You are on page 1of 6

ENGINEER’S STICKER: CONTRACTOR’S STICKER:

0 APPROVAL AM EB WB 20-07-2020
A APPROVAL AM EB WB 30-03-2019
‫ﺗﻧﻘﯾﺢ‬ ‫ﺳﺑب اﻹﺻدار‬ ‫ﺑواﺳط‬ ‫راﺟﻌﮭﺎ‬ ‫واﻓﻖ ﻋﻠﯾﮭﺎ‬ ‫اﻟﺗﺎرﯾﺦ‬
REV. ISSUED FOR PREPARED CHECKED APPROVED DATE

‫اﻟﻣﻣﻠﻛﺔ اﻟﻌرﺑﯾـــﺔ اﻟﺳـــــﻌودﯾــــﺔ‬


KINGDOM OF SAUDI ARABIA

‫اﻟﻣؤﺳﺳﺔ اﻟـﻌـﺎﻣـــﺔ ﻟﺗﺣﻠﯾــﺔ اﻟﻣﯾـــﺎه اﻟﻣﺎﻟﺣـــــﺔ‬


SALINE WATER CONVERSION CORPORATION (SWCC)

Project No. ‫رﻗم اﻟﻣﺷروع‬


‫ﻣﺸﺮوع أﻧﻈﻤﺔ ﻧﻘﻞ ﻣﯿﺎه اﻟﺸﻘﯿﻖ – اﻟﻤﺮﺣﻠﺔ اﻟﺜﺎﻟﺜﺔ‬
20407 SHUQAIQ WATER TRANSMISSION PROJECT, PHASE-3

‫اﻟﻣﮭﻧدس‬
ENGINEER

‫اﻟﻣﻘـــﺎول‬
CONTRACTOR

INSPECTION AND TEST PLAN FOR


ABOVE GRADE AND EMBEDDED CONDUITS
DOCUMENT No. SHEET REV.
C 0 6 - Y E 0 1 - F - 0 9 1 4 1 of 5 0

Subcontractor
KINGDOM OF SAUDI ARABIA Page 2 OF 5
SALINE WATER CONVERSION CORPORATION (SWCC)
SHUQAIQ WATER TRANSMISSION SYSTEMS-PHASE-3
Subject:
Spec. No. QC10-H-094 E14 REV.3
INSPECTION & TEST PLAN FOR ABOVE GRADE AND
EMBEDDED CONDUITS
PÖYRY

First Rev. A 0 Document Number


Revision
Index

C06-YE01-F-0914
Issue Date: 30-03-2019 20-07-2020

TABLE OF CONTENTS

SN. DESCRIPTION PAGE NO.

1. Cover Page ------------------------------------------------------------------------------------------ 1

2. Table of Contents --------------------------------------------------------------------------------- 2

3. Inspection & Test Plan for Above Grade and Embedded Conduits ------------------ 3-4

4. Above Grade and Embedded Conduits Check List --------------------------------------- 5

Sub-contractor Contractor

AL-RASHID TRADING & CONTRACTING CO.


ITP- INSPECTION AND TEST PLAN
Project Tittle: Shuqaiq Water Transmission System Phase - 3- B1,B2 & C

ITP Tittle: INSPECTION AND TEST PLAN FOR ABOVE GRADE AND EMBEDDED CONDUITS ITP No.: C06-YE01-F-0914

System Name: System No.: Rev. No.: 0


Quality
Reference Doc. RTCC EF SF
Records/Verif Inspections Verifications
Item No. Task/ Activity Codes & Inspection Third Party Inspection Inspection Remarks
ying Frequency Personnel
Standards Requiremen Inspection Requiremen Requiremen
Document
t ts (POYRY) ts (SWCC)

1 GENERAL

Conduits Storage, Handling SWCC Spec. QCF-067 & QC engineer /


1.1 EVERY RFI H/R N/A R R
and preservation QC10-H-094 E14 NFPA 70 Site Engineer

SWCC Spec. QCF-067 & QC engineer /


1.2 Conduits Material Receiving EVERY RFI H/R N/A R R
QC10-H-094 E14 NFPA 70 Site Engineer

Conduits fitting and SWCC Spec. QCF-067 & QC engineer /


1.3 EVERY RFI H/R N/A R R
accessories QC10-H-094 E14 NFPA 70 Site Engineer

2.0 INSTALLATION

QCF-067 &
SWCC Spec. QC & site
2.1 Conduits installation APPROVED Every RFI H N/A W S/W
QC10-H-094 E14 Engineer
MATERIAL

QCF-067 &
Conduits fitting fabrication SWCC Spec. QC & site
2.2 APPROVED Every RFI H N/A W S/W
and installation QC10-H-094 E14 Engineer
MATERIAL

QCF-067 &
SWCC Spec. QC & site
2.3 Conduits sealing APPROVED Every RFI H N/A W S/W
QC10-H-094 E14 Engineer
MATERIAL

LEGEND:
RFI=REQUIST FOR INSPECTION W=WITNESS R= REVIEW H= HOLD S= SURVEILLANCE Page 3 of 5
ITP- INSPECTION AND TEST PLAN
Project Tittle: Shuqaiq Water Transmission System Phase - 3- B1,B2 & C

ITP Tittle: INSPECTION AND TEST PLAN FOR ABOVE GRADE AND EMBEDDED CONDUITS ITP No.: C06-YE01-F-0914

System Name: System No.: Rev. No.: 0


Quality
Reference Doc. RTCC EF SF
Records/Verif Inspections Verifications
Item No. Task/ Activity Codes & Inspection Third Party Inspection Inspection Remarks
ying Frequency Personnel
Standards Requiremen Inspection Requiremen Requiremen
Document
t ts (POYRY) ts (SWCC)

3.0 PRE-COMMISSIONING

Conduits inspection before SWCC Spec. AFTER


3.1 QCF-067 QC Engineer H N/A W S/W
cable pulling QC10-H-094 E14 ERECTION

Conduits fitting inspection SWCC Spec. AFTER


3.2 QCF-067 QC Engineer H N/A W S/W
before cable pulling QC10-H-094 E14 ERECTION

Conduits sealing inspection SWCC Spec. AFTER


3.3 QCF-067 QC Engineer H N/A W S/W
before cable pulling QC10-H-094 E14 ERECTION

LEGEND:
RFI=REQUIST FOR INSPECTION W=WITNESS R= REVIEW H= HOLD S= SURVEILLANCE Page 4 of 5
AREA: RFI NO.:
ABOVE GRADE AND EMBEDDED
LOCATION : CONDUITS CHECKLIST DATE:

DESCRIPTION:

DRAWING REFERENCE:
RTCC SITE RTCC QC
S ACTIVITY ENGINEER ENGINEER REMARKS
YES NO YES NO
1 verify for manufacturer's name trademark.
2 Verify the parchase order and delivery note.
3 Verify conduits and their type pvc or emt or flexibale.
4 Verify minimum and maximum trade size of conduits.
5 Verify all fitting for conduits.
A Conduit system, containing all wires, shall be laid inside the walls
6 respective in plaster. Conduits in the screed closed to the walls are also
allowed.
The jointing of PVC conduits shall be done with suitable couplers
6
and solvent cement.
Make sure that the joint is tight enough and entry of water into the
7
conduits through joints is not possible.
8 Verify that conduits, fitting and accessories are free from damage.
verify that liquid primer and solvent cement shall be the correct type
9
and have valid expiration date.
10 verify all materials as per approved material and specefication.
verify that all connection between coduits and boxes by suitable
11
adaptor.
all work inside wall or at slab shall be pvc conduit type, and exposed
12
shall be emt type.
13 Sufficient gap shall be provided between conduits at cross-over location.
Ensure all open end of the conduit are capped and plugged properly
14
before concrete pouring.
The installation of conduits has to be carried out using quick-mounting
clamps and rails.
Conduits shall be laid inside the walls respective in plaster. Conduits
15
shall be laid horizontally and vertically respective parallel to the walls.
Approved saddles shall be used at every 1200 mm for fixing EMT
16
conduits and 200 mm before pull poxes.
Liquid tight flexible conduits shall be used at wet areas and opening
17
areas.
18 verify that the conduits are mechanically and electrically continuous.
verify that the conduits are cleaned and dry internally before wiring
19
installation.
REMARKS:

RTCC CONSTRUCTION ELECTRICAL ENGINEER: DATE:

RTCC QC ELECTRICAL ENGINEER: DATE:

SWCC/POYRY ELECTRICAL ENGINEER: DATE:

QCF-067 Rev.0 Page 1 of 1


Date Issue: 20-JULY-2020 Page 5 of 5
Shuqaiq WTS Phase 3
RESPONSE FOR OE'S COMMENT REVIEW SHEET

DT No. Doc. & Dwg. No. Rev. Title OE CRS No.

RF-EF-D-0057 C06-YE01-F-0914 A Inspection & Test Plan for above grade and embedded conduits. EF-RF-C-0057

RF-EF-D-0000 C06-YE01-F-0914 0 Inspection & Test Plan for above grade and embedded conduits.

Reference Contract Section (if


No. Description of Comment / Remark RTCC RESPONSE OE REPLY
applicable)

In Reference to document transmittal of inspection & testing plan for


1 bove grade and embedded conduits, have been comply
reviewed and approved with the attached comments.