LAYOUT
panel which enables to gas panel to shut down in
VENTILATION SYSTEM LAYOUT FOR ROBTSTONE KITCHEN AREA the gas valve serving. The kitchen hood panel is
FOR ROBTSTONE KITCHEN AREA
SCALE: 1:75 continuously monitored by FACP.. ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
NOTES: ظحالت: 3.The kitchen hood fans shall be shut down in the 1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
ا ع ا أا رر ظا رح احخ احعيلا محااا حعا يأ ار احمدع
event of hood fire.
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/VS-01 04
NOT A MAKE ANY MODIFICATION TO THE SITE CONTRARY TO WHAT WAS STATED IN THE PLAN
shall be submitted to ADCD for both architectural and shop approvals.
THE WORKS MUST BE ASSIGNED TO COMPANIES LICENSED AND APPROVED BY THE CIVIL DEFENSE ر د رج ظريج احراعاح عمششع ححصأراظ احعأمشع ياحعاظع ع عج اح ااا احع جر ROBSTONE -KITCHEN FANS 3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
ENSURE THAT THE EQUIPMENT AND MATERIALS ARE APPROVED BY THE CIVIL DEFENSE DEPARTMENT احظرر عج ااظعا احعا اظ ياحعيا عج لدح ا اأع اح ااا احع جر
CALCULATED PROPOSED installed as per approved Shop drawing. 09.08.2023 N.T.S
COMPLIANCE WITH WORKPLACES SAFETY AND PREVENTION REQUIREMENT احاعظ اح حعظدحداظ احلحاعع ياحيلارع ار رعارج احاعح QTY FIRE RATING 4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
FAN SERVING FLOW RATE FLOW RATE Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
NOTE: THE PROJECT CONSULTANT IS LEGALLY REQUESTED FOR EXECUTING THE OBOVEMENTIONED عحالتع: ردحد عج الظصاأر احعصأيا لاجيجا ظجار احع رأع احع ريأع L/S L/S Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
EXTRACT FAN-1 1 1,490 1,500 400°C @ 120 Min
10)
CODE NUMBER
BS EN 1366−1:FIRE RESISTANCE TEST, PART 1: DUCTS KEF 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
BS 476,PART 24, FIRE TESTS ON BUILDING MATERIALS AND STRUCTURES EXTRACT FAN-2 1 8,879.4 8,900 400°C @ 120 Min NFPA 101) KKI MRJ
CARBON STEEL 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
1.37 MM NO.16 MSG
DUCT SIZE KITCHEN MAKE-UP -1 1 1,266.8 1,275 No by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
NOTE: MAKE UP AIR EQUAL 85% OF EXHAUST AIR
KMAF 8. All portions of these building shall be fully protected by automatic sprinklers system according to
KITCHEN MAKE-UP -2 1 7,547.4 7,565 No (NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
KITCHEN DUCT ADCD LICENCE EXHAUST FAN ADCD LICENCE 22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
OVEN 6 BURNER FRYER FRYER HOTPLATE BRATT PAN BRATT PAN BRATT PAN
880 1190 1600 800 1180 1180 1180 CHAPATTI ROOM
201 E
N
W N E
BU-800 HIGH
PRESSURE WI
2500
GENERAL NOTES :
1. DO NOT SCALE THIS DRAWING.
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
UNLESS OTHERWISE NOTED.
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
BOILING PAN BOILING PAN BOILING PAN BOILING PAN BOILING PAN BOILING PAN BRATT PAN BRATT PAN ROBTSTONE CHAPATTI ROOM EQUIPMENT DETAILS CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
SCALE: N.T.S.
6900 660 2380
CONSULTANT :
FIRE CONTRACTOR
PROJECT NAME
DRAWING TITLE :
SHUT DOWN
SHUT DOWN
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
CONTROL PANEL standards.
(FACP) NFPA-10 SIGN: SIGN: CD CARD No: 101110379
FRESH AIR UNIT IFU IFU FRESH AIR UNIT 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP:
INPUT INITIALING
FIRE ALARM ACTIVATION: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
X X X and tested in accordance with (UAE fire and life safety code and other relevant international standards).
IFU GENERAL FIRE
SIGNAL
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
KITCHEN HOOD FIRE X X X
LPG GAS PANEL under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
LEGEND safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
FIRE ALARM INTERFACING DIAGRAM X IMMEDIATE ACTIVATION NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
W N E
B
C
F
A
AIR FLOW-2125 L/S 1500 x 900 mm
KITCHEN EXHAUST DUCT 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
KMAF-AIR FLOW- 1800 L/S
ECOLOGY UNIT (KEF) (1.5mm CARBON STEEL FIRE RATED DUCT)
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
FRESH AIR FAN (KMAF) KED MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
KITCHEN MAKE UP AIR DUCT ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
MSFD MSD CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
KMAD (1.5mm CARBON STEEL FIRE RATED DUCT)
1
ECOLOGY UNIT
2550
KEF
POT STORE
ACCESS DOOR 1 HR FIRE
CHEMICAL MOTORIZED SMOKE DAMPER
(OR)
500x400mm RATED DUCT ACCESS DOOR STORE 04 FOR APPROVAL 09.08.2023 KKI MRJ
IF SIZE NOT POSSIBLE, SMALL
ACCESS DOOR EVERY 3.7m
EXHAUST AIR DUCT (OR)
IF SIZE NOT POSSIBLE, SMALL EXAUST OUT MOTORIZED SMOKE FIRE DAMPER 03 FOR APPROVAL 07.08.2023 KKI MRJ
1.5mm CS Fire Rated Duct ACCESS DOOR EVERY 3.7m
KKI MRJ
02 FOR APPROVAL 28.07.2023
2
FLOURECENT LAMP
01 FOR APPROVAL 24.07.2023 KKI MRJ
FRESH
S/S BAFFLE TYPE AIR OUTLET
GREASE FILTER
00 FOR APPROVAL 28.03.2023 KKI MRJ
REV. NO. DESCRIPTION DATE DRAWN CHKD
CLIENT:
ELECTRIC KITCHEN
400x400mm
3550
300 250
300
3
EXTRACT AIR : 2125 L/S
SHELTER
1450
85% OF TOTAL EXTRACT
INTERFACED WITH
FIRE ALARM SYSTEM
ECOLOGY UNIT
FIRE CONTRACTOR
ROOF FLOOR
4
SHELTER
INTERFACED WITH
FIRE ALARM SYSTEM
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
P.O. Box: 91962, Mussafah 14, Abu Dhabi
T: +971 25535167, F: +971 25535159
TOILET E-mail: speedfse@eim.ae, www.speedsafetyuae.com
CHEF ROOM
18225
EXAUST OUT FRESH AIR PROJECT NAME
FLOURECENT LAMP
TEMPORARY CAMP ACCOMMODATION
@ BUHASA
5050
FRESH
S/S BAFFLE TYPE AIR OUTLET
GREASE FILTER
VENTILATION SYSTEM LAYOUT FOR ADNOC KITCHEN AREA SECTION FOR MAKE UP & EXTRACT DUCT
SCALE: 1:50 SEQUENCE OF OPERATION IN THE EVENT VENTILATION SYSTEM LAYOUT
OF GENERAL FIRE:-
FOR ADNOC KITCHEN
1. Fire alarm system is interfaced with gas panel ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
ظحالت: 2. In the event of fire FACP will provide signal to gas REVISION NO:
NOTES: 1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO :
panel which enable to gas panel to shut down the drawings.
NOT A MAKE ANY MODIFICATION TO THE SITE CONTRARY TO WHAT WAS STATED IN THE PLAN ا ع ا أا رر ظا رح احخ احعيلا محااا حعا يأ ار احمدع gas valve serving. 2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/VS-03 04
THE WORKS MUST BE ASSIGNED TO COMPANIES LICENSED AND APPROVED BY THE CIVIL DEFENSE ر د رج ظريج احراعاح عمششع ححصأراظ احعأمشع ياحعاظع ع عج اح ااا احع جر
ROBSTONE -KITCHEN FANS shall be submitted to ADCD for both architectural and shop approvals.
3.The kitchen hood fan shall be shut down in the SUBMISSION DATE : SCALE :
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
ENSURE THAT THE EQUIPMENT AND MATERIALS ARE APPROVED BY THE CIVIL DEFENSE DEPARTMENT احظرر عج ااظعا احعا اظ ياحعيا عج لدح ا اأع اح ااا احع جر CALCULATED PROPOSED event of general fire
QTY FIRE RATING installed as per approved Shop drawing. 09.08.2023 N.T.S
COMPLIANCE WITH WORKPLACES SAFETY AND PREVENTION REQUIREMENT احاعظ اح حعظدحداظ احلحاعع ياحيلارع ار رعارج احاعح FAN SERVING FLOW RATE FLOW RATE
SEQUENCE OF OPERATION IN THE EVENT OF 4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
NOTE: THE PROJECT CONSULTANT IS LEGALLY REQUESTED FOR EXECUTING THE OBOVEMENTIONED عحالتع: ردحد عج الظصاأر احعصأيا لاجيجا ظجار احع رأع احع ريأع L/S L/S KITCHEN HOOD SYSTEM ACTIVATION (HOOD FIRE):-
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
EXTRACT FAN-1 1 2,085.6 2,125 400°C @ 120 Min B3N-2022-000555-CD-SHD-02 A1
KEF 1. Kitchen hood system is connected to LPG panel 5.
10)
All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA
CODE NUMBER
BS EN 1366−1:FIRE RESISTANCE TEST, PART 1: DUCTS through FACP. DRAWN BY : CHECKED BY :
BS 476,PART 24, FIRE TESTS ON BUILDING MATERIALS AND STRUCTURES 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and
KMAF KITCHEN MAKE-UP-01 1 1,772.8 1,800 No 2. In the event of activation of kitchen hood system
NFPA 101) KKI MRJ
CARBON STEEL
1.37 MM NO.16 MSG
by a hood fire , the FACP will provide signal to gas
DUCT SIZE
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
panel which enables to gas panel to shut down in by voice announcement system according to (NFPA 72).
NOTE: MAKE UP AIR EQUAL 85% OF EXHAUST AIR
the gas valve serving. The kitchen hood panel is FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
continuously monitored by FACP.. (NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
3.The kitchen hood fans shall be shut down in the
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
event of hood fire. in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
KITCHEN DUCT ADCD LICENCE EXHAUST FAN ADCD LICENCE 23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
W N E
GENERAL NOTES :
900
1. DO NOT SCALE THIS DRAWING.
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
HVAC LEGEND: UNLESS OTHERWISE NOTED.
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
KITCHEN EXHAUST DUCT RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
KED (1.5mm CARBON STEEL FIRE RATED DUCT) MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
KITCHEN MAKE UP AIR DUCT CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
4- BURNER HOT PLATE FRYER BRATT COMBI OVEN
127
KMAD (1.5mm CARBON STEEL FIRE RATED DUCT)
PAN KMAF FRESH AIR HANDLING UNIT
CONSULTANT :
NOTES: ظحالت:
LABOUR CAMP @ BUHASA
NOT A MAKE ANY MODIFICATION TO THE SITE CONTRARY TO WHAT WAS STATED IN THE PLAN ا ع ا أا رر ظا رح احخ احعيلا محااا حعا يأ ار احمدع
THE WORKS MUST BE ASSIGNED TO COMPANIES LICENSED AND APPROVED BY THE CIVIL DEFENSE ر د رج ظريج احراعاح عمششع ححصأراظ احعأمشع ياحعاظع ع عج اح ااا احع جر
ENSURE THAT THE EQUIPMENT AND MATERIALS ARE APPROVED BY THE CIVIL DEFENSE DEPARTMENT احظرر عج ااظعا احعا اظ ياحعيا عج لدح ا اأع اح ااا احع جر DRAWING TITLE :
COMPLIANCE WITH WORKPLACES SAFETY AND PREVENTION REQUIREMENT احاعظ اح حعظدحداظ احلحاعع ياحيلارع ار رعارج احاعح
NOTE: THE PROJECT CONSULTANT IS LEGALLY REQUESTED FOR EXECUTING THE OBOVEMENTIONED عحالتع: ردحد عج الظصاأر احعصأيا لاجيجا ظجار احع رأع احع ريأع
VENTILATION SYSTEM DETAILS
BS EN 1366−1:FIRE RESISTANCE TEST, PART 1: DUCTS FOR ADNOC KITCHEN
CODE NUMBER
BS 476,PART 24, FIRE TESTS ON BUILDING MATERIALS AND STRUCTURES FLOW CALCULATION FOR ADNOC KITCHEN ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
CARBON STEEL
DUCT SIZE
1.37 MM NO.16 MSG SCALE: N.T.S. 1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
NOTE: MAKE UP AIR EQUAL 85% OF EXHAUST AIR
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/VS-04 04
shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
installed as per approved Shop drawing. 09.08.2023 N.T.S
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
CAUSE AND EFFECT MATRIX 10)
DRAWN BY : CHECKED BY :
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and
NFPA 101) KKI MRJ
OUT PUT ACTIVITIES 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
EVACUATION
SHUT DOWN
8. All portions of these building shall be fully protected by automatic sprinklers system according to
HOOD FAN
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
INPUT INITIALING
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
FIRE ALARM ACTIVATION:
GENERAL FIRE X X X IFU STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
SIGNAL
W N E
GATE
6000 15000 30000 40000
3000
4981
X
20000
6000 6000
BU-800 HIGH
X
PP01
R7000 15000 PRESSURE WI
PP04 B
28000 4000 6000 4000 10000 28000 10000 4000 10000 28000 R7000 15000
22 21 20
PP04C
PP04 D
W/P W/P 10000
PP05
PP06
W/P W/P W/P W/P W/P W/P
PP04 A
PP02
10600
W/P
W/P
W/P
W/P
4 4 4
W/P
W/P
8500 8500
W/P
W/P
8500
X
5 14000
5 5 14000
30 2400
W/P
30
W/P
33
W/P
W/P
GENERAL NOTES :
2400
W/P W/P W/P
2400
X
2400
X
6000 6000
8500 4 4 8500 4 8500 1. DO NOT SCALE THIS DRAWING.
W/P
W/P
34
X
W/P
W/P
W/P
W/P
W/P
X
HDD AREA
6000 W/P
W/P
6000
5 14000 W/P
W/P
6000
X
8500 4 4 8500 4 8500
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
X
FIRE WATER TANK CAPACITY WITH
6000 WASHING
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
W/P W/P W/P
W/P
2400
X
W/P W/P W/P
30
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
2400
60,000 GAL.
10000
X
4 4 4 ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
30,000 GAL.
30,000 GAL.
8500 8500 8500
X
W/P
W/P
10000
5 14000
5 W/P
W/P
5 14000
W/P
W/P
X
W/P W/P W/P
W/P
W/P
PATH WAY
PATH WAY
X
4 4 4 17
PATH WAY
PATH WAY
6000 8500 6000 8500 6500
8500
X
3000
109428
W/P W/P W/P
6000 28000
6000
WATER TANK
WATER TANK
WATER TANK
WATER TANK
W/P W/P W/P
X
POTABLE
POTABLE
POTABLE
POTABLE
302400 30
5 14000 5 W/P
5 14000
S W/P
8 NOS.15000 GAL.
10400
4 4 4
X
8500 8500 8500 2000
X
W/P W/P W/P
WASHING
WATER TANK
WATER TANK
WATER TANK
WATER TANK
POTABLE
POTABLE
POTABLE
POTABLE
W/P W/P W/P
10400
X
W/P W/P W/P
10000
10000
4 4 4
X
8500 8500 8500
6000
6000
4000
04 FOR APPROVAL 09.08.2023 KKI MRJ
HYDRO TESTING AREA
X
10000
5 5 5
W/P W/P W/P
14000 73.0x70.0M
2400
6626
MRJ
W/P 14000
W/P W/P
6000 W/P
30
W/P
6000 W/P
6000
03 FOR APPROVAL 07.08.2023 KKI
X
W/P S 2400
W/P W/P
10001
DIESEL GENERATOR
8500 4 4 8500 4 8500
6000
02 FOR APPROVAL 28.07.2023 KKI MRJ
X
5400
6000 6000
W/P
W/P
01 FOR APPROVAL 24.07.2023 KKI MRJ
X
W/P W/P W/P
2400
6000 W/P
6000 W/P W/P
6000
W/P W/P
30 2400
W/P
X
5 14000 5 4A 5 14000 21300
X
R7000
PSU
PSU
PSU
4B R7000
CABIN TYPE OF
QUANTITY AREA OF
TOTAL AREA TYPE OF TYPE OF FIRE REV. NO. DESCRIPTION DATE DRAWN CHKD
W/P
W/P
9991 10000
W/P W/P SLOPE 8% SLOPE 8%
W/P
SLOPE 8% SLOPE 8% W/P W/P
NAME OF UNIT USAGE OF UNIT / BUILDING (m²)
X
R7000
W/P W/P W/P
4000 10000 W/P
28000 W/P
R7000 R15000 No. UNIT (m²) PROTECTION ALARM SYSTEM
2500 BLOCK GROUND FLOOR CLIENT:
2500 2500
6
X
6000 6000 5061
6
W/P
W/P
1 SENIOR STAFF ACCOMMODATION BLOCK - 1 ACCOMMODATION 4 86.40 m² 345.60 m² FHR + EXTINGUISHER
X X X
2500
W/P
8000 R7000
W/P
GATE
ROBT STONE (ME)LLC
W/P W/P
6390 39900 3 STAFF ACCOMMODATION TYPE - 2 BLOCK - 3 ACCOMMODATION 1 86.40 m² 86.40 m² FHR + EXTINGUISHER
LPG STORAGE
W/P W/P
W/P
10000 10000
TANK 16 4 WORKERS ACCOMMODATION TYPE - 1 BLOCK - 4 ACCOMMODATION 26 238.00 m² 6188.00 m² FHR + EXTINGUISHER
W/P
5400
R7000
R7000
4A WORKERS ACCOMMODATION TYPE - 2 BLOCK - 4A ACCOMMODATION 1 119.00 m² 119.00 m² FHR + EXTINGUISHER
P.O. Box. 39588
R10000
8463 21300 23000 X X X X X X X X X X X
2500
X X X X X X X X 25000
2400
20000 4B WORKERS ACCOMMODATION TYPE - 3 BLOCK - 4B ACCOMMODATION 1 119.00 m² 119.00 m² FHR + EXTINGUISHER Abu Dhabi, U.A.E
11322
15 14 23770 18000 2500 6
X
W/P
W/P
20000 14000 30 EXTINGUISHER
X
2400
X
R15000
10674 12000
R15000
6000
6 GUARD ROOM BLOCK - 6 GUARD ROOM 4 6.25m² 25.00 m² EXTINGUISHER
X
TRUCK PARKING 6000
X
X
3600
PARKING 6000 7 CLINIC BLOCK - 7 CLINIC 1 86.40 m² 86.40 m² EXTINGUISHER
Gatch Road
FACP
X
7200
X
X
X
2900
14400 31 VOLLEY BALL
6000
TENNIS COURT
COURT
FOOT BALL
COURT
18
7A MEDICAL WASTE ROOM BLOCK - 7A WASTE ROOM 1 4.00 m² 4.00 m² EXTINGUISHER
FIRE DETECTION SYSTEM CONSULTANT :
7 12000 30000
X
W/P
W/P
3400
X X X X X X X X X
7230 8 108.00 m²
X
DIESEL CAMP OFFICE & CAMP STORE BLOCK - 8 OFFICE & STORE 1 108.00 m² FHR + EXTINGUISHER
X
GENERATOR
9 STAFF GYM & RECREATION BLOCK - 9 GYM & RECREATION 1 172.80 m² 172.80 m² FHR + EXTINGUISHER
12200
AREA FOR
X
W/P
X
2900 6000 2000
X
2000
2900
32 18000
13
X
6000
X
SL
OP
E 8%
10800
W/P
W/P
11 WORKERS RECREATION BLOCK - 11 RECREATION 1 172.80 m² 172.80 m² EXTINGUISHER
6500
2400 30 X X X X X X X X 12
W/P
W/P
9
20000
X
W
2400
/P
12 14400 W
/P 16400
12000 10000
8 13 432.00 m² 432.00 m²
SPRINKLER + FHR +
STAFF DINING HALL BLOCK - 13 DINING HALL 1
W/P
24000
X
X
X
EXTINGUISHER
W/P
7082
FACP FACP FACP 3000 12000 6000 12000 6000 12000 Gatch Road
8000 10800 12000 SPRINKLER + FHR +
W/P
23 23 23
X
3600
X
14 WORKERS DINING HALL BLOCK - 14 DINING HALL 951.85 m² 951.85 m²
X
W/P
6000 COURT
SPRINKLER + FHR +
X
X H
W/P
W/P
15 GENERAL KITCHEN BLOCK - 15 KITCHEN 1 798.00 m² 798.00 m² FIRE CONTRACTOR
R7000 24000 6000 24000 6000 24000 6000 24000 6000 24000 EXTINGUISHER
W/P
23 23 23
X
X
S S S S 3600
S S S S S S S S
3600 S S S S S S S S 3600
6000 6000
X
17 FIRE PUMP ROOM BLOCK - 17 FIRE PUMP ROOM 1 84.50 m² 84.50 m² EXTINGUISHER
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
W/P W/P W/P W/P 12000
35 9000
X
6000 6000 6000
W/P W/P W/P W/P W/P
23 23 23 3600 18 ROBT STONE OFFICE BLOCK - 18 OFFICE 1 600.00 m² 600.00 m² FHC + EXTINGUISHER
X
1 1 2 2 2
W/P W/P
X
12000
3600 3600 3600
29 P.O. Box: 91962, Mussafah 14, Abu Dhabi
W/P
S S S S S S S S S S S S S S S S S S S S W/P W/P
2400
2X2 ROAD
6000 W/P
X
W/P
2400
2400 6000
W/P
30 20 STORE SHED -1 (OPEN SHED) BLOCK - 20 STORE SHED 1 600.00 m² 600.00 m² EXTINGUISHER
BARRIER
CRASH
X
23 23 23 10000
T: +971 25535167, F: +971 25535159
W
/P
3600
30
W
24000 2400 /P
X
21 STORE SHED -2 (OPEN SHED) BLOCK - 21 STORE SHED 1 450.00 m² 450.00 m² EXTINGUISHER
3600 2 2 2 3600 SMDB - 1 2 2 3600
2400 30
PSU
X
S S S S S S S S S S S S S S S S S S S S
2400 6000 22 WORKSHOP (OPEN SHED) BLOCK - 22 WORKSHOP 1 225.00 m² 225.00 m² EXTINGUISHER
25
X
30 14500
W/P W/P W/P W/P W/P
2400
6000 6000 6000 23 ADNOC STAFF ACCOMMODATION BLOCK - 23 ACCOMMODATION 30 46.75 m² 1402.50 m² EXTINGUISHER
23 23 23
X
2400
24000 3600
X
S S S S
3600 S S S S S S S S
3600 S S S S S S S S
3600 W/P W/P
FIRE ALARM SYSTEM &
X PROJECT NAME
6000 6000 W/P
25 EXTINGUISHER
X
20000
2400
W/P
23 3600
23 23 3600
26 ADNOC STAFF LAUNDRY BLOCK -26 LAUNDRY 1 43.20 m² 43.20 m² EXTINGUISHER
TEMPORARY CAMP ACCOMMODATION
X
6000
X
16000
S S
2 S S
3600
W/P
S S
2 S S S S
2 S S
3600 S S
2 S S
W/P
S S
2 S S
3600
6000 27 ADNOC STAFF DINING HALL BLOCK - 27 DINING HALL 1 219.98 m² 219.98 m² EXTINGUISHER
X
@ BUHASA
X
315.19 m²
2400
30
W/P
2400
24000
W/P
W/P
W/P
W/P
W/P
W/P
W/P
W/P
6000
23 23 23 3600
27 13500 DIESEL DISPENSER PETROL DISPENSER 29 ADNOC STAFF MOSQUE BLOCK - 29 1 80.00 m² 80.00 m² EXTINGUISHER
X
PRAYER ROOM
X
2 2 2 2 2
W/P W/P
3600 S S S S S S S S S S S S
3600 S S S S S S S S
3600
PSU
W/P W/P
6000 6000
R7000 30
W/P
30 ELECTRICAL ROOM TYPE -1 BLOCK - 30 SMDB ROOM 20 5.76 m² 115.20 m² EXTINGUISHER
X
W/P
X
R7000 3400
2400
23 23 23 31
W/P
2400
3600
312900
6000 10000 W/P ELECTRICAL ROOM TYPE -2 BLOCK - 31 SMDB ROOM 2 9.86 m² 19.72 m² EXTINGUISHER ZONE :
6000 6000
MADINAT ZAYED
X
2400 30
X
7000
12000
X
10000
3600 S S
2 S S S S
2 S S S S
2 S S S S
2 S S S S
2 S S
23 23 23 3600
34 BOOSTER PUMP ROOM BLOCK - 34 PUMP ROOM 1 20.25 m² 20.25 m² EXTINGUISHER
28 19
X
W/P W/P
18225 12200
W/P
X
SECTOR NO : PLOT NO :
W/P W/P
35
W/P W/P W/P
6000
W/P W/P
W/P W/P
W/P 2900 MAJLIS BLOCK - 35 MAJLIS 1 103.73 m² 103.73 m² EXTINGUISHER
W/P
PSU
2500 2900
X
32
W/P
36
HABSHAN T1019
X
DIESEL TANK WITH SHED-1 BLOCK - 36 DIESEL TANK WITH SHED 1 97.00 m² 97.00 m² EXTINGUISHER
2 2 2 2 23 23 23
SLOPE 8%
2
W/P
3600
3600 S S S S S S S S S S S S S S S S S S S S
3600 DIESEL TANK WITH SHED - PETROL TANK WITH SHED - 21600
2500
6
FACP
26 3600
8000 37 PETROL TANK WITH SHED-2 BLOCK - 36 PETROL TANK WITH SHED 1 58.91 m² 58.91 m² EXTINGUISHER
W/P
10,000 GALLON
W/P
FACP 7000
X
24000 6000 24000 6000 24000 6000 24000 6000 24000 12000 6000 12000 6000 12000 17075
4500 4000 3000
TOTAL UNITS 173 TOTAL AREA 19,411.80m²
GATE
8000 6372 12000
PROJECT DESCRIPTION :
PLOT LIMIT PLOT LIMIT
BU HASA ACCOMMODATION (RSME AND ADNOC) PLAN
LABOUR CAMP @ BUHASA
DRAWING TITLE :
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/FA-01 04
shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
installed as per approved Shop drawing. 09.08.2023 1:1000
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
BU HASA ROAD 10)
DRAWN BY : CHECKED BY :
TOWARDS CICPA GATE 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and
NFPA 101) KKI MRJ
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
28000
1 2 3 4 5 6 7
14000
14000
W/P
CONNECTED TO N
W/P
DEVICES IN NEARBY W N
S
E
A CARAVAN
BED ROOM - 12 BED ROOM - 11 BED ROOM - 10 BED ROOM - 9 BED ROOM - 8 BED ROOM - 7
2027
2027
2027
2027
2027
2027
CARAVAN
GENERAL NOTES :
8500
PSU
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
2280 2250 2326 2275 2326 2326 ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
S S S S S S CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
CONNECTED FROM
DEVICES IN NEARBY
2027
2027
2027
2027
2027
2027
CARAVAN
B W/P
W/P
ADDRESSABLE SMOKE DETECTOR WITH STANDARD 00 FOR APPROVAL 28.03.2023 KKI MRJ
S CONTEXTPLUS
BASE DRAWN CHKD
REV. NO. DESCRIPTION DATE
ADDRESSABLE SMOKE DETECTOR WITH SOUNDER CLIENT:
S BASE CONTEXTPLUS
CONNECTED TO
DEVICES IN NEARBY W/P
FIRE ALARM SOUNDER FLASHER WEATHER
CARAVAN 2250 CONTEXTPLUS
PROOF
S S S S
2250 2250 7300 2250
1300
1300
SM
B W/P
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
CONNECTED TO DEVICES IN CONNECTED FROM DEVICES P.O. Box: 91962, Mussafah 14, Abu Dhabi
SLOPE 8%
W/P
1700
1700
1700
FIRE ALARM SYSTEM FOR
B
BLOCK-1,2,3 & 4
W/P
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
CONNECTED TO DEVICES IN
NEARBY CARAVAN CONNECTED FROM DEVICES
W/P
IN NEARBY CARAVAN
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
BLOCK-2 STAFF ACCOMMODATION TYPE-1 1. FIRE ALARM MANUAL CALL POINT AND SOUNDER 2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/FA-02 04
NUMBER OF BLOCKS: 35 CUM FLASHER IS NOT PLACED IN ALL CARAVANS. shall be submitted to ADCD for both architectural and shop approvals.
SUBMISSION DATE : SCALE :
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
2. REFER: SFS/RS/BHS/FA-01 FOR LOCATION installed as per approved Shop drawing. 09.08.2023 1:75
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
10)
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
1 2 3 4 5
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
24000 in this building in accordance to the relevant NFPA code and standards.
12000 12000 11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
A CONNECTED FROM (and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
BED ROOM - 1 TOILET BED ROOM - 2 BED ROOM - 3 TOILET BED ROOM - 4
DEVICES IN NEARBY
CARAVAN PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ
3600
CONNECTED TO
2425 2425 2425 2425 and NFPA 101).
DEVICES IN NEARBY
CARAVAN
S S S S
TOILET TOILET 15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
1700
1700
1700
1700
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
CONNECTED TO DEVICES IN code (including local power authority standards) and the relevant NFPA codes and standards.
NEARBY CARAVAN
B NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
W/P
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
W/P
CONNECTED FROM DEVICES 18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
BLOCK-1 SENIOR STAFF ACCOMMODATION IN NEARBY CARAVAN
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
NUMBER OF BLOCKS: 04 19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
28000
1 2 3 4 5 6 7
N
A
W N E
BED ROOM - 1 BED ROOM - 2 BED ROOM - 3 BED ROOM - 4 BED ROOM - 5 BED ROOM - 6
CONNECTED TO
DEVICES IN NEARBY
CARAVAN ASPHALT ROAD TO BUHASA
4250
2250 2250 2300 2250 2250 2300 CONNECTED FROM
S S S S S S DEVICES IN NEARBY
BU-800 HIGH
CARAVAN PRESSURE WI
2025
2025
2025
2025
2025
2025
LEGEND :- GENERAL NOTES :
B SYMBOL DESCRIPTION MAKE 1. DO NOT SCALE THIS DRAWING.
W/P
4 LOOP ADDRESSABLE FIRE ALARM CONTROL 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
CONNECTED TO DEVICES CONNECTED FROM DEVICES IN
FACP CONTEXTPLUS UNLESS OTHERWISE NOTED.
W/P
PANEL
IN NEARBY CARAVAN NEARBY CARAVAN
ADDRESSABLE SMOKE DETECTOR WITH STANDARD 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
S CONTEXTPLUS
BASE RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
ADDRESSABLE SMOKE DETECTOR WITH SOUNDER MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
BLOCK-4A WORKERS ACCOMMODATION TYPE-2 S CONTEXTPLUS ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
BASE
NUMBER OF BLOCKS: 01 CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
ADDRESSABLE SMOKE DETECTOR WITH STANDARD
S CONTEXTPLUS
RI BASE & REMOTE INDICATOR ABOVE VOID
BED ROOM - 1 BED ROOM - 2 BED ROOM - 3 BED ROOM - 4 IFU INTERFACING UNIT CONTEXTPLUS
00 FOR APPROVAL 28.03.2023 KKI MRJ
1074
1074
1075
CONNECTED TO
CONNECTED FROM ROBT STONE (ME)LLC
DEVICES IN NEARBY B DEVICES IN NEARBY P.O. Box. 39588
CARAVAN
W/P
CARAVAN Abu Dhabi, U.A.E
SLOPE 8% SLOPE 8% SLOPE 8% SLOPE 8%
W/P
CONSULTANT :
W/P
W/P
P.O. Box: 91962, Mussafah 14, Abu Dhabi
1150 BLOCK
2500
CONNECTED FROM HAND
SHOWER-1 SHOWER-2 SHOWER-3 SHOWER-4 SHOWER-5 SHOWER-6 SHOWER-7 SHOWER-8 SHOWER-9
HAND
CONNECTED FROM S T: +971 25535167, F: +971 25535159
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
1150
DEVICES IN NEARBY WASH WASH DEVICES IN NEARBY
900
TOILET BLOCK TOILET BLOCK PROJECT NAME
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/FA-03 04
shall be submitted to ADCD for both architectural and shop approvals.
1 2 3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
12000 installed as per approved Shop drawing. 09.08.2023 1:75
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
A Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
OBSERVATION WARD Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
1700
10)
1900 8000 1900 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
3600
CONNECTED FROM
S S DEVICES IN NEARBY
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
BLOCK FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
7200
TOILET 11. All fire door and windows shall be according to (NFPA 80).
WAITING AREA CONSULTING ROOM
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
CONNECTED TO
DEVICES IN NEARBY
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
2040 2040 BLOCK
3600
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
S S STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
1720 15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
S
1750
1750
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
1025
B W/P
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
W/P NFPA-20 STAMP: safety code and NFPA 101 and 5000).
CONNECTED FROM 19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
DEVICES IN NEARBY BLOCK under construction.
EXIT-1 SHELTER NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
BLOCK-7 CLINIC NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
NUMBER OF BLOCKS: 01 23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
1 2
10000 14400
EXIT-4 EXIT-3
SHELTER SHELTER
1 2 3 N
SHELTER W N
S
E
A
A STAFF GYM RECREATION
1900
1900
STORE ASPHALT ROAD TO BUHASA
3525 3525
SHELTER S S BU-800 HIGH
3500
PRESSURE WI
CONNECTED FROM
S S DEVICES IN NEARBY
BLOCK 4 LOOP ADDRESSABLE FIRE ALARM CONTROL 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
FACP CONTEXTPLUS UNLESS OTHERWISE NOTED.
PANEL
ADDRESSABLE SMOKE DETECTOR WITH STANDARD 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
S CONTEXTPLUS
BASE RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
10800
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
12000
ADDRESSABLE SMOKE DETECTOR WITH SOUNDER
8000
8000
S BASE CONTEXTPLUS ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
ADDRESSABLE SMOKE DETECTOR WITH STANDARD
S CONTEXTPLUS
RI BASE & REMOTE INDICATOR ABOVE VOID
BLOCK
3850 04 FOR APPROVAL 09.08.2023 KKI MRJ
S ADDRESSABLE FIRE ALARM SOUNDER CONTEXTPLUS
CONNECTED FROM
03 FOR APPROVAL 07.08.2023 KKI MRJ
S S DEVICES IN NEARBY W/P
FIRE ALARM SOUNDER FLASHER WEATHER
1750
1900
1900
675
1 14400 2
1200 1200
SHELTER FIRE CONTRACTOR
1200
1200
SHELTER SPEED FIRE & SAFETY EQUIPMENT L.L.C.
A P.O. Box: 91962, Mussafah 14, Abu Dhabi
T: +971 25535167, F: +971 25535159
WORKERS WORKERS
RECREATION-1 E-mail: speedfse@eim.ae, www.speedsafetyuae.com
RECREATION-2
1900
1900
PROJECT NAME
3525 3525
S S TEMPORARY CAMP ACCOMMODATION
@ BUHASA
ZONE :
MADINAT ZAYED
SECTOR NO : PLOT NO :
HABSHAN T1019
PROJECT DESCRIPTION :
12000
8000
8000
DRAWING TITLE :
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
CONNECTED FROM
SFS/RS/BHS/FA-04 04
S S DEVICES IN NEARBY
BLOCK
2. Any architectural changes like addition, deletion, modification during construction or in future
shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
1:75
1900
1900
2000
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
SHELTER SHELTER 8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
2000 9. Standpipe system shall be provided in these building according to (NFPA 14).
2000
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
BLOCK-11 WORKERS RECREATION
11. All fire door and windows shall be according to (NFPA 80).
NUMBER OF BLOCKS: 01 12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
45150
KEY PLAN :
11700 5255 1736 8114 13196 2600
1 2500
2 3 4 5 6 7 2500
8
SHELTER
SHELTER
1 1
1500
2 2
3 3 N
A W N
S
E
1500
DISH WASH ROOM
COLLECTION AREA
1750
HAND WASH AREA 818 HAND WASH AREA
WATER DRINKING
3634
4030
SHADED AREA COOLER S S SHADED AREA
ASPHALT ROAD TO BUHASA
1700
BU-800 HIGH
B PRESSURE WI
(TYP)
1650
4475 9000 9000 9000 9000 4475
(TYP) (TYP) (TYP) (TYP) (TYP) (TYP) LEGEND :- GENERAL NOTES :
S S S S S
SYMBOL DESCRIPTION MAKE 1. DO NOT SCALE THIS DRAWING.
4 LOOP ADDRESSABLE FIRE ALARM CONTROL 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
FACP CONTEXTPLUS UNLESS OTHERWISE NOTED.
PANEL
ADDRESSABLE SMOKE DETECTOR WITH STANDARD 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
S CONTEXTPLUS
BASE RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
9442
PROOF
01 FOR APPROVAL 24.07.2023 KKI MRJ
CONNECTED TO
DEVICES IN NEARBY
IFU INTERFACING UNIT CONTEXTPLUS
BLOCK-15 00 FOR APPROVAL 28.03.2023 KKI MRJ
CONSULTANT :
S S S S S
(TYP)
1650
CONNECTED FROM
FOR ZCV DEVICES IN NEARBY
BLOCK
IFU IFU
C 3
2
SHELTER
2
1200 1 SHELTER 1 1200
1600 1600
1 2 FIRE CONTRACTOR
2000
BLOCK-14 WORKERS DINNING HALL
NUMBER OF BLOCKS: 01 A SPEED FIRE & SAFETY EQUIPMENT L.L.C.
CONNECTED FROM P.O. Box: 91962, Mussafah 14, Abu Dhabi
DEVICES IN NEARBY T: +971 25535167, F: +971 25535159
1 1200 2 BLOCK
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
10800 900
2000
EXIT-3 S PROJECT NAME
900
CONNECTED TO
1200
DEVICES IN NEARBY
SHELTER
BLOCK TEMPORARY CAMP ACCOMMODATION
A B @ BUHASA
C
SHELTER
STORE
DEVICES IN NEARBY
DEVICES IN NEARBY
CONNECTED FROM
2000 ZONE :
CONNECTED TO
1800
MADINAT ZAYED
BLOCK-15
BLOCK-15
1950
S
3075
1150
SECTOR NO : PLOT NO :
S BLOCK-7A MEDICAL WAST ROOM
2000
SHELTER
1800
WASHING AREA
1330
W/P
W/P
SHELTER
5300 4050
LABOUR CAMP @ BUHASA
1500
S
FOR ZCV IFU CONNECTED FROM DEVICES DRAWING TITLE :
IN NEARBY BLOCK
IFU
14250
IRON PRESSING
12000
8000
1460
BLOCK-7A,12,13 & 14
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
4500
18000
H 1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/FA-05 04
shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
installed as per approved Shop drawing. 09.08.2023 1:75
S S S LINE SORTING
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
1800
Approval Department.
SHELTER
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
1500
3075
10)
DRAWN BY : CHECKED BY :
10500
S 5300
S
4050 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and
KKI MRJ
EXIT-2
ENTRANCE 9. Standpipe system shall be provided in these building according to (NFPA 14).
4000 2250 6000 2250 10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
B
3750
1200
1000
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
1825
1775
1775
WC WC (and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
A 1200 this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
W/P
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
1 2 3
W/P
EXIT -1 4 5 STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
SHELTER
standards.
2650 5500 5200 10650 NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
24000 STAMP: STAMP:
NFPA-14 SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
BLOCK-13 STAFF DINNING HALL and tested in accordance with (UAE fire and life safety code and other relevant international standards).
NUMBER OF BLOCKS: 01 18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
39900
2500 W N
S
E
1200
1 2 3 4 5 6 7
1500
1200
SHELTER
SHELTER
A
GARBAGE
ASPHALT ROAD TO BUHASA
ROOM
SALAD ROOM
2650
2100
RECEIVING AREA 1000
S H BU-800 HIGH
3000
FOR WET CHEMICAL
3500
1175
1175
SYSTEM
PROTEIN FREEZER
2750 IFU
S
VEG FREEZER
FISH FREEZER
VEG CHILLER
B
LEGEND :-
1500
PRE WASH AREA 3150
H
GENERAL NOTES :
PACKING ROOM
CHAPATTI ROOM
850
S 1800 SYMBOL DESCRIPTION MAKE 1. DO NOT SCALE THIS DRAWING.
VEGETABLE ROOM
3700
3200 S S 4 LOOP ADDRESSABLE FIRE ALARM CONTROL 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
S FACP CONTEXTPLUS
4000 8000 8000 8000 1950 3500 PANEL UNLESS OTHERWISE NOTED.
1750
2750
S ADDRESSABLE SMOKE DETECTOR WITH STANDARD 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
S CONTEXTPLUS
IFU
BASE RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
1500
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
4150
4150
C ADDRESSABLE SMOKE DETECTOR WITH SOUNDER
FOR WET CHEMICAL S BASE CONTEXTPLUS ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
1750
SYSTEM
8000
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
PVC CURTAIN
ADDRESSABLE SMOKE DETECTOR WITH STANDARD
2151
MEAT ROOM
S CONTEXTPLUS
3200
FD 60
S S S
1500 2750 H ADDRESSABLE HEAT DETECTOR WITH STANDARD BASE CONTEXTPLUS
1500
S S
HOT KITCHEN
9000
3000
1425
SHADED
1500
RECEIVING OFFICE
D ADDRESSABLE MANUAL CALL POINT CONTEXTPLUS
20000
FD 60
3850
9000
STAFF ENTRANCE S S S
S S S S RI
1200
CONTEXTPLUS
DEFROST CHILLER
FISH DE-CHILLER
CHICKEN ROOM PROOF
EGG CHILLER
DAIRY CHILLER
SHELTER
H ADDRESSABLE FIRE ALARM SOUNDER CONTEXTPLUS 04 FOR APPROVAL 09.08.2023 KKI MRJ
6000
800 W/P
FIRE ALARM SOUNDER FLASHER WEATHER
TOILET IFU CONTEXTPLUS KKI MRJ
LOCKERS
1500
IFU PROOF
S
3000
PVC CURTAIN
TOILET
FISH ROOM 00 FOR APPROVAL 28.03.2023 KKI MRJ
1900
SM SOUNDER MODULE CONTEXTPLUS REV. NO. DESCRIPTION DATE DRAWN CHKD
7088
E S CLIENT:
2750
S
S
5588
3425
GARBAGE ROOM
2150
1500
1500
1800
S P.O. Box. 39588
1075
Abu Dhabi, U.A.E
5250
S S S 1200
4500
9000 3149 1325
DISPOSABLE DRY7000
STORE
S CHEMICAL STORAGE
1799 7000
STORE 1900
FD 60
S H 1800 CONSULTANT :
2100
S
1500
1075
FOR ZCV W/P
IFU IFU
W/P
IFU IFU IFU IFU
F 1200
FOR KITCHEN FOR KITCHEN
1200 VENTILATION SYSTEM VENTILATION SYSTEM
SHELTER
3000
2000
BLOCK-15 GENERAL KITCHEN
NUMBER OF BLOCKS: 01 CHEMICAL STORAGE DETAILS FIRE CONTRACTOR
S
1425 1. DISH WASHING LIQUID SPEED FIRE & SAFETY EQUIPMENT L.L.C.
2. ALL PURPOSE CLEANER P.O. Box: 91962, Mussafah 14, Abu Dhabi
T: +971 25535167, F: +971 25535159
3. FLOOR CLEANER ETC..
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
PROJECT NAME
H MDB-1
COUPLER
MDB-2
5400
DRAWING TITLE :
1596 1580 7000 1420
S S S
QRM ROOM FIRE ALARM SYSTEM FOR
2928
2350
BLOCK-15 & 16
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
SFS/RS/BHS/FA-06 04
CONNECTED TO B W/P W/P CONNECTED FROM
2. Any architectural changes like addition, deletion, modification during construction or in future
DEVICES IN NEARBY DEVICES IN NEARBY shall be submitted to ADCD for both architectural and shop approvals.
BLOCK W/P W/P BLOCK 3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
installed as per approved Shop drawing. 09.08.2023 1:100
1600 3400 2650 2650 7338 3662 4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
10)
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
BLOCK-16 SUB-STATION 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
NUMBER OF BLOCKS: 02 by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
1 2 3 4 5 6 N
W N E
30000
S
1400 1400 1400 1400 1400 2500 5000 1500 7500 6500
1200
SHELTER
ASPHALT ROAD TO BUHASA
A
WC WC WC WC WC PANTRY STORE ROOM DOCUMENT CONTROL ROOM QA/QC ROOM BU-800 HIGH
PRESSURE WI
2350
2550
4000
1200 2450 700 3700 3175
H S S S S SYMBOL DESCRIPTION MAKE 1. DO NOT SCALE THIS DRAWING.
4 LOOP ADDRESSABLE FIRE ALARM CONTROL 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
FACP
1950
1950
1950
1950
CONTEXTPLUS
2000
PANEL UNLESS OTHERWISE NOTED.
HAND WASH AREA ADDRESSABLE SMOKE DETECTOR WITH STANDARD 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
S CONTEXTPLUS
2450
SERVER ROOM S BASE CONTEXTPLUS ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
SHELTER CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
ADDRESSABLE SMOKE DETECTOR WITH STANDARD
B S CONTEXTPLUS
RI BASE & REMOTE INDICATOR ABOVE VOID
3500
1450 ADDRESSABLE HEAT DETECTOR WITH STANDARD BASE CONTEXTPLUS
S H
2050
1650
ADDRESSABLE MANUAL CALL POINT CONTEXTPLUS
S S S
W/P ADDRESSABLE MANUAL CALL POINT WEATHER
CONTEXTPLUS
PROOF
PRINTER CONTEXTPLUS 04 FOR APPROVAL 09.08.2023 KKI MRJ
ADDRESSABLE FIRE ALARM SOUNDER
2425
2000
W/P
WORK STATION WORK STATION FIRE ALARM SOUNDER FLASHER WEATHER
CONTEXTPLUS 02 FOR APPROVAL 28.07.2023 KKI MRJ
PROOF
01 FOR APPROVAL 24.07.2023 KKI MRJ
2000 IFU INTERFACING UNIT CONTEXTPLUS
S 00 FOR APPROVAL 28.03.2023 KKI MRJ
20000
11898
MANAGER OFFICE-6
7000
4600
1450 P.O. Box. 39588
S Abu Dhabi, U.A.E
2300
MEETING ROOM
2200
3050
CONNECTED TO
H
12950
BLOCK
S S S
ADMINISTRATION
2452
OFFICE
FIRE CONTRACTOR
13000
8000
C
MANAGER OFFICE -1 MANAGER OFFICE -2 MANAGER OFFICE -3 MANAGER OFFICE -4 RECEIPTION MANAGER OFFICE -5
W/P
W/P
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
5800
1228
1900
S P.O. Box: 91962, Mussafah 14, Abu Dhabi
S T: +971 25535167, F: +971 25535159
2225 1750 1750 1750 2090 1750 E-mail: speedfse@eim.ae, www.speedsafetyuae.com
FACP
S S S S S S
2900
2425
PROJECT NAME
1900
1900
1900
1900
1900 H TEMPORARY CAMP ACCOMMODATION
@ BUHASA
2300
D
TO NEARBY BLOCK-30 FROM BLOCK-36 ZONE :
ELECTRICAL ROOM
FROM BLOCK-30
AIR LOCK TO BLOCK-19 DIESEL TANK MADINAT ZAYED
ELECTRICAL ROOM SUPER MARKET B
4050 4550 3600 3600 3600 4292 3600 2706 CONNECTED FROM SECTOR NO : PLOT NO :
DEVICES IN NEARBY
BLOCK
HABSHAN T1019
30000 BLOCK-17 FIRE PUMP ROOM
NUMBER OF BLOCKS: 01 PROJECT DESCRIPTION :
1500
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/FA-02 04
shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
installed as per approved Shop drawing. 09.08.2023 1:75
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
1 2 3 5 Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
B3N-2022-000555-CD-SHD-02 A1
12000 5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA
10)
4150 1750 1750 4350 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
A 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
LIVING ROOM by voice announcement system according to (NFPA 72).
PANTRY TOILET BED ROOM FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
825
H 9. Standpipe system shall be provided in these building according to (NFPA 14).
1050
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
3600
2000 2100 in this building in accordance to the relevant NFPA code and standards.
S S 11. All fire door and windows shall be according to (NFPA 80).
600
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
1700
1700
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
1700
CONNECTED TO DEVICES S CONNECTED FROM DEVICES
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
IN NEARBY BLOCK this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
IN NEARBY BLOCK
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
B W/P STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
W/P
standards.
AIR LOCK NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
BLOCK-23 ADNOC STAFF ACCOMMODATION NFPA-20 STAMP: safety code and NFPA 101 and 5000).
NUMBER OF BLOCKS: 30 1. FIRE ALARM MANUAL CALL POINT AND SOUNDER 19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
CUM FLASHER IS NOT PLACED IN ALL CARAVANS. NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
2. REFER: SFS/RS/BHS/FA-01 FOR LOCATION safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
CONNECTED TO DEVICES
KEY PLAN :
IN NEARBY BLOCK
SHELTER
1 2
20000
N
15795 3905 W N
S
E
AIR LOCK
A
CONNECTED FROM
LOUNGE-1 LOUNGE-2
DEVICES IN NEARBY
BLOCK W/P
SHELTER ASPHALT ROAD TO BUHASA
1950
C
3146
3200
BU-800 HIGH
PRESSURE WI
STORE
2000
2000
3895 8000 3900
CASH COUNTER
MOBILE COUNTER 9000 3500
6400
GENERAL NOTES :
3500 S S
4100
S S S S
SUPER MARKET HALL 1. DO NOT SCALE THIS DRAWING.
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
6250
SHELF SHELF SHELF UNLESS OTHERWISE NOTED.
OFFICE 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
1450
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
4100
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
1400 TOILET ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
S CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
SHELF SHELF SHELF B
RECREATION AREA
14500
12200
12000
8000
B
SALOON
SHELTER
3900
1417
CONNECTED TO
DEVICES IN NEARBY SHELF SHELF SHELF SHELF S
BLOCK SHELTER
04 FOR APPROVAL 09.08.2023 KKI MRJ
1950
4432 8000 4433 03 FOR APPROVAL 07.08.2023 KKI MRJ
CHILLER
7800
5950
REFRESHMENT
3800 S S TOILET
01 FOR APPROVAL 24.07.2023 KKI MRJ
SHELF SHELF SHELF SHELF
00 FOR APPROVAL 28.03.2023 KKI MRJ
SHELTER
1900
S S STORE DRAWN CHKD
3500
REV. NO. DESCRIPTION DATE
CLIENT:
1100 600 TOILET
2000
S H
1100
ROBT STONE (ME)LLC
COLD&FOOD ITEMS CLOTHES CLOTHES WALL SHELF WALL SHELF
P.O. Box. 39588
TOILET Abu Dhabi, U.A.E
A
16150 5450
21600 C CONSULTANT :
2 14100 2400 3500
3 1
W/P
FIRE CONTRACTOR
S H TOILET
1240
1240
3150 7000 3150 SECTOR NO : PLOT NO :
S HABSHAN T1019
S S LEGEND :-
PROJECT DESCRIPTION :
SYMBOL DESCRIPTION MAKE
BASE
7000
7000
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/FA-08 04
9165
S S S W/P
FIRE ALARM SOUNDER FLASHER WEATHER
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
CONTEXTPLUS 10)
PROOF 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
2400
IFU INTERFACING UNIT CONTEXTPLUS 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
2934
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
10000 in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
2150 BLOCK-24 ADNOC STAFF GYM 12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
H 4200 NUMBER OF BLOCKS: 01 (and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
H CONNECTED FROM PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
STORE
2830
BLOCK 14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
2000
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
TOILET 900 TOILET TOILET TOILET
S NFPA-10 SIGN: SIGN: CD CARD No: 101110379
standards.
16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
B STAMP: STAMP:
code (including local power authority standards) and the relevant NFPA codes and standards.
6022 2280 NFPA-14 SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
2410
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
BLOCK-27 ADNOC STAFF DINNING HALL 21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NUMBER OF BLOCKS: 01 SHELTER NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
CONNECTED TO
CONNECTED TO DEVICES IN
DEVICES IN
NEARBY BLOCK
A NEARBY BLOCK B
1 2 3400
12000 A B
N
W N E
2400 1
SLOPE 8% W/P
W/P
1 SUB ELECTRICAL
A SUB ELECTRICAL ROOM ASPHALT ROAD TO BUHASA
STORE ROOM
(DRY AREA)
1500
2900
WASHING BU-800 HIGH
WASHING
S
DRYER MACHINE PRESSURE WI
MACHINE
2400
MACHINE
LAUNDRY
(WET AREA) S
3600
1250
1000
1010
S S S 952 LEGEND :- GENERAL NOTES :
CONNECTED TO DEVICES IN 1847 6000 1848
NEARBY BLOCK
SYMBOL DESCRIPTION MAKE 1. DO NOT SCALE THIS DRAWING.
1700
CONNECTED FROM DEVICES
IN NEARBY BLOCK
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
IRONING 2 2 FACP
4 LOOP ADDRESSABLE FIRE ALARM CONTROL
PANEL
CONTEXTPLUS UNLESS OTHERWISE NOTED.
TABLE CONNECTED FROM CONNECTED FROM
B DEVICES IN DEVICES IN
S ADDRESSABLE SMOKE DETECTOR WITH STANDARD
CONTEXTPLUS
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
NEARBY BLOCK NEARBY BLOCK BASE RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
ADDRESSABLE SMOKE DETECTOR WITH SOUNDER MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
S BASE CONTEXTPLUS ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
BLOCK-30 ELECTRICAL ROOM TYPE-1 BLOCK-31 ELECTRICAL ROOM TYPE-2 CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
ADDRESSABLE SMOKE DETECTOR WITH STANDARD
SHELTER
NUMBER OF BLOCKS: 20 S CONTEXTPLUS
NUMBER OF BLOCKS: 02 RI BASE & REMOTE INDICATOR ABOVE VOID
BLOCK-26 ADNOC STAFF LAUNDRY H ADDRESSABLE HEAT DETECTOR WITH STANDARD BASE CONTEXTPLUS
NUMBER OF BLOCKS: 01
ADDRESSABLE MANUAL CALL POINT CONTEXTPLUS
W/P
CHEMICAL BAKERY CHEFROOM DAILYSTORAGE DRY STORE ROOM P.O. Box. 39588
STORE 875 Abu Dhabi, U.A.E
S
2543
1125 1250
775
2900
S 1525 S
2663
S
3225
3325
1137
S CONSULTANT :
1388
1250
1200
B
DISH WASH
FOR KITCHEN IFU AREA 1675
S VEGETABLE&SALAD FREEZER
VENTILATION SYSTEM IFU S PREPARATIONROOM (INSULATED COLD
2
CONTAINED)
600
CONNECTED FROM DEVICES
4207
1125
S 2425 IN NEARBY BLOCK FIRE CONTRACTOR
S
4500
BLOCK-32 ELECTRICAL ROOM TYPE-3 SPEED FIRE & SAFETY EQUIPMENT L.L.C.
1985
1750
PROJECT NAME
S
W/P
H S
TEMPORARY CAMP ACCOMMODATION
1425
17075
D S RI
RI
@ BUHASA
POTSTORE CHICKENPREPARATION
ROOM ZONE :
IFU FOR ZCV 2425 CHILLER
MADINAT ZAYED
5988
DEVICES IN NEARBY
SECTOR NO : PLOT NO :
5600
Packing Tables
BLOCK
HABSHAN T1019
6000
MEATPREPARATION
ROOM PROJECT DESCRIPTION :
2426
1150 S LABOUR CAMP @ BUHASA
S
1000
CHILLER
(INSULATED COLD
E CONTAINED)
DRAWING TITLE :
FISH PREPARATION
ROOM
S
2425
H S FIRE ALARM SYSTEM FOR
2920
988
BLOCK-26,28,29,30,31 & 32
1775
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
IFU
RECIVING AREA PRE WASH GARBAGE 1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
ELECTRICKITCHEN TOILET ROOM
416
drawings.
FOR WET CHEMICAL 3288AREA 838 2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/FA-09 04
SYSTEM S S
1418
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
CONNECTED FROM
DEVICES IN NEARBY installed as per approved Shop drawing. 09.08.2023 1:75
F BLOCK 4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
SHELTER Approval Department.
LOCK
AIR
SHELTER 5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
10)
BLOCK-28 ADNOC STAFF KITCHEN 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NUMBER OF BLOCKS: 01 NFPA 101) KKI MRJ
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
SHELTER 9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
1 2 W
N
S
E
8500
A
ASPHALT ROAD TO BUHASA
8500
4000 RI BASE & REMOTE INDICATOR ABOVE VOID
4500
H H
2000 H ADDRESSABLE HEAT DETECTOR WITH STANDARD BASE CONTEXTPLUS
ROLLING SHUTTER
2000
W/P ADDRESSABLE MANUAL CALL POINT WEATHER
CONTEXTPLUS
PROOF
04 FOR APPROVAL 09.08.2023 KKI MRJ
ADDRESSABLE FIRE ALARM SOUNDER CONTEXTPLUS
4000
03 FOR APPROVAL 07.08.2023 KKI MRJ
W/P
FIRE ALARM SOUNDER FLASHER WEATHER
CONTEXTPLUS
W/P
W/P
FIRE CONTRACTOR
W/P
HABSHAN T1019
PROJECT DESCRIPTION :
4400
DRAWING TITLE :
S MAJLIS S ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/FA-10 04
shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
installed as per approved Shop drawing. 09.08.2023 1:75
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
4400
10)
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
CONNECTED FROM FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
DEVICES IN NEARBY (NFPA 13).
BLOCK 9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
B PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379
BLOCK-35 MAJLIS 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NUMBER OF BLOCKS: 01 NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
BUND WALL
W/P CONNECTED FROM & TO
756
N
S
E
W/P
1261
ASPHALT ROAD TO BUHASA
1430
1430
BU-800 HIGH
756 PRESSURE WI
FLAMMABLE LIQUID
FLAMMABLE LIQUID
LEGEND :- GENERAL NOTES :
3
SYMBOL DESCRIPTION MAKE 1. DO NOT SCALE THIS DRAWING.
4 LOOP ADDRESSABLE FIRE ALARM CONTROL 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
FACP CONTEXTPLUS UNLESS OTHERWISE NOTED.
PANEL
ADDRESSABLE SMOKE DETECTOR WITH STANDARD 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
S CONTEXTPLUS
BASE RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
B-42/O-1/T-2
B-42/O-1/T-1
ADDRESSABLE SMOKE DETECTOR WITH SOUNDER MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
S BASE CONTEXTPLUS ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
ADDRESSABLE SMOKE DETECTOR WITH STANDARD
S CONTEXTPLUS
RI BASE & REMOTE INDICATOR ABOVE VOID
6191
6191
10000
H ADDRESSABLE HEAT DETECTOR WITH STANDARD BASE CONTEXTPLUS
1430
1430
P.O. Box. 39588
Abu Dhabi, U.A.E
364
CONSULTANT :
1
1008 9706
A
B
10000
BUND WALL
LABOUR CAMP @ BUHASA
2860
365
FIRE ALARM SYSTEM FOR
FLAMMABLE LIQUID
BLOCK-36 (SHED-1 & 2)
3 ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/FA-11 04
1255
1385
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
B3N-2022-000555-CD-SHD-02 A1
B 5.
10)
All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA
753
753
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
1255 8. All portions of these building shall be fully protected by automatic sprinklers system according to
FOR CIVIL DEFENSE APPROVAL :
BLOCK-37 9.
(NFPA 13).
Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
LOOP-4 IN
BLOCK-5 WORKERS TOILET
H H
P1/L4/D47 P1/L4/D46
W/P W/P
S S S S S S S S S S S S S S S
N
P1/L4/D30 P1/L4/D29 P1/L4/D28 P1/L4/D27 P1/L4/D26 P1/L4/D25 P1/L4/D24 P1/L4/D23 P1/L4/D22 P1/L4/D21 P1/L4/D20 P1/L4/D19 P1/L4/D18 P1/L4/D17 P1/L4/D16 W N E
W/P W/P S
LOOP-4 OUT
S S S S S S S S S S S S S S S
LOOP-4 IN W/P W/P
P1/L4/D01 P1/L4/D02 P1/L4/D03 P1/L4/D04 P1/L4/D05 P1/L4/D06 P1/L4/D07 P1/L4/D08 P1/L4/D09 P1/L4/D10 P1/L4/D11 P1/L4/D12 P1/L4/D13 P1/L4/D14 P1/L4/D15
BLOCK-4 WORKERS ACCOMMODATION TYPE-1 BLOCK-5 WORKERS TOILET BLOCK-2,& 30
W/P W/P W/P W/P W/P W/P W/P W/P
H H H H S S S W/P W/P
P4/L4/D31 P4/L4/D32 P4/L4/D33 P4/L4/D34 P4/L4/D35 P4/L4/D36 P4/L4/D37 P4/L4/D38 P4/L4/D39 P4/L4/D40 P4/L4/D41
P1/L3/D49 P1/L3/D48 P1/L3/D47 P1/L3/D46 CONNECTED TO
ASPHALT ROAD TO BUHASA
DB NEARBY
W/P W/P
S S S S S S
W/P W/P W/P W/P W/P W/P W/P
S SM S S S S S S S S S S S S S S S
LOOP-3 IN
PSU P4/L4/D30 P4/L4/D29 P4/L4/D28 P4/L4/D27 P4/L4/D26 P4/L4/D25 P4/L4/D24 P4/L4/D23 P4/L4/D22 P4/L4/D20 P4/L4/D19 P4/L4/D18 P4/L4/D17 P4/L4/D16 BU-800 HIGH
P1/L3/D31 P1/L3/D32 P1/L3/D33 P1/L3/D34 P1/L3/D35 P1/L3/D36 P1/L3/D37 P1/L3/D38 P1/L3/D39 P1/L3/D40 P1/L3/D41 P1/L3/D42 P1/L3/D43 P1/L3/D44 P1/L3/D45 P4/L4/D21 PRESSURE WI
BLOCK-30 ELECTRICAL
W/P W/P
ROOM TYPE-1
LOOP-4 OUT
S S S S S S S S S S S S S S S W/P W/P S S S S S S S S S S S S S S S
P4/L4/D09
P4/L4/D01 P4/L4/D02 P4/L4/D03 P4/L4/D04 P4/L4/D05 P4/L4/D06 P4/L4/D07 P4/L4/D08 P4/L4/D10 P4/L4/D11 P4/L4/D12 P4/L4/D13 P4/L4/D14 P4/L4/D15 W/P W/P
P1/L3/D30 P1/L3/D29 P1/L3/D28 P1/L3/D27 P1/L3/D26 P1/L3/D25 P1/L3/D24 P1/L3/D23 P1/L3/D22 P1/L3/D21 P1/L3/D20 P1/L3/D19 P1/L3/D18 P1/L3/D17 P1/L3/D16
LOOP-3 OUT
BLOCK-2, 3 & 30 CONNECTED TO
W/P W/P
W/P W/P W/P W/P W/P W/P W/P W/P DB NEARBY
S S S S SM
S S S S S S S S S S S S S S S W/P W/P
LOOP-3 IN
P1/L3/D01 P1/L3/D02 P1/L3/D03 P1/L3/D04 P1/L3/D05 P1/L3/D06 P1/L3/D07 P1/L3/D08 P1/L3/D09 P1/L3/D10 P1/L3/D11 P1/L3/D12 P1/L3/D13 P1/L3/D14 P1/L3/D15 W/P W/P
P4/L3/D31 P4/L3/D32 P4/L3/D33 P4/L3/D34 P4/L3/D35 P4/L3/D36 P4/L3/D37 P4/L3/D38 P4/L3/D39 P4/L3/D40 P4/L3/D41 P4/L3/D42 P4/L3/D43 PSU
LEGEND :- GENERAL NOTES :
W/P W/P
BLOCK-5
WORKERS TOILET
H H H S S S S S S S S S S S S S S S
P1/L2/D48 P1/L2/D47 P1/L2/D46
W/P W/P
P4/L3/D30 P4/L3/D29 P4/L3/D28 P4/L3/D27 P4/L3/D26 P4/L3/D25 P4/L3/D24 P4/L3/D23 P4/L3/D22 P4/L3/D21 P4/L3/D20 P4/L3/D19 P4/L3/D18 P4/L3/D17 P4/L3/D16 SYMBOL DESCRIPTION MAKE 1. DO NOT SCALE THIS DRAWING.
BLOCK-30 ELECTRICAL W/P W/P
ROOM TYPE-1
S S S S S S
W/P W/P W/P W/P W/P W/P
S S H W/P W/P
LOOP-3
OUT S S S S S S S S S S S S S S S 4 LOOP ADDRESSABLE FIRE ALARM CONTROL 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
P4/L3/D01 P4/L3/D02 P4/L3/D03 P4/L3/D04 P4/L3/D05 P4/L3/D06 P4/L3/D07 P4/L3/D08 P4/L3/D09 P4/L3/D10 P4/L3/D11 P4/L3/D12 P4/L3/D13 P4/L3/D14 P4/L3/D15 FACP CONTEXTPLUS UNLESS OTHERWISE NOTED.
P1/L2/D31 P1/L2/D32 P1/L2/D33 P1/L2/D34 P1/L2/D35 P1/L2/D36 P1/L2/D37 P1/L2/D38 P1/L2/D39 P1/L2/D40 P1/L2/D41 P1/L2/D42 P1/L2/D43 P1/L2/D44 P1/L2/D45 PANEL
LOOP-2 IN
CONNECTED TO
W/P W/P BLOCK-2 W/P W/P
W/P W/P W/P W/P W/P W/P W/P W/P DB NEARBY
LOOP-2 IN
S S S S S S S S S S S S S S S S S SM ADDRESSABLE SMOKE DETECTOR WITH STANDARD 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
P4/L2/D31 P4/L2/D32 P4/L2/D33 P4/L2/D34 P4/L2/D35 P4/L2/D36 P4/L2/D37 P4/L2/D38 P4/L2/D39 P4/L2/D40 P4/L2/D41 PSU S CONTEXTPLUS
P1/L2/D30 P1/L2/D29 P1/L2/D28 P1/L2/D27 P1/L2/D26 P1/L2/D25 P1/L2/D24 P1/L2/D23 P1/L2/D22 P1/L2/D21 P1/L2/D20 P1/L2/D19 P1/L2/D18 P1/L2/D17 P1/L2/D16
W/P W/P W/P W/P
BASE RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
LOOP-2 OUT S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S ADDRESSABLE SMOKE DETECTOR WITH SOUNDER MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
LOOP-2 OUT
P1/L2/D01 P1/L2/D02 P1/L2/D03 P1/L2/D04 P1/L2/D05 P1/L2/D06 P1/L2/D07 P1/L2/D08 P1/L2/D09 P1/L2/D10 P1/L2/D11 P1/L2/D12 P1/L2/D13 P1/L2/D14 P1/L2/D15
W/P W/P
P4/L2/D30 P4/L2/D29 P4/L2/D28 P4/L2/D27 P4/L2/D26 P4/L2/D25 P4/L2/D24 P4/L2/D23 P4/L2/D22 P4/L2/D21 P4/L2/D20 P4/L2/D19 P4/L2/D18 P4/L2/D17 P4/L2/D16 W/P W/P S BASE CONTEXTPLUS ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
BLOCK-4 WORKERS ACCOMMODATION TYPE-1 CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
S H H S S S S S S S S S S S S S S S ADDRESSABLE SMOKE DETECTOR WITH STANDARD
BLOCK-30 ELECTRICAL
W/P W/P W/P W/P
S CONTEXTPLUS
ROOM TYPE-1 P1/L1/D47 P1/L1/D46 P1/L1/D45
BLOCK-5
P4/L2/D01 P4/L2/D02 P4/L2/D03 P4/L2/D04 P4/L2/D05 P4/L2/D06 P4/L2/D07 P4/L2/D08 P4/L2/D09 P4/L2/D11 P4/L2/D10 P4/L2/D12 P4/L2/D13 P4/L2/D14 P4/L2/D15
RI BASE & REMOTE INDICATOR ABOVE VOID
WORKERS TOILET W/P W/P
W/P W/P W/P W/P W/P W/P W/P W/P W/P W/P W/P W/P W/P W/P W/P W/P W/P
S S S S S S H H S S S S
LOOP-1 IN
LOOP-1 IN
P1/L1/D30 P1/L1/D31 P1/L1/D32 P1/L1/D33 P1/L1/D34 P1/L1/D35 P1/L1/D36 P1/L1/D37 P1/L1/D38 P1/L1/D39 P1/L1/D40 P1/L1/D41 P1/L1/D42 P1/L1/D43 P1/L1/D44 H ADDRESSABLE HEAT DETECTOR WITH STANDARD BASE CONTEXTPLUS
P4/L1/D31 P4/L1/D32 P4/L1/D33 P4/L1/D34 P4/L1/D35 P4/L1/D36 P4/L1/D37 P4/L1/D38 P4/L1/D39 P4/L1/D40 P4/L1/D41 P4/L1/D42
W/P W/P
S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S
P1/L1/D29 P1/L1/D28 P1/L1/D27 P1/L1/D26 P1/L1/D25 P1/L1/D24 P1/L1/D23 P1/L1/D22 P1/L1/D21 P1/L1/D20 P1/L1/D19 P1/L1/D18 P1/L1/D17 P1/L1/D16 P4/L1/D30 P4/L1/D29 P4/L1/D28 P4/L1/D27 P4/L1/D26 P4/L1/D25 P4/L1/D24 P4/L1/D23 P4/L1/D22 P4/L1/D21 P4/L1/D20 P4/L1/D19 P4/L1/D18 P4/L1/D17 P4/L1/D16 W/P W/P
ADDRESSABLE MANUAL CALL POINT CONTEXTPLUS
LOOP-1 OUT
CONTEXTPLUS P1/L1/D01 P1/L1/D02 P1/L1/D03 P1/L1/D04 P1/L1/D05 P1/L1/D06 P1/L1/D07 P1/L1/D08 P1/L1/D09 P1/L1/D10 P1/L1/D11 P1/L1/D12 P1/L1/D13 P1/L1/D14 P1/L1/D15 CONTEXTPLUS
P4/L1/D01 P4/L1/D02 P4/L1/D03 P4/L1/D04 P4/L1/D05 P4/L1/D06 P4/L1/D07 P4/L1/D08 P4/L1/D09 P4/L1/D10 P4/L1/D11 P4/L1/D12 P4/L1/D13 P4/L1/D14 P4/L1/D15
POWER SUPPLY POWER SUPPLY
LOOP-04
LOOP-04
IN
IN
-VE & + VE -VE & + VE
LOOP-04
LOOP-04
OUT
OUT
DISPLAY DISPLAY
BLOCK-1,2 & 30
LOOP-03
LOOP-03
W/P W/P
MRJ
IN
IN
04 FOR APPROVAL 09.08.2023 KKI
MUTE BUZZER FIRE MUTE BUZZER FIRE
LOOP-03
OUT
OUT
SILENCE FAULT SILENCE FAULT
CONTEXTPLUS
LOOP-02
LOOP-02
ADDRESSABLE FIRE ALARM SOUNDER
IN
IN
EVACUATION POWER SUPPLY FAULT EVACUATION POWER SUPPLY FAULT
LOOP-02
LOOP-02
OUT
OUT
LOOP-01
LOOP-01
FUSE
FUSE
IN
IN
LOOP 1 LOOP 1
LOOP-01
LOOP-01
OUT
OUT
03 FOR APPROVAL 07.08.2023 KKI MRJ
NETWORKING NETWORKING
CIRCUIT-01
CIRCUIT-01
SOUNDER
SOUNDER
EARTH EARTH
W/P
NETWORKING CABLE
OUTPUT
OUTPUT
FIRE
FIRE
W/P
FIRE ALARM SOUNDER FLASHER WEATHER
OUTPUT
OUTPUT
FAULT
FAULT
LOOP CARD LOOP CARD
CONTEXTPLUS
LOOP 1 LOOP 1
BUZZER
_ _
BUZZER
_ _
PROOF 02 FOR APPROVAL 28.07.2023 KKI MRJ
+ + + +
H TOILET
H IFU IFU S SOUNDER MODULE CONTEXTPLUS DRAWN CHKD
LOOP-4 IN P5/L4/D61 P5/L4/D62 P5/L4/D63 P5/L4/D64 P5/L4/D65 P5/L4/D67 P5/L4/D68 P5/L4/D69 SM REV. NO. DESCRIPTION DATE
P2/L4/D47 P2/L4/D46
BLOCK-30 ELECTRICAL
CLIENT:
NETWORKING CABLE
ROOM TYPE-1 W/P W/P W/P W/P W/P W/P W/P W/P W/P
S S S S S S
W/P W/P W/P W/P W/P W/P
S H H S
P5/L4/D60 P5/L4/D59 P5/L4/D58 P5/L4/D57 P5/L4/D56 P5/L4/D55 P5/L4/D54 P5/L4/D53 P5/L4/D52 P5/L4/D46
LOOP-4 IN
P2/L4/D31 P2/L4/D32 P2/L4/D33 P2/L4/D34 P2/L4/D35 P2/L4/D36 P2/L4/D37 P2/L4/D38 P2/L4/D39 P2/L4/D40 P2/L4/D41 P2/L4/D42 P2/L4/D43 P2/L4/D44 P2/L4/D45
W/P W/P
NETWORKING CABLE
LOOP-3 IN
BLOCK-30 ELECTRICAL
ROOM TYPE-1 PSU P5/L3/D32 P5/L3/D33 P5/L3/D34 P5/L3/D35 P5/L3/D36 P5/L3/D37 P5/L3/D38 P5/L3/D39 P5/L3/D40 P5/L3/D41 P5/L3/D42 P5/L3/D43 P5/L3/D44 P5/L3/D45 P5/L3/D46
P2/L3/D30 P2/L3/D31 P2/L3/D32 P2/L3/D33 P2/L3/D34 P2/L3/D35 P2/L3/D36 P2/L3/D37 P2/L3/D38 P2/L3/D39 P2/L3/D40 P2/L3/D41 P2/L3/D42 P2/L3/D43 P2/L3/D44 CONNECTED TO
DB NEARBY W/P W/P
S S S S S S S S S S S S S S S W/P W/P H H H H H H H H H H S S S S S
P5/L3/D31 P5/L3/D30 P5/L3/D29 P5/L3/D28 P5/L3/D27 P5/L3/D26 P5/L3/D25 P5/L3/D24 P5/L3/D23 P5/L3/D22 P5/L3/D21 P5/L3/D20 P5/L3/D19 P5/L3/D18 P5/L3/D17
P2/L3/D29 P2/L3/D28 P2/L3/D27 P2/L3/D26 P2/L3/D25 P2/L3/D24 P2/L3/D23 P2/L3/D22 P2/L3/D21 P2/L3/D20 P2/L3/D19 P2/L3/D18 P2/L3/D17 P2/L3/D16 SM PSU
LOOP-3 OUT
W/P
W/P W/P
P5/L3/D16
S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S
P5/L3/D01 P5/L3/D02 P5/L3/D03 P5/L3/D04 P5/L3/D05 P5/L3/D06 P5/L3/D07 P5/L3/D08 P5/L3/D09 P5/L3/D10 P5/L3/D11 P5/L3/D12 P5/L3/D13 P5/L3/D14 P5/L3/D15 W/P
P2/L3/D01 P2/L3/D02 P2/L3/D03 P2/L3/D04 P2/L3/D05 P2/L3/D06 P2/L3/D07 P2/L3/D08 P2/L3/D09 P2/L3/D10 P2/L3/D11 P2/L3/D12 P2/L3/D13 P2/L3/D14 P2/L3/D15 W/P W/P
BLOCK-4 WORKERS ACCOMMODATION TYPE-1 W/P W/P W/P W/P W/P W/P W/P
H H W/P W/P
BLOCK- 23, 30 & 32 W/P
FIRE CONTRACTOR
P5/L2/D82 P5/L2/D81 P5/L2/D80 P5/L2/D79 P5/L2/D78 P5/L2/D77 P5/L2/D76
BLOCK-4 WORKERS ACCOMMODATION TYPE-1 P2/L2/D47 P2/L2/D46
BLOCK-5 WORKERS TOILET
W/P W/P W/P W/P
W/P W/P W/P W/P W/P W/P
S S S S S S S S S S S S
S S S S S S S H H W/P W/P
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
LOOP-2 IN
P5/L2/D61 P5/L2/D62 P5/L2/D63 P5/L2/D64 P5/L2/D65 P5/L2/D66 P5/L2/D67 P5/L2/D68 P5/L2/D69 P5/L2/D70 P5/L2/D71 P5/L2/D72 P5/L2/D73 P5/L2/D74 P5/L2/D75
P2/L2/D31 P2/L2/D32 P2/L2/D33 P2/L2/D34 P2/L2/D35 P2/L2/D36 P2/L2/D37 P2/L2/D38 P2/L2/D39 P2/L2/D40 P2/L2/D41 P2/L2/D42 P2/L2/D43 P2/L2/D44 P2/L2/D45
W/P
W/P W/P
S S S S S S S S S S H H H H H P.O. Box: 91962, Mussafah 14, Abu Dhabi
S S S S S S S S S S S S S S S
P2/L2/D30 P2/L2/D29 P2/L2/D28 P2/L2/D27 P2/L2/D26 P2/L2/D25 P2/L2/D24 P2/L2/D23 P2/L2/D22 P2/L2/D21 P2/L2/D20 P2/L2/D19 P2/L2/D18 P2/L2/D17 P2/L2/D16 W/P W/P
P5/L2/D60 P5/L2/D59 P5/L2/D58 P5/L2/D57 P5/L2/D56 P5/L2/D55 P5/L2/D54 P5/L2/D53 P5/L2/D52 P5/L2/D51 P5/L2/D50 P5/L2/D49 P5/L2/D48 P5/L2/D47 P5/L2/D46
T: +971 25535167, F: +971 25535159
LOOP-2 OUT
LOOP-2 IN
S S S S S S S S S S H H H H H E-mail: speedfse@eim.ae, www.speedsafetyuae.com
S S S S S S S S S S S S S S S W/P W/P P5/L2/D31 P5/L2/D32 P5/L2/D33 P5/L2/D34 P5/L2/D35 P5/L2/D36 P5/L2/D37 P5/L2/D38 P5/L2/D39 P5/L2/D40 P5/L2/D41 P5/L2/D42 P5/L2/D43 P5/L2/D44 P5/L2/D45
P2/L2/D01 P2/L2/D02 P2/L2/D03 P2/L2/D04 P2/L2/D05 P2/L2/D06 P2/L2/D07 P2/L2/D08 P2/L2/D09 P2/L2/D10 P2/L2/D11 P2/L2/D12 P2/L2/D13 P2/L2/D14 P2/L2/D15
BLOCK-5 WORKERS TOILET
W/P W/P W/P W/P W/P W/P
S S S S S S S S S S S S S S S PROJECT NAME
S S S S S S H H H H W/P W/P
LOOP-1 IN
P5/L2/D30 P5/L2/D29 P5/L2/D28 P5/L2/D27 P5/L2/D26 P5/L2/D25 P5/L2/D24 P5/L2/D23 P5/L2/D22 P5/L2/D21 P5/L2/D20 P5/L2/D19 P5/L2/D18 P5/L2/D17 P5/L2/D16
LOOP-1 IN
S S S S S S S S S S S S S S S
ZONE :
LOOP-1 OUT
P5/L1/D31 P5/L1/D32 P5/L1/D33 P5/L1/D34 P5/L1/D35 P5/L1/D36 P5/L1/D37 P5/L1/D38 P5/L1/D39 P5/L1/D40
MADINAT ZAYED
CONTEXTPLUS
POWER SUPPLY
P2/L1/D01 P2/L1/D02 P2/L1/D03 P2/L1/D04 P2/L1/D05 P2/L1/D06 P2/L1/D07 P2/L1/D08 P2/L1/D09 P2/L1/D10 P2/L1/D11 P2/L1/D12 P2/L1/D13 P2/L1/D14 P2/L1/D15
LOOP-04
IN
-VE & + VE
LOOP-04
OUT
DISPLAY
LOOP-03
S S S S S S S S S S S S S S S
IN
SILENCE FAULT
LOOP-02
IN
P5/L1/D30 P5/L1/D29 P5/L1/D28 P5/L1/D27 P5/L1/D26 P5/L1/D25 P5/L1/D24 P5/L1/D23 P5/L1/D22 P5/L1/D21 P5/L1/D20 P5/L1/D19 P5/L1/D18 P5/L1/D17 P5/L1/D16
IN
LOOP 1
LOOP-01
OUT
NETWORKING
CIRCUIT-01
SOUNDER
SECTOR NO : PLOT NO :
EARTH
OUTPUT
FIRE
S S S S S S S S S S S S S S S
OUTPUT
FAULT
LOOP CARD
LOOP 1
HABSHAN T1019
LOOP-1 OUT
BUZZER
CONTEXTPLUS
+
_
+
_ POWER SUPPLY
P5/L1/D01 P5/L1/D02 P5/L1/D03 P5/L1/D04 P5/L1/D05 P5/L1/D06 P5/L1/D07 P5/L1/D08 P5/L1/D09 P5/L1/D10 P5/L1/D11 P5/L1/D12 P5/L1/D13 P5/L1/D14 P5/L1/D15
LOOP-04
IN
-VE & + VE
LOOP-04
OUT
SILENCE FAULT
LOOP-02
PROJECT DESCRIPTION :
IN
IN
LOOP 1
LOOP-01
OUT
NETWORKING
CIRCUIT-01
SOUNDER
EARTH
OUTPUT
BUZZER
_ _
+ +
BLOCK-6,16,17,30,33 & 34
W/P W/P W/P W/P W/P
LOOP-4 IN
FIRE ALARM PANEL -5
P3/L4/D21 P3/L4/D20 P3/L4/D19 P3/L4/D18 P3/L4/D16 DRAWING TITLE :
LOCATION: BLOCK-6 GUARD ROOM
LOOP-4 OUT W/P W/P W/P
S S S S S H H H S S H S
P3/L4/D01 P3/L4/D02 P3/L4/D03 P3/L4/D04 P3/L4/D05 P3/L4/D06 P3/L4/D07 P3/L4/D08 P3/L4/D09 P3/L4/D10 P3/L4/D11 P3/L4/D12 P3/L4/D13 P3/L4/D14 P3/L4/D15
W/P W/P
BLOCK-9,11,12,15,16,31 & 32
W/P W/P W/P W/P W/P W/P
BLOCK- 6,20,21,22 & 30
FIRE ALARM SYSTEM
P3/L3/D60 P3/L3/D61 P3/L3/D62 P3/L3/D63 P3/L3/D64 P3/L3/D65 P3/L3/D66 P3/L3/D67 P3/L3/D68 P3/L3/D69 P3/L3/D70 P3/L3/D71 P3/L3/D72 W/P W/P W/P W/P W/P W/P W/P W/P W/P W/P W/P W/P
SCHEMATIC LAYOUT
W/P W/P W/P W/P S S S ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
NETWORKING CABLE
S S S S S S S S H P6/L2/D01 P6/L2/D02 P6/L2/D03 P6/L2/D04 P6/L2/D05 P6/L2/D06 P6/L2/D07 P6/L2/D08 P6/L2/D09 P6/L2/D10 P6/L2/D11 P6/L2/D12 P6/L2/D13 P6/L2/D14 P6/L2/D15
LOOP-3IN
P3/L3/D59 P3/L3/D58 P3/L3/D57 P3/L3/D56 P3/L3/D55 P3/L3/D54 P3/L3/D53 P3/L3/D52 P3/L3/D51 P3/L3/D50 P3/L3/D49 P3/L3/D48 P3/L3/D46
W/P W/P W/P W/P W/P
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
S H S S S S S S S S H S S S SFS/RS/BHS/FA-12 04
SPARE
P6/L1/D31 P6/L1/D32 P6/L1/D33 P6/L1/D34 P6/L1/D35 2. Any architectural changes like addition, deletion, modification during construction or in future
LOOP
RI RI RI RI RI
NETWORKING CABLE
P3/L3/D30 P3/L3/D31 P3/L3/D32 P3/L3/D33 P3/L3/D34 P3/L3/D35 P3/L3/D36 P3/L3/D37 P3/L3/D38 P3/L3/D39 P3/L3/D40 P3/L3/D41 P3/L3/D42 P3/L3/D43 P3/L3/D44
shall be submitted to ADCD for both architectural and shop approvals.
H H S S S S S S S 3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
S S S S S S S S S S S H H H H P6/L1/D30 P6/L1/D29 P6/L1/D28 P6/L1/D27 P6/L1/D26 P6/L1/D25 P6/L1/D24 P6/L1/D23 P6/L1/D22 P6/L1/D21 P6/L1/D20 P6/L1/D19 P6/L1/D18 P6/L1/D17 P6/L1/D16
P3/L3/D29 P3/L3/D28 P3/L3/D27 P3/L3/D26 P3/L3/D25 P3/L3/D24 P3/L3/D23 P3/L3/D22 P3/L3/D21 P3/L3/D20 P3/L3/D19 P3/L3/D18 P3/L3/D17 P3/L3/D16
W/P W/P
installed as per approved Shop drawing. 09.08.2023 1:75
LOOP-3 OUT
S S S S S S S S S S S S S S S 4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
S S S S S S S S S S S S S S S CONTEXTPLUS P6/L1/D01 P6/L1/D02 P6/L1/D03 P6/L1/D04 P6/L1/D05 P6/L1/D06 P6/L1/D07 P6/L1/D08 P6/L1/D09 P6/L1/D10 P6/L1/D11 P6/L1/D12 P6/L1/D13 P6/L1/D14 P6/L1/D15 Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
W/P W/P
Approval Department.
POWER SUPPLY
LOOP-04
IN
-VE & + VE
P3/L3/D01 P3/L3/D02 P3/L3/D03 P3/L3/D04 P3/L3/D05 P3/L3/D06 P3/L3/D07 P3/L3/D08 P3/L3/D09 P3/L3/D10 P3/L3/D11 P3/L3/D12 P3/L3/D13 P3/L3/D14 P3/L3/D15
LOOP-04
OUT
A1
DISPLAY
B3N-2022-000555-CD-SHD-02
LOOP-03
IN
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA
OUT
SILENCE FAULT
LOOP-02
IN
W/P
LOOP-02
OUT
IN
10)
LOOP-01
LOOP-2 IN
RI RI
OUT
NETWORKING
DRAWN BY : CHECKED BY :
CIRCUIT-01
SOUNDER
EARTH
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and
FIRE
OUTPUT
FAULT
LOOP CARD
KKI MRJ
LOOP 1
W/P W/P
W/P W/P W/P W/P W/P BUZZER
NFPA 101)
_ _
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
+ +
W/P W/P
11. All fire door and windows shall be according to (NFPA 80).
S S S S S S S S S S S S S S S
P3/L2/D01 P3/L2/D02 P3/L2/D03 P3/L2/D04 P3/L2/D05 P3/L2/D06 P3/L2/D07 P3/L2/D08 P3/L2/D09 P3/L2/D10 P3/L2/D11 P3/L2/D12 P3/L2/D13 P3/L2/D14 P3/L2/D15 12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
W/P W/P
BLOCK-5 WORKERS TOILET (and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
H H H
P3/L1/D48 P3/L1/D47 P3/L1/D46
W/P W/P PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
W/P W/P W/P W/P W/P W/P W/P
S S S S S S SM H 14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME:
LOOP-1 IN
P3/L1/D31 P3/L1/D32 P3/L1/D33 P3/L1/D34 P3/L1/D35 P3/L1/D36 P3/L1/D37 P3/L1/D38 P3/L1/D39 P3/L1/D40 P3/L1/D41 P3/L1/D42 P3/L1/D43 P3/L1/D44 P3/L1/D45
PSU Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
CONNECTED TO
S S S S S S S S S S S S S S S standards.
P3/L1/D30 P3/L1/D29 P3/L1/D28 P3/L1/D27 P3/L1/D26 P3/L1/D25 P3/L1/D24 P3/L1/D23 P3/L1/D22 P3/L1/D21 P3/L1/D20 P3/L1/D19 P3/L1/D18 P3/L1/D17 P3/L1/D16
DB NEARBY
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
S S S S S S S S S S S S S S S STAMP: STAMP:
NFPA-14 SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
LOOP-1 OUT
CONTEXTPLUS
P3/L1/D01 P3/L1/D02 P3/L1/D03 P3/L1/D04 P3/L1/D05 P3/L1/D06 P3/L1/D07 P3/L1/D08 P3/L1/D09 P3/L1/D10 P3/L1/D11 P3/L1/D12 P3/L1/D13 P3/L1/D14 P3/L1/D15
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
POWER SUPPLY
LOOP-04
IN
-VE & + VE
LOOP-04
OUT
DISPLAY
LOOP-03
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
OUT
STAMP:
SILENCE FAULT
LOOP-02
IN
NFPA-20
LOOP-02
OUT
IN
LOOP 1
LOOP-01
OUT
NETWORKING
CIRCUIT-01
SOUNDER
EARTH
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
OUTPUT
FIRE
NETWORKING CABLE
OUTPUT
FAULT
LOOP CARD
LOOP 1
under construction.
NFPA-72
BUZZER
BATTERY 12V
_ +
BATTERY 12V
_
20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
FIRE ALARM PANEL -3 21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
LOCATION: BLOCK-8 CAMP OFFICE
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
1 2
B SHOWER-1 SHOWER-2 SHOWER-3 SHOWER-4 SHOWER-5 SHOWER-6 SHOWER-7 SHOWER-8 SHOWER-9
N
HAND HAND 1 2 W N
S
E
EXIT
EXIT
610
E E
4000
2500
BU-800 HIGH
PRESSURE WI
E
900
CONNECTED TO GENERAL NOTES :
HAND HAND DB NEARBY
WASH WASH 1. DO NOT SCALE THIS DRAWING.
TOILET-3 TOILET-9
B 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
TOILET-1 TOILET-2 TOILET-4 TOILET-5 TOILET-6 TOILET-7 TOILET-8
SHELTER UNLESS OTHERWISE NOTED.
A 3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
BLOCK-6 GUARD ROOM RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
NUMBER OF BLOCKS: 04 LEGEND:-
14000 MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
SYMBOL DESCRIPTION MAKE ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
E 3W, EMERGENCY LIGHT SURFACE MOUNTED DENKO/
BLOCK-5 WORKERS TOILET NON-MOUNTED TYPE SECURE/
NUMBER OF BLOCKS: 18 EXIT
1W, EXIT LIGHT WALL MOUNTED - DOWN ARROW FONUX
TYPE, NON-MONITORED
1700
10000 ROBT STONE (ME)LLC
2400 7000 2400 P.O. Box. 39588
SHELTER Abu Dhabi, U.A.E
3600
1 2 3 E E
CONSULTANT :
1700
CONNECTED TO
DB NEARBY
A
EXIT
7200
STORE
1000
3600
1024
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
@ BUHASA
5000
EXIT
ZONE :
B MADINAT ZAYED
SECTOR NO : PLOT NO :
DRAWING TITLE :
10)
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
CAMP OFFICE 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
C 8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
FOR CIVIL DEFENSE APPROVAL :
NUMBER OF BLOCKS: 01 this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
16400
1 2 1 2
14400 N
W N E
EXIT-4 EXIT-3 S
SHELTER
SHELTER A
A ASPHALT ROAD TO BUHASA
3000
2400
2400
BU-800 HIGH
PRESSURE WI
5700
3525 3525 GENERAL NOTES :
E E E E
1. DO NOT SCALE THIS DRAWING.
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
UNLESS OTHERWISE NOTED.
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
LEGEND:- RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
SYMBOL DESCRIPTION MAKE ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
B
12200
6000
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
E 3W, EMERGENCY LIGHT SURFACE MOUNTED
12000
DENKO/
7000
7000
NON-MOUNTED TYPE SECURE/
EXIT
1W, EXIT LIGHT WALL MOUNTED - DOWN ARROW FONUX
TYPE, NON-MONITORED
SHADED AREA
6500
E E 04 FOR APPROVAL 09.08.2023 KKI MRJ
03 FOR APPROVAL 07.08.2023 KKI MRJ
CONNECTED TO KKI MRJ
02 FOR APPROVAL 28.07.2023
E E DB NEARBY
01 FOR APPROVAL 24.07.2023 KKI MRJ
3000
00 FOR APPROVAL 28.03.2023 KKI MRJ
2400
2400
CONNECTED TO
EXIT EXIT
DB NEARBY C
B ROBT STONE (ME)LLC
P.O. Box. 39588
EXIT-1 EXIT-2 SLOPE 8% Abu Dhabi, U.A.E
SHELTER
SHELTER SHELTER BLOCK-10 MOSQUE
NUMBER OF BLOCKS: 01
BLOCK-9 STAFF GYM & RECREATION CONSULTANT :
NUMBER OF BLOCKS: 01
39900
1200
SHELTER
SHELTER
P.O. Box: 91962, Mussafah 14, Abu Dhabi
A
GARBAGE T: +971 25535167, F: +971 25535159
EXIT
C1/D04 ROOM E-mail: speedfse@eim.ae, www.speedsafetyuae.com
C1/D05 SALAD ROOM
2650
RECEIVING AREA
(INSULATED COLD CONTAINED)
2100
E PROJECT NAME
PROTEIN FREEZER
4000
4007
LEGEND:-
772
C1/D03
VEG FREEZER
B
SYMBOL DESCRIPTION MAKE
EXIT PRE WASH AREA
@ BUHASA
PACKING ROOM
CHAPATTI ROOM
C1/D02
C1/D09 C1/D13
C1/D15 C1/D17
CMP
CENTRAL MONITORING CONTROL PANEL EML
3150
E VEGETABLE ROOM E ZONE :
3700
4150
4150
C 1W, EXIT LIGHT HANGING MOUNTED MOUNTED -
CMP EXIT EML
SIDE ARROW TYPE PROJECT DESCRIPTION :
PVC CURTAIN
C1/D10
C1/D08
MEAT ROOM
EXIT
7198
7198
LABOUR CAMP @ BUHASA
3200
EXIT
C1/D07 4000
FD 60
E
8000
HOT KITCHEN
DRAWING TITLE :
SHADED
RECEIVING OFFICE
D C1/D74 C1/D16
20000
FD 60
3850
STAFF ENTRANCE E E
EXIT
EXIT
C1/D44
1200
EMERGENCY LIGHTING SYSTEM
1200
C1/D75
DEFROST CHILLER
FISH DE-CHILLER
CHICKEN ROOM
EGG CHILLER
DAIRY CHILLER
C1/D12
SHELTER
C1/D73 C1/D11
E E WASHROOM POT POT STORE
FOR BLOCK: 9,10,& 15
800 TO BLOCK-14 ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
5200
E C1/D14
TOILET E 1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
LOCKERS
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/EL-02 04
2700
C1/D72
PVC CURTAIN
1500 shall be submitted to ADCD for both architectural and shop approvals.
TOILET SUBMISSION DATE : SCALE :
E FISH ROOM 3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
installed as per approved Shop drawing. 09.08.2023 1:50
6601
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
E C1/D46
5792
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
2993
E
2950
Approval Department.
GARBAGE ROOM
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
LOW HEIGHT POT WASH AREA
10)
1500
C1/D70 C1/D69 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
3525
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
1200
7002 7000 1898 C1/D66 C1/D47 CHEMICAL STORAGE DETAILS by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
DISPOSABLE DRY STORE 7000 3147 CHEMICAL STORAGE FROM BLOCK-14 8. All portions of these building shall be fully protected by automatic sprinklers system according to
C1/D71 E EXIT
EXIT
STORE
FD 60
1500
C1/D67
C1/D48 2. ALL PURPOSE CLEANER 10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
EXIT in this building in accordance to the relevant NFPA code and standards.
EXIT
3. FLOOR CLEANER ETC.. 11. All fire door and windows shall be according to (NFPA 80).
F 1200
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
1200 (and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
SHELTER
BLOCK-15 GENERAL KITCHEN PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
NUMBER OF BLOCKS: 01 this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
2000
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
E FROM AND TO
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
C1/D43
BLOCK-13
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
45150 KEY PLAN :
11700 5255 1736 8114 13196 2600
1 2500
2 3 4 5 6 7 2500
8
SHELTER
SHELTER
1 1
1500
2 2 N
3 3 W N
S
E
A
1500
DISH WASH ROOM
COLLECTION AREA
HAND WASH AREA C1/D22 HAND WASH AREA
WATER DRINKING
3634
SHADED AREA COOLER E SHADED AREA LEGEND:- ASPHALT ROAD TO BUHASA
C1/D25
SYMBOL DESCRIPTION MAKE
EXIT
BU-800 HIGH
PRESSURE WI
B CMP
CENTRAL MONITORING CONTROL PANEL EML
EXIT EXIT
C1/D18 C1/D28 E 3W, EMERGENCY LIGHT SURFACE MOUNTED
EML
MOUNTED TYPE GENERAL NOTES :
2650
FROM BLOCK-15 1W, EXIT LIGHT WALL MOUNTED MOUNTED - DOWN
2478 7995 8000 8000 8000 8000 2473 EXIT EML 1. DO NOT SCALE THIS DRAWING.
ARROW TYPE
C1/D24 C1/D26 C1/D27 1W, EXIT LIGHT HANGING MOUNTED MOUNTED - 2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
E C1/D19 E C1/D20 E C1/D21 E E E EXIT EML UNLESS OTHERWISE NOTED.
SIDE ARROW TYPE
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
9442
E E E E E E CONSULTANT :
2636
C1/D42
TO BLOCK-15 C1/D41
EXIT EXIT
C 3
2
SHELTER
2
1200 1 SHELTER BLOCK-14 WORKERS DINNING HALL 1 1200
FIRE CONTRACTOR
NUMBER OF BLOCKS: 01
1600 1600
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
P.O. Box: 91962, Mussafah 14, Abu Dhabi
1 1200 2 T: +971 25535167, F: +971 25535159
10800 E-mail: speedfse@eim.ae, www.speedsafetyuae.com
EXIT-3
PROJECT NAME
1200
1 14400 2 SHELTER
1200 1200 TEMPORARY CAMP ACCOMMODATION
SHELTER
A @ BUHASA
EXIT
SHELTER
STORE
1200
1200
2000
SHELTER
1950 LEGEND:- ZONE :
A E MADINAT ZAYED
SYMBOL DESCRIPTION MAKE
1150
EXIT
WORKERS
2000
2400
E WASHING AREA 1W, EXIT LIGHT WALL MOUNTED - DOWN ARROW FONUX
EXIT
TYPE, NON-MONITORED PROJECT DESCRIPTION :
SHELTER
DRAWING TITLE :
IRON PRESSING
EMERGENCY LIGHTING SYSTEM
12000
1250
FOR BLOCK:11,12 &14
E ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
12000
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
7000
7000
drawings.
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/EL-03 04
shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
LINE SORTING
installed as per approved Shop drawing. 09.08.2023 1:100
4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
5000 10)
DRAWN BY : CHECKED BY :
E 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and
NFPA 101) KKI MRJ
CONNECTED TO 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
DB NEARBY
E E by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
CONNECTED TO 8. All portions of these building shall be fully protected by automatic sprinklers system according to
DB NEARBY EXIT (NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
2400
2400
B 10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
SHELTER in this building in accordance to the relevant NFPA code and standards.
1200
BLOCK-12 LAUNDRY 11. All fire door and windows shall be according to (NFPA 80).
EXIT EXIT NUMBER OF BLOCKS: 01 12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
B
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
2000
2000
NUMBER OF BLOCKS: 01 18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
FROM AND TO
BLOCK-15
C N
W N E
3500
3500
SHELTER
SHELTER
3000
14250
MOBILE COUNTER C1/D24
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
7500
6250
C1/D33 C1/D35
E SHELF SHELF E SHELF RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
18000
4000 8000 4000 OFFICE MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
4000
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
2150 6500 6500 6500 2150
EXIT
C1/D54 C1/D55
SHELF SHELF SHELF C1/D25
C1/D65 C1/D64
12200
E E E E
EXIT
6000
C1/D32
B
SALOON
SHELTER
SHELTER
1500
3150
EXIT
EXIT-2
C1/D63 1800 C1/D26
C1/D56
3500 FOR APPROVAL 09.08.2023 KKI MRJ
CHILLER
EXIT C1/D30 C1/D29 E 04
5950
B E E 03 FOR APPROVAL 07.08.2023 KKI MRJ
COLLECTION AREA
HAND WASH ROOM DISH WASH ROOM SHELF SHELF SHELF SHELF
02 FOR APPROVAL 28.07.2023 KKI MRJ
ENTRANCE 2250 6000 2250
SHELTER
STORE
3500
01 FOR APPROVAL 24.07.2023 KKI MRJ
EXIT
3000
C1/D57 C1/D58 C1/D61 C1/D62 C1/D31 C1/D28
3750
4000 1500
E E E E MRJ
EXIT
E 00 FOR APPROVAL 28.03.2023 KKI
C1/D27
1346
WC WC C1/D59
COLD&FOOD ITEMS CLOTHES CLOTHES WALL SHELF WALL SHELF
CLIENT:
EXIT A
A 16150 5450
21600 ROBT STONE (ME)LLC
1 2 3 EXIT -1 4 5
2 P.O. Box. 39588
SHELTER 3 1 Abu Dhabi, U.A.E
2650 5500 5200 10650
24000
BLOCK-19 SUPER MARKET CONSULTANT :
BLOCK-13 STAFF DINNING HALL NUMBER OF BLOCKS: 01
NUMBER OF BLOCKS: 01
1 2 3 4 TO BLOCK-19 5 6
30000
1400 1400 1400 1400 1400 2500 5000 1500 7500 6500
FIRE CONTRACTOR
1200
SHELTER
A
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
WC WC WC WC WC PANTRY STORE ROOM EXIT DOCUMENT CONTROL ROOM QA/QC ROOM P.O. Box: 91962, Mussafah 14, Abu Dhabi
LEGEND:-
T: +971 25535167, F: +971 25535159
1943
1943
2350
C1/D17
2550
4000
1200 2450
E C1/D15
E E CMP
CENTRAL MONITORING CONTROL PANEL EML PROJECT NAME
C1/D18
3W, EMERGENCY LIGHT SURFACE MOUNTED
HAND WASH AREA
E
MOUNTED TYPE
EML TEMPORARY CAMP ACCOMMODATION
@ BUHASA
2450
3430
E C1/D14
1W, EXIT LIGHT WALL MOUNTED MOUNTED - DOWN
EML
1207
EXIT
SERVER ROOM ARROW TYPE
SHELTER ZONE :
1642
C1/D13
EXIT C1/D19 C1/D20
C1/D21
SECTOR NO : PLOT NO :
E E E
C1/D12
C1/D11 HABSHAN T1019
EXIT
PRINTER
PROJECT DESCRIPTION :
C1/D10
2000
C1/D09
20000
MANAGER OFFICE-6
E
7000
drawings.
C1/D07 E E E 2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/EL-04 04
EXIT
DRAWN BY : CHECKED BY :
1890
E 6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and
C1/D01
NFPA 101) KKI MRJ
2100 7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
E by voice announcement system according to (NFPA 72).
2925
(NFPA 13).
C1/D02
9. Standpipe system shall be provided in these building according to (NFPA 14).
EXIT 10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
D in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
AIR LOCK
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
4050 4550 3600 3600 3600 4292 3600 2706
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
30000
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
1500
1 2
6500
3000
A W
N
N E
SHELTER
A B
1900
2800
ASPHALT ROAD TO BUHASA
2
LOCKER / STORE EXIT TOILET
3050 1 2 3 21300 4 5 ROOM BU-800 HIGH
PRESSURE WI
E
1703 1000
4300 3350 3350 10300 E E TOILET
GENERAL NOTES :
1242
1242
A
1. DO NOT SCALE THIS DRAWING.
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
UNLESS OTHERWISE NOTED.
2495
1609
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
TRF1 TRF2 RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
13000
BUS
7000
5400
2000 2000 6000 2000 ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
E E E E 1902 6000 1903 CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
QRM ROOM
TRANSFORMER ROOM CB-1 CB-2
12000
2500
EXIT
CONNECTED TO
CONNECTED TO EXIT EXIT DB NEARBY
6000
DB NEARBY
B
E 04 FOR APPROVAL 09.08.2023 KKI MRJ
1600 3400 2650 2650 7338 3662 03 FOR APPROVAL 07.08.2023 KKI MRJ
02 FOR APPROVAL 28.07.2023 KKI MRJ
2800
1607
CONNECTED TO
DB NEARBY
BLOCK-17 FIRE PUMP ROOM ROBT STONE (ME)LLC
NUMBER OF BLOCKS: 01 P.O. Box. 39588
1
Abu Dhabi, U.A.E
10000
BLOCK-24 ADNOC STAFF GYM
NUMBER OF BLOCKS: 01 CONSULTANT :
1 2
20000 FIRE CONTRACTOR
15795 3905
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
A
LOUNGE-1 LOUNGE-2 P.O. Box: 91962, Mussafah 14, Abu Dhabi
T: +971 25535167, F: +971 25535159
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
3200
3200
LEGEND:-
1 2
12000 PROJECT NAME
3900 8000 3900 1950 SYMBOL DESCRIPTION MAKE
TEMPORARY CAMP ACCOMMODATION
6400
A MADINAT ZAYED
STORE
(DRY AREA)
TOILET WASHING WASHING
DRYER MACHINE
EXIT MACHINE MACHINE SECTOR NO : PLOT NO :
LAUNDRY
B (WET AREA) HABSHAN T1019
3600
RECREATION AREA 4850 1000
14500
E E PROJECT DESCRIPTION :
1706
1705
CONNECTED TO
DB NEARBY
LABOUR CAMP @ BUHASA
EXIT IRONING
TABLE
B DRAWING TITLE :
7800
REFRESHMENT
E E
TOILET
4432 8000 4432
EMERGENCY LIGHTING SYSTEM
1900
TOILET
SHELTER FOR BLOCK:16, 17, 24, 25 & 26
3900
ABU DHABI CIVIL DEFENSE AUTHORITY GENERAL NOTES FOR SHOP DRAWING
E BLOCK-26 ADNOC STAFF LAUNDRY
NUMBER OF BLOCKS: 01
1. All the shop/executive drawings architectural layout shall be as per ADCD approved fire life safety initial architectural DRAWING NO : REVISION NO:
drawings.
TOILET
2. Any architectural changes like addition, deletion, modification during construction or in future SFS/RS/BHS/EL-05 04
EXIT EXIT shall be submitted to ADCD for both architectural and shop approvals.
3. Fire Alarm, Fire Fighting, Emergency/Exit light system and voice evacuation system and all other active systems shall be
SUBMISSION DATE : SCALE :
C 1:75
installed as per approved Shop drawing. 09.08.2023
14100 2400 3500 4. All the Materials, Systems, Assemblies, equipment, Products and Accessories, referred to in this drawing with respect to
Life Safety, Fire Safety and Emergency Services shall be Listed, Approved and Registered by the Civil Defence Material PROJECT ID : DRAWING SIZE :
Approval Department.
BLOCK-25 ADNOC STAFF RECREATION 5. All portable fire extinguishers shall be provided as per (UAE fire and life safety code and NFPA B3N-2022-000555-CD-SHD-02 A1
NUMBER OF BLOCKS: 01 10)
6. Emergency light and exit sings shall be provided according to (UAE fire and life safety code and DRAWN BY : CHECKED BY :
NFPA 101) KKI MRJ
7. All portions of these buildings and common and services areas shall be fully cover by smoke detections and fully covered
by voice announcement system according to (NFPA 72).
FOR CIVIL DEFENSE APPROVAL :
8. All portions of these building shall be fully protected by automatic sprinklers system according to
(NFPA 13).
9. Standpipe system shall be provided in these building according to (NFPA 14).
10. All special system like Clean agent, Foam, water spray, water mist, wet chemical kitchen hood systems shall be installed
in this building in accordance to the relevant NFPA code and standards.
11. All fire door and windows shall be according to (NFPA 80).
12. All types of smoke ventilation systems shall be installed in this building in accordance with (UAE fire and life safety code
(and other international codes and standards only if a requirement of these systems is not mentioned on UAEFC).
PARTY CONSULTANT MAIN CONTRACTOR APPROVED INSTTALLER 13.Fire and smoke damper or (combination of Fire and smoke damper systems) shall be installed in
this building according to UAE fire and life safety code and the relevant NFPA codes and standards.
14. All interiors finishing material shall be provided in accordance with (UAE fire and life safety code
STANDARD Engr.NAME: Engr.NAME: Engr.NAME: ARFAZ and NFPA 101).
15.Fire pump and firewater tank shall be listed, tested, and installed according to civil defense requirement and international
standards.
NFPA-10 SIGN: SIGN: CD CARD No: 101110379 16. Emergency power system and standby system shall be installed in this building in accordance to UAE fire and life safety
code (including local power authority standards) and the relevant NFPA codes and standards.
NFPA-14 STAMP: STAMP: SIGN: 17. All penetrations through fire resistance rated walls shall be protected by approved fire stop system and materials, installed
and tested in accordance with (UAE fire and life safety code and other relevant international standards).
18.All means of egress components details and dimensions shall be provided and constructed according to (UAE fire and life
NFPA-20 STAMP: safety code and NFPA 101 and 5000).
19. Consultant and contractor shall comply with UAE fire and life safety code chapter 12 in terms of requirements of building
under construction.
NFPA-72 20. Emergency action plan shall be implementing in these buildings according to UAE fire and life
safety code.
21. All decoration design and materials and all service systems in this building shall not obstruct all fire safety system
NFPA-110 especially sprinkler system.
22. Air condition equipment's is not allowed inside a protected staircase.
23. Consultant and contractors must comply with the general notes and applicable codes and standards even if the code
NFPA-101 requirement was missed during plan review.
KEY PLAN :
W N E
BU-800 HIGH
PRESSURE WI
GENERAL NOTES :
1. DO NOT SCALE THIS DRAWING.
2. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS IN METERS
UNLESS OTHERWISE NOTED.
3. ALL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE
RELEVANT ARCHITECTURAL, CIVIL, LANDSCAPE, STRUCTURAL,
MECHANICAL, ELECTRICAL AND TELECOMMUNICATION,
ENGINEERING SERVICES DRAWINGS, TOGETHER WITH THE
CONTRACT DOCUMENTS & PROJECT SPECIFICATIONS.
LEGEND:-
SYMBOL DESCRIPTION MAKE
CMP
CENTRAL MONITORING CONTROL PANEL EML
CHEMICAL STORAGE DETAILS
E 3W, EMERGENCY LIGHT SURFACE MOUNTED
1. DISH WASHING LIQUID EML
MOUNTED TYPE 04 FOR APPROVAL 09.08.2023 KKI MRJ
1 2 2. ALL PURPOSE CLEANER 18225 1W, EXIT LIGHT WALL MOUNTED MOUNTED - DOWN
13500 EXIT EML 03 FOR APPROVAL 07.08.2023 KKI MRJ
1
2550
2
3550
3
1450
4
5050
5
5625
6 ARROW TYPE
3. FLOOR CLEANER ETC.. 02 FOR APPROVAL 28.07.2023 KKI MRJ
EXIT 1W, EXIT LIGHT HANGING MOUNTED MOUNTED - EML
SHELTER SIDE ARROW TYPE 01 FOR APPROVAL 24.07.2023 KKI MRJ
SHELTER A 00 FOR APPROVAL 28.03.2023 KKI MRJ
CHEMICAL BAKERY C1/D12 EXIT CHEFROOM DAILYSTORAGE DRY STORE
A STORE REV. NO. DESCRIPTION DATE DRAWN CHKD
EXIT C1/D05
FOR LADIES
2543
C1/D09
2200
1125 2410 C1/D15 CLIENT:
E 2665
E
3315
1095
C1/D14
2934
623
1380
ROBT STONE (ME)LLC
3705
B E
3150 7002 3150
DISH WASH C1/D10 P.O. Box. 39588
C1/D04 AREA 1675 VEGETABLE&SALAD FREEZER Abu Dhabi, U.A.E
E E
E E PREPARATIONROOM (INSULATED COLD
CONTAINED)
C1/D06 C1/D13
C1/D08
4207
3000
E
3230
CONSULTANT :
1985
1125
C1/D16
E FREEZER
(INSULATED COLD
C CONTAINED)
7000
5265
EXIT
C1/D11 C1/D17
E C1/D07
EXIT
E
17075
16000
D FIRE CONTRACTOR
CHICKENPREPARATION
9165
POTSTORE
6000
ROOM
CHILLER
SPEED FIRE & SAFETY EQUIPMENT L.L.C.
5988
(INSULATED COLD
FROM AND TO CONTAINED)
C1/D24
BLOCK-27 P.O. Box: 91962, Mussafah 14, Abu Dhabi
4000
PackingTables
E E FROM AND TO
BLOCK-28
T: +971 25535167, F: +971 25535159
MEATPREPARATION
C1/D03
1148 ROOM
E-mail: speedfse@eim.ae, www.speedsafetyuae.com
2375 C1/D18
2935