elum_id description table address number access type unit

Activate the EMS.


Values:
True: active
act_ems False: inactive COIL 1 2 RW bool
gridbk_entry_activated Boolean indicating if a grid breaker is cabled to the
COIL
Multi-purpose IO
11 module. 12 RW bool
load_bk_present Boolean indicating if a load breaker is cabled to the
COIL
Multi-purpose 12
IO module. 13 RW bool
Activate grid control.
Values:
True: active
grid_ctl/act False: inactive COIL 20 21 RW bool
Activate active power export control.
Values:
True: active
grid_ctl/export_ctl/act False: inactive COIL 22 23 RW bool
Activate peak shaving.
Values:
True: active
grid_ctl/peak_shaving/act False: inactive COIL 24 25 RW bool
Activate peak shaving SoC reserve.
Values:
True: active
grid_ctl/peak_shaving/soc_reserve/act False: inactive COIL 25 26 RW bool
Activate automatic blackstart in islanding mode.
Values:
True: active
act_auto_blackstart False: inactive COIL 60 61 RW bool
Activate automatic grid reconnection.
Values:
True: active
act_auto_grid_reco False: inactive COIL 61 62 RW bool
Activate PV control.
Values:
True: active
pv_ctl/act False: inactive COIL 80 81 RW bool
Activate genset control.
Values:
True: active
ge_ctl/act False: inactive COIL 100 101 RW bool
Activate automated genset start/stop.
Values:
True: active
ge_ctl/start_stop_ctl/act False: inactive COIL 102 103 RW bool
Activate deferrable load control.
Values:
True: active
def_load/act False: inactive COIL 124 125 RW bool
elum_id description table address number access type unit
Parameter of deferrable load control:
Activate control based on load active power.
Values:
True: active
def_load/w_load/act False: inactive COIL 125 126 RW bool
Parameter of deferrable load control:
Activate control based on BESS SoC.
Values:
True: active
def_load/soc/act False: inactive COIL 126 127 RW bool
dcvbased_derating/act Activate BESS charging power voltage based control.
COIL 150 151 RW bool
bess_ctl/socbased_derating/act Activate BESS charging power soc based control.
COIL 151 152 RW bool
Activate BESS control.
Values:
True: active
bess_ctl/act False: inactive COIL 200 201 RW bool
Activate the SoC equalization.
Values:
True: active
bess_ctl/soc_eq/act False: inactive COIL 201 202 RW bool
bess_ctl/soc_target/act Activate bess control - State of Charge target COIL 400 401 WO bool
Activate grid reactive power control.
Values:
True: active
gridvarctl/act False: inactive COIL 500 501 RW bool bool
Activate grid reactive power control by the PV.
Values:
True: active
gridvarctl_pv/act False: inactive COIL 501 502 RW bool bool
Activate grid reactive power control by the BESS.
Values:
True: active
gridvarctl_bess/act False: inactive COIL 502 503 RW bool bool
Activate genset reactive power control.
Values:
True: active
gevarctl/act False: inactive COIL 600 601 RW bool bool
Activate genset reactive power control by the PV.
Values:
True: active
gevarctl_pv/act False: inactive COIL 601 602 RW bool bool
Activate genset reactive power control by the BESS.
Values:
True: active
gevarctl_bess/act False: inactive COIL 602 603 RW bool bool
elum_id description table address number access type unit
Activate reactive ramp rate control for PV.
Values:
True: active
varrmprate_pv/act False: inactive COIL 800 801 RW bool
Activate reactive ramp rate control for BESS.
Values:
True: active
varrmprate_bess/act False: inactive COIL 801 802 RW bool
sd_cmd Shutdown Command. Any value written triggers a
COIL
Shutdown command.
902 903 RW bool
bess_ctl/tum/act Activate bess control - Time of Use managementCOIL 2000 2001 WO bool
Activate BESS reactive power production priority over BESS active power production.
Values:
True: Priority for the reactive power production
var_prio_bess False: Priority for the active power production COIL 5000 5001 RW bool
Activate PV reactive power production priority over PV active power production.
Values:
True: Priority for the reactive power production
var_prio_pv False: Priority for the active power production COIL 5002 5003 RW bool
isl01_cmd BESS Prime Command. Any value written triggers
COIL
a BESS prime command.
10305 10306 RW bool
isl02_cmd Genset Prime Command. Any value written triggers
COILa Genset Prime
10306
command. 10307 RW bool
grid_cmd Grid Prime Command. Any value written triggersCOIL
a Gride Prime command.
10307 10308 RW bool
Parameter for the active power export control:
Minimum active power at the point of common coupling.
Convention:
Negative: injection
kwmin_pcc Positive: absorption HOLDING 1 400002 RW int32 kW
Parameter for the active power export control:
Phase aggregation method.
Accepted values:
0: Sum of all phases
wgrid_aggopt_expctl 1: 3 times the value of the phase with the lowest HOLDING
measured active 35
power 400036 RW int32
Parameter for peak shaving:
Phase aggregation method.
Accepted values:
0: Sum of all phases
wgrid_aggopt_peakshave 2: 3 times the value of the phase with the highestHOLDING
measured active37
power 400038 RW int32
Parameter for peak shaving:
kwmax_pcc_1 Maximum active power absorption at the point ofHOLDING
common coupling100
for the timeslot 1. 400101 RW int32 kW
Parameter for peak shaving:
kwmax_pcc_2 Maximum active power absorption at the point ofHOLDING
common coupling102
for the timeslot 2. 400103 RW int32 kW
Parameter for peak shaving:
kwmax_pcc_3 Maximum active power absorption at the point ofHOLDING
common coupling104
for the timeslot 3. 400105 RW int32 kW
Parameter for peak shaving:
kwmax_pcc_4 Maximum active power absorption at the point ofHOLDING
common coupling106
for the timeslot 4. 400107 RW int32 kW
Parameter for peak shaving:
kwmax_pcc_5 Maximum active power absorption at the point ofHOLDING
common coupling108
for the timeslot 5. 400109 RW int32 kW
elum_id description table address number access type unit
Parameter for peak shaving:
kwmax_pcc_6 Maximum active power absorption at the point ofHOLDING
common coupling110
for the timeslot 6. 400111 RW int32 kW
Parameter for peak shaving:
kwmax_pcc_start_1 Hour of the beginning of the timeslot 1 for the maximum
HOLDING
active power
150absorption. 400151 RW int32 h
Parameter for peak shaving:
kwmax_pcc_start_2 Hour of the beginning of the timeslot 2 for the maximum
HOLDING
active power
152absorption. 400153 RW int32 h
Parameter for peak shaving:
kwmax_pcc_start_3 Hour of the beginning of the timeslot 3 for the maximum
HOLDING
active power
154absorption. 400155 RW int32 h
Parameter for peak shaving:
kwmax_pcc_start_4 Hour of the beginning of the timeslot 4 for the maximum
HOLDING
active power
156absorption. 400157 RW int32 h
Parameter for peak shaving:
kwmax_pcc_start_5 Hour of the beginning of the timeslot 5 for the maximum
HOLDING
active power
158absorption. 400159 RW int32 h
Parameter for peak shaving:
kwmax_pcc_start_6 Hour of the beginning of the timeslot 6 for the maximum
HOLDING
active power
160absorption. 400161 RW int32 h
max_ramp_bess Maximum BESS active power setpoint ramp. TheHOLDING
difference between
202the total command sent400203
to the BESS
RW and the observed
int32 output is limited
kW by this parameter.
soc_max Maximum allowed SoC for induced charge of theHOLDING
BESS. 204 400205 RW int32 %
soc_min Minimum allowed SoC for induced discharge of the
HOLDING
BESS. 206 400207 RW int32 %
Parameter of peak shaving SoC reserve:
soc_res_1 SoC reserve for the timeslot 1. Only the peak shaving
HOLDING
function can220
discharge the BESS below
400221
the SoC
RWreserve defined.int32 %
Parameter of peak shaving SoC reserve:
soc_res_2 SoC reserve for the timeslot 2. Only the peak shaving
HOLDING
function can222
discharge the BESS below
400223
the SoC
RWreserve defined.int32 %
Parameter of peak shaving SoC reserve:
soc_res_3 SoC reserve for the timeslot 3. Only the peak shaving
HOLDING
function can224
discharge the BESS below
400225
the SoC
RWreserve defined.int32 %
Parameter of peak shaving SoC reserve:
soc_res_4 SoC reserve for the timeslot 4. Only the peak shaving
HOLDING
function can226
discharge the BESS below
400227
the SoC
RWreserve defined.int32 %
Parameter of peak shaving SoC reserve:
soc_res_5 SoC reserve for the timeslot 5. Only the peak shaving
HOLDING
function can228
discharge the BESS below
400229
the SoC
RWreserve defined.int32 %
Parameter of peak shaving SoC reserve:
soc_res_6 SoC reserve for the timeslot 6. Only the peak shaving
HOLDING
function can230
discharge the BESS below
400231
the SoC
RWreserve defined.int32 %
Parameter of peak shaving SoC reserve:
soc_res_start_1 Hour of the beginning of the timeslot 1 for the SoC
HOLDING
reserve. 240 400241 RW int32 h
Parameter of peak shaving SoC reserve:
soc_res_start_2 Hour of the beginning of the timeslot 2 for the SoC
HOLDING
reserve. 242 400243 RW int32 h
Parameter of peak shaving SoC reserve:
soc_res_start_3 Hour of the beginning of the timeslot 3 for the SoC
HOLDING
reserve. 244 400245 RW int32 h
Parameter of peak shaving SoC reserve:
soc_res_start_4 Hour of the beginning of the timeslot 4 for the SoC
HOLDING
reserve. 246 400247 RW int32 h
Parameter of peak shaving SoC reserve:
soc_res_start_5 Hour of the beginning of the timeslot 5 for the SoC
HOLDING
reserve. 248 400249 RW int32 h
Parameter of peak shaving SoC reserve:
soc_res_start_6 Hour of the beginning of the timeslot 6 for the SoC
HOLDING
reserve. 250 400251 RW int32 h
soc_target_1 State of Charge target for the timeslot 1 HOLDING 260 400261 RW int32 %
soc_target_2 State of Charge target for the timeslot 2 HOLDING 262 400263 RW int32 %
soc_target_3 State of Charge target for the timeslot 3 HOLDING 264 400265 RW int32 %
elum_id description table address number access type unit
soc_target_4 State of Charge target for the timeslot 4 HOLDING 266 400267 RW int32 %
soc_target_5 State of Charge target for the timeslot 5 HOLDING 268 400269 RW int32 %
soc_target_6 State of Charge target for the timeslot 6 HOLDING 270 400271 RW int32 %
soc_target_start_1 Hour of the beginning of the timeslot 1 for State of
HOLDING
Charge target 280 400281 RW int32 h
soc_target_start_2 Hour of the beginning of the timeslot 2 for State of
HOLDING
Charge target 282 400283 RW int32 h
soc_target_start_3 Hour of the beginning of the timeslot 3 for State of
HOLDING
Charge target 284 400285 RW int32 h
soc_target_start_4 Hour of the beginning of the timeslot 4 for State of
HOLDING
Charge target 286 400287 RW int32 h
soc_target_start_5 Hour of the beginning of the timeslot 5 for State of
HOLDING
Charge target 288 400289 RW int32 h
soc_target_start_6 Hour of the beginning of the timeslot 6 for State of
HOLDING
Charge target 290 400291 RW int32 h
kva_max_bess_1 BESS nominal apparent power. HOLDING 500 400501 RW int32 kVA
kva_max_bess_2 BESS nominal apparent power. HOLDING 502 400503 RW int32 kVA
kva_max_bess_3 BESS nominal apparent power. HOLDING 504 400505 RW int32 kVA
kva_max_bess_4 BESS nominal apparent power. HOLDING 506 400507 RW int32 kVA
kva_max_bess_5 BESS nominal apparent power. HOLDING 508 400509 RW int32 kVA
kva_max_bess_6 BESS nominal apparent power. HOLDING 510 400511 RW int32 kVA
kva_max_bess_7 BESS nominal apparent power. HOLDING 512 400513 RW int32 kVA
kva_max_bess_8 BESS nominal apparent power. HOLDING 514 400515 RW int32 kVA
kva_max_bess_9 BESS nominal apparent power. HOLDING 516 400517 RW int32 kVA
kva_max_bess_10 BESS nominal apparent power. HOLDING 518 400519 RW int32 kVA
kva_max_bess_11 BESS nominal apparent power. HOLDING 520 400521 RW int32 kVA
kva_max_bess_12 BESS nominal apparent power. HOLDING 522 400523 RW int32 kVA
kva_max_bess_13 BESS nominal apparent power. HOLDING 524 400525 RW int32 kVA
kva_max_bess_14 BESS nominal apparent power. HOLDING 526 400527 RW int32 kVA
kva_max_bess_15 BESS nominal apparent power. HOLDING 528 400529 RW int32 kVA
kva_max_bess_16 BESS nominal apparent power. HOLDING 530 400531 RW int32 kVA
kwdisc_bess_1 BESS maximum induced discharging power. HOLDING 600 400601 RW int32 kW
kwdisc_bess_2 BESS maximum induced discharging power. HOLDING 602 400603 RW int32 kW
kwdisc_bess_3 BESS maximum induced discharging power. HOLDING 604 400605 RW int32 kW
kwdisc_bess_4 BESS maximum induced discharging power. HOLDING 606 400607 RW int32 kW
kwdisc_bess_5 BESS maximum induced discharging power. HOLDING 608 400609 RW int32 kW
kwdisc_bess_6 BESS maximum induced discharging power. HOLDING 610 400611 RW int32 kW
kwdisc_bess_7 BESS maximum induced discharging power. HOLDING 612 400613 RW int32 kW
kwdisc_bess_8 BESS maximum induced discharging power. HOLDING 614 400615 RW int32 kW
kwdisc_bess_9 BESS maximum induced discharging power. HOLDING 616 400617 RW int32 kW
kwdisc_bess_10 BESS maximum induced discharging power. HOLDING 618 400619 RW int32 kW
kwdisc_bess_11 BESS maximum induced discharging power. HOLDING 620 400621 RW int32 kW
kwdisc_bess_12 BESS maximum induced discharging power. HOLDING 622 400623 RW int32 kW
kwdisc_bess_13 BESS maximum induced discharging power. HOLDING 624 400625 RW int32 kW
elum_id description table address number access type unit
kwdisc_bess_14 BESS maximum induced discharging power. HOLDING 626 400627 RW int32 kW
kwdisc_bess_15 BESS maximum induced discharging power. HOLDING 628 400629 RW int32 kW
kwdisc_bess_16 BESS maximum induced discharging power. HOLDING 630 400631 RW int32 kW
kwchar_bess_1 BESS maximum induced charging power. HOLDING 700 400701 RW int32 kW
kwchar_bess_2 BESS maximum induced charging power. HOLDING 702 400703 RW int32 kW
kwchar_bess_3 BESS maximum induced charging power. HOLDING 704 400705 RW int32 kW
kwchar_bess_4 BESS maximum induced charging power. HOLDING 706 400707 RW int32 kW
kwchar_bess_5 BESS maximum induced charging power. HOLDING 708 400709 RW int32 kW
kwchar_bess_6 BESS maximum induced charging power. HOLDING 710 400711 RW int32 kW
kwchar_bess_7 BESS maximum induced charging power. HOLDING 712 400713 RW int32 kW
kwchar_bess_8 BESS maximum induced charging power. HOLDING 714 400715 RW int32 kW
kwchar_bess_9 BESS maximum induced charging power. HOLDING 716 400717 RW int32 kW
kwchar_bess_10 BESS maximum induced charging power. HOLDING 718 400719 RW int32 kW
kwchar_bess_11 BESS maximum induced charging power. HOLDING 720 400721 RW int32 kW
kwchar_bess_12 BESS maximum induced charging power. HOLDING 722 400723 RW int32 kW
kwchar_bess_13 BESS maximum induced charging power. HOLDING 724 400725 RW int32 kW
kwchar_bess_14 BESS maximum induced charging power. HOLDING 726 400727 RW int32 kW
kwchar_bess_15 BESS maximum induced charging power. HOLDING 728 400729 RW int32 kW
kwchar_bess_16 BESS maximum induced charging power. HOLDING 730 400731 RW int32 kW
kwh_bess_1 BESS total energy. HOLDING 800 400801 RW int32 kWH
kwh_bess_2 BESS total energy. HOLDING 802 400803 RW int32 kWH
kwh_bess_3 BESS total energy. HOLDING 804 400805 RW int32 kWH
kwh_bess_4 BESS total energy. HOLDING 806 400807 RW int32 kWH
kwh_bess_5 BESS total energy. HOLDING 808 400809 RW int32 kWH
kwh_bess_6 BESS total energy. HOLDING 810 400811 RW int32 kWH
kwh_bess_7 BESS total energy. HOLDING 812 400813 RW int32 kWH
kwh_bess_8 BESS total energy. HOLDING 814 400815 RW int32 kWH
kwh_bess_9 BESS total energy. HOLDING 816 400817 RW int32 kWH
kwh_bess_10 BESS total energy. HOLDING 818 400819 RW int32 kWH
kwh_bess_11 BESS total energy. HOLDING 820 400821 RW int32 kWH
kwh_bess_12 BESS total energy. HOLDING 822 400823 RW int32 kWH
kwh_bess_13 BESS total energy. HOLDING 824 400825 RW int32 kWH
kwh_bess_14 BESS total energy. HOLDING 826 400827 RW int32 kWH
kwh_bess_15 BESS total energy. HOLDING 828 400829 RW int32 kWH
kwh_bess_16 BESS total energy. HOLDING 830 400831 RW int32 kWH
max_ramp_pv Maximum PV active power setpoint ramp. The difference
HOLDING between1000
the total command sent to401001
the PV inverters
RW and the observed
int32 production
kWis limited by this parameter.
kva_max_pv_1 PV Inverter nominal apparent power. HOLDING 1100 401101 RW int32 kVA
kva_max_pv_2 PV Inverter nominal apparent power. HOLDING 1102 401103 RW int32 kVA
elum_id description table address number access type unit
kva_max_pv_3 PV Inverter nominal apparent power. HOLDING 1104 401105 RW int32 kVA
kva_max_pv_4 PV Inverter nominal apparent power. HOLDING 1106 401107 RW int32 kVA
kva_max_pv_5 PV Inverter nominal apparent power. HOLDING 1108 401109 RW int32 kVA
kva_max_pv_6 PV Inverter nominal apparent power. HOLDING 1110 401111 RW int32 kVA
kva_max_pv_7 PV Inverter nominal apparent power. HOLDING 1112 401113 RW int32 kVA
kva_max_pv_8 PV Inverter nominal apparent power. HOLDING 1114 401115 RW int32 kVA
kva_max_pv_9 PV Inverter nominal apparent power. HOLDING 1116 401117 RW int32 kVA
kva_max_pv_10 PV Inverter nominal apparent power. HOLDING 1118 401119 RW int32 kVA
kva_max_pv_11 PV Inverter nominal apparent power. HOLDING 1120 401121 RW int32 kVA
kva_max_pv_12 PV Inverter nominal apparent power. HOLDING 1122 401123 RW int32 kVA
kva_max_pv_13 PV Inverter nominal apparent power. HOLDING 1124 401125 RW int32 kVA
kva_max_pv_14 PV Inverter nominal apparent power. HOLDING 1126 401127 RW int32 kVA
kva_max_pv_15 PV Inverter nominal apparent power. HOLDING 1128 401129 RW int32 kVA
kva_max_pv_16 PV Inverter nominal apparent power. HOLDING 1130 401131 RW int32 kVA
kva_max_pv_17 PV Inverter nominal apparent power. HOLDING 1132 401133 RW int32 kVA
kva_max_pv_18 PV Inverter nominal apparent power. HOLDING 1134 401135 RW int32 kVA
kva_max_pv_19 PV Inverter nominal apparent power. HOLDING 1136 401137 RW int32 kVA
kva_max_pv_20 PV Inverter nominal apparent power. HOLDING 1138 401139 RW int32 kVA
kva_max_pv_21 PV Inverter nominal apparent power. HOLDING 1140 401141 RW int32 kVA
kva_max_pv_22 PV Inverter nominal apparent power. HOLDING 1142 401143 RW int32 kVA
kva_max_pv_23 PV Inverter nominal apparent power. HOLDING 1144 401145 RW int32 kVA
kva_max_pv_24 PV Inverter nominal apparent power. HOLDING 1146 401147 RW int32 kVA
kva_max_pv_25 PV Inverter nominal apparent power. HOLDING 1148 401149 RW int32 kVA
kva_max_pv_26 PV Inverter nominal apparent power. HOLDING 1150 401151 RW int32 kVA
kva_max_pv_27 PV Inverter nominal apparent power. HOLDING 1152 401153 RW int32 kVA
kva_max_pv_28 PV Inverter nominal apparent power. HOLDING 1154 401155 RW int32 kVA
kva_max_pv_29 PV Inverter nominal apparent power. HOLDING 1156 401157 RW int32 kVA
kva_max_pv_30 PV Inverter nominal apparent power. HOLDING 1158 401159 RW int32 kVA
kva_max_pv_31 PV Inverter nominal apparent power. HOLDING 1160 401161 RW int32 kVA
kva_max_pv_32 PV Inverter nominal apparent power. HOLDING 1162 401163 RW int32 kVA
kva_max_pv_33 PV Inverter nominal apparent power. HOLDING 1164 401165 RW int32 kVA
kva_max_pv_34 PV Inverter nominal apparent power. HOLDING 1166 401167 RW int32 kVA
kva_max_pv_35 PV Inverter nominal apparent power. HOLDING 1168 401169 RW int32 kVA
kva_max_pv_36 PV Inverter nominal apparent power. HOLDING 1170 401171 RW int32 kVA
kva_max_pv_37 PV Inverter nominal apparent power. HOLDING 1172 401173 RW int32 kVA
kva_max_pv_38 PV Inverter nominal apparent power. HOLDING 1174 401175 RW int32 kVA
kva_max_pv_39 PV Inverter nominal apparent power. HOLDING 1176 401177 RW int32 kVA
kva_max_pv_40 PV Inverter nominal apparent power. HOLDING 1178 401179 RW int32 kVA
elum_id description table address number access type unit
kva_max_pv_41 PV Inverter nominal apparent power. HOLDING 1180 401181 RW int32 kVA
kva_max_pv_42 PV Inverter nominal apparent power. HOLDING 1182 401183 RW int32 kVA
kva_max_pv_43 PV Inverter nominal apparent power. HOLDING 1184 401185 RW int32 kVA
kva_max_pv_44 PV Inverter nominal apparent power. HOLDING 1186 401187 RW int32 kVA
kva_max_pv_45 PV Inverter nominal apparent power. HOLDING 1188 401189 RW int32 kVA
kva_max_pv_46 PV Inverter nominal apparent power. HOLDING 1190 401191 RW int32 kVA
kva_max_pv_47 PV Inverter nominal apparent power. HOLDING 1192 401193 RW int32 kVA
kva_max_pv_48 PV Inverter nominal apparent power. HOLDING 1194 401195 RW int32 kVA
kva_max_pv_49 PV Inverter nominal apparent power. HOLDING 1196 401197 RW int32 kVA
kva_max_pv_50 PV Inverter nominal apparent power. HOLDING 1198 401199 RW int32 kVA
kva_max_pv_51 PV Inverter nominal apparent power. HOLDING 1200 401201 RW int32 kVA
kva_max_pv_52 PV Inverter nominal apparent power. HOLDING 1202 401203 RW int32 kVA
kva_max_pv_53 PV Inverter nominal apparent power. HOLDING 1204 401205 RW int32 kVA
kva_max_pv_54 PV Inverter nominal apparent power. HOLDING 1206 401207 RW int32 kVA
kva_max_pv_55 PV Inverter nominal apparent power. HOLDING 1208 401209 RW int32 kVA
kva_max_pv_56 PV Inverter nominal apparent power. HOLDING 1210 401211 RW int32 kVA
kva_max_pv_57 PV Inverter nominal apparent power. HOLDING 1212 401213 RW int32 kVA
kva_max_pv_58 PV Inverter nominal apparent power. HOLDING 1214 401215 RW int32 kVA
kva_max_pv_59 PV Inverter nominal apparent power. HOLDING 1216 401217 RW int32 kVA
kva_max_pv_60 PV Inverter nominal apparent power. HOLDING 1218 401219 RW int32 kVA
kva_max_pv_61 PV Inverter nominal apparent power. HOLDING 1220 401221 RW int32 kVA
kva_max_pv_62 PV Inverter nominal apparent power. HOLDING 1222 401223 RW int32 kVA
kva_max_pv_63 PV Inverter nominal apparent power. HOLDING 1224 401225 RW int32 kVA
kva_max_pv_64 PV Inverter nominal apparent power. HOLDING 1226 401227 RW int32 kVA
kva_max_pv_65 PV Inverter nominal apparent power. HOLDING 1228 401229 RW int32 kVA
kva_max_pv_66 PV Inverter nominal apparent power. HOLDING 1230 401231 RW int32 kVA
kva_max_pv_67 PV Inverter nominal apparent power. HOLDING 1232 401233 RW int32 kVA
kva_max_pv_68 PV Inverter nominal apparent power. HOLDING 1234 401235 RW int32 kVA
kva_max_pv_69 PV Inverter nominal apparent power. HOLDING 1236 401237 RW int32 kVA
kva_max_pv_70 PV Inverter nominal apparent power. HOLDING 1238 401239 RW int32 kVA
kva_max_pv_71 PV Inverter nominal apparent power. HOLDING 1240 401241 RW int32 kVA
kva_max_pv_72 PV Inverter nominal apparent power. HOLDING 1242 401243 RW int32 kVA
kva_max_pv_73 PV Inverter nominal apparent power. HOLDING 1244 401245 RW int32 kVA
kva_max_pv_74 PV Inverter nominal apparent power. HOLDING 1246 401247 RW int32 kVA
kva_max_pv_75 PV Inverter nominal apparent power. HOLDING 1248 401249 RW int32 kVA
kva_max_pv_76 PV Inverter nominal apparent power. HOLDING 1250 401251 RW int32 kVA
kva_max_pv_77 PV Inverter nominal apparent power. HOLDING 1252 401253 RW int32 kVA
kva_max_pv_78 PV Inverter nominal apparent power. HOLDING 1254 401255 RW int32 kVA
elum_id description table address number access type unit
kva_max_pv_79 PV Inverter nominal apparent power. HOLDING 1256 401257 RW int32 kVA
kva_max_pv_80 PV Inverter nominal apparent power. HOLDING 1258 401259 RW int32 kVA
kva_max_pv_81 PV Inverter nominal apparent power. HOLDING 1260 401261 RW int32 kVA
kva_max_pv_82 PV Inverter nominal apparent power. HOLDING 1262 401263 RW int32 kVA
kva_max_pv_83 PV Inverter nominal apparent power. HOLDING 1264 401265 RW int32 kVA
kva_max_pv_84 PV Inverter nominal apparent power. HOLDING 1266 401267 RW int32 kVA
kva_max_pv_85 PV Inverter nominal apparent power. HOLDING 1268 401269 RW int32 kVA
kva_max_pv_86 PV Inverter nominal apparent power. HOLDING 1270 401271 RW int32 kVA
kva_max_pv_87 PV Inverter nominal apparent power. HOLDING 1272 401273 RW int32 kVA
kva_max_pv_88 PV Inverter nominal apparent power. HOLDING 1274 401275 RW int32 kVA
kva_max_pv_89 PV Inverter nominal apparent power. HOLDING 1276 401277 RW int32 kVA
kva_max_pv_90 PV Inverter nominal apparent power. HOLDING 1278 401279 RW int32 kVA
kva_max_pv_91 PV Inverter nominal apparent power. HOLDING 1280 401281 RW int32 kVA
kva_max_pv_92 PV Inverter nominal apparent power. HOLDING 1282 401283 RW int32 kVA
kva_max_pv_93 PV Inverter nominal apparent power. HOLDING 1284 401285 RW int32 kVA
kva_max_pv_94 PV Inverter nominal apparent power. HOLDING 1286 401287 RW int32 kVA
kva_max_pv_95 PV Inverter nominal apparent power. HOLDING 1288 401289 RW int32 kVA
kva_max_pv_96 PV Inverter nominal apparent power. HOLDING 1290 401291 RW int32 kVA
kva_max_pv_97 PV Inverter nominal apparent power. HOLDING 1292 401293 RW int32 kVA
kva_max_pv_98 PV Inverter nominal apparent power. HOLDING 1294 401295 RW int32 kVA
kva_max_pv_99 PV Inverter nominal apparent power. HOLDING 1296 401297 RW int32 kVA
kva_max_pv_100 PV Inverter nominal apparent power. HOLDING 1298 401299 RW int32 kVA
kva_max_pv_101 PV Inverter nominal apparent power. HOLDING 1300 401301 RW int32 kVA
kva_max_pv_102 PV Inverter nominal apparent power. HOLDING 1302 401303 RW int32 kVA
kva_max_pv_103 PV Inverter nominal apparent power. HOLDING 1304 401305 RW int32 kVA
kva_max_pv_104 PV Inverter nominal apparent power. HOLDING 1306 401307 RW int32 kVA
kva_max_pv_105 PV Inverter nominal apparent power. HOLDING 1308 401309 RW int32 kVA
kva_max_pv_106 PV Inverter nominal apparent power. HOLDING 1310 401311 RW int32 kVA
kva_max_pv_107 PV Inverter nominal apparent power. HOLDING 1312 401313 RW int32 kVA
kva_max_pv_108 PV Inverter nominal apparent power. HOLDING 1314 401315 RW int32 kVA
kva_max_pv_109 PV Inverter nominal apparent power. HOLDING 1316 401317 RW int32 kVA
kva_max_pv_110 PV Inverter nominal apparent power. HOLDING 1318 401319 RW int32 kVA
kva_max_pv_111 PV Inverter nominal apparent power. HOLDING 1320 401321 RW int32 kVA
kva_max_pv_112 PV Inverter nominal apparent power. HOLDING 1322 401323 RW int32 kVA
kva_max_pv_113 PV Inverter nominal apparent power. HOLDING 1324 401325 RW int32 kVA
kva_max_pv_114 PV Inverter nominal apparent power. HOLDING 1326 401327 RW int32 kVA
kva_max_pv_115 PV Inverter nominal apparent power. HOLDING 1328 401329 RW int32 kVA
kva_max_pv_116 PV Inverter nominal apparent power. HOLDING 1330 401331 RW int32 kVA
elum_id description table address number access type unit
kva_max_pv_117 PV Inverter nominal apparent power. HOLDING 1332 401333 RW int32 kVA
kva_max_pv_118 PV Inverter nominal apparent power. HOLDING 1334 401335 RW int32 kVA
kva_max_pv_119 PV Inverter nominal apparent power. HOLDING 1336 401337 RW int32 kVA
kva_max_pv_120 PV Inverter nominal apparent power. HOLDING 1338 401339 RW int32 kVA
Parameter of automated genset start/stop:
soc_start_ge BESS SoC triggering genset start. HOLDING 2004 402005 RW int32 %
Parameter of automated genset start/stop:
soc_stop_ge BESS SoC triggering genset stop. HOLDING 2006 402007 RW int32 %
kvar_max_ramp_bess Maximum BESS reactive power setpoint ramp. The
HOLDING
difference between
2008 the total command sent
402009
to theRW
PV inverters andint32
the observed power
kVAris limited by this parameter.
kvar_max_ramp_pv Maximum PV reactive power setpoint ramp. The HOLDING
difference between
2010
the total command sent 402011
to the PVRW
inverters and theint32
observed power kVAr
is limited by this parameter.
max_ramp_ge Maximum genset active power setpoint ramp. The
HOLDING
difference between
2012the total command sent
402013
to the gensets
RW and the observed
int32 production
kWis limited by this parameter.
pct_min_ge Minimum active power loading setpoint in percentage
HOLDING
of genset primary
2014 rated power. 402015 RW int32 %
kva_max_ge_1 Genset rated apparent power. HOLDING 2200 402201 RW int32 kVA
kva_max_ge_2 Genset rated apparent power. HOLDING 2202 402203 RW int32 kVA
kva_max_ge_3 Genset rated apparent power. HOLDING 2204 402205 RW int32 kVA
kva_max_ge_4 Genset rated apparent power. HOLDING 2206 402207 RW int32 kVA
kva_max_ge_5 Genset rated apparent power. HOLDING 2208 402209 RW int32 kVA
kva_max_ge_6 Genset rated apparent power. HOLDING 2210 402211 RW int32 kVA
kva_max_ge_7 Genset rated apparent power. HOLDING 2212 402213 RW int32 kVA
kva_max_ge_8 Genset rated apparent power. HOLDING 2214 402215 RW int32 kVA
kva_max_ge_9 Genset rated apparent power. HOLDING 2216 402217 RW int32 kVA
kva_max_ge_10 Genset rated apparent power. HOLDING 2218 402219 RW int32 kVA
kva_max_ge_11 Genset rated apparent power. HOLDING 2220 402221 RW int32 kVA
kva_max_ge_12 Genset rated apparent power. HOLDING 2222 402223 RW int32 kVA
kva_max_ge_13 Genset rated apparent power. HOLDING 2224 402225 RW int32 kVA
kva_max_ge_14 Genset rated apparent power. HOLDING 2226 402227 RW int32 kVA
kva_max_ge_15 Genset rated apparent power. HOLDING 2228 402229 RW int32 kVA
kva_max_ge_16 Genset rated apparent power. HOLDING 2230 402231 RW int32 kVA
Parameter of deferrable load control based on BESS SoC:
low_soc_bess_defload SoC below which an opening signal is sent to theHOLDING
load breaker. 2600 402601 RW int32 %
Parameter of deferrable load control based on load active power:
high_W_load_defload Load active power above which an opening signal HOLDING
is sent to the load
2604
breaker. 402605 RW int32 kW
Grid reactive power control strategy.
Accepted values:
1: Power Factor Respecting a Defined Range
var_ctl_at_grid_func 2: Power Factor Equal to a Target HOLDING 3000 403001 RW int32 enum
grid_min_capacitive_pf Minimum capacitive grid power factor. Required parameter
HOLDING for the 3002
grid power factor range control
403003 RW float32 enum
grid_min_inductive_pf Minimum inductive grid power factor. Required parameter
HOLDINGfor the grid
3004power factor range control
403005 RW float32 enum
grid_pf_target_value Absolute value of the grid power factor target. Required
HOLDING parameter3006
for the grid power factor target
403007control
RW float32 enum
elum_id description table address number access type unit
Type of the grid power factor target. Required parameter for the grid power factor target control.
Accepted values:
-1: Inductive
grid_pf_target_type 1: Capacitive HOLDING 3008 403009 RW int32 enum
gridvarctl_kvar_max_abs_pv Maximum absolute value of the reactive power that
HOLDING
PV can exchange
3012while doing reactive power
403013
control
RWat the grid float32 kVAr
gridvarctl_kvar_max_abs_bess Maximum absolute value of the reactive power that
HOLDING
BESS can exchange
3014 while doing reactive403015
power control
RW at the grid float32 kVAr
Genset reactive power control strategy.
Accepted values:
1: Power Factor Respecting a Defined Range
var_ctl_at_ge_func 2: Power Factor Equal to a Target HOLDING 4000 404001 RW int32 enum
ge_min_capacitive_pf Minimum capacitive grid power factor. Required parameter
HOLDING for the 4002
grid power factor range control
404003 RW float32 enum
ge_min_inductive_pf Minimum inductive grid power factor. Required parameter
HOLDINGfor the grid
4004power factor range control
404005 RW float32 enum
ge_pf_target_value Absolute value of the grid power factor target. Required
HOLDING parameter4006
for the grid power factor target
404007control
RW float32 enum
Type of the grid power factor target. Required parameter for the grid power factor target control.
Accepted values:
-1: Inductive
ge_pf_target_type 1: Capacitive HOLDING 4008 404009 RW int32 enum
gevarctl_kvar_max_abs_pv Maximum absolute value of the reactive power that
HOLDING
PV can exchange
4012while doing reactive power
404013
control
RWat the genset float32 kVAr
gevarctl_kvar_max_abs_bess Maximum absolute value of the reactive power that
HOLDING
BESS can exchange
4014 while doing reactive404015
power control
RW at the genset
float32 kVAr
kva_peak_pv Theoretical PV subsystem AC power output under
HOLDING
standard irradiance,
4200 temperature, and air mass
404201
conditions
RW (20 degC,int32
1000W/m2, 1.5 AM)
kVA
irr_threshold Solar irradiance threshold below which it is considered
HOLDINGas night time.
4202 404203 RW int32 W/m2
pct_curtailment_tol Extra-curtailment periods are identified when theHOLDING
the total active power
4204 produced by the PV subsystem
404205 RWis below the total
int32
command and the
% difference exceeds this perce
gref Standard Irradiance. HOLDING 4206 404207 RW int32 kW/m2
W_pv Total active power produced by solar inverters. HOLDING 6000 406001 RO float32
Total reactive power produced by solar inverters.
Convention:
Negative: capacitive
VAR_pv Positive: inductive HOLDING 6002 406003 RO float32
Active power at the point of common coupling.
Convention:
Negative: injection
W_grid Positive: absorption HOLDING 6004 406005 RO float32
Reactive power at the point of common coupling.
Convention:
Negative: capacitive
VAR_grid Positive: inductive HOLDING 6006 406007 RO float32
TanPhi_grid Tan phi at the point of common coupling. HOLDING 6008 406009 RO float32
CosPhi_grid Cos phi at the point of common coupling. HOLDING 6010 406011 RO float32
soc_target_6 State of Charge target for the timeslot 6 HOLDING 270 400271 RW int32 %
soc_target_start_1 Hour of the beginning of the timeslot 1 for State of
HOLDING
Charge target 280 400281 RW int32 h
soc_target_start_2 Hour of the beginning of the timeslot 2 for State of
HOLDING
Charge target 282 400283 RW int32 h
soc_target_start_3 Hour of the beginning of the timeslot 3 for State of
HOLDING
Charge target 284 400285 RW int32 h
soc_target_start_4 Hour of the beginning of the timeslot 4 for State of
HOLDING
Charge target 286 400287 RW int32 h
elum_id description table address number access type unit
soc_target_start_5 Hour of the beginning of the timeslot 5 for State of
HOLDING
Charge target 288 400289 RW int32 h
soc_target_start_6 Hour of the beginning of the timeslot 6 for State of
HOLDING
Charge target 290 400291 RW int32 h
kw_nom_bess_1 BESS nominal power. HOLDING 500 400501 RW int32 kW
kw_nom_bess_2 BESS nominal power. HOLDING 502 400503 RW int32 kW
kw_nom_bess_3 BESS nominal power. HOLDING 504 400505 RW int32 kW
kw_nom_bess_4 BESS nominal power. HOLDING 506 400507 RW int32 kW
kw_nom_bess_5 BESS nominal power. HOLDING 508 400509 RW int32 kW
kw_nom_bess_6 BESS nominal power. HOLDING 510 400511 RW int32 kW
kw_nom_bess_7 BESS nominal power. HOLDING 512 400513 RW int32 kW
kw_nom_bess_8 BESS nominal power. HOLDING 514 400515 RW int32 kW
kw_nom_bess_9 BESS nominal power. HOLDING 516 400517 RW int32 kW
kw_nom_bess_10 BESS nominal power. HOLDING 518 400519 RW int32 kW
kw_nom_bess_11 BESS nominal power. HOLDING 520 400521 RW int32 kW
kw_nom_bess_12 BESS nominal power. HOLDING 522 400523 RW int32 kW
kw_nom_bess_13 BESS nominal power. HOLDING 524 400525 RW int32 kW
kw_nom_bess_14 BESS nominal power. HOLDING 526 400527 RW int32 kW
kw_nom_bess_15 BESS nominal power. HOLDING 528 400529 RW int32 kW
kw_nom_bess_16 BESS nominal power. HOLDING 530 400531 RW int32 kW
kwdisc_bess_1 BESS maximum induced discharging power. HOLDING 600 400601 RW int32 kW
kwdisc_bess_2 BESS maximum induced discharging power. HOLDING 602 400603 RW int32 kW
kwdisc_bess_3 BESS maximum induced discharging power. HOLDING 604 400605 RW int32 kW
kwdisc_bess_4 BESS maximum induced discharging power. HOLDING 606 400607 RW int32 kW
kwdisc_bess_5 BESS maximum induced discharging power. HOLDING 608 400609 RW int32 kW
kwdisc_bess_6 BESS maximum induced discharging power. HOLDING 610 400611 RW int32 kW
kwdisc_bess_7 BESS maximum induced discharging power. HOLDING 612 400613 RW int32 kW
kwdisc_bess_8 BESS maximum induced discharging power. HOLDING 614 400615 RW int32 kW
kwdisc_bess_9 BESS maximum induced discharging power. HOLDING 616 400617 RW int32 kW
kwdisc_bess_10 BESS maximum induced discharging power. HOLDING 618 400619 RW int32 kW
kwdisc_bess_11 BESS maximum induced discharging power. HOLDING 620 400621 RW int32 kW
kwdisc_bess_12 BESS maximum induced discharging power. HOLDING 622 400623 RW int32 kW
kwdisc_bess_13 BESS maximum induced discharging power. HOLDING 624 400625 RW int32 kW
kwdisc_bess_14 BESS maximum induced discharging power. HOLDING 626 400627 RW int32 kW
kwdisc_bess_15 BESS maximum induced discharging power. HOLDING 628 400629 RW int32 kW
kwdisc_bess_16 BESS maximum induced discharging power. HOLDING 630 400631 RW int32 kW
kwchar_bess_1 BESS maximum induced charging power. HOLDING 700 400701 RW int32 kW
kwchar_bess_2 BESS maximum induced charging power. HOLDING 702 400703 RW int32 kW
kwchar_bess_3 BESS maximum induced charging power. HOLDING 704 400705 RW int32 kW
kwchar_bess_4 BESS maximum induced charging power. HOLDING 706 400707 RW int32 kW
elum_id description table address number access type unit
kwchar_bess_5 BESS maximum induced charging power. HOLDING 708 400709 RW int32 kW
kwchar_bess_6 BESS maximum induced charging power. HOLDING 710 400711 RW int32 kW
kwchar_bess_7 BESS maximum induced charging power. HOLDING 712 400713 RW int32 kW
kwchar_bess_8 BESS maximum induced charging power. HOLDING 714 400715 RW int32 kW
kwchar_bess_9 BESS maximum induced charging power. HOLDING 716 400717 RW int32 kW
kwchar_bess_10 BESS maximum induced charging power. HOLDING 718 400719 RW int32 kW
kwchar_bess_11 BESS maximum induced charging power. HOLDING 720 400721 RW int32 kW
kwchar_bess_12 BESS maximum induced charging power. HOLDING 722 400723 RW int32 kW
kwchar_bess_13 BESS maximum induced charging power. HOLDING 724 400725 RW int32 kW
kwchar_bess_14 BESS maximum induced charging power. HOLDING 726 400727 RW int32 kW
kwchar_bess_15 BESS maximum induced charging power. HOLDING 728 400729 RW int32 kW
kwchar_bess_16 BESS maximum induced charging power. HOLDING 730 400731 RW int32 kW
max_ramp_pv Maximum PV active power setpoint ramp. The difference
HOLDING between the total command
1000 401001
sent to the PV inverters
RW and the observed
int32 production
kWis limited by this parameter.
kw_nom_inverter_1 PV Inverter nominal power. HOLDING 1100 401101 RW int32 kW
kw_nom_inverter_2 PV Inverter nominal power. HOLDING 1102 401103 RW int32 kW
kw_nom_inverter_3 PV Inverter nominal power. HOLDING 1104 401105 RW int32 kW
kw_nom_inverter_4 PV Inverter nominal power. HOLDING 1106 401107 RW int32 kW
kw_nom_inverter_5 PV Inverter nominal power. HOLDING 1108 401109 RW int32 kW
kw_nom_inverter_6 PV Inverter nominal power. HOLDING 1110 401111 RW int32 kW
kw_nom_inverter_7 PV Inverter nominal power. HOLDING 1112 401113 RW int32 kW
kw_nom_inverter_8 PV Inverter nominal power. HOLDING 1114 401115 RW int32 kW
kw_nom_inverter_9 PV Inverter nominal power. HOLDING 1116 401117 RW int32 kW
kw_nom_inverter_10 PV Inverter nominal power. HOLDING 1118 401119 RW int32 kW
kw_nom_inverter_11 PV Inverter nominal power. HOLDING 1120 401121 RW int32 kW
kw_nom_inverter_12 PV Inverter nominal power. HOLDING 1122 401123 RW int32 kW
kw_nom_inverter_13 PV Inverter nominal power. HOLDING 1124 401125 RW int32 kW
kw_nom_inverter_14 PV Inverter nominal power. HOLDING 1126 401127 RW int32 kW
kw_nom_inverter_15 PV Inverter nominal power. HOLDING 1128 401129 RW int32 kW
kw_nom_inverter_16 PV Inverter nominal power. HOLDING 1130 401131 RW int32 kW
kw_nom_inverter_17 PV Inverter nominal power. HOLDING 1132 401133 RW int32 kW
kw_nom_inverter_18 PV Inverter nominal power. HOLDING 1134 401135 RW int32 kW
kw_nom_inverter_19 PV Inverter nominal power. HOLDING 1136 401137 RW int32 kW
kw_nom_inverter_20 PV Inverter nominal power. HOLDING 1138 401139 RW int32 kW
kw_nom_inverter_21 PV Inverter nominal power. HOLDING 1140 401141 RW int32 kW
kw_nom_inverter_22 PV Inverter nominal power. HOLDING 1142 401143 RW int32 kW
kw_nom_inverter_23 PV Inverter nominal power. HOLDING 1144 401145 RW int32 kW
kw_nom_inverter_24 PV Inverter nominal power. HOLDING 1146 401147 RW int32 kW
kw_nom_inverter_25 PV Inverter nominal power. HOLDING 1148 401149 RW int32 kW
elum_id description table address number access type unit
kw_nom_inverter_26 PV Inverter nominal power. HOLDING 1150 401151 RW int32 kW
kw_nom_inverter_27 PV Inverter nominal power. HOLDING 1152 401153 RW int32 kW
kw_nom_inverter_28 PV Inverter nominal power. HOLDING 1154 401155 RW int32 kW
kw_nom_inverter_29 PV Inverter nominal power. HOLDING 1156 401157 RW int32 kW
kw_nom_inverter_30 PV Inverter nominal power. HOLDING 1158 401159 RW int32 kW
kw_nom_inverter_31 PV Inverter nominal power. HOLDING 1160 401161 RW int32 kW
kw_nom_inverter_32 PV Inverter nominal power. HOLDING 1162 401163 RW int32 kW
kw_nom_inverter_33 PV Inverter nominal power. HOLDING 1164 401165 RW int32 kW
kw_nom_inverter_34 PV Inverter nominal power. HOLDING 1166 401167 RW int32 kW
kw_nom_inverter_35 PV Inverter nominal power. HOLDING 1168 401169 RW int32 kW
kw_nom_inverter_36 PV Inverter nominal power. HOLDING 1170 401171 RW int32 kW
kw_nom_inverter_37 PV Inverter nominal power. HOLDING 1172 401173 RW int32 kW
kw_nom_inverter_38 PV Inverter nominal power. HOLDING 1174 401175 RW int32 kW
kw_nom_inverter_39 PV Inverter nominal power. HOLDING 1176 401177 RW int32 kW
kw_nom_inverter_40 PV Inverter nominal power. HOLDING 1178 401179 RW int32 kW
kw_nom_inverter_41 PV Inverter nominal power. HOLDING 1180 401181 RW int32 kW
kw_nom_inverter_42 PV Inverter nominal power. HOLDING 1182 401183 RW int32 kW
kw_nom_inverter_43 PV Inverter nominal power. HOLDING 1184 401185 RW int32 kW
kw_nom_inverter_44 PV Inverter nominal power. HOLDING 1186 401187 RW int32 kW
kw_nom_inverter_45 PV Inverter nominal power. HOLDING 1188 401189 RW int32 kW
kw_nom_inverter_46 PV Inverter nominal power. HOLDING 1190 401191 RW int32 kW
kw_nom_inverter_47 PV Inverter nominal power. HOLDING 1192 401193 RW int32 kW
kw_nom_inverter_48 PV Inverter nominal power. HOLDING 1194 401195 RW int32 kW
kw_nom_inverter_49 PV Inverter nominal power. HOLDING 1196 401197 RW int32 kW
kw_nom_inverter_50 PV Inverter nominal power. HOLDING 1198 401199 RW int32 kW
kw_nom_inverter_51 PV Inverter nominal power. HOLDING 1200 401201 RW int32 kW
kw_nom_inverter_52 PV Inverter nominal power. HOLDING 1202 401203 RW int32 kW
kw_nom_inverter_53 PV Inverter nominal power. HOLDING 1204 401205 RW int32 kW
kw_nom_inverter_54 PV Inverter nominal power. HOLDING 1206 401207 RW int32 kW
kw_nom_inverter_55 PV Inverter nominal power. HOLDING 1208 401209 RW int32 kW
kw_nom_inverter_56 PV Inverter nominal power. HOLDING 1210 401211 RW int32 kW
kw_nom_inverter_57 PV Inverter nominal power. HOLDING 1212 401213 RW int32 kW
kw_nom_inverter_58 PV Inverter nominal power. HOLDING 1214 401215 RW int32 kW
kw_nom_inverter_59 PV Inverter nominal power. HOLDING 1216 401217 RW int32 kW
kw_nom_inverter_60 PV Inverter nominal power. HOLDING 1218 401219 RW int32 kW
kw_nom_inverter_61 PV Inverter nominal power. HOLDING 1220 401221 RW int32 kW
kw_nom_inverter_62 PV Inverter nominal power. HOLDING 1222 401223 RW int32 kW
kw_nom_inverter_63 PV Inverter nominal power. HOLDING 1224 401225 RW int32 kW
elum_id description table address number access type unit
kw_nom_inverter_64 PV Inverter nominal power. HOLDING 1226 401227 RW int32 kW
kw_nom_inverter_65 PV Inverter nominal power. HOLDING 1228 401229 RW int32 kW
kw_nom_inverter_66 PV Inverter nominal power. HOLDING 1230 401231 RW int32 kW
kw_nom_inverter_67 PV Inverter nominal power. HOLDING 1232 401233 RW int32 kW
kw_nom_inverter_68 PV Inverter nominal power. HOLDING 1234 401235 RW int32 kW
kw_nom_inverter_69 PV Inverter nominal power. HOLDING 1236 401237 RW int32 kW
kw_nom_inverter_70 PV Inverter nominal power. HOLDING 1238 401239 RW int32 kW
kw_nom_inverter_71 PV Inverter nominal power. HOLDING 1240 401241 RW int32 kW
kw_nom_inverter_72 PV Inverter nominal power. HOLDING 1242 401243 RW int32 kW
kw_nom_inverter_73 PV Inverter nominal power. HOLDING 1244 401245 RW int32 kW
kw_nom_inverter_74 PV Inverter nominal power. HOLDING 1246 401247 RW int32 kW
kw_nom_inverter_75 PV Inverter nominal power. HOLDING 1248 401249 RW int32 kW
kw_nom_inverter_76 PV Inverter nominal power. HOLDING 1250 401251 RW int32 kW
kw_nom_inverter_77 PV Inverter nominal power. HOLDING 1252 401253 RW int32 kW
kw_nom_inverter_78 PV Inverter nominal power. HOLDING 1254 401255 RW int32 kW
kw_nom_inverter_79 PV Inverter nominal power. HOLDING 1256 401257 RW int32 kW
kw_nom_inverter_80 PV Inverter nominal power. HOLDING 1258 401259 RW int32 kW
kw_nom_inverter_81 PV Inverter nominal power. HOLDING 1260 401261 RW int32 kW
kw_nom_inverter_82 PV Inverter nominal power. HOLDING 1262 401263 RW int32 kW
kw_nom_inverter_83 PV Inverter nominal power. HOLDING 1264 401265 RW int32 kW
kw_nom_inverter_84 PV Inverter nominal power. HOLDING 1266 401267 RW int32 kW
kw_nom_inverter_85 PV Inverter nominal power. HOLDING 1268 401269 RW int32 kW
kw_nom_inverter_86 PV Inverter nominal power. HOLDING 1270 401271 RW int32 kW
kw_nom_inverter_87 PV Inverter nominal power. HOLDING 1272 401273 RW int32 kW
kw_nom_inverter_88 PV Inverter nominal power. HOLDING 1274 401275 RW int32 kW
kw_nom_inverter_89 PV Inverter nominal power. HOLDING 1276 401277 RW int32 kW
kw_nom_inverter_90 PV Inverter nominal power. HOLDING 1278 401279 RW int32 kW
kw_nom_inverter_91 PV Inverter nominal power. HOLDING 1280 401281 RW int32 kW
kw_nom_inverter_92 PV Inverter nominal power. HOLDING 1282 401283 RW int32 kW
kw_nom_inverter_93 PV Inverter nominal power. HOLDING 1284 401285 RW int32 kW
kw_nom_inverter_94 PV Inverter nominal power. HOLDING 1286 401287 RW int32 kW
kw_nom_inverter_95 PV Inverter nominal power. HOLDING 1288 401289 RW int32 kW
kw_nom_inverter_96 PV Inverter nominal power. HOLDING 1290 401291 RW int32 kW
kw_nom_inverter_97 PV Inverter nominal power. HOLDING 1292 401293 RW int32 kW
kw_nom_inverter_98 PV Inverter nominal power. HOLDING 1294 401295 RW int32 kW
kw_nom_inverter_99 PV Inverter nominal power. HOLDING 1296 401297 RW int32 kW
kw_nom_inverter_100 PV Inverter nominal power. HOLDING 1298 401299 RW int32 kW
kw_nom_inverter_101 PV Inverter nominal power. HOLDING 1300 401301 RW int32 kW
elum_id description table address number access type unit
kw_nom_inverter_102 PV Inverter nominal power. HOLDING 1302 401303 RW int32 kW
kw_nom_inverter_103 PV Inverter nominal power. HOLDING 1304 401305 RW int32 kW
kw_nom_inverter_104 PV Inverter nominal power. HOLDING 1306 401307 RW int32 kW
kw_nom_inverter_105 PV Inverter nominal power. HOLDING 1308 401309 RW int32 kW
kw_nom_inverter_106 PV Inverter nominal power. HOLDING 1310 401311 RW int32 kW
kw_nom_inverter_107 PV Inverter nominal power. HOLDING 1312 401313 RW int32 kW
kw_nom_inverter_108 PV Inverter nominal power. HOLDING 1314 401315 RW int32 kW
kw_nom_inverter_109 PV Inverter nominal power. HOLDING 1316 401317 RW int32 kW
kw_nom_inverter_110 PV Inverter nominal power. HOLDING 1318 401319 RW int32 kW
kw_nom_inverter_111 PV Inverter nominal power. HOLDING 1320 401321 RW int32 kW
kw_nom_inverter_112 PV Inverter nominal power. HOLDING 1322 401323 RW int32 kW
kw_nom_inverter_113 PV Inverter nominal power. HOLDING 1324 401325 RW int32 kW
kw_nom_inverter_114 PV Inverter nominal power. HOLDING 1326 401327 RW int32 kW
kw_nom_inverter_115 PV Inverter nominal power. HOLDING 1328 401329 RW int32 kW
kw_nom_inverter_116 PV Inverter nominal power. HOLDING 1330 401331 RW int32 kW
kw_nom_inverter_117 PV Inverter nominal power. HOLDING 1332 401333 RW int32 kW
kw_nom_inverter_118 PV Inverter nominal power. HOLDING 1334 401335 RW int32 kW
kw_nom_inverter_119 PV Inverter nominal power. HOLDING 1336 401337 RW int32 kW
kw_nom_inverter_120 PV Inverter nominal power. HOLDING 1338 401339 RW int32 kW
Parameter of automated genset start/stop:
soc_start_ge BESS SoC triggering genset start. HOLDING 2004 402005 RW int32 %
Parameter of automated genset start/stop:
soc_stop_ge BESS SoC triggering genset stop. HOLDING 2006 402007 RW int32 %
max_ramp_ge Maximum genset active power setpoint ramp. The
HOLDING
difference between the total2012
command
402013
sent to the gensets
RW and the observed
int32 production
kWis limited by this parameter.
pct_min_ge Minimum active power loading setpoint in percentage
HOLDING
of genset primary rated 2014
power.402015 RW int32 %
ge_kw_prp_1 Genset primary rated power. HOLDING 2200 402201 RW int32 kW
ge_kw_prp_2 Genset primary rated power. HOLDING 2202 402203 RW int32 kW
ge_kw_prp_3 Genset primary rated power. HOLDING 2204 402205 RW int32 kW
ge_kw_prp_4 Genset primary rated power. HOLDING 2206 402207 RW int32 kW
ge_kw_prp_5 Genset primary rated power. HOLDING 2208 402209 RW int32 kW
ge_kw_prp_6 Genset primary rated power. HOLDING 2210 402211 RW int32 kW
ge_kw_prp_7 Genset primary rated power. HOLDING 2212 402213 RW int32 kW
ge_kw_prp_8 Genset primary rated power. HOLDING 2214 402215 RW int32 kW
ge_kw_prp_9 Genset primary rated power. HOLDING 2216 402217 RW int32 kW
ge_kw_prp_10 Genset primary rated power. HOLDING 2218 402219 RW int32 kW
ge_kw_prp_11 Genset primary rated power. HOLDING 2220 402221 RW int32 kW
ge_kw_prp_12 Genset primary rated power. HOLDING 2222 402223 RW int32 kW
ge_kw_prp_13 Genset primary rated power. HOLDING 2224 402225 RW int32 kW
elum_id description table address number access type unit
ge_kw_prp_14 Genset primary rated power. HOLDING 2226 402227 RW int32 kW
ge_kw_prp_15 Genset primary rated power. HOLDING 2228 402229 RW int32 kW
ge_kw_prp_16 Genset primary rated power. HOLDING 2230 402231 RW int32 kW
Parameter of deferrable load control based on BESS SoC:
low_soc_bess_defload SoC below which an opening signal is sent to theHOLDING
load breaker. 2600 402601 RW int32 %
Parameter of deferrable load control based on load active power:
high_W_load_defload Load active power above which an opening signal HOLDING
is sent to the load breaker. 2604 402605 RW int32 kW
W_pv Total active power produced by solar inverters. HOLDING 6000 406001 RO float32
Total reactive power produced by solar inverters.
Convention:
Negative: capacitive
VAR_pv Positive: inductive HOLDING 6002 406003 RO float32
Active power at the point of common coupling.
Convention:
Negative: injection
W_grid Positive: absorption HOLDING 6004 406005 RO float32
Reactive power at the point of common coupling.
Convention:
Negative: capacitive
VAR_grid Positive: inductive HOLDING 6006 406007 RO float32
TanPhi_grid Tan phi at the point of common coupling. HOLDING 6008 406009 RO float32
elum_id description table address number access type unit
Activate the EMS.
Values:
True: active
act_ems False: inactive COIL 1 000002 RW bool
Activate grid control.
Values:
True: active
grid_ctl/act False: inactive COIL 20 000021 RW bool
Activate active power export control.
Values:
True: active
grid_ctl/export_ctl/act False: inactive COIL 22 000023 RW bool
Activate peak shaving.
Values:
True: active
grid_ctl/peak_shaving/act False: inactive COIL 24 000025 RW bool
Activate peak shaving SoC reserve.
Values:
True: active
grid_ctl/peak_shaving/soc_reserve/act False: inactive COIL 25 000026 RW bool
Activate automatic blackstart in islanding mode.
Values:
True: active
act_auto_blackstart False: inactive COIL 60 000061 RW bool
elum_id description table address number access type unit
Activate automatic grid reconnection.
Values:
True: active
act_auto_grid_reco False: inactive COIL 61 000062 RW bool
Activate PV control.
Values:
True: active
pv_ctl/act False: inactive COIL 80 000081 RW bool
Activate genset control.
Values:
True: active
ge_ctl/act False: inactive COIL 100 000101 RW bool
Activate automated genset start/stop.
Values:
True: active
ge_ctl/start_stop_ctl/act False: inactive COIL 102 000103 RW bool
Activate deferrable load control.
Values:
True: active
def_load/act False: inactive COIL 124 000125 RW bool
Parameter of deferrable load control:
Activate control based on load active power.
Values:
True: active
def_load/w_load/act False: inactive COIL 125 000126 RW bool
Parameter of deferrable load control:
Activate control based on BESS SoC.
Values:
True: active
def_load/soc/act False: inactive COIL 126 000127 RW bool
dcvbased_derating/act Activate BESS charging power voltage based control.
COIL 150 000151 RW bool
bess_ctl/socbased_derating/act Activate BESS charging power soc based control.
COIL 151 000152 RW bool
Activate BESS control.
Values:
True: active
bess_ctl/act False: inactive COIL 200 000201 RW bool
bess_ctl/soc_target/act Activate bess control - State of Charge target COIL 400 000401 WO bool
bess_ctl/tum/act Activate bess control - Time of Use managementCOIL 2000 002001 WO bool
Parameter for the active power export control:
Minimum active power at the point of common coupling.
Convention:
Negative: injection
kwmin_pcc Positive: absorption HOLDING 1 400002 RW int32 kW
elum_id description table address number access type unit
Parameter for the active power export control:
Phase aggregation method.
Accepted values:
0: Sum of all phases
1: 3 times the value of the phase with the lowest measured active power
wgrid_aggopt_expctl HOLDING 35 400036 RW int32
Parameter for peak shaving:
Phase aggregation method.
Accepted values:
0: Sum of all phases
2: 3 times the value of the phase with the highest measured active power
wgrid_aggopt_peakshave HOLDING 37 400038 RW int32
Parameter for peak shaving:
kwmax_pcc_1 Maximum active power absorption at the point ofHOLDING
common coupling for the timeslot
100 1.
400101 RW int32 kW
Parameter for peak shaving:
kwmax_pcc_2 Maximum active power absorption at the point ofHOLDING
common coupling for the timeslot
102 2.
400103 RW int32 kW
Parameter for peak shaving:
kwmax_pcc_3 Maximum active power absorption at the point ofHOLDING
common coupling for the timeslot
104 3.
400105 RW int32 kW
Parameter for peak shaving:
kwmax_pcc_4 Maximum active power absorption at the point ofHOLDING
common coupling for the timeslot
106 4.
400107 RW int32 kW
Parameter for peak shaving:
kwmax_pcc_5 Maximum active power absorption at the point ofHOLDING
common coupling for the timeslot
108 5.
400109 RW int32 kW
Parameter for peak shaving:
kwmax_pcc_6 Maximum active power absorption at the point ofHOLDING
common coupling for the timeslot
110 6.
400111 RW int32 kW
Parameter for peak shaving:
kwmax_pcc_start_1 Hour of the beginning of the timeslot 1 for the maximum
HOLDING
active power absorption.
150 400151 RW int32 h
Parameter for peak shaving:
kwmax_pcc_start_2 Hour of the beginning of the timeslot 2 for the maximum
HOLDING
active power absorption.
152 400153 RW int32 h
Parameter for peak shaving:
kwmax_pcc_start_3 Hour of the beginning of the timeslot 3 for the maximum
HOLDING
active power absorption.
154 400155 RW int32 h
Parameter for peak shaving:
kwmax_pcc_start_4 Hour of the beginning of the timeslot 4 for the maximum
HOLDING
active power absorption.
156 400157 RW int32 h
Parameter for peak shaving:
kwmax_pcc_start_5 Hour of the beginning of the timeslot 5 for the maximum
HOLDING
active power absorption.
158 400159 RW int32 h
Parameter for peak shaving:
kwmax_pcc_start_6 Hour of the beginning of the timeslot 6 for the maximum
HOLDING
active power absorption.
160 400161 RW int32 h
max_ramp_bess Maximum BESS active power setpoint ramp. TheHOLDING
difference between the total command
202 400203
sent to the BESS
RW and the observed
int32 output is limited
kW by this parameter.
soc_max Maximum allowed SoC for induced charge of theHOLDING
BESS. 204 400205 RW int32 %
soc_min Minimum allowed SoC for induced discharge of the
HOLDING
BESS. 206 400207 RW int32 %
Parameter of peak shaving SoC reserve:
soc_res_1 SoC reserve for the timeslot 1. Only the peak shaving
HOLDING
function can discharge the
220BESS
400221
below the SoC
RWreserve defined.int32 %
Parameter of peak shaving SoC reserve:
soc_res_2 SoC reserve for the timeslot 2. Only the peak shaving
HOLDING
function can discharge the
222BESS
400223
below the SoC
RWreserve defined.int32 %
Parameter of peak shaving SoC reserve:
soc_res_3 SoC reserve for the timeslot 3. Only the peak shaving
HOLDING
function can discharge the
224BESS
400225
below the SoC
RWreserve defined.int32 %
elum_id description table address number access type unit
Parameter of peak shaving SoC reserve:
soc_res_4 SoC reserve for the timeslot 4. Only the peak shaving
HOLDING
function can discharge the
226BESS
400227
below the SoC
RWreserve defined.int32 %
Parameter of peak shaving SoC reserve:
soc_res_5 SoC reserve for the timeslot 5. Only the peak shaving
HOLDING
function can discharge the
228BESS
400229
below the SoC
RWreserve defined.int32 %
Parameter of peak shaving SoC reserve:
soc_res_6 SoC reserve for the timeslot 6. Only the peak shaving
HOLDING
function can discharge the
230BESS
400231
below the SoC
RWreserve defined.int32 %
Parameter of peak shaving SoC reserve:
soc_res_start_1 Hour of the beginning of the timeslot 1 for the SoC
HOLDING
reserve. 240 400241 RW int32 h
Parameter of peak shaving SoC reserve:
soc_res_start_2 Hour of the beginning of the timeslot 2 for the SoC
HOLDING
reserve. 242 400243 RW int32 h
Parameter of peak shaving SoC reserve:
soc_res_start_3 Hour of the beginning of the timeslot 3 for the SoC
HOLDING
reserve. 244 400245 RW int32 h
Parameter of peak shaving SoC reserve:
soc_res_start_4 Hour of the beginning of the timeslot 4 for the SoC
HOLDING
reserve. 246 400247 RW int32 h
Parameter of peak shaving SoC reserve:
soc_res_start_5 Hour of the beginning of the timeslot 5 for the SoC
HOLDING
reserve. 248 400249 RW int32 h
Parameter of peak shaving SoC reserve:
soc_res_start_6 Hour of the beginning of the timeslot 6 for the SoC
HOLDING
reserve. 250 400251 RW int32 h
soc_target_1 State of Charge target for the timeslot 1 HOLDING 260 400261 RW int32 %
soc_target_2 State of Charge target for the timeslot 2 HOLDING 262 400263 RW int32 %
soc_target_3 State of Charge target for the timeslot 3 HOLDING 264 400265 RW int32 %
soc_target_4 State of Charge target for the timeslot 4 HOLDING 266 400267 RW int32 %
soc_target_5 State of Charge target for the timeslot 5 HOLDING 268 400269 RW int32 %
soc_target_6 State of Charge target for the timeslot 6 HOLDING 270 400271 RW int32 %
soc_target_start_1 Hour of the beginning of the timeslot 1 for State of
HOLDING
Charge target 280 400281 RW int32 h
soc_target_start_2 Hour of the beginning of the timeslot 2 for State of
HOLDING
Charge target 282 400283 RW int32 h
soc_target_start_3 Hour of the beginning of the timeslot 3 for State of
HOLDING
Charge target 284 400285 RW int32 h
soc_target_start_4 Hour of the beginning of the timeslot 4 for State of
HOLDING
Charge target 286 400287 RW int32 h
soc_target_start_5 Hour of the beginning of the timeslot 5 for State of
HOLDING
Charge target 288 400289 RW int32 h
soc_target_start_6 Hour of the beginning of the timeslot 6 for State of
HOLDING
Charge target 290 400291 RW int32 h
kw_nom_bess_1 BESS nominal power. HOLDING 500 400501 RW int32 kW
kw_nom_bess_2 BESS nominal power. HOLDING 502 400503 RW int32 kW
kw_nom_bess_3 BESS nominal power. HOLDING 504 400505 RW int32 kW
kw_nom_bess_4 BESS nominal power. HOLDING 506 400507 RW int32 kW
kw_nom_bess_5 BESS nominal power. HOLDING 508 400509 RW int32 kW
kw_nom_bess_6 BESS nominal power. HOLDING 510 400511 RW int32 kW
kw_nom_bess_7 BESS nominal power. HOLDING 512 400513 RW int32 kW
kw_nom_bess_8 BESS nominal power. HOLDING 514 400515 RW int32 kW
kw_nom_bess_9 BESS nominal power. HOLDING 516 400517 RW int32 kW
kw_nom_bess_10 BESS nominal power. HOLDING 518 400519 RW int32 kW
kw_nom_bess_11 BESS nominal power. HOLDING 520 400521 RW int32 kW
elum_id description table address number access type unit
kw_nom_bess_12 BESS nominal power. HOLDING 522 400523 RW int32 kW
kw_nom_bess_13 BESS nominal power. HOLDING 524 400525 RW int32 kW
kw_nom_bess_14 BESS nominal power. HOLDING 526 400527 RW int32 kW
kw_nom_bess_15 BESS nominal power. HOLDING 528 400529 RW int32 kW
kw_nom_bess_16 BESS nominal power. HOLDING 530 400531 RW int32 kW
kwdisc_bess_1 BESS maximum induced discharging power. HOLDING 600 400601 RW int32 kW
kwdisc_bess_2 BESS maximum induced discharging power. HOLDING 602 400603 RW int32 kW
kwdisc_bess_3 BESS maximum induced discharging power. HOLDING 604 400605 RW int32 kW
kwdisc_bess_4 BESS maximum induced discharging power. HOLDING 606 400607 RW int32 kW
kwdisc_bess_5 BESS maximum induced discharging power. HOLDING 608 400609 RW int32 kW
kwdisc_bess_6 BESS maximum induced discharging power. HOLDING 610 400611 RW int32 kW
kwdisc_bess_7 BESS maximum induced discharging power. HOLDING 612 400613 RW int32 kW
kwdisc_bess_8 BESS maximum induced discharging power. HOLDING 614 400615 RW int32 kW
kwdisc_bess_9 BESS maximum induced discharging power. HOLDING 616 400617 RW int32 kW
kwdisc_bess_10 BESS maximum induced discharging power. HOLDING 618 400619 RW int32 kW
kwdisc_bess_11 BESS maximum induced discharging power. HOLDING 620 400621 RW int32 kW
kwdisc_bess_12 BESS maximum induced discharging power. HOLDING 622 400623 RW int32 kW
kwdisc_bess_13 BESS maximum induced discharging power. HOLDING 624 400625 RW int32 kW
kwdisc_bess_14 BESS maximum induced discharging power. HOLDING 626 400627 RW int32 kW
kwdisc_bess_15 BESS maximum induced discharging power. HOLDING 628 400629 RW int32 kW
kwdisc_bess_16 BESS maximum induced discharging power. HOLDING 630 400631 RW int32 kW
kwchar_bess_1 BESS maximum induced charging power. HOLDING 700 400701 RW int32 kW
kwchar_bess_2 BESS maximum induced charging power. HOLDING 702 400703 RW int32 kW
kwchar_bess_3 BESS maximum induced charging power. HOLDING 704 400705 RW int32 kW
kwchar_bess_4 BESS maximum induced charging power. HOLDING 706 400707 RW int32 kW
kwchar_bess_5 BESS maximum induced charging power. HOLDING 708 400709 RW int32 kW
kwchar_bess_6 BESS maximum induced charging power. HOLDING 710 400711 RW int32 kW
kwchar_bess_7 BESS maximum induced charging power. HOLDING 712 400713 RW int32 kW
kwchar_bess_8 BESS maximum induced charging power. HOLDING 714 400715 RW int32 kW
kwchar_bess_9 BESS maximum induced charging power. HOLDING 716 400717 RW int32 kW
kwchar_bess_10 BESS maximum induced charging power. HOLDING 718 400719 RW int32 kW
kwchar_bess_11 BESS maximum induced charging power. HOLDING 720 400721 RW int32 kW
kwchar_bess_12 BESS maximum induced charging power. HOLDING 722 400723 RW int32 kW
kwchar_bess_13 BESS maximum induced charging power. HOLDING 724 400725 RW int32 kW
kwchar_bess_14 BESS maximum induced charging power. HOLDING 726 400727 RW int32 kW
kwchar_bess_15 BESS maximum induced charging power. HOLDING 728 400729 RW int32 kW
kwchar_bess_16 BESS maximum induced charging power. HOLDING 730 400731 RW int32 kW
max_ramp_pv Maximum PV active power setpoint ramp. The difference
HOLDING between the total command
1000 401001
sent to the PV inverters
RW and the observed
int32 production
kWis limited by this parameter.
elum_id description table address number access type unit
kw_nom_inverter_1 PV Inverter nominal power. HOLDING 1100 401101 RW int32 kW
kw_nom_inverter_2 PV Inverter nominal power. HOLDING 1102 401103 RW int32 kW
kw_nom_inverter_3 PV Inverter nominal power. HOLDING 1104 401105 RW int32 kW
kw_nom_inverter_4 PV Inverter nominal power. HOLDING 1106 401107 RW int32 kW
kw_nom_inverter_5 PV Inverter nominal power. HOLDING 1108 401109 RW int32 kW
kw_nom_inverter_6 PV Inverter nominal power. HOLDING 1110 401111 RW int32 kW
kw_nom_inverter_7 PV Inverter nominal power. HOLDING 1112 401113 RW int32 kW
kw_nom_inverter_8 PV Inverter nominal power. HOLDING 1114 401115 RW int32 kW
kw_nom_inverter_9 PV Inverter nominal power. HOLDING 1116 401117 RW int32 kW
kw_nom_inverter_10 PV Inverter nominal power. HOLDING 1118 401119 RW int32 kW
kw_nom_inverter_11 PV Inverter nominal power. HOLDING 1120 401121 RW int32 kW
kw_nom_inverter_12 PV Inverter nominal power. HOLDING 1122 401123 RW int32 kW
kw_nom_inverter_13 PV Inverter nominal power. HOLDING 1124 401125 RW int32 kW
kw_nom_inverter_14 PV Inverter nominal power. HOLDING 1126 401127 RW int32 kW
kw_nom_inverter_15 PV Inverter nominal power. HOLDING 1128 401129 RW int32 kW
kw_nom_inverter_16 PV Inverter nominal power. HOLDING 1130 401131 RW int32 kW
kw_nom_inverter_17 PV Inverter nominal power. HOLDING 1132 401133 RW int32 kW
kw_nom_inverter_18 PV Inverter nominal power. HOLDING 1134 401135 RW int32 kW
kw_nom_inverter_19 PV Inverter nominal power. HOLDING 1136 401137 RW int32 kW
kw_nom_inverter_20 PV Inverter nominal power. HOLDING 1138 401139 RW int32 kW
kw_nom_inverter_21 PV Inverter nominal power. HOLDING 1140 401141 RW int32 kW
kw_nom_inverter_22 PV Inverter nominal power. HOLDING 1142 401143 RW int32 kW
kw_nom_inverter_23 PV Inverter nominal power. HOLDING 1144 401145 RW int32 kW
kw_nom_inverter_24 PV Inverter nominal power. HOLDING 1146 401147 RW int32 kW
kw_nom_inverter_25 PV Inverter nominal power. HOLDING 1148 401149 RW int32 kW
kw_nom_inverter_26 PV Inverter nominal power. HOLDING 1150 401151 RW int32 kW
kw_nom_inverter_27 PV Inverter nominal power. HOLDING 1152 401153 RW int32 kW
kw_nom_inverter_28 PV Inverter nominal power. HOLDING 1154 401155 RW int32 kW
kw_nom_inverter_29 PV Inverter nominal power. HOLDING 1156 401157 RW int32 kW
kw_nom_inverter_30 PV Inverter nominal power. HOLDING 1158 401159 RW int32 kW
kw_nom_inverter_31 PV Inverter nominal power. HOLDING 1160 401161 RW int32 kW
kw_nom_inverter_32 PV Inverter nominal power. HOLDING 1162 401163 RW int32 kW
kw_nom_inverter_33 PV Inverter nominal power. HOLDING 1164 401165 RW int32 kW
kw_nom_inverter_34 PV Inverter nominal power. HOLDING 1166 401167 RW int32 kW
kw_nom_inverter_35 PV Inverter nominal power. HOLDING 1168 401169 RW int32 kW
kw_nom_inverter_36 PV Inverter nominal power. HOLDING 1170 401171 RW int32 kW
kw_nom_inverter_37 PV Inverter nominal power. HOLDING 1172 401173 RW int32 kW
kw_nom_inverter_38 PV Inverter nominal power. HOLDING 1174 401175 RW int32 kW
elum_id description table address number access type unit
kw_nom_inverter_39 PV Inverter nominal power. HOLDING 1176 401177 RW int32 kW
kw_nom_inverter_40 PV Inverter nominal power. HOLDING 1178 401179 RW int32 kW
kw_nom_inverter_41 PV Inverter nominal power. HOLDING 1180 401181 RW int32 kW
kw_nom_inverter_42 PV Inverter nominal power. HOLDING 1182 401183 RW int32 kW
kw_nom_inverter_43 PV Inverter nominal power. HOLDING 1184 401185 RW int32 kW
kw_nom_inverter_44 PV Inverter nominal power. HOLDING 1186 401187 RW int32 kW
kw_nom_inverter_45 PV Inverter nominal power. HOLDING 1188 401189 RW int32 kW
kw_nom_inverter_46 PV Inverter nominal power. HOLDING 1190 401191 RW int32 kW
kw_nom_inverter_47 PV Inverter nominal power. HOLDING 1192 401193 RW int32 kW
kw_nom_inverter_48 PV Inverter nominal power. HOLDING 1194 401195 RW int32 kW
kw_nom_inverter_49 PV Inverter nominal power. HOLDING 1196 401197 RW int32 kW
kw_nom_inverter_50 PV Inverter nominal power. HOLDING 1198 401199 RW int32 kW
kw_nom_inverter_51 PV Inverter nominal power. HOLDING 1200 401201 RW int32 kW
kw_nom_inverter_52 PV Inverter nominal power. HOLDING 1202 401203 RW int32 kW
kw_nom_inverter_53 PV Inverter nominal power. HOLDING 1204 401205 RW int32 kW
kw_nom_inverter_54 PV Inverter nominal power. HOLDING 1206 401207 RW int32 kW
kw_nom_inverter_55 PV Inverter nominal power. HOLDING 1208 401209 RW int32 kW
kw_nom_inverter_56 PV Inverter nominal power. HOLDING 1210 401211 RW int32 kW
kw_nom_inverter_57 PV Inverter nominal power. HOLDING 1212 401213 RW int32 kW
kw_nom_inverter_58 PV Inverter nominal power. HOLDING 1214 401215 RW int32 kW
kw_nom_inverter_59 PV Inverter nominal power. HOLDING 1216 401217 RW int32 kW
kw_nom_inverter_60 PV Inverter nominal power. HOLDING 1218 401219 RW int32 kW
kw_nom_inverter_61 PV Inverter nominal power. HOLDING 1220 401221 RW int32 kW
kw_nom_inverter_62 PV Inverter nominal power. HOLDING 1222 401223 RW int32 kW
kw_nom_inverter_63 PV Inverter nominal power. HOLDING 1224 401225 RW int32 kW
kw_nom_inverter_64 PV Inverter nominal power. HOLDING 1226 401227 RW int32 kW
kw_nom_inverter_65 PV Inverter nominal power. HOLDING 1228 401229 RW int32 kW
kw_nom_inverter_66 PV Inverter nominal power. HOLDING 1230 401231 RW int32 kW
kw_nom_inverter_67 PV Inverter nominal power. HOLDING 1232 401233 RW int32 kW
kw_nom_inverter_68 PV Inverter nominal power. HOLDING 1234 401235 RW int32 kW
kw_nom_inverter_69 PV Inverter nominal power. HOLDING 1236 401237 RW int32 kW
kw_nom_inverter_70 PV Inverter nominal power. HOLDING 1238 401239 RW int32 kW
kw_nom_inverter_71 PV Inverter nominal power. HOLDING 1240 401241 RW int32 kW
kw_nom_inverter_72 PV Inverter nominal power. HOLDING 1242 401243 RW int32 kW
kw_nom_inverter_73 PV Inverter nominal power. HOLDING 1244 401245 RW int32 kW
kw_nom_inverter_74 PV Inverter nominal power. HOLDING 1246 401247 RW int32 kW
kw_nom_inverter_75 PV Inverter nominal power. HOLDING 1248 401249 RW int32 kW
kw_nom_inverter_76 PV Inverter nominal power. HOLDING 1250 401251 RW int32 kW
elum_id description table address number access type unit
kw_nom_inverter_77 PV Inverter nominal power. HOLDING 1252 401253 RW int32 kW
kw_nom_inverter_78 PV Inverter nominal power. HOLDING 1254 401255 RW int32 kW
kw_nom_inverter_79 PV Inverter nominal power. HOLDING 1256 401257 RW int32 kW
kw_nom_inverter_80 PV Inverter nominal power. HOLDING 1258 401259 RW int32 kW
kw_nom_inverter_81 PV Inverter nominal power. HOLDING 1260 401261 RW int32 kW
kw_nom_inverter_82 PV Inverter nominal power. HOLDING 1262 401263 RW int32 kW
kw_nom_inverter_83 PV Inverter nominal power. HOLDING 1264 401265 RW int32 kW
kw_nom_inverter_84 PV Inverter nominal power. HOLDING 1266 401267 RW int32 kW
kw_nom_inverter_85 PV Inverter nominal power. HOLDING 1268 401269 RW int32 kW
kw_nom_inverter_86 PV Inverter nominal power. HOLDING 1270 401271 RW int32 kW
kw_nom_inverter_87 PV Inverter nominal power. HOLDING 1272 401273 RW int32 kW
kw_nom_inverter_88 PV Inverter nominal power. HOLDING 1274 401275 RW int32 kW
kw_nom_inverter_89 PV Inverter nominal power. HOLDING 1276 401277 RW int32 kW
kw_nom_inverter_90 PV Inverter nominal power. HOLDING 1278 401279 RW int32 kW
kw_nom_inverter_91 PV Inverter nominal power. HOLDING 1280 401281 RW int32 kW
kw_nom_inverter_92 PV Inverter nominal power. HOLDING 1282 401283 RW int32 kW
kw_nom_inverter_93 PV Inverter nominal power. HOLDING 1284 401285 RW int32 kW
kw_nom_inverter_94 PV Inverter nominal power. HOLDING 1286 401287 RW int32 kW
kw_nom_inverter_95 PV Inverter nominal power. HOLDING 1288 401289 RW int32 kW
kw_nom_inverter_96 PV Inverter nominal power. HOLDING 1290 401291 RW int32 kW
kw_nom_inverter_97 PV Inverter nominal power. HOLDING 1292 401293 RW int32 kW
kw_nom_inverter_98 PV Inverter nominal power. HOLDING 1294 401295 RW int32 kW
kw_nom_inverter_99 PV Inverter nominal power. HOLDING 1296 401297 RW int32 kW
kw_nom_inverter_100 PV Inverter nominal power. HOLDING 1298 401299 RW int32 kW
kw_nom_inverter_101 PV Inverter nominal power. HOLDING 1300 401301 RW int32 kW
kw_nom_inverter_102 PV Inverter nominal power. HOLDING 1302 401303 RW int32 kW
kw_nom_inverter_103 PV Inverter nominal power. HOLDING 1304 401305 RW int32 kW
kw_nom_inverter_104 PV Inverter nominal power. HOLDING 1306 401307 RW int32 kW
kw_nom_inverter_105 PV Inverter nominal power. HOLDING 1308 401309 RW int32 kW
kw_nom_inverter_106 PV Inverter nominal power. HOLDING 1310 401311 RW int32 kW
kw_nom_inverter_107 PV Inverter nominal power. HOLDING 1312 401313 RW int32 kW
kw_nom_inverter_108 PV Inverter nominal power. HOLDING 1314 401315 RW int32 kW
kw_nom_inverter_109 PV Inverter nominal power. HOLDING 1316 401317 RW int32 kW
kw_nom_inverter_110 PV Inverter nominal power. HOLDING 1318 401319 RW int32 kW
kw_nom_inverter_111 PV Inverter nominal power. HOLDING 1320 401321 RW int32 kW
kw_nom_inverter_112 PV Inverter nominal power. HOLDING 1322 401323 RW int32 kW
kw_nom_inverter_113 PV Inverter nominal power. HOLDING 1324 401325 RW int32 kW
kw_nom_inverter_114 PV Inverter nominal power. HOLDING 1326 401327 RW int32 kW
elum_id description table address number access type unit
kw_nom_inverter_115 PV Inverter nominal power. HOLDING 1328 401329 RW int32 kW
kw_nom_inverter_116 PV Inverter nominal power. HOLDING 1330 401331 RW int32 kW
kw_nom_inverter_117 PV Inverter nominal power. HOLDING 1332 401333 RW int32 kW
kw_nom_inverter_118 PV Inverter nominal power. HOLDING 1334 401335 RW int32 kW
kw_nom_inverter_119 PV Inverter nominal power. HOLDING 1336 401337 RW int32 kW
kw_nom_inverter_120 PV Inverter nominal power. HOLDING 1338 401339 RW int32 kW
Parameter of automated genset start/stop:
soc_start_ge BESS SoC triggering genset start. HOLDING 2004 402005 RW int32 %
Parameter of automated genset start/stop:
soc_stop_ge BESS SoC triggering genset stop. HOLDING 2006 402007 RW int32 %
max_ramp_ge Maximum genset active power setpoint ramp. The
HOLDING
difference between the total2012
command
402013
sent to the gensets
RW and the observed
int32 production
kWis limited by this parameter.
pct_min_ge Minimum active power loading setpoint in percentage
HOLDING
of genset primary rated 2014
power.402015 RW int32 %
ge_kw_prp_1 Genset primary rated power. HOLDING 2200 402201 RW int32 kW
ge_kw_prp_2 Genset primary rated power. HOLDING 2202 402203 RW int32 kW
ge_kw_prp_3 Genset primary rated power. HOLDING 2204 402205 RW int32 kW
ge_kw_prp_4 Genset primary rated power. HOLDING 2206 402207 RW int32 kW
ge_kw_prp_5 Genset primary rated power. HOLDING 2208 402209 RW int32 kW
ge_kw_prp_6 Genset primary rated power. HOLDING 2210 402211 RW int32 kW
ge_kw_prp_7 Genset primary rated power. HOLDING 2212 402213 RW int32 kW
ge_kw_prp_8 Genset primary rated power. HOLDING 2214 402215 RW int32 kW
ge_kw_prp_9 Genset primary rated power. HOLDING 2216 402217 RW int32 kW
ge_kw_prp_10 Genset primary rated power. HOLDING 2218 402219 RW int32 kW
ge_kw_prp_11 Genset primary rated power. HOLDING 2220 402221 RW int32 kW
ge_kw_prp_12 Genset primary rated power. HOLDING 2222 402223 RW int32 kW
ge_kw_prp_13 Genset primary rated power. HOLDING 2224 402225 RW int32 kW
ge_kw_prp_14 Genset primary rated power. HOLDING 2226 402227 RW int32 kW
ge_kw_prp_15 Genset primary rated power. HOLDING 2228 402229 RW int32 kW
ge_kw_prp_16 Genset primary rated power. HOLDING 2230 402231 RW int32 kW
Parameter of deferrable load control based on BESS SoC:
low_soc_bess_defload SoC below which an opening signal is sent to theHOLDING
load breaker. 2600 402601 RW int32 %
Parameter of deferrable load control based on load active power:
high_W_load_defload Load active power above which an opening signal HOLDING
is sent to the load breaker. 2604 402605 RW int32 kW
W_pv Total active power produced by solar inverters. HOLDING 6000 406001 RO float32
Total reactive power produced by solar inverters.
Convention:
Negative: capacitive
VAR_pv Positive: inductive HOLDING 6002 406003 RO float32
Active power at the point of common coupling.
Convention:
Negative: injection
W_grid Positive: absorption HOLDING 6004 406005 RO float32
elum_id description table address number access type unit
Reactive power at the point of common coupling.
Convention:
Negative: capacitive
VAR_grid Positive: inductive HOLDING 6006 406007 RO float32
TanPhi_grid Tan phi at the point of common coupling. HOLDING 6008 406009 RO float32
elum_id description table address number access type unit
elum_id description table address number access type unit
elum_id description table address number access type unit
elum_id description table address number access type unit
elum_id description table address number access type unit
elum_id description table address number access type unit