You are on page 1of 72

TITLE 0

DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

INDEX
SR. NO. DESCRIPTION PAGE NO.

1) INTRODUCTION 3

2) MATERIAL SPECIFICATION 4

3) LOAD CALCULATION 5

4) DESIGN CALCULATION 7

4.1) DESIGN OF JACK SUPPORT BEAM 7

4.2) DESIGN OF ROLLER BEAM 10

4.3) DESIGN OF TROLLEY BEAM 13

4.4) DESIGN OF SPREADER BEAM 16

4.5) DESIGN OF TOWER TIE BEAM 19

5) DESIGN OF TOWERS  22

5.1) DESIGN OF TOWER BASE STOOLS 69

Page‐2

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

1) INTRODUCTION
The design calculation invloves design of temporary structural components used for 
lifting of Turbine and Generator in PT area

The following componnts will be used for the erection operation:
A) Jack support beam ‐ 12m
B) Bridge beam ‐ 27m
C) Spreader beam ‐ 4m
D) Tower tie beam

The temporary lifting arrangement will be checked in accordance with the following codes 
and standards:
IS 800:2007 – “General Construction in Steel – Code of Practice‐Third revision”
IS 2062 – “Hot rolled  medium and high tensile structural steel – specification (7th revision)” 

Page‐3

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

2) MATERIAL SPECIFICATION
The towers are made with steel grade IS 2062 or equivalent IS 800:2007.
 And the other steel materials are with steel grade E350 or equivalent.

Page‐4

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

3) LOAD CALCULATION
The check for temporary lifting arrangement is carried out considering the 
following loads and effects:

A) DEAD LOAD(DL.)
following dead load are considerd for the design purpose
a. Self weight of Strand Jack = 1.71 T
b. self weight of jack support beam = 7.00 T
c. self weight of Roller beam = 27.00 T
d. Rigging equipment = 2.00 T
e. Self weight of strand guide = 1.00 T
B) LIFT LOAD (LL.)
The Lifted Load (LL) is the weight carried by lifting device it is calculated multiplying
 the Item erection weight W by the contingency  5% and D.A.F 5%.
Weight of euipment = 400 T
d.a.f & conitinency (10%) = 40 T
total lift load = 440 T
= 4400 KN

C) DYNAIC AMPLIFICATION FACTOR
Strand jacks operate at low speed and give rise to little or no dynamic loads. 
However, the load transfer between upper and lower gripping mechanism can give
 rise to a small amount of load bounce resulting in an effective additional load of 
up to 5% of the erection weight along with the contingency.
For the design of the temporary system the lifting weight at strand jack point will 
be increased by a factor equal to 1.05 including contingency to take this effect into 
account.

D) WIND LOAD(WL.)
The design wind speeds will be considered corresponding with:
Erection phase/Stand/by phase:  (WL.st)
while the temporary system is erected but out of service (not lifting).
Basic wind speed for Goa = 39 m/s

Service phase: (WL.se)
 that defines the upper wind speed allowable during lifting operations.
Basic wind speed considered while service face = 16 m/s
(As height of the temporary structure is not more than 15 mtrs hence wind load is not 

take into account but for the safe working condition velocity of 16 m/s is to consider.)
Page‐5

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

E) HORIZONTAL NOTIONAL LOAD(NL.)
The structure will be checked against horizontal loads considering notional load 
acting in any direction
Horizontal notional load considerd is 5.00 % of lifted load (LL)
This load covers the requirements of BS 5950 Part 1:
Minimum horizontal force in combinations including dead and live load but 
excluding wind load = 0.5% of all vertical loads (BS 5950 Part 1, Ch. 2.4.2.4).

Minimum horizontal force in combinations including wind load = 1.0% of all vertical
 loads (BS 5950 Part 1, Ch. 2.4.2.3).

Note: load HL is un/factored and it is applied to the entire TLS in any direction.

The Horizontal Notional Load covers the Service Wind Load on Items, which
 therefore will not be considered in our calculations.
notional load = 24.00 T
= 240.00 KN

Page‐6

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

4) DESIGN CALCULATION

4.1 Design of jack support beam 
grade of steel  = 250 N/mm2
loading on jack support beam will be as follows
self weight of beam = 15.00 T
Lifted load = 87.50 T
weight of strand jack = 2.00 T
weight of strand guide = 0.50 T
Total load on jack support beam = 105.00 T

No. of beams for lifting = 2 Nos.
Load on each beam = 52.50 T
factored load ( x 1.25 )  65.00 T
= 650 KN

2.85 65.00 65.00 2.85 m

65.00 65.00

11.00 m

shear force = 52.00 T
bending moment = 148.20 T.m
Factored shear force = 65.00 T
Factored bending moment = 185.25 T.m

Page‐7

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Section Property of Jack suppport  beam

overall depth of section(D) = 920 mm
cross sectional area(A) = 54600.00 mm2
width of flange(b) = 420 mm
thickness of flange(tf) = 40 mm
depth of web (d) = 840 mm
thickness of web(tw) = 65 mm
shear area(Av) = 54600 mm2
Moment of inertia along X‐X(Ixx) = 7.74E+09 mm4
Moment of inertia along Y‐Y (Iyy) = 4.95E+08 mm4
Neutral axis (Yb) = 460 mm
Elastic Section Modulus(Zexx) = 1.68E+07 mm3
Plastic Section Modulus(Zpxx) = 1.89E+07 mm3

Page‐8

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Section Classification
Outstanding element of compression flange = b/T =  (198)/ (25) = 7.92

e = (350/fy) 1/2= (250/350)1/2 = 0.845

For web = (840)/ (25) = 33.6

For Class 1, Compact =9.4e =9.4 x 0.845 = 7.943 > 7.92 hence compression act as a plastic

For Class 1, Plastic =84e = 84 x 0.845 = 70.98 > 33.6 hence web act as a plastic 

d/tw = 840/25 = 33.6 <  67e =67 x 0.845 = 56.62 Web is resistant to shear bucking

Check for shear:
Factored design shear  = 65 T
Allowable shear foece(Vd) = Av X fyw / (√3 x γm0) 
Alowable shear force  = 21000 x 330/ (√3 x 1.1)
Allowable shear force(Vd) = 716.44 T
SAFE

Check for bending:
Factored bending moment = 185.25 T.m
allowable bending moment = bb X Zp X fy /γm0 
allowable bending moment = 1 x 1.89x 10^7 x 250/1.1
allowable bending moment = 428.54 T.m
SAFE

Check for deflection:
Deflection is a serviceability limit state and must be calculated on the basis of 
unfactored imposed load.

maximum deflection (δmax) = P x a x (3l^2 ‐ 4a^2)/24 x E x Ixx
maximum deflection (δmax) = 13.30

allowable deflection = L/300 mm
allowable deflection = 36.67 mm SAFE

Page‐8

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

4.2 Design of Bridge cross head roller beam
grade of steel  = 330 N/mm2
Shell weight per roller = 37.5 T
Selfweight of trolley and rollers = 10.00 T
Factor of safety = 1.25 T
Total load on crosshead roller beam = 47.50 T
Factored load 59.38 T
say = 65 T

65 65 T
5.00 m

55.00 T 125.00 T
27.60 m

shear force = 85.00 T
bending moment = 200.00 T.m
Factored shear force = 127.50 T
Factored bending moment = 300.00 T.m

Section Property of roller beam
overall depth of section(D) = 824 mm
cross sectional area(A) = 80800 mm2
width of flange(b) = 550 mm
thickness of flange(tf) = 62 mm
depth of web (d) = 700 mm
thickness of web(tw) = 20 mm
shear area(Av) = 14000 mm2
Moment of inertia along X‐X(Ixx) = 1.03E+10 mm4
Moment of inertia along Y‐Y (Iyy) = 1.65E+09 mm4
Neutral axis (Yb) = 404.1584158 mm
Elastic Section Modulus(Zexx) = 2.56E+07 mm3
Plastic Section Modulus(Zpxx) = 2.79E+07 mm3

Page‐8

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Section Classification
Outstanding element of compression flange = b/T = (255)/ (40) = 6.375

e = (250/fy) 1/2= (250/350)1/2 = 0.845

For web = (720)/ (20) = 36

For Class 1, Compact =9.4e =9.4 x 0.845 = 7.94 > 6.375 hence compression act as a plastic

For Class 1, Plastic =84e = 84 x 0.845 = 70.98 > 36 hence web act as a plastic 

d/tw = 720/20 = 36 <  67e =67 x 0.845 = 56.62Web is resistant to shear bucking

Page‐9

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Check for shear:
Factored design shear  = 127.50 T
Allowable shear foece(Vd) = Av X fyw / (√3 x γm0) 
Alowable shear force  = 14000 x 330/ (√3 x 1.1)
Allowable shear foece(Vd) = 242.49 T
SAFE

Check for bending:
Factored bending moment = 300.00 T.m
allowable bending moment = bb X Zp X fy /γm0 
allowable bending moment = 1 x 2.79x 10^7 x 330/1.1
allowable bending moment = 836.75 T.m
SAFE

Check for deflection:
Deflection is a serviceability limit state and must be calculated on the basis of 
unfactored imposed load.
Maximum deflection.
maximum deflection (δmax) = P x a x (3l^2 ‐ 4a^2)/24 x E x Ixx
= 26.07 mm
allowable deflection = L/300 mm
allowable deflection = 50.00 mm SAFE

Check for connection
Maximum Shear Force (V) = 85.00 T
Maximum Bending Moment(BM) = 200.00 Tm
Factored shear force = 127.5 T
Factored bending moment = 300 Tm

Check of Bolt Shear
Dia. Of bolt  = 42 mm
No of Bolts = 10 Nos.
Grade of bolt = 10.9 grade
Ultimate stress (Fu) = 1040 N/mm2
Yield stress (Fy) = 940 N/mm2
Factored Shear Force = V = 127.5 T
Shear Capacity of the bolt  = 58.95801687 T
Capacity of 10 shear bolts = 589.5801687
SAFE

Page‐10

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Check of Mac‐alloy bar for Tension (75 dia ‐ 3 nos) 

Grade of Mac‐ally bar = 10.9 grade


Leaver Arm (L.A) = 980.00 mm
FactoredMoment (M) = 300.00 Tm
Tension (T) = M/L.A = 306.12 T
Dia. Of Mac‐alloy bar (d) = 75.00 mm
No. of Mac‐alloy bar = 3.00 Nos.
Tension Capacity of one Mac‐alloy bar = 257.90 T
Total tension capacity = 773.70 T
SAFE

Page‐11

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Check of Mac‐alloy bar for Tension (56 dia ‐ 4 nos)

Grade of Mac‐ally bar = 10.9 grade


Leaver Arm (L.A) = 945.00 mm
FactoredMoment (M) = 300.00 Tm
Tension (T) = M/L.A = 317.46 T
Dia. Of Mac‐alloy bar (d) = 56.00 mm
No. of Mac‐alloy bar = 4.00 Nos.
Tension Capacity of one Mac‐alloy bar = 143.78 T
Total tension capacity = 575.13 T
SAFE

Page‐12

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

4.2 Design of Trolley beam
grade of steel  = 330 N/mm2
Shell weight per point = 50 T
Factor of safety = 1.50
Total load on crosshead roller beam = 50.00 T
Factored load 75.00 T
say = 750 KN

75 75 T
2.00 m 2.00 m

75.00 T 75.00 T
10.00 m

shear force = 50.00 T
bending moment = 100.00 T.m
Factored shear force = 75.00 T
Factored bending moment = 150.00 T.m

Section Property of roller beam
overall depth of section(D) = 780 mm
cross sectional area(A) = 64475 mm2
width of flange(b) = 500 mm
thickness of flange(tf) = 40 mm
depth of web (d) = 315 mm
thickness of web(tw) = 25 mm
shear area(Av) = 20475 mm2
Moment of inertia along X‐X(Ixx) = 6.20E+09 mm4
Moment of inertia along Y‐Y (Iyy) = 8.34E+08 mm4
Neutral axis (Yb) = 390 mm
Elastic Section Modulus(Zexx) = 1.59E+07 mm3
Plastic Section Modulus(Zpxx) = 1.78E+07 mm3

Page‐13

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Section Classification
Outstanding element of compression flange = b/T = (92.5)/ (25) = 3.7

e = (250/fy) 1/2= (250/350)1/2 = 0.845

For web = (720)/ (25) = 28.8

For Class 1, Compact =9.4e =9.4 x 0.845 = 7.94 > 3.7 hence compression act as a plastic

For Class 1, Plastic =84e = 84 x 0.845 = 70.98 > 28.8 hence web act as a plastic 

d/tw = 720/25 = 28.8 <  67e =67 x 0.845 = 56.62Web is resistant to shear bucking

Page‐14

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Check for shear:
Factored design shear  = 75.00 T
Allowable shear foece(Vd) = Av X fyw / (√3 x γm0) 
Alowable shear force  = 20475 x 330/ (√3 x 1.1)
Allowable shear foece(Vd) = 354.64 T
SAFE

Check for bending:
Factored bending moment = 150.00 T.m
allowable bending moment = bb X Zp X fy /γm0 
allowable bending moment = 1 x 1.79x 10^7 x 330/1.1
allowable bending moment = 533.80 T.m
SAFE

Check for deflection:
Deflection is a serviceability limit state and must be calculated on the basis of 
unfactored imposed load.
Maximum deflection.
maximum deflection (δmax) = P x a x (3l^2 ‐ 4a^2)/24 x E x Ixx
= 9.55 mm
allowable deflection = L/300 mm
allowable deflection = 33.33 mm SAFE

Page‐15

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

4.4 Design of Spreader beam

a) when load is acting on center on the beam
grade of steel  = 330 N/mm2
The load from bridge beam beam will be transferred to spacer beam
reaction from tower tie bridge beam = 65.00 T
self weight of beam (1No.) = 10.00 T
Total load on roller beam = 75.00 T
Say 80.00 T
= 800.00 KN

1.50 m 80 T 1.50 m

40 40

3.00 m

shear force = 40.00 T
bending moment = 60 T.m

Factored shear force = 60 T
Factored bending moment = 90 T.m

Section Property of roller beam
overall depth of section(D) = 700 mm
cross sectional area(A) = 62499.00 mm2
width of flange(b) = 600 mm
thickness of flange(tf) = 25 mm
depth of web (d) = 650 mm
thickness of web(tw) = 50 mm
shear area(Av) = 32500 mm2
Moment of inertia along X‐X(Ixx) = 4.56E+09 mm4
Moment of inertia along Y‐Y (Iyy) = 1.77E+09 mm4
Neutral axis (Yb) = 350 mm
Elastic Section Modulus(Zexx) = 1.30E+07 mm3
Plastic Section Modulus(Zpxx) = 1.46E+07 mm3

Page‐16

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Section Classification
Outstanding element of compression flange = b/T = (164)/( 25) = 6.7

e = (250/fy)^1/2= (250/350)^1/2 = 0.845

For web = 650/(50) = 13

For Class 1, Plastic =8.4e =8.4 x 0.845 = 7.1 > 6.7 hence compression act as a plastic
 
For Class 1, Plastic =84e = 84 x 0.845 = 71> 14.72 hence web act as a plastic 

d/tw =650/(25) = 26 <  67e =67 x 0.845 = 56.615 Web is resistant to shear bucking

Page‐17

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Check for shear:

Factored design shear  = 60 T
Allowable shear foece(Vd) = Av X fyw / (√3 x γm0) 
Alowable shear force  = 32500 x 330/ (√3 x 1.1)
Allowable shear foece(Vd) = 562.92 T
SAFE

Check for bending:

Factored bending moment = 90 T.m
allowable bending moment = bb X Zp X fy /γm0 
allowable bending moment = 1 x 14.60x 10^6 x 330/1.1
allowable bending moment = 438.05 T.m
SAFE

Check for deflection:

Deflection is a serviceability limit state and must be calculated on the basis of 
unfactored imposed load.

maximum deflection (δmax) = PxL^3/48xExI
maximum deflection (δmax) = 0.49 mm

allowable deflection = L/300 mm
allowable deflection = 10.00 mm SAFE

Page‐18

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

4.5 Design of Tower tie beam
grade of steel  = 330 N/mm2
The load from spreader beam will be transferred to tower tie beam
reaction from girder beam = 40.00 T
self weight of beam (1No.) = 3.00 T
= T
Say 45.00 T
= 450.00 KN

1.50 m 45 T 1.50 m

22.5 22.5

3.00 m

shear force = 22.50 T
bending moment = 33.75 T.m

Factored shear force = 33.75 T
Factored bending moment = 50.625 T.m

Section Property of roller beam
overall depth of section(D) = 800 mm
cross sectional area(A) = 75040.00 mm2
width of flange(b) = 650 mm
thickness of flange(tf) = 40 mm
depth of web (d) = 720 mm
thickness of web(tw) = 32 mm
shear area(Av) = 23040 mm2
Moment of inertia along X‐X(Ixx) = 8.51E+09 mm4
Moment of inertia along Y‐Y (Iyy) = 1.83E+09 mm4
Neutral axis (Yb) = 400 mm
Elastic Section Modulus(Zexx) = 2.13E+07 mm3
Plastic Section Modulus(Zpxx) = 2.39E+07 mm3

Page‐19

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Section Classification
Outstanding element of compression flange = b/T = (325)/ (40) = 8.125

e = (250/fy) 1/2= (250/350)1/2 = 0.845

For web = (720)/ (32) = 22.50

For Class 1, Compact =9.4e =9.4 x 0.845 = 7.94 > 8.125 hence compression act as a compact
 
For Class 1, Plastic =84e = 84 x 0.845 = 70.98 > 22.50 hence web act as a plastic 

d/tw = 720/32 = 22.50 <  67e =67 x 0.845 = 56.62Web is resistant to shear bucking

Page‐20

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Check for shear:

Factored design shear  = 33.75 T
Allowable shear foece(Vd) = Av X fyw / (√3 x γm0) 
Alowable shear force  = 23040 x 330/ (√3 x 1.1)
Allowable shear foece(Vd) = 399.06 T
SAFE

Check for bending:

Factored bending moment = 50.625 T.m


allowable bending moment = bb X Zp X fy /γm0 
allowable bending moment = 1 x 23.90x 10^6 x 330/1.1
allowable bending moment = 717.22 T.m
SAFE

Check for deflection:

Deflection is a serviceability limit state and must be calculated on the basis of 
unfactored imposed load.

maximum deflection (δmax) = PxL^3/48xExI
maximum deflection (δmax) = 0.15 mm

allowable deflection = L/300 mm
allowable deflection = 10.00 mm SAFE

Page‐21

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

5 Check for Tower 

Page‐22

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

5.1  SPECIFICATIONS

Dimensions
Height of Tower = 16 m
Length of tower = 3m
Width of tower 3m

Member Specifications

Pipe Section vertical 
Outer dia = 457 mm
Thickness = 16 mm

Pipe Section diagonal
Outer dia = 165 mm
Thickness = 6 mm

5.2 LOAD CALCULATIONS
Primary load considered
A) Dead Load (DL):
The load under this category includes self weight of structure.
A 10% increment of self weight of structure has been considered for ladder and wires 
loading.
B) Reaction Load(RL):
the lift load will be considered as the reaction load 
Reaction Load = 40 T
= 400 KN

Page‐23

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

D) Wind Load (WL.)
The design wind speeds will be considered corresponding with:
Erection phase/Stand/by phase:  (WL.st)
while the temporary system is erected but out of service (not lifting).
Basic wind speed for Goa = 39 m/s

Design wind presuure is calculated below.

height  topography  basic wind  design wind 


Height  risk coefficient design wind pressure
coefficient coefficient speed speed
10.00 0.73 1.00 1.00 39.00 28.47 0.49
12.00 0.73 1.02 1.00 39.00 29.04 0.51

Wind load acting on face
Wind load on tower
Height of pannel = 2.000 m
width of tower = 3.000 m
diagonal length = 3.606 m
dia. Of  vertical = 0.457 m
dia. Of  diagonal = 0.165 m
gross area  = 6.000 m2
area of vertical  = 0.914 m2
area of diagonal = 0.595 m2
net area  = 1.509 m2
solidity ratio  = 0.25
D*Vz = 13.271 > 6 m2/s
Cf, round = 1.400 (From Table‐34)

UDL on Tower Members :
upto 10m height
Vertical members = 0.311 KN/m
diagonal members = 0.112 KN/m

10m to 12m
Vertical members = 0.324 KN/m
diagonal members = 0.117 KN/m

Page‐24

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Service phase: (WL.se)
 that defines the upper wind speed allowable during lifting operations.
Basic wind speed considered while service face = 16 m/s
(As height of the temporary structure is not more than 10 mtrs hence wind load is not 
take into account but for the safe working condition velocity of 16 m/s is to consider.)
height  topography  basic wind  design wind 
Height  risk coefficient design wind pressure
coefficient coefficient speed speed

10.00 0.73 1.00 1.00 16.00 11.68 0.08


12.00 0.73 1.02 1.00 16.00 11.91 0.09

Wind load on tower
Height of pannel = 2.000 m
width of tower = 3.000 m
diagonal length = 3.606 m
dia. Of  vertical = 0.457 mm
dia. Of  diagonal = 0.165 mm
gross area  = 6.000 m2
area of vertical  = 0.914 m2
area of diagonal = 0.595 m2
net area  = 1.509 m2 `
solidity ratio  = 0.25
D*Vz = 5.445 > 6 m2/s
Cf, round = 1.400 (From Table‐34)

UDL on Tower Members :
upto 10m height
Vertical members = 0.052 KN/m
diagonal members = 0.019 KN/m
10m to 12m
Vertical members = 0.054 KN/m
diagonal members = 0.020 KN/m

For diagonal wind:
The diagonal wind can be resolved into X,Z directions having component of 0.707 each.
 As per codal provisions the load has to be factored by 1.2 times.

Page‐25

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

5.3 Load Combination considered

LOAD COMB 1004 DL+RL+WLST.(X)
1 1.0 2 1.0 
LOAD COMB 1005 DL+RL+WLST.(‐X)
1 1.0 2 1.0 8 1.0 
LOAD COMB 1006 DL+RL+WLST.(Z)
1 1.0 2 1.0 9 1.0 
LOAD COMB 1007 DL+RL+WLST.(‐Z)
1 1.0 2 1.0 10 1.0 
LOAD COMB 1008 DL+RL+WLST.(D1)
1 1.0 2 1.0 9 0.707 
LOAD COMB 1009 DL+RL‐WLST.(D2)
1 1.0 2 1.0 8 0.707 10 0.707 
LOAD COMB 1034 DL+RL+WLSE.(X)
1 1.0 2 1.0 15 1.0 
LOAD COMB 1035 DL+RL+WLSE.(‐X)
1 1.0 2 1.0 16 1.0 
LOAD COMB 1036 DL+RL+WLSE.(Z)
1 1.0 2 1.0 17 1.0 
LOAD COMB 1037 DL+RL+WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 1038 DL+RL+WLSE.(D1)
1 1.0 2 1.0 15 0.707 17 0.707 
LOAD COMB 1039 DL+RL‐WLSE.(D2)
1 1.0 2 1.0 16 0.707 18 0.707 
LOAD COMB 1040 DL+RL+NL(X)+WLSE.(X)
1 1.0 2 1.0 15 1.0 
LOAD COMB 1041 DL+RL+NL(X)+WLSE.(‐X)
1 1.0 2 1.0 16 1.0 
LOAD COMB 1042 DL+RL+NL(X)+WLSE.(Z)

Page‐26

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

1 1.0 2 1.0 17 1.0 
LOAD COMB 1043 DL+RL+NL(X)+WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 1044 DL+RL+NL(X)+WLSE.(D1)
1 1.0 2 1.0 15 0.707 17 0.707 
LOAD COMB 1045 DL+RL+LN(X)+WLSE.(D2)
1 1.0 2 1.0 16 0.707 18 0.707 
LOAD COMB 1046 DL+RL+NL(‐X)+WLSE.(X)
1 1.0 2 1.0 15 1.0 
LOAD COMB 1047 DL+RL+NL(‐X)+WLSE.(‐X)
1 1.0 2 1.0 16 1.0 
LOAD COMB 1048 DL+RL+NL(‐X)+WLSE.(Z)
1 1.0 2 1.0 17 1.0 
LOAD COMB 1049 DL+RL+NL(‐X)+WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 1050 DL+RL+NL(‐X)+WLSE.(D1)
1 1.0 2 1.0 15 0.707 17 0.707 
LOAD COMB 1051 DL+RL+NL(‐X)+WLSE.(D2)
1 1.0 2 1.0 16 0.707 18 0.707 
LOAD COMB 1052 DL+RL+NL(Z)+WLSE.(X)
1 1.0 2 1.0 15 1.0 
LOAD COMB 1053 DL+RL+NL(Z)+WLSE.(‐X)
1 1.0 2 1.0 16 1.0 
LOAD COMB 1054 DL+RL+NL(Z)+WLSE.(Z)
1 1.0 2 1.0 17 1.0 
LOAD COMB 1055 DL+RL+NL(Z)+WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 1056 DL+RL+NL(Z)+WLSE.(D1)
1 1.0 2 1.0 15 0.707 17 0.707 
LOAD COMB 1057 DL+RL+NL(Z)+WLSE.(D2)
1 1.0 2 1.0 8 0.707 18 0.707 
LOAD COMB 1058 DL+RL+NL(‐Z)+WLSE.(X)
1 1.0 2 1.0 15 1.0 
LOAD COMB 1059 DL+RL+NL(‐Z)+WLSE.(‐X)
1 1.0 2 1.0 16 1.0 
LOAD COMB 1060 DL+RL+NL(‐Z)+WLSE.(Z)
1 1.0 2 1.0 17 1.0 
LOAD COMB 1061 DL+RL+NL(‐Z)+WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 1062 DL+RL+NL(‐Z)+WLSE.(D1)
1 1.0 2 1.0 15 0.707 17 0.707 
LOAD COMB 1063 DL+RL+NL(‐Z)+WLSE.(D2)
1 1.0 2 1.0 16 0.707 18 0.707 

Page‐27

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

********** STRENGTH CRIETERIA ‐ FACTORED LOAD CASES********
LOAD COMB 2000 1.50DL+1.50RL+1.50NL(X)
1 1.5 2 1.5 
LOAD COMB 2001 1.50DL+1.50RL+1.50NL(‐X)
1 1.5 2 1.5 
LOAD COMB 2002 1.50DL+1.50RL+1.50NL(Z)
1 1.5 2 1.5 
LOAD COMB 2003 1.50DL+1.50RL+1.50NL(‐Z)
1 1.5 2 1.5 
LOAD COMB 2004 1.50DL+1.50RL+1.20WLST.(X)
1 1.5 2 1.5 
LOAD COMB 2005 1.50DL+1.50RL+1.20WLST.(‐X)
1 1.5 2 1.5 8 1.2 
LOAD COMB 2006 1.50DL+1.50RL+1.20WLST.(Z)
1 1.5 2 1.5 9 1.2 
LOAD COMB 2007 1.50DL+1.50RL+1.20WLST.(‐Z)
1 1.5 2 1.5 10 1.2 
LOAD COMB 2008 1.50DL+1.50RL+1.20WLST.(D1)
1 1.5 2 1.5 9 1.0605 
LOAD COMB 2009 1.50DL+1.50RL‐1.20WLST.(D2)
1 1.5 2 1.5 8 1.0605 10 1.0605 
LOAD COMB 2010 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(X)
1 1.5 2 1.5 
LOAD COMB 2011 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(‐X)
1 1.5 2 1.5 8 1.2 
LOAD COMB 2012 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(Z)
1 1.5 2 1.5 9 1.2 
LOAD COMB 2013 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(‐Z)
1 1.5 2 1.5 10 1.2 
LOAD COMB 2014 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(D1)
1 1.5 2 1.5 9 1.0605 
LOAD COMB 2015 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(D2)
1 1.5 2 1.5 8 1.0605 10 1.0605 
LOAD COMB 2016 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(X)
1 1.5 2 1.5 
LOAD COMB 2017 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(‐X)
1 1.5 2 1.5 8 1.2 
LOAD COMB 2018 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(Z)
1 1.5 2 1.5 9 1.2 

Page‐28

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

LOAD COMB 2019 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(‐Z)
1 1.5 2 1.5 10 1.2 
LOAD COMB 2020 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(D1)
1 1.5 2 1.5 9 1.0605 
LOAD COMB 2021 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(D2)
1 1.5 2 1.5 8 1.0605 10 1.0605 
LOAD COMB 2022 1.50DL+1.50RL+1.50NL(Z)+1.20WLST.(X)
1 1.5 2 1.5 
LOAD COMB 2023 1.50DL+1.50RL+1.50NL(Z)+1.20WLST.(‐X)
1 1.5 2 1.5 8 1.2 
LOAD COMB 2024 1.50DL+1.50RL+1.50NL(Z)+1.20WLST.(Z)
1 1.5 2 1.5 9 1.2 
LOAD COMB 2025 1.50DL+1.50RL+1.50NL(Z)+1.20WLST.(‐Z)
1 1.5 2 1.5 10 1.2 
LOAD COMB 2026 1.50DL+1.50RL+1.50NL(Z)+1.20WLST.(D1)
1 1.5 2 1.5 9 1.0605 
LOAD COMB 2027 1.50DL+1.50RL+1.50NL(Z)+1.20WLST.(D2)
1 1.5 2 1.5 8 1.0605 10 1.0605 
LOAD COMB 2028 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLST.(X)
1 1.5 2 1.5 
LOAD COMB 2029 1.50DL+1.50RL+1.50NL(‐Z)+1.50WLST.(‐X)
1 1.5 2 1.5 8 1.2 
LOAD COMB 2030 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLST.(Z)
1 1.5 2 1.5 9 1.2 
LOAD COMB 2031 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLST.(‐Z)
1 1.5 2 1.5 10 1.2 
LOAD COMB 2032 1.50DL+1.50RL+1.50NL(‐Z)+1.2WLST.(D1)
1 1.5 2 1.5 9 1.0605 
LOAD COMB 2033 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLST.(D2)
1 1.5 2 1.5 8 1.0605 10 1.0605 

Page‐29

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

LOAD COMB 2037 1.50DL+1.50RL+1.20WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 2038 1.50DL+1.50RL+1.20WLSE.(D1)
1 1.5 2 1.5 15 1.0605 17 1.0605 
LOAD COMB 2039 1.50DL+1.50RL‐1.20WLSE.(D2)
1 1.5 2 1.5 16 1.0605 18 1.0605 
LOAD COMB 2040 1.50DL+1.50RL+1.50NL(X)+1.20WLSE.(X)
1 1.5 2 1.5 15 1.2 
LOAD COMB 2041 1.50DL+1.50RL+1.50NL(X)+1.20WLSE.(‐X)
1 1.5 2 1.5 16 1.2 
LOAD COMB 2042 1.50DL+1.50RL+1.50NL(X)+1.20WLSE.(Z)
1 1.5 2 1.5 17 1.2 
LOAD COMB 2043 1.50DL+1.50RL+1.50NL(X)+1.20WLSE.(‐Z)
1 1.5 2 1.5 18 1.2 
LOAD COMB 2044 1.50DL+1.50RL+1.50NL(X)+1.20WLSE.(D1)
1 1.5 2 1.5 15 1.0605 17 1.0605 
LOAD COMB 2045 1.50DL+1.50RL+1.50NL(X)+1.50WLSE.(D2)
1 1.5 2 1.5 16 1.0605 18 1.0605 
LOAD COMB 2046 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(X)
1 1.5 2 1.5 15 1.2 
LOAD COMB 2047 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(‐X)
1 1.5 2 1.5 16 1.2 
LOAD COMB 2048 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(Z)
1 1.5 2 1.5 17 1.2 
LOAD COMB 2049 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(‐Z)
1 1.5 2 1.5 18 1.2 
LOAD COMB 2050 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(D1)
1 1.5 2 1.5 15 1.0605 17 1.0605 
LOAD COMB 2051 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(D2)
1 1.5 2 1.5 16 1.0605 18 1.0605 
LOAD COMB 2052 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(X)
1 1.5 2 1.5 15 1.2 
LOAD COMB 2053 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(‐X)
1 1.5 2 1.5 16 1.2 
LOAD COMB 2054 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(Z)
1 1.5 2 1.5 17 1.2 

Page‐30

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

LOAD COMB 2055 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(‐Z)
1 1.5 2 1.5 18 1.2 
LOAD COMB 2056 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(D1)
1 1.5 2 1.5 15 1.0605 17 1.0605 
LOAD COMB 2057 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(D2)
1 1.0 2 1.0 8 0.707 18 0.707 
LOAD COMB 2058 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(X)
1 1.5 2 1.5 15 1.2 
LOAD COMB 2059 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(‐X)
1 1.5 2 1.5 16 1.2 
LOAD COMB 2060 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(Z)
1 1.5 2 1.5 17 1.2 
LOAD COMB 2061 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(‐Z)
1 1.5 2 1.5 18 1.2 
LOAD COMB 2062 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(D1)
1 1.5 2 1.5 15 1.0605 17 1.0605 
LOAD COMB 2063 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(D2)
1 1.5 2 1.5 16 1.0605 18 1.0605 
******* Deflection check criteria******
LOAD COMB 3001 DL+RL+WLST.(X)
1 1.0 2 1.0 
LOAD COMB 3002 DL+RL+WLST.(‐X)
1 1.0 2 1.0 8 0.5625 
LOAD COMB 3003 DL+RL+WLST.(Z)
1 1.0 2 1.0 9 0.5625 
LOAD COMB 3004 DL+RL+WLST.(‐Z)
1 1.0 2 1.0 10 0.5625 
LOAD COMB 3005 DL+RL+WLST.(D1)
1 1.0 2 1.0 9 0.4 
LOAD COMB 3006 DL+RL‐WLST.(D2)
1 1.0 2 1.0 8 0.4 10 0.4 
LOAD COMB 3007 DL+RL+NL(X)+WLST.(X)
1 1.0 2 1.0 
LOAD COMB 3008 DL+RL+NL(X)+WLST.(‐X)
1 1.0 2 1.0 8 0.5625 
LOAD COMB 3009 DL+RL+NL(X)+WLST.(Z)
1 1.0 2 1.0 9 0.5625 
LOAD COMB 3010 DL+RL+NL(X)+WLST.(‐Z)
1 1.0 2 1.0 10 0.5625 
LOAD COMB 3011 DL+RL+NL(X)+WLST.(D1)
1 1.0 2 1.0 9 0.4 
LOAD COMB 3012 DL+RL+LN(X)+WLST.(D2)
1 1.0 2 1.0 8 0.4 10 0.4 
LOAD COMB 3013 DL+RL+NL(‐X)+WLST.(X)
1 1.0 2 1.0 
LOAD COMB 3014 DL+RL+NL(‐X)+WLST.(‐X)
1 1.0 2 1.0 8 0.5625 
LOAD COMB 3015 DL+RL+NL(‐X)+WLST.(Z)
1 1.0 2 1.0 9 0.5625 
LOAD COMB 3016 DL+RL+NL(‐X)+WLST.(‐Z)
1 1.0 2 1.0 10 0.5625 
LOAD COMB 3017 DL+RL+NL(‐X)+WLST.(D1)
1 1.0 2 1.0 9 0.4 

Page‐31

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT LTD AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020
©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

LOAD COMB 3018 DL+RL+NL(‐X)+WLST.(D2)
1 1.0 2 1.0 8 0.4 10 0.4 
LOAD COMB 3019 DL+RL+NL(Z)+WLST.(X)
1 1.0 2 1.0 
LOAD COMB 3020 DL+RL+NL(Z)+WLST.(‐X)
1 1.0 2 1.0 8 0.5625 
LOAD COMB 3021 DL+RL+NL(Z)+WLST.(Z)
1 1.0 2 1.0 9 0.5625 
LOAD COMB 3022 DL+RL+NL(Z)+WLST.(‐Z)
1 1.0 2 1.0 10 0.5625 
LOAD COMB 3023 DL+RL+NL(Z)+WLST.(D1)
1 1.0 2 1.0 9 0.4 
LOAD COMB 3024 DL+RL+NL(Z)+WLST.(D2)
1 1.0 2 1.0 8 0.4 10 0.4 
LOAD COMB 3025 DL+RL+NL(‐Z)+WLST.(X)
1 1.0 2 1.0 
LOAD COMB 3026 DL+RL+NL(‐Z)+WLST.(‐X)
1 1.0 2 1.0 8 0.5625 
LOAD COMB 3027 DL+RL+NL(‐Z)+WLST.(Z)
1 1.0 2 1.0 9 0.5625 
LOAD COMB 3028 DL+RL+NL(‐Z)+WLST.(‐Z)
1 1.0 2 1.0 10 0.5625 
LOAD COMB 3029 DL+RL+NL(‐Z)+WLST.(D1)
1 1.0 2 1.0 9 0.4 
LOAD COMB 3030 DL+RL+NL(‐Z)+WLST.(D2)
1 1.0 2 1.0 8 0.4 10 0.4 
************************
LOAD COMB 3031 DL+RL+WLSE.(X)
1 1.0 2 1.0 15 0.5625 
LOAD COMB 3032 DL+RL+WLSE.(‐X)
1 1.0 2 1.0 16 0.5625 
LOAD COMB 3033 DL+RL+WLSE.(Z)
1 1.0 2 1.0 17 0.5625 

Page‐32

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

LOAD COMB 3034 DL+RL+WLSE.(‐Z)
1 1.0 2 1.0 18 0.5625 
LOAD COMB 3035 DL+RL+WLSE.(D1)
1 1.0 2 1.0 15 0.4 17 0.4 
LOAD COMB 3036 DL+RL‐WLSE.(D2)
1 1.0 2 1.0 16 0.4 18 0.4 
LOAD COMB 3037 DL+RL+NL(X)+WLSE.(X)
1 1.0 2 1.0 15 0.5625 
LOAD COMB 3038 DL+RL+NL(X)+WLSE.(‐X)
1 1.0 2 1.0 16 0.5625 
LOAD COMB 3039 DL+RL+NL(X)+WLSE.(Z)
1 1.0 2 1.0 17 0.5625 
LOAD COMB 3040 DL+RL+NL(X)+WLSE.(‐Z)
1 1.0 2 1.0 18 0.5625 
LOAD COMB 3041 DL+RL+NL(X)+WLSE.(D1)
1 1.0 2 1.0 15 0.4 17 0.4 
LOAD COMB 3042 DL+RL+LN(X)+WLSE.(D2)
1 1.0 2 1.0 16 0.4 18 0.4 
LOAD COMB 3043 DL+RL+NL(‐X)+WLSE.(X)
1 1.0 2 1.0 15 0.5625 
LOAD COMB 3044 DL+RL+NL(‐X)+WLSE.(‐X)
1 1.0 2 1.0 16 0.5625 
LOAD COMB 3045 DL+RL+NL(‐X)+WLSE.(Z)
1 1.0 2 1.0 17 0.5625 
LOAD COMB 3046 DL+RL+NL(‐X)+WLSE.(‐Z)
1 1.0 2 1.0 18 0.5625 
LOAD COMB 3047 DL+RL+NL(‐X)+WLSE.(D1)
1 1.0 2 1.0 15 0.4 17 0.4 
LOAD COMB 3048 DL+RL+NL(‐X)+WLSE.(D2)
1 1.0 2 1.0 16 0.4 18 0.4 
LOAD COMB 3049 DL+RL+NL(Z)+WLSE.(X)
1 1.0 2 1.0 15 0.5625 
LOAD COMB 3050 DL+RL+NL(Z)+WLSE.(‐X)
1 1.0 2 1.0 16 0.5625 
LOAD COMB 3051 DL+RL+NL(Z)+WLSE.(Z)
1 1.0 2 1.0 17 0.5625 
LOAD COMB 3052 DL+RL+NL(Z)+WLSE.(‐Z)
1 1.0 2 1.0 18 0.5625 
LOAD COMB 3053 DL+RL+NL(Z)+WLSE.(D1)
1 1.0 2 1.0 15 0.4 17 0.4 
LOAD COMB 3054 DL+RL+NL(Z)+WLSE.(D2)
1 1.0 2 1.0 8 0.4 18 0.4 
LOAD COMB 3055 DL+RL+NL(‐Z)+WLSE.(X)
1 1.0 2 1.0 15 0.5625 
LOAD COMB 3056 DL+RL+NL(‐Z)+WLSE.(‐X)
1 1.0 2 1.0 16 0.5625 
LOAD COMB 3057 DL+RL+NL(‐Z)+WLSE.(Z)
1 1.0 2 1.0 17 0.5625 
LOAD COMB 3058 DL+RL+NL(‐Z)+WLSE.(‐Z)
1 1.0 2 1.0 18 0.5625 

Page‐33

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

STAAD PRO INPUT

STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 15‐Jul‐20
END JOB INFORMATION
INPUT WIDTH 79
UNIT METER KN
JOINT COORDINATES
1 0.15 0 0; 2 3.15 0 0; 3 0.15 0 3; 4 3.15 0 3; 5 0.15 2 0; 6 3.15 2 0;
7 0.15 2 3; 8 3.15 2 3; 9 0.15 4 0; 10 3.15 4 0; 11 0.15 4 3; 12 3.15 4 3;
13 0.15 6 0; 14 3.15 6 0; 15 0.15 6 3; 16 3.15 6 3; 17 0.15 8 0; 18 3.15 8 0;
19 0.15 8 3; 20 3.15 8 3; 21 0.15 10 0; 22 3.15 10 0; 23 0.15 10 3;
24 3.15 10 3; 25 0.15 12 0; 26 3.15 12 0; 27 0.15 12 3; 28 3.15 12 3;
117 9.55 0 0; 118 12.55 0 0; 119 9.55 0 3; 120 12.55 0 3; 121 9.55 2 0;
122 12.55 2 0; 123 9.55 2 3; 124 12.55 2 3; 125 9.55 4 0; 126 12.55 4 0;
127 9.55 4 3; 128 12.55 4 3; 129 9.55 6 0; 130 12.55 6 0; 131 9.55 6 3;
132 12.55 6 3; 133 9.55 8 0; 134 12.55 8 0; 135 9.55 8 3; 136 12.55 8 3;
137 9.55 10 0; 138 12.55 10 0; 139 9.55 10 3; 140 12.55 10 3; 141 10.5 12 0;
142 13.5 12 0; 143 10.5 12 3; 144 13.5 12 3; 145 0.15 14 0; 146 3.15 14 0;
147 0.15 14 3; 148 3.15 14 3; 149 0.15 16 0; 150 3.15 16 0; 151 0.15 16 3;
152 3.15 16 3; 153 9.55 14 0; 154 12.55 14 0; 155 9.55 14 3; 156 12.55 14 3;
157 9.55 16 0; 158 12.55 16 0; 159 9.55 16 3; 160 12.55 16 3; 161 9.55 12 0;
162 9.55 12 3; 163 12.55 12 0; 164 12.55 12 3;
MEMBER INCIDENCES
5 1 5; 6 2 6; 7 4 8; 8 3 7; 9 5 9; 10 6 10; 11 8 12; 12 7 11; 13 9 13;
14 10 14; 15 12 16; 16 11 15; 17 13 17; 18 14 18; 19 16 20; 20 15 19; 21 17 21;
22 18 22; 23 20 24; 24 19 23; 25 21 25; 26 22 26; 27 24 28; 28 23 27; 29 12 9;
30 19 18; 31 3 5; 32 5 11; 33 11 13; 34 13 19; 35 19 21; 36 21 27; 37 4 7;
38 7 12; 39 12 15; 40 15 20; 41 20 23; 42 23 28; 43 1 6; 44 6 9; 45 9 14;
46 14 17; 47 17 22; 48 22 25; 49 2 8; 50 8 10; 51 10 16; 52 16 18; 53 18 24;
54 24 26; 224 117 121; 225 118 122; 226 120 124; 227 119 123; 228 121 125;
229 122 126; 230 124 128; 231 123 127; 232 125 129; 233 126 130; 234 128 132;
235 127 131; 236 129 133; 237 130 134; 238 132 136; 239 131 135; 240 133 137;
241 134 138; 242 136 140; 243 135 139; 244 137 161; 245 138 163; 246 140 164;
247 139 162; 248 128 125; 249 135 134; 250 119 121; 251 121 127; 252 127 129;
253 129 135; 254 135 137; 255 137 162; 256 120 123; 257 123 128; 258 128 131;
259 131 136; 260 136 139; 261 139 164; 262 117 122; 263 122 125; 264 125 130;
265 130 133; 266 133 138; 267 138 161; 268 118 124; 269 124 126; 270 126 132;
271 132 134; 272 134 140; 273 140 163; 276 25 145; 277 26 146; 278 28 148;
279 27 147; 280 145 149; 281 146 150; 282 148 152; 283 147 151; 284 27 145;
285 145 151; 286 28 147; 287 147 152; 288 25 146; 289 146 149; 290 26 148;
291 148 150; 292 151 149; 293 152 150; 294 161 153; 295 163 154; 296 164 156;
297 162 155; 298 153 157; 299 154 158; 300 156 160; 301 155 159; 302 162 153;
303 153 159; 304 164 155; 305 155 160; 306 161 154; 307 154 157; 308 163 156;
309 156 158; 310 159 157; 311 160 158;

Page‐34

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

START USER TABLE
END
DEFINE MATERIAL START
ISOTROPIC STEEL
E 2.05e+008
POISSON 0.3
DENSITY 76.8195
ALPHA 1.2e‐005

DAMP 0.03
TYPE STEEL
STRENGTH FY 253200 FU 407800 RY 1.5 RT 1.2
END DEFINE MATERIAL
MEMBER PROPERTY INDIAN
5 TO 28 224 TO 247 276 TO 283 294 TO 301 TABLE ST PIPE OD 0.457 ID 0.425
29 TO 54 248 TO 273 284 TO 291 302 TO 309 TABLE ST PIPE OD 0.165 ID 0.153
MEMBER PROPERTY
292 293 310 311 TAPERED 0.7 0.032 0.7 0.65 0.04 0.65 0.04
CONSTANTS
MATERIAL STEEL ALL
SUPPORTS
1 TO 4 117 TO 120 FIXED
MEMBER RELEASE
29 TO 54 248 TO 273 284 TO 291 302 TO 309 START MPY 0.9999 MPZ 0.9999
29 TO 54 248 TO 273 284 TO 291 302 TO 309 END MY MZ
**** PRIMARY LOAD CASES****
**** DEAD LOAD OF TOWER + REACTION DUE TO TOP STRUCTURE****
LOAD 1 LOADTYPE Dead  TITLE DEAD LOAD
SELFWEIGHT Y ‐1.1 
SELFWEIGHT Y ‐1.1 LIST 311
SELFWEIGHT Y ‐1.1 LIST 310
SELFWEIGHT Y ‐1.1 LIST 293
SELFWEIGHT Y ‐1.1 LIST 292
**** REACTION FROM LIFT LOAD = 160 TON =1600/2 = 800KN****
LOAD 2 LOADTYPE Dead  TITLE REACTION
MEMBER LOAD
292 293 310 311 CON GY ‐400 1.5
*LOAD 7 LOADTYPE Wind  TITLE WLST.(X)
MEMBER LOAD
5 8 9 12 13 16 17 20 21 24 224 227 228 231 232 235 236 239 240 243 276 279 ‐
294 297 UNI GX 0.396
31 TO 35 250 TO 254 284 302 UNI GX 0.143
25 28 244 247 280 283 298 301 UNI GX 0.412
36 255 285 303 UNI GX 0.149
LOAD 8 LOADTYPE Wind  TITLE WLST(‐X)

Page‐35

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

MEMBER LOAD
6 7 10 11 14 15 18 19 22 23 225 226 229 230 233 234 237 238 241 242 277 278 ‐
295 296 UNI GX ‐0.396
50 TO 53 269 TO 272 290 308 UNI GX ‐0.143
26 27 245 246 281 282 299 300 UNI GX ‐0.412
54 273 291 309 UNI GX ‐0.149
LOAD 9 LOADTYPE Wind  TITLE WLST.(Z)
MEMBER LOAD
5 6 9 10 13 14 17 18 21 22 224 225 228 229 232 233 236 237 240 241 276 277 ‐
294 295 UNI GZ 0.396
43 TO 47 262 TO 266 288 306 UNI GZ 0.143
25 26 244 245 280 281 298 299 UNI GZ 0.412

48 267 289 307 UNI GZ 0.149
LOAD 10 LOADTYPE Wind  TITLE WLST.(‐Z)
MEMBER LOAD
7 8 11 12 15 16 19 20 23 24 226 227 230 231 234 235 238 239 242 243 278 279 ‐
296 297 UNI GZ ‐0.396
37 TO 41 256 TO 260 286 304 UNI GZ ‐0.149
27 28 246 247 282 283 300 301 UNI GZ ‐0.412
42 261 287 305 UNI GZ ‐0.149
***** WIND LOAD DURING SERVICE PHASE*****
***** WIND SPEED = 16M/S*****
LOAD 15 LOADTYPE Wind  TITLE WLSE.(X)
MEMBER LOAD
5 8 9 12 13 16 17 20 21 24 224 227 228 231 232 235 236 239 240 243 276 279 ‐
294 297 UNI GX 0.052
31 TO 35 250 TO 254 284 302 UNI GX 0.019
25 28 244 247 280 283 298 301 UNI GX 0.054
36 255 285 303 UNI GX 0.02
LOAD 16 LOADTYPE Wind  TITLE WLSE.(‐X)
MEMBER LOAD
6 7 10 11 14 15 18 19 22 23 225 226 229 230 233 234 237 238 241 242 277 278 ‐
295 296 UNI GX ‐0.052
50 TO 53 269 TO 272 290 308 UNI GX ‐0.019
26 27 245 246 281 282 299 300 UNI GX ‐0.054
54 273 291 309 UNI GX ‐0.02
LOAD 17 LOADTYPE Wind  TITLE WLSE.(Z)
MEMBER LOAD
5 6 9 10 13 14 17 18 21 22 224 225 228 229 232 233 236 237 240 241 276 277 ‐
294 295 UNI GZ 0.052
43 TO 47 262 TO 266 288 306 UNI GZ 0.019
25 26 244 245 280 281 298 299 UNI GZ 0.054
48 267 289 307 UNI GZ 0.02
LOAD 18 LOADTYPE Wind  TITLE WLSE.(‐Z)
MEMBER LOAD
7 8 11 12 15 16 19 20 23 24 226 227 230 231 234 235 238 239 242 243 278 279 ‐
296 297 UNI GZ ‐0.052
37 TO 41 256 TO 260 286 304 UNI GZ ‐0.019
27 28 246 247 282 283 300 301 UNI GZ ‐0.054

Page‐36

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

42 261 287 305 UNI GZ ‐0.02
**** SERVICIBILITY CRITERIA ‐ UNFACTORED LOAD CASES******
LOAD COMB 1004 DL+RL+WLST.(X)
1 1.0 2 1.0 
LOAD COMB 1005 DL+RL+WLST.(‐X)
1 1.0 2 1.0 8 1.0 
LOAD COMB 1006 DL+RL+WLST.(Z)
1 1.0 2 1.0 9 1.0 
LOAD COMB 1007 DL+RL+WLST.(‐Z)
1 1.0 2 1.0 10 1.0 
LOAD COMB 1008 DL+RL+WLST.(D1)
1 1.0 2 1.0 9 0.707 
LOAD COMB 1009 DL+RL‐WLST.(D2)
1 1.0 2 1.0 8 0.707 10 0.707 
LOAD COMB 1034 DL+RL+WLSE.(X)
1 1.0 2 1.0 15 1.0 
LOAD COMB 1035 DL+RL+WLSE.(‐X)
1 1.0 2 1.0 16 1.0 
LOAD COMB 1036 DL+RL+WLSE.(Z)
1 1.0 2 1.0 17 1.0 
LOAD COMB 1037 DL+RL+WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 1038 DL+RL+WLSE.(D1)
1 1.0 2 1.0 15 0.707 17 0.707 
LOAD COMB 1039 DL+RL‐WLSE.(D2)
1 1.0 2 1.0 16 0.707 18 0.707 
LOAD COMB 1040 DL+RL+NL(X)+WLSE.(X)
1 1.0 2 1.0 15 1.0 
LOAD COMB 1041 DL+RL+NL(X)+WLSE.(‐X)
1 1.0 2 1.0 16 1.0 
LOAD COMB 1042 DL+RL+NL(X)+WLSE.(Z)
1 1.0 2 1.0 17 1.0 
LOAD COMB 1043 DL+RL+NL(X)+WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 1044 DL+RL+NL(X)+WLSE.(D1)
1 1.0 2 1.0 15 0.707 17 0.707 
LOAD COMB 1045 DL+RL+LN(X)+WLSE.(D2)
1 1.0 2 1.0 16 0.707 18 0.707 
LOAD COMB 1046 DL+RL+NL(‐X)+WLSE.(X)
1 1.0 2 1.0 15 1.0 
LOAD COMB 1047 DL+RL+NL(‐X)+WLSE.(‐X)
1 1.0 2 1.0 16 1.0 
LOAD COMB 1048 DL+RL+NL(‐X)+WLSE.(Z)
1 1.0 2 1.0 17 1.0 
LOAD COMB 1049 DL+RL+NL(‐X)+WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 1050 DL+RL+NL(‐X)+WLSE.(D1)
1 1.0 2 1.0 15 0.707 17 0.707 
LOAD COMB 1051 DL+RL+NL(‐X)+WLSE.(D2)

Page‐37

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

1 1.0 2 1.0 16 0.707 18 0.707 
LOAD COMB 1052 DL+RL+NL(Z)+WLSE.(X)
1 1.0 2 1.0 15 1.0 
LOAD COMB 1053 DL+RL+NL(Z)+WLSE.(‐X)
1 1.0 2 1.0 16 1.0 
LOAD COMB 1054 DL+RL+NL(Z)+WLSE.(Z)
1 1.0 2 1.0 17 1.0 
LOAD COMB 1055 DL+RL+NL(Z)+WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 1056 DL+RL+NL(Z)+WLSE.(D1)
1 1.0 2 1.0 15 0.707 17 0.707 
LOAD COMB 1057 DL+RL+NL(Z)+WLSE.(D2)
1 1.0 2 1.0 8 0.707 18 0.707 
LOAD COMB 1058 DL+RL+NL(‐Z)+WLSE.(X)
1 1.0 2 1.0 15 1.0 
LOAD COMB 1059 DL+RL+NL(‐Z)+WLSE.(‐X)
1 1.0 2 1.0 16 1.0 
LOAD COMB 1060 DL+RL+NL(‐Z)+WLSE.(Z)
1 1.0 2 1.0 17 1.0 
LOAD COMB 1061 DL+RL+NL(‐Z)+WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 1062 DL+RL+NL(‐Z)+WLSE.(D1)
1 1.0 2 1.0 15 0.707 17 0.707 
LOAD COMB 1063 DL+RL+NL(‐Z)+WLSE.(D2)
1 1.0 2 1.0 16 0.707 18 0.707 
********** STRENGTH CRIETERIA ‐ FACTORED LOAD CASES********
LOAD COMB 2000 1.50DL+1.50RL+1.50NL(X)
1 1.5 2 1.5 
LOAD COMB 2001 1.50DL+1.50RL+1.50NL(‐X)
1 1.5 2 1.5 
LOAD COMB 2002 1.50DL+1.50RL+1.50NL(Z)
1 1.5 2 1.5 
LOAD COMB 2003 1.50DL+1.50RL+1.50NL(‐Z)
1 1.5 2 1.5 
LOAD COMB 2004 1.50DL+1.50RL+1.20WLST.(X)
1 1.5 2 1.5 
LOAD COMB 2005 1.50DL+1.50RL+1.20WLST.(‐X)

Page‐38

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

1 1.5 2 1.5 8 1.2 
LOAD COMB 2006 1.50DL+1.50RL+1.20WLST.(Z)
1 1.5 2 1.5 9 1.2 
LOAD COMB 2007 1.50DL+1.50RL+1.20WLST.(‐Z)
1 1.5 2 1.5 10 1.2 
LOAD COMB 2008 1.50DL+1.50RL+1.20WLST.(D1)
1 1.5 2 1.5 9 1.0605 
LOAD COMB 2009 1.50DL+1.50RL‐1.20WLST.(D2)
1 1.5 2 1.5 8 1.0605 10 1.0605 
LOAD COMB 2010 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(X)
1 1.5 2 1.5 
LOAD COMB 2011 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(‐X)
1 1.5 2 1.5 8 1.2 
LOAD COMB 2012 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(Z)
1 1.5 2 1.5 9 1.2 
LOAD COMB 2013 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(‐Z)
1 1.5 2 1.5 10 1.2 
LOAD COMB 2014 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(D1)
1 1.5 2 1.5 9 1.0605 
LOAD COMB 2015 1.50DL+1.50RL+1.50NL(X)+1.20WLST.(D2)
1 1.5 2 1.5 8 1.0605 10 1.0605 
LOAD COMB 2016 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(X)
1 1.5 2 1.5 
LOAD COMB 2017 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(‐X)
1 1.5 2 1.5 8 1.2 
LOAD COMB 2018 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(Z)
1 1.5 2 1.5 9 1.2 
LOAD COMB 2019 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(‐Z)
1 1.5 2 1.5 10 1.2 
LOAD COMB 2020 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(D1)
1 1.5 2 1.5 9 1.0605 
LOAD COMB 2021 1.50DL+1.50RL+1.50NL(‐X)+1.20WLST.(D2)
1 1.5 2 1.5 8 1.0605 10 1.0605 
LOAD COMB 2022 1.50DL+1.50RL+1.50NL(Z)+1.20WLST.(X)
1 1.5 2 1.5 
LOAD COMB 2023 1.50DL+1.50RL+1.50NL(Z)+1.20WLST.(‐X)
1 1.5 2 1.5 8 1.2 
LOAD COMB 2024 1.50DL+1.50RL+1.50NL(Z)+1.20WLST.(Z)
1 1.5 2 1.5 9 1.2 

Page‐39

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

1 1.5 2 1.5 
LOAD COMB 2029 1.50DL+1.50RL+1.50NL(‐Z)+1.50WLST.(‐X)
1 1.5 2 1.5 8 1.2 
LOAD COMB 2030 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLST.(Z)
1 1.5 2 1.5 9 1.2 
LOAD COMB 2031 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLST.(‐Z)
1 1.5 2 1.5 10 1.2 
LOAD COMB 2032 1.50DL+1.50RL+1.50NL(‐Z)+1.2WLST.(D1)
1 1.5 2 1.5 9 1.0605 
LOAD COMB 2033 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLST.(D2)
1 1.5 2 1.5 8 1.0605 10 1.0605 
************************
LOAD COMB 2034 1.50DL+1.50RL+1.20WLSE.(X)
1 1.5 2 1.5 15 1.2 
LOAD COMB 2035 1.50DL+1.50RL+1.20WLSE.(‐X)
1 1.5 2 1.5 16 1.2 
LOAD COMB 2036 1.50DL+1.50RL+1.20WLSE.(Z)
1 1.5 2 1.5 17 1.2 
LOAD COMB 2037 1.50DL+1.50RL+1.20WLSE.(‐Z)
1 1.0 2 1.0 18 1.0 
LOAD COMB 2038 1.50DL+1.50RL+1.20WLSE.(D1)
1 1.5 2 1.5 15 1.0605 17 1.0605 
LOAD COMB 2039 1.50DL+1.50RL‐1.20WLSE.(D2)
1 1.5 2 1.5 16 1.0605 18 1.0605 
LOAD COMB 2040 1.50DL+1.50RL+1.50NL(X)+1.20WLSE.(X)
1 1.5 2 1.5 15 1.2 
LOAD COMB 2041 1.50DL+1.50RL+1.50NL(X)+1.20WLSE.(‐X)
1 1.5 2 1.5 16 1.2 
LOAD COMB 2042 1.50DL+1.50RL+1.50NL(X)+1.20WLSE.(Z)
1 1.5 2 1.5 17 1.2 
LOAD COMB 2043 1.50DL+1.50RL+1.50NL(X)+1.20WLSE.(‐Z)
1 1.5 2 1.5 18 1.2 
LOAD COMB 2044 1.50DL+1.50RL+1.50NL(X)+1.20WLSE.(D1)
1 1.5 2 1.5 15 1.0605 17 1.0605 
LOAD COMB 2045 1.50DL+1.50RL+1.50NL(X)+1.50WLSE.(D2)
1 1.5 2 1.5 16 1.0605 18 1.0605 
LOAD COMB 2046 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(X)
1 1.5 2 1.5 15 1.2 
LOAD COMB 2047 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(‐X)
1 1.5 2 1.5 16 1.2 
LOAD COMB 2048 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(Z)
1 1.5 2 1.5 17 1.2 
LOAD COMB 2049 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(‐Z)

Page‐40

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

1 1.5 2 1.5 18 1.2 
LOAD COMB 2050 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(D1)
1 1.5 2 1.5 15 1.0605 17 1.0605 
LOAD COMB 2051 1.50DL+1.50RL+1.50NL(‐X)+1.20WLSE.(D2)
1 1.5 2 1.5 16 1.0605 18 1.0605 
LOAD COMB 2052 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(X)
1 1.5 2 1.5 15 1.2 
LOAD COMB 2053 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(‐X)
1 1.5 2 1.5 16 1.2 
LOAD COMB 2054 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(Z)
1 1.5 2 1.5 17 1.2 
LOAD COMB 2055 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(‐Z)
1 1.5 2 1.5 18 1.2 
LOAD COMB 2056 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(D1)
1 1.5 2 1.5 15 1.0605 17 1.0605 
LOAD COMB 2057 1.50DL+1.50RL+1.50NL(Z)+1.20WLSE.(D2)
1 1.0 2 1.0 8 0.707 18 0.707 
LOAD COMB 2058 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(X)
1 1.5 2 1.5 15 1.2 
LOAD COMB 2059 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(‐X)
1 1.5 2 1.5 16 1.2 
LOAD COMB 2060 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(Z)
1 1.5 2 1.5 17 1.2 
LOAD COMB 2061 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(‐Z)
1 1.5 2 1.5 18 1.2 
LOAD COMB 2062 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(D1)
1 1.5 2 1.5 15 1.0605 17 1.0605 
LOAD COMB 2063 1.50DL+1.50RL+1.50NL(‐Z)+1.20WLSE.(D2)
1 1.5 2 1.5 16 1.0605 18 1.0605 
******* Deflection check criteria******
LOAD COMB 3001 DL+RL+WLST.(X)
1 1.0 2 1.0 
LOAD COMB 3002 DL+RL+WLST.(‐X)
1 1.0 2 1.0 8 0.5625 
LOAD COMB 3003 DL+RL+WLST.(Z)
1 1.0 2 1.0 9 0.5625 
LOAD COMB 3004 DL+RL+WLST.(‐Z)
1 1.0 2 1.0 10 0.5625 
LOAD COMB 3005 DL+RL+WLST.(D1)
1 1.0 2 1.0 9 0.4 
LOAD COMB 3006 DL+RL‐WLST.(D2)
1 1.0 2 1.0 8 0.4 10 0.4 
LOAD COMB 3007 DL+RL+NL(X)+WLST.(X)

Page‐41

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

1 1.0 2 1.0 
LOAD COMB 3008 DL+RL+NL(X)+WLST.(‐X)
1 1.0 2 1.0 8 0.5625 
LOAD COMB 3009 DL+RL+NL(X)+WLST.(Z)
1 1.0 2 1.0 9 0.5625 
LOAD COMB 3010 DL+RL+NL(X)+WLST.(‐Z)
1 1.0 2 1.0 10 0.5625 
LOAD COMB 3011 DL+RL+NL(X)+WLST.(D1)
1 1.0 2 1.0 9 0.4 
LOAD COMB 3012 DL+RL+LN(X)+WLST.(D2)
1 1.0 2 1.0 8 0.4 10 0.4 
LOAD COMB 3013 DL+RL+NL(‐X)+WLST.(X)
1 1.0 2 1.0 
LOAD COMB 3014 DL+RL+NL(‐X)+WLST.(‐X)
1 1.0 2 1.0 8 0.5625 
LOAD COMB 3015 DL+RL+NL(‐X)+WLST.(Z)
1 1.0 2 1.0 9 0.5625 
LOAD COMB 3016 DL+RL+NL(‐X)+WLST.(‐Z)
1 1.0 2 1.0 10 0.5625 
LOAD COMB 3017 DL+RL+NL(‐X)+WLST.(D1)
1 1.0 2 1.0 9 0.4 
LOAD COMB 3018 DL+RL+NL(‐X)+WLST.(D2)
1 1.0 2 1.0 8 0.4 10 0.4 
LOAD COMB 3019 DL+RL+NL(Z)+WLST.(X)
1 1.0 2 1.0 
LOAD COMB 3020 DL+RL+NL(Z)+WLST.(‐X)
1 1.0 2 1.0 8 0.5625 
LOAD COMB 3021 DL+RL+NL(Z)+WLST.(Z)
1 1.0 2 1.0 9 0.5625 
LOAD COMB 3022 DL+RL+NL(Z)+WLST.(‐Z)
1 1.0 2 1.0 10 0.5625 
LOAD COMB 3023 DL+RL+NL(Z)+WLST.(D1)
1 1.0 2 1.0 9 0.4 
LOAD COMB 3024 DL+RL+NL(Z)+WLST.(D2)
1 1.0 2 1.0 8 0.4 10 0.4 
LOAD COMB 3025 DL+RL+NL(‐Z)+WLST.(X)
1 1.0 2 1.0 
LOAD COMB 3026 DL+RL+NL(‐Z)+WLST.(‐X)
1 1.0 2 1.0 8 0.5625 
LOAD COMB 3027 DL+RL+NL(‐Z)+WLST.(Z)
1 1.0 2 1.0 9 0.5625 
LOAD COMB 3028 DL+RL+NL(‐Z)+WLST.(‐Z)
1 1.0 2 1.0 10 0.5625 
LOAD COMB 3029 DL+RL+NL(‐Z)+WLST.(D1)
1 1.0 2 1.0 9 0.4 
LOAD COMB 3030 DL+RL+NL(‐Z)+WLST.(D2)
1 1.0 2 1.0 8 0.4 10 0.4 

Page‐42

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

LOAD COMB 3034 DL+RL+WLSE.(‐Z)
1 1.0 2 1.0 18 0.5625 
LOAD COMB 3035 DL+RL+WLSE.(D1)
1 1.0 2 1.0 15 0.4 17 0.4 
LOAD COMB 3036 DL+RL‐WLSE.(D2)
1 1.0 2 1.0 16 0.4 18 0.4 
LOAD COMB 3037 DL+RL+NL(X)+WLSE.(X)
1 1.0 2 1.0 15 0.5625 
LOAD COMB 3038 DL+RL+NL(X)+WLSE.(‐X)
1 1.0 2 1.0 16 0.5625 
LOAD COMB 3039 DL+RL+NL(X)+WLSE.(Z)
1 1.0 2 1.0 17 0.5625 
LOAD COMB 3040 DL+RL+NL(X)+WLSE.(‐Z)
1 1.0 2 1.0 18 0.5625 
LOAD COMB 3041 DL+RL+NL(X)+WLSE.(D1)
1 1.0 2 1.0 15 0.4 17 0.4 
LOAD COMB 3042 DL+RL+LN(X)+WLSE.(D2)
1 1.0 2 1.0 16 0.4 18 0.4 
LOAD COMB 3043 DL+RL+NL(‐X)+WLSE.(X)
1 1.0 2 1.0 15 0.5625 
LOAD COMB 3044 DL+RL+NL(‐X)+WLSE.(‐X)
1 1.0 2 1.0 16 0.5625 
LOAD COMB 3045 DL+RL+NL(‐X)+WLSE.(Z)
1 1.0 2 1.0 17 0.5625 
LOAD COMB 3046 DL+RL+NL(‐X)+WLSE.(‐Z)
1 1.0 2 1.0 18 0.5625 
LOAD COMB 3047 DL+RL+NL(‐X)+WLSE.(D1)
1 1.0 2 1.0 15 0.4 17 0.4 
LOAD COMB 3048 DL+RL+NL(‐X)+WLSE.(D2)
1 1.0 2 1.0 16 0.4 18 0.4 
LOAD COMB 3049 DL+RL+NL(Z)+WLSE.(X)
1 1.0 2 1.0 15 0.5625 
LOAD COMB 3050 DL+RL+NL(Z)+WLSE.(‐X)
1 1.0 2 1.0 16 0.5625 
LOAD COMB 3051 DL+RL+NL(Z)+WLSE.(Z)
1 1.0 2 1.0 17 0.5625 
LOAD COMB 3052 DL+RL+NL(Z)+WLSE.(‐Z)
1 1.0 2 1.0 18 0.5625 
LOAD COMB 3053 DL+RL+NL(Z)+WLSE.(D1)
1 1.0 2 1.0 15 0.4 17 0.4 
LOAD COMB 3054 DL+RL+NL(Z)+WLSE.(D2)

Page‐43

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

1 1.0 2 1.0 8 0.4 18 0.4 
LOAD COMB 3055 DL+RL+NL(‐Z)+WLSE.(X)
1 1.0 2 1.0 15 0.5625 
LOAD COMB 3056 DL+RL+NL(‐Z)+WLSE.(‐X)
1 1.0 2 1.0 16 0.5625 
LOAD COMB 3057 DL+RL+NL(‐Z)+WLSE.(Z)
1 1.0 2 1.0 17 0.5625 
LOAD COMB 3058 DL+RL+NL(‐Z)+WLSE.(‐Z)
1 1.0 2 1.0 18 0.5625 
LOAD COMB 3059 DL+RL+NL(‐Z)+WLSE.(D1)
1 1.0 2 1.0 15 0.4 17 0.4 
LOAD COMB 3060 DL+RL+NL(‐Z)+WLSE.(D2)
1 1.0 2 1.0 16 0.4 18 0.4 
PERFORM ANALYSIS
PARAMETER 1
CODE IS800 LSD
FU 420000 MEMB 5 TO 54 224 TO 273 276 TO 291 294 TO 309
FYLD 350000 MEMB 5 TO 54 224 TO 273 276 TO 291 294 TO 309
LZ 12 MEMB 5 TO 28 224 TO 247 276 TO 283 294 TO 301
LY 12 MEMB 5 TO 28 224 TO 247 276 TO 283 294 TO 301
LX 12 MEMB 5 TO 28 224 TO 247 276 TO 283 294 TO 301
MAIN 180 MEMB 5 TO 28 224 TO 247 276 TO 283 294 TO 301
MAIN 200 MEMB 29 TO 54 248 TO 273 284 TO 291 302 TO 309
RATIO 1 MEMB 5 TO 54 224 TO 273 276 TO 291 294 TO 309
TRACK 0 MEMB 5 TO 54 224 TO 273 276 TO 291 294 TO 309
CHECK CODE MEMB 5 TO 54 224 TO 273 276 TO 291 294 TO 309
PARAMETER 2
CODE IS800 LSD
STEEL MEMBER TAKE OFF LIST 5 TO 54 224 TO 273 276 TO 291 294 TO 309
FINISH

Page‐44

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

STAAD PRO OUTPUT

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:      5                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.094  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:      6                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.108  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:      7                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.103  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:      8                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.087  Critical Load Case:    51  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   12

Page‐45

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:      9                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.086  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     10                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.092  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     11                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.095  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     12                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.085  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   13

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

Page‐46

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     13                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.084  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     14                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.088  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     15                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.088  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     16                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    51  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   14

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     17                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.080  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     18                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.083  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

Page‐47

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     19                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.083  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     20                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.080  Critical Load Case:    52  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   15

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     21                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     22                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.081  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     23                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     24                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    51  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   16

Page‐48

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     25                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.076  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     26                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.078  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     27                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.077  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     28                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.078  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   17

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

Page‐49

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     29                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    46  Location:       0.00   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     30                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    53  Location:       2.12   |
 |  Critical Condition: Sec. 8.2.1.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     31                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.003  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     32                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   18

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     33                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     34                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

Page‐50

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     35                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     36                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   19

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     37                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.003  Critical Load Case:    80  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     38                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     39                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.003  Critical Load Case:    80  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     40                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

    STAAD SPACE                                              ‐‐ PAGE NO.   20

Page‐51

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     41                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     42                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     43                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     44                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.003  Critical Load Case:    80  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   21

Page‐52

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     45                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     46                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     47                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     48                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   22

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     49                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.003  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     50                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

Page‐53

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     51                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     52                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   23

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     53                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    55  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:     54                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    53  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    224                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.094  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    225                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.108  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   24

Page‐54

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    226                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.103  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    227                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.087  Critical Load Case:    51  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    228                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.086  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    229                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.092  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   25

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

Page‐55

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    230                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.095  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    231                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.085  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    232                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.084  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    233                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.088  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   26

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    234                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.088  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    235                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    51  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    236                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.080  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

Page‐56

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    237                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.083  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   27

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    238                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.083  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    239                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.080  Critical Load Case:    52  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    240                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    241                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.081  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   28

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)

Page‐57

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    242                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    243                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    51  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    244                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.076  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    245                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.078  Critical Load Case:    53  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   29

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    246                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.077  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    247                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.078  Critical Load Case:    52  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    248                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    46  Location:       0.00   |
 |  Critical Condition: Sec. 6.3                                                    |

Page‐58

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    249                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    53  Location:       2.12   |
 |  Critical Condition: Sec. 8.2.1.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   30

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    250                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.003  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    251                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    252                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    253                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   31

Page‐59

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    254                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    255                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    256                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.003  Critical Load Case:    80  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    257                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

    STAAD SPACE                                              ‐‐ PAGE NO.   32

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    258                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.003  Critical Load Case:    80  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    259                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

Page‐60

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    260                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    261                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

    STAAD SPACE                                              ‐‐ PAGE NO.   33

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    262                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    263                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.003  Critical Load Case:    80  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    264                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    265                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   34

Page‐61

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    266                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    80  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    267                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    268                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.003  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    269                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   35

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    270                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    271                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    272                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    55  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

Page‐62

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    273                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    53  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

    STAAD SPACE                                              ‐‐ PAGE NO.   36

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    276                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.075  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    277                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    55  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    278                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.075  Critical Load Case:    51  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    279                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    51  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   37

Page‐63

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    280                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.086  Critical Load Case:    53  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    281                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.085  Critical Load Case:    53  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    282                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.086  Critical Load Case:    52  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    283                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.085  Critical Load Case:    52  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   38

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    284                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    53  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

Page‐64

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    285                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    52  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    286                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    287                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    55  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   39

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    288                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    51  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    289                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    290                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

Page‐65

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    291                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    53  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

    STAAD SPACE                                              ‐‐ PAGE NO.   40

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    294                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.075  Critical Load Case:    55  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    295                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    55  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    296                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.075  Critical Load Case:    51  Location:       0.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    297                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.079  Critical Load Case:    51  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   41

Page‐66

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    298                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.086  Critical Load Case:    53  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    299                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.085  Critical Load Case:    53  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    300                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.086  Critical Load Case:    52  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    301                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.085  Critical Load Case:    52  Location:       2.00   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   42

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    302                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    53  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

Page‐67

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    303                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    52  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    304                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    53  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    305                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    55  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

    STAAD SPACE                                              ‐‐ PAGE NO.   43

                       STAAD.PRO CODE CHECKING ‐ IS‐800‐2007‐LSD (V2.0)
                     ****************************************************

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    306                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    51  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    307                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    52  Location:       1.80   |
 |  Critical Condition: Sec. 9.3.2.2                                                |

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    308                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.002  Critical Load Case:    52  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

Page‐68

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

 |‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐|
 |  Member Number:    309                                                           |
 |  Member Section:  ST   PIP E           (INDIAN SECTIONS)                         |
 |  Status: PASS  Ratio:   0.001  Critical Load Case:    53  Location:       3.61   |
 |  Critical Condition: Sec. 6.3                                                    |

   477. PARAMETER 2
   478. CODE IS800 LSD
   479. STEEL MEMBER TAKE OFF LIST 5 TO 54 224 TO 273 276 TO 291 294 TO 309
    STAAD SPACE                                              ‐‐ PAGE NO.   44

   STEEL TAKE‐OFF
   ‐‐‐‐‐‐‐‐‐‐‐‐‐‐
 
      PROFILE                 LENGTH(METE)      WEIGHT(KN  )

   ST  PIP E                      128.00           217.966
   ST  PIP E                      247.73            57.035
                                          ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐
                                    TOTAL =        275.001

Check for tower base stool
grade = 250 N/mm2
Length = 750 mm
width  = 750 mm
Depth = 410 mm
thickness of flange = 25 mm
thickness of web = 25 mm
cross sectional area = 64500 mm2
shear area = 27000 mm2
rarius of gyration = 161.54 mm

check for compression capacity
KL/r  = 1000/161.54 = 6.2
For bucling class C from table 9‐c
design comperessive stress (Fcd) = 218 N/mm2
Compressive capacity of stool = 14061 KN
Compressive load = 630 KN
Safe

Page‐69

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.
TITLE 0
DOCUMENT NO. REVSION NO.
PAGE NO
STRUCTURAL CHECK FOR TEMPORARY 
HL‐626‐MSKEBF‐CR‐001
ERECTION ARRANGEMENT
DATE 10/10/2020

Check for shear capacity

Factored shear force = 945 KN
Allowable shear force = 3542.831197 KN
Safe

Tower leg will be bolted to tower base stool using 4‐Nos ,M42 bolts 

Check for bolts
dia. Of bolts = 42 mm
grade of bolt = 10.9
yield strength = 1040 N/mm2
ultimate tensile strength = 940 N/mm2

No. of bolts = 4 Nos.
Shear Force = 40 KN
Tension Force = 150 KN

Check for shear capacity of bolts
Shear force = 40 KN
No of bolts = 4 Nos
Shear  force per bolts = 10 KN
bolt dia = 42 mm
Shear capacity of Bolt = 546.553608 KN safe

Check for tension capacity of bolts
tension force = 150 KN
No of bolts = 4
tension  force per bolts = 75 KN
bolt dia = 42 Nos.
tension capacity of bolt = 829.5146496 KN safe

Check for combined shear and tension
calculated tension force = 75 KN
allowable tension force = 829.5146496 KN
calculated shear force = 10 KN
allowable shear force = 546.553608 KN
combined shear and tension = 0.008509509 safe

Page‐70

©FAGIOLI 2013 ‐ THIS DOCUMENT IS THE PROPERTY OF FAGIOLI INDIA PVT. LTD. AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING.

You might also like