Air Treatment Engineering Pvt. Ltd., Chennai - 41.

Project : MALLESWARM MASheet No: 1


Site Location : bangalore Date : 28.03.08
Room : Departmental storePrep. By: kotti
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 12345.651 Sq.ft
Wall Height 14.76 Feet
Occupants 493.826 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 12.345651 kW
Terminal Heater
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 159.76224 Sq.ft
Roof
South East 1643.5129 Sq.ft
South West 816.966 Sq.ft
North West 1936.512 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 1622.5066 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 2
Site Location : Date :
Room : 2 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 3
Site Location : Date :
Room : 3 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Exposed Wall &
Roof

Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 4
Site Location : Date :
Room : 4 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
Exposed Wall &
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 5
Site Location : Date :
Room : 5 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft

Exposed Wall &


Roof
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 6
Site Location : Date :
Room : 6 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
Exposed Glass

South West 0 Sq.ft


North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 7
Site Location : Date :
Room : 7 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft

Exposed Glass
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 8
Site Location : Date :
Room : 8 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 9
Site Location : Date :
Room : 9 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 10
Site Location : Date :
Room : 10 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 11
Site Location : Date :
Room : 11 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 12
Site Location : Date :
Room : 12 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 13
Site Location : Date :
Room : 13 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 14
Site Location : Date :
Room : 14 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
Exposed Wall &
Roof
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 15
Site Location : Date :
Room : 15 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 16
Site Location : Date :
Room : 16 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 17
Site Location : Date :
Room : 17 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 18
Site Location : Date :
Room : 18 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 19
Site Location : Date :
Room : 19 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 20
Site Location : Date :
Room : 20 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 21
Site Location : Date :
Room : 21 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 22
Site Location : Date :
Room : 22 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 23
Site Location : Date :
Room : 23 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 24
Site Location : Date :
Room : 24 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
Exposed Wall &
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 25
Site Location : Date :
Room : 25 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
Air Treatment Engineering Pvt. Ltd., Chennai - 41.
Project : Sheet No: 26
Site Location : Date :
Room : 26 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 27
Site Location : Date :
Room : 27 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
Exposed Wall &
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 28
Site Location : Date :
Room : 28 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft

Exposed Wall &


South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 29
Site Location : Date :
Room : 29 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
Exposed Glass
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft

Air Treatment Engineering Pvt. Ltd., Chennai - 41.


Project : Sheet No: 30
Site Location : Date :
Room : 30 Prep. By:
Floor : Grid No:
Est.For : Summer Above:
Site & Season Code 1 Below:
ROOM DESCRIPTION AND DATA SHEET
Area 0 Sq.ft
Wall Height 14.76 Feet
Occupants 0 Persons
Fresh Air per person 20 CFM
Room Details
Light per Sq.ft Area 5 Watts
Appliances 0 kW
Terminal Heater 0
Pre Heater 0
North 0 Sq.ft

Exposed Glass
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Glass
North East 0 Sq.ft
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
North 0 Sq.ft
South 0 Sq.ft
East 0 Sq.ft
West 0 Sq.ft
Exposed Wall & North East 0 Sq.ft
Roof
South East 0 Sq.ft
South West 0 Sq.ft
North West 0 Sq.ft
Roof 0 Sq.ft
Glass 0 Sq.ft
Partition
Wall 0 Sq.ft
Ceiling 0 Sq.ft
Floor 0 Sq.ft
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 1 Date :
Site Location : ----------- --------- -------- --------
Room : Departmental store DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 12346 182222 3.3 494 9877
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.79
EAST 0 0 0.00 0 | ADP 51.32
WEST 0 0 0.00 0 | CFM 27160
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 100.51 TR
EAST 0 0 0.00 0 | AIR 27160 cfm
WEST 0 0 0.00 0 | ADP 51.32 F
NORTH EAST 160 17 0.36 978 |
SOUTH EAST 1644 25 0.36 14792 |
SOUTH WEST 817 21 0.36 6176 |
NORTH WEST 1937 13 0.36 9063 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR 123
PARTITION (W) 1623 18 0.40 11682 |
CEILING 0 0 0.00 0 | CFM/TR 270
FLOOR 0 0 0.00 0 | CFM/SFT 2.20
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 9877 23 0.12 1.08 29440 |
----------------- ---------- ------- ------- ------- ----------- | RSH 559618
PEOPLE 494 245 120987 | RLH 146915
LIGHTS 5.0 12346 1.25 3.4 262345 | RTH 706533
APPLIANCE 12.3 1 3400 41975 | GTH 1206111
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 497438 | TR 100.51
ADD : 5% Safety+ADD FAN 7.5% 62180 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 559618 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 9877 48 0.12 0.68 38684 | NOTES :
PEOPLE 494 205 101234 |
----------------- ---------- ------- ------- ------- ----------- | ED 81.36
SUB TOTAL ROOM LATENT HEAT 139919 | LD 54.93
ADD : 5% Safety 6996 |
TOTAL ROOM LATENT HEAT 146915 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 706533 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 9877 23 0.88 1.08 215893 |
OA Latent 9877 48 0.88 0.68 283685 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 100.51 TR 1206111 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 2 Date :
Site Location : ----------- --------- -------- --------
Room : 2 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 3 Date :
Site Location : ----------- --------- -------- --------
Room : 3 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 4 Date :
Site Location : ----------- --------- -------- --------
Room : 4 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 5 Date :
Site Location : ----------- --------- -------- --------
Room : 5 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 6 Date :
Site Location : ----------- --------- -------- --------
Room : 6 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 7 Date :
Site Location : ----------- --------- -------- --------
Room : 7 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 8 Date :
Site Location : ----------- --------- -------- --------
Room : 8 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 9 Date :
Site Location : ----------- --------- -------- --------
Room : 9 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 10 Date :
Site Location : ----------- --------- -------- --------
Room : 10 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 11 Date :
Site Location : ----------- --------- -------- --------
Room : 11 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 12 Date :
Site Location : ----------- --------- -------- --------
Room : 12 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 13 Date :
Site Location : ----------- --------- -------- --------
Room : 13 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 14 Date :
Site Location : ----------- --------- -------- --------
Room : 14 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 15 Date :
Site Location : ----------- --------- -------- --------
Room : 15 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ------------------ ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 16 Date :
Site Location : ----------- --------- -------- --------
Room : 16 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 17 Date :
Site Location : ----------- --------- -------- --------
Room : 17 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 18 Date :
Site Location : ----------- --------- -------- --------
Room : 18 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 19 Date :
Site Location : ----------- --------- -------- --------
Room : 19 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 20 Date :
Site Location : ----------- --------- -------- --------
Room : 20 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 21 Date :
Site Location : ----------- --------- -------- --------
Room : 21 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 22 Date :
Site Location : ----------- --------- -------- --------
Room : 22 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 23 Date :
Site Location : ----------- --------- -------- --------
Room : 23 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 24 Date :
Site Location : ----------- --------- -------- --------
Room : 24 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 25 Date :
Site Location : ----------- --------- -------- --------
Room : 25 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 26 Date :
Site Location : ----------- --------- -------- --------
Room : 26 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 27 Date :
Site Location : ----------- --------- -------- --------
Room : 27 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 28 Date :
Site Location : ----------- --------- -------- --------
Room : 28 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 29 Date :
Site Location : ----------- --------- -------- --------
Room : 29 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 30 Date :
Site Location : ----------- --------- -------- --------
Room : 30 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 31 Date :
Site Location : ----------- --------- -------- --------
Room : 31 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 32 Date :
Site Location : ----------- --------- -------- --------
Room : 32 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 33 Date :
Site Location : ----------- --------- -------- --------
Room : 33 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 34 Date :
Site Location : ----------- --------- -------- --------
Room : 34 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 35 Date :
Site Location : ----------- --------- -------- --------
Room : 35 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 36 Date :
Site Location : ----------- --------- -------- --------
Room : 36 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 37 Date :
Site Location : ----------- --------- -------- --------
Room : 37 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | 0 0
Site Location : ----------- --------- -------- --------
Room : 38 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 39 Date :
Site Location : ----------- --------- -------- --------
Room : 39 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 40 Date :
Site Location : ----------- --------- -------- --------
Room : 40 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 41 Date :
Site Location : ----------- --------- -------- --------
Room : 41 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 42 Date :
Site Location : ----------- --------- -------- --------
Room : 42 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 43 Date :
Site Location : ----------- --------- -------- --------
Room : 43 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | 0 0
Site Location : ----------- --------- -------- --------
Room : 44 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 45 Date :
Site Location : ----------- --------- -------- --------
Room : 45 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 46 Date :
Site Location : ----------- --------- -------- --------
Room : 46 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 47 Date :
Site Location : ----------- --------- -------- --------
Room : 47 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 48 Date :
Site Location : ----------- --------- -------- --------
Room : 48 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 49 Date :
Site Location : ----------- --------- -------- --------
Partition 49 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
CM/4PM
Project : | Sheet No: 50 Date :
Site Location : ----------- --------- -------- --------
Room : 50 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF #DIV/0!
EAST 0 0 0.00 0 | ADP #DIV/0!
WEST 0 0 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
----------------- --------- ------- ------- ------- ----------- --------- -------- --------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- --------
INFILTRATION | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION |-------- -------- --------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
Project :
Client :

Heat Load Summary


Project Name

Sl Area Lights Appliances Fresh


No: Room (Sq.ft) occ (Watt/Sqft) (kW) Deh.CFM CFM ACPH SHF ADP TR

1 Departmental store 12346 494 5.0 12.35 27160 9877 3.3 0.79 51.32 100.51
2 2 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
3 3 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
4 4 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
5 5 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
6 6 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
7 7 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
8 8 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
9 9 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
10 10 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
11 11 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
12 12 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
13 13 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
14 14 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
15 15 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
16 16 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
17 17 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
18 18 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
19 19 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
20 20 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
21 21 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
22 22 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
23 23 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
24 24 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
25 25 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
26 26 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
27 27 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
28 28 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
29 29 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
30 30 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00

Last Modified : Architect :


Ver : HVAC : Air Treatment Engg. Pvt. Ltd.,
Project :
Client :

Sl Area Lights Appliances Fresh


Room occ Deh.CFM ACPH SHF ADP TR
No: (Sq.ft) (Watt/Sqft) (kW) CFM

31 31 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00


32 32 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
33 33 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
34 34 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
35 35 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
36 36 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
37 37 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
38 38 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
39 39 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
40 40 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
41 41 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
42 42 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
43 43 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
44 44 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
45 45 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
46 46 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
47 47 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
48 48 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
49 49 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
50 50 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00

Design Considerations
Occupancy:

Equipment: 150 Watts/computer/person Floor Height (Floor to Bottom of Slab): Outside(DBT & WBT ) : °F & °F
Inside(DBT & RH) : 73°F & 55%
Light:1 Watts/sq.ft Glass height:
FA cfm: 20 cfm/person for Offices Windows :
: 5 cfm/person + 0.06 cfm/sq.ft Structural Glazing :

Type of Glass :
Glass : SF = & U = W/m2 0K

Heat Recovery : Not Considered

Last Modified : Architect :


Ver : HVAC : Air Treatment Engg. Pvt. Ltd.,
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
Zone : TM/4PM
Project : | Sheet No: 1 Date :
Site Location : -----------
--------- -------- -------
Room : Departmental store DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- -------------------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 12346 182222 3.3 494 9877
----------------- ---------- ------- ------- ------- -------------------- -------- -------
Area BTU/Hr/sq.ft. Watts/sq.m | WORKINGS
NORTH 0.00 0 3.15 0.00 | 0
SOUTH 0.00 0 3.15 0.00 0
| SHF 0.79
EAST 0.00 0 3.15 0.00 0
| ADP 51.32
WEST 0.00 0 3.15 0.00 0
| CFM 27160
NORTH EAST 0.00 0 3.15 0.00 | 0
SOUTH EAST 0.00 0 3.15 0.00 | 0
SOUTH WEST 0.00 0 3.15 0.00 | 0
NORTH WEST 0.00 0 3.15 0.00 | 0
----------------- ---------- ------- ------- ------- -------------------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 | 0
SOUTH 0 0 0.00 0
| LOAD 100.51 TR
EAST 0 0 0.00 0
| AIR 27160 cfm
WEST 0 0 0.00 0
| ADP 51.32 F
NORTH EAST 160 17 0.36 978
|
SOUTH EAST 1644 25 0.36 14792
|
SOUTH WEST 817 21 0.36 6176
|
NORTH WEST 1937 13 0.36 9063
|
ROOF 0 0 0.00 | 0
----------------- ---------- ------- ------- ------- -------------------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR 123
PARTITION (W) 1623 18 0.40 11682 |
CEILING 0 0 0.00 0 | CFM/TR 270
FLOOR 0 0 0.00 0 | CFM/SFT 2.20
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 9877 23 0.12 1.08 29440 |
----------------- ---------- ------- ------- ------- ----------- | RSH 559618
PEOPLE 494 245 120987 | RLH 146915
LIGHTS 5.0 12346 1.25 3.4 262345 | RTH 706533
APPLIANCE 12.3 1 3400 41975 | GTH 1206111
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 497438 | TR 100.51
ADD : 5% Safety+ADD FAN 7.5% 62180 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 559618 |

----------------- ---------- ------- ------- ------- ----------- |


INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 9877 48 0.12 0.68 38684 | NOTES :
PEOPLE 494 205 101234 |
----------------- ---------- ------- ------- ------- ----------- | ED 81.36
SUB TOTAL ROOM LATENT HEAT 139919 | LD 54.93
ADD : 5% Safety 6996 |
TOTAL ROOM LATENT HEAT 146915 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 706533 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 9877 23 0.88 1.08 215893 |
OA Latent 9877 48 0.88 0.68 283685 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 100.51 TR 1206111 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 2 Date :
Site Location : ----------- --------- -------- -------
Room : 2 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 3 Date :
Site Location : ----------- --------- -------- -------
Room : 3 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 4 Date :
Site Location : ----------- --------- -------- -------
Room : 4 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR| WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1 3.4 0 | RTH 0
APPLIANCE 0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 5 Date :
Site Location : ----------- --------- -------- -------
Room : 5 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR| WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 6 Date :
Site Location : ----------- --------- -------- -------
Room : 6 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR| WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 7 Date :
Site Location : ----------- --------- -------- -------
Room : 7 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 8 Date :
Site Location : ----------- --------- -------- -------
Room : 8 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 9 Date :
Site Location : ----------- --------- -------- -------
Room : 9 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 10 Date :
Site Location : ----------- --------- -------- -------
Room : 10 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 11 Date :
Site Location : ----------- --------- -------- -------
Room : 11 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 12 Date :
Site Location : ----------- --------- -------- -------
Room : 12 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 13 Date :
Site Location : ----------- --------- -------- -------
Room : 13 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 14 Date :
Site Location : ----------- --------- -------- -------
Room : 14 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 15 Date :
Site Location : ----------- --------- -------- -------
Room : 15 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ------------------ ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 16 Date :
Site Location : ----------- --------- -------- -------
Room : 16 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 17 Date :
Site Location : ----------- --------- -------- -------
Room : 17 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 18 Date :
Site Location : ----------- --------- -------- -------
Room : 18 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 19 Date :
Site Location : ----------- --------- -------- -------
Room : 19 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 20 Date :
Site Location : ----------- --------- -------- -------
Room : 20 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 3.15 0.00 0 |
SOUTH 0 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0 0 3.15 0.00 0 |
SOUTH EAST 0 0 3.15 0.00 0 |
SOUTH WEST 0 0 3.15 0.00 0 |
NORTH WEST 0 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 21 Date :
Site Location : ----------- --------- -------- -------
Room : 21 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 22 Date :
Site Location : ----------- --------- -------- -------
Room : 22 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 23 Date :
Site Location : ----------- --------- -------- -------
Room : 23 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 24 Date :
Site Location : ----------- --------- -------- -------
Room : 24 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 25 Date :
Site Location : ----------- --------- -------- -------
Room : 25 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 26 Date :
Site Location : ----------- --------- -------- -------
Room : 26 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 27 Date :
Site Location : ----------- --------- -------- -------
Room : 27 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 28 Date :
Site Location : ----------- --------- -------- -------
Room : 28 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 29 Date :
Site Location : ----------- --------- -------- -------
Room : 29 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 30 Date :
Site Location : ----------- --------- -------- -------
Room : 30 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 31 Date :
Site Location : ----------- --------- -------- -------
Room : 31 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 32 Date :
Site Location : ----------- --------- -------- -------
Room : 32 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 33 Date :
Site Location : ----------- --------- -------- -------
Room : 33 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 34 Date :
Site Location : ----------- --------- -------- -------
Room : 34 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 35 Date :
Site Location : ----------- --------- -------- -------
Room : 35 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 36 Date :
Site Location : ----------- --------- -------- -------
Room : 36 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 37 Date :
Site Location : ----------- --------- -------- -------
Room : 37 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Site & Season Code | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 38 Date :
Site Location : ----------- --------- -------- -------
Room : 38 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 39 Date :
Site Location : ----------- --------- -------- -------
Room : 39 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 40 Date :
Site Location : ----------- --------- -------- -------
Room : 40 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 41 Date :
Site Location : ----------- --------- -------- -------
Room : 41 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 42 Date :
Site Location : ----------- --------- -------- -------
Room : 42 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 43 Date :
Site Location : ----------- --------- -------- -------
Room : 43 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 44 Date :
Site Location : ----------- --------- -------- -------
Room : 44 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 45 Date :
Site Location : ----------- --------- -------- -------
Room : 45 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 46 Date :
Site Location : ----------- --------- -------- -------
Room : 46 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 47 Date :
Site Location : ----------- --------- -------- -------
Room : 47 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 48 Date :
Site Location : ----------- --------- -------- -------
Room : 48 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 49 Date :
Site Location : ----------- --------- -------- -------
Room : 49 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
AIR TREATMENT ENGINEERING PVT. LTD. CHENNAI-41.
TM/4PM
Project : | Sheet No: 50 Date :
Site Location : ----------- --------- -------- -------
Room : 50 DBT WBT RH GR/LB
Floor : | ODC 96 78 45 116
Est.For : Summer | IDC 73 62 55 68
| Diff 23 48
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 0.00 0.00 14.76 0 0 #DIV/0! 0 0
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0.00 0 3.15 0.00 0 |
SOUTH 0.00 0 3.15 0.00 0 | SHF #DIV/0!
EAST 0.00 0 3.15 0.00 0 | ADP #DIV/0!
WEST 0.00 0 3.15 0.00 0 | CFM #DIV/0!
NORTH EAST 0.00 0 3.15 0.00 0 |
SOUTH EAST 0.00 0 3.15 0.00 0 |
SOUTH WEST 0.00 0 3.15 0.00 0 |
NORTH WEST 0.00 0 3.15 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 0.00 TR
EAST 0 0 0.00 0 | AIR #DIV/0! cfm
WEST 0 0 0.00 0 | ADP #DIV/0! F
NORTH EAST 0 0 0.00 0 |
SOUTH EAST 0 0 0.00 0 |
SOUTH WEST 0 0 0.00 0 |
NORTH WEST 0 0 0.00 0 |
ROOF 0 0 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
TRANSMISSION GAIN | CHECK FIGURE
|
PARTITION (G) 0 0 0.00 0 | AREA/TR #DIV/0!
PARTITION (W) 0 0 0.00 0 |
CEILING 0 0 0.00 0 | CFM/TR #DIV/0!
FLOOR 0 0 0.00 0 | CFM/SFT #DIV/0!
----------------- ---------- ------- ------- ------- ----------- --------- -------- -------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- | RSH 0
PEOPLE 0 0 0 | RLH 0
LIGHTS 5.0 0 1.25 3.4 0 | RTH 0
APPLIANCE 0.0 0 0 0 | GTH 0
TERMINAL HEATERS 0 0 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 0 | TR 0.00
ADD : 5% Safety+ADD FAN 7.5% 0 |
PREHEATERS 0 0 0 0 0 |
TOTAL ROOM SENSIBLE HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
INFILTRATION 0 |-------- -------- -------
OUTSIDE AIR 0 0 0.00 0.00 0 | NOTES :
PEOPLE 0 0 0 |
----------------- ---------- ------- ------- ------- ----------- | ED #DIV/0!
SUB TOTAL ROOM LATENT HEAT 0 | LD #DIV/0!
ADD : 5% Safety 0 |
TOTAL ROOM LATENT HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- |
ROOM TOTAL HEAT 0 |
----------------- ---------- ------- ------- ------- ----------- | Offer :
OA Sensible 0 0 0.00 0.00 0 |
OA Latent 0 0 0.00 0.00 0 |
----------------- ---------- ------- ------- ------- ----------- |
GRAND TOTAL HEAT 0.00 TR 0 |
----------------------------------------------------------------------------------
Project:
Client:

Heat Load Summary


Project Name
Area Lights Appliances Fresh
Sl No: DESCRIPTION occ Deh.CFM ACPH SHF ADP TR
(Sq.ft) (Watt/Sqft) (kW) CFM
1 Departmental store 12346 494 5.0 12.35 27160 9877 3.3 0.79 51.32 100.51
2 2 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
3 3 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
4 4 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
5 5 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
6 6 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
7 7 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
8 8 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
9 9 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
10 10 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
11 11 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
12 12 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
13 13 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
14 14 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
15 15 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
16 16 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
17 17 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
18 18 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
19 19 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
20 20 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
21 21 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
22 22 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
23 23 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
24 24 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
25 25 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00

Last Modified: Architect:


Ver: HVAC:Air Treatment Engg. Pvt. Ltd.,
Project:
Client:

Area Lights Appliances Fresh


Sl No: DESCRIPTION occ Deh.CFM ACPH SHF ADP TR
(Sq.ft) (Watt/Sqft) (kW) CFM
26 26 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
27 27 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
28 28 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
29 29 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
30 30 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
31 31 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
32 32 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
33 33 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
34 34 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
35 35 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
36 36 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
37 37 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
38 38 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
39 39 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
40 40 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
41 41 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
42 42 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
43 43 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
44 44 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
45 45 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
46 46 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
47 47 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
48 48 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
49 49 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
50 50 0 0 5.0 0.00 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
101
Design Considerations
Occupancy:
a. 25sq.ft/person Floor Height (Floor to Bottom of Slab):
1. Anchor Stores
2. Hypermarket Glass height:
3. Shops (Ground Floor)
4. Food court
5. Fine Dining Windows :
6. Structural Glazing :
b. 30sq.ft/person
1. Shops (Other Floors) Type of Glass :
2. Corridor (Ground Floor) Glass : SF = & U = W/m2 0K
3. Atrium (Ground Floor)
3.
c. 40sq.ft/person
1. Corridor (Other Floors)
2. Atrium (Other Floors) Outside(DBT & WBT ) : °F & °F
3. Inside(DBT & RH) : 73°F & 55%
d. 60sq.ft/person
1. Workstation
2.
Equipment : Light :
a. 2.0 Watts/sq.ft a. 7.5Watts/sq.ft
1. Anchor Stores 1. Anchor Stores
b. 3.7 Watts/sq.ft 2. Hypermarket
1. Hypermarket b. 5Watts/sq.ft
c. 1.0 Watts/sq.ft 1. Shops
1. Shops c. 3Watts/sq.ft
d. 150 Watts/computer/person 1. Corridor
1. Office or Workstation 2. Atrium
e. 0.5kVA/computer 3. Food court
1. Office or Workstation 4. Fine Dining
(if not Given UPS load)
f. 200Watts/Plotter
g. 250Watts/Refrigerator
h. 10kW/projector Room

FA cfm: 20 cfm/person for Offices


: 5 cfm/person + 0.06 cfm/sq.ft
Heat Recovery : Not Considered

Last Modified: Architect:


Ver: HVAC:Air Treatment Engg. Pvt. Ltd.,
Project:
Client:

Site Survey Summary


Project Name
Exposed Glass area in Sq.ft Exposed Wall & Roof area in Sq.ft Partition area in Sq.ft
Area Lights Appliances
Sl No: DESCRIPTION occ
(Sq.ft) (Watt/Sqft) (kW)
North South South North North South South North
North South East West North South East West Roof Glass Wall Ceiling Floor Deh.CFM Fresh CFM ACPH SHF ADP TR
east east west west east east west west
1 Departmental store 12346 494 5.0 12.35 0 0 0 0 0 0 0 0 0 0 0 0 160 1644 817 1937 0 0 1623 0 0 27160 9877 3.25 0.79 51.32 100.51
2 2 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
3 3 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
4 4 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
5 5 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
6 6 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
7 7 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
8 8 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
9 9 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
10 10 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
11 11 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
12 12 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
13 13 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
14 14 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
15 15 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
16 16 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
17 17 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
18 18 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
19 19 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
20 20 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
21 21 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
22 22 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
23 23 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
24 24 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
25 25 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
26 26 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
27 27 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
28 28 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
29 29 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
30 30 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
31 31 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
32 32 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
33 33 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
34 34 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
35 35 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
36 36 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
37 37 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
38 38 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
39 39 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
40 40 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
41 41 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
42 42 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
43 43 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
44 44 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
45 45 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
46 46 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
47 47 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
48 48 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
49 49 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
50 50 0 0 5.0 0.00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 #DIV/0! 0 #DIV/0! #DIV/0! #DIV/0! 0.00
12346 494 12 0 0 0 0 0 0 0 0 0 0 0 0 160 1644 817 1937 0 0 1623 0 0 #DIV/0! 9877 101
Load in TR 20 24.6 3.9 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 0.0 0.0 1.1 0.0 0.0 48

North South South North


Orientations North South East West
east east west west
Glass Type
Solar Factor 0.82 0.82 0.82 0.82 0.82 0.82 0.82 0.82

U-Value in W/sq.m K 5.70 5.70 5.70 5.70 5.70 5.70 5.70 5.70
Site Location :
Description DBT WBT RH GR/LB
ODC : 96 78 45 116
IDC : 73 62 55 68

Last Modified: Architect:


Ver: HVAC:Air Treatment Engg. Pvt. Ltd.,
Number of
Sl No Room Direction Area (sq.m) Load (btu/Hr) TR Glass Code similar TR Area
rooms

1 Departmental store NORTH 0.00 0 0.00 10 1 0.00 0.00


SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
2 2 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00

WEST 0.00 0 0.00 10 1 0.00 0.00

NORTH EAST 0.00 0 0.00 10 1 0.00 0.00


SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
3 3 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
4 4 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
5 5 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00

NORTH WEST 0.00 0 0.00 10 1 0.00 0.00


6 6 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
7 7 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
8 8 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
9 9 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00

EAST 0.00 0 0.00 10 1 0.00 0.00


WEST 0.00 0 0.00 10 1 0.00 0.00

NORTH EAST 0.00 0 0.00 10 1 0.00 0.00


SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
10 10 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
11 11 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
12 12 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
13 13 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
14 14 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
15 15 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
16 16 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
17 17 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
18 18 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
19 19 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
20 20 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
21 21 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
22 22 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
23 23 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
24 24 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
25 25 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
26 26 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
27 27 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
28 28 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
29 29 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
30 30 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
31 31 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
32 32 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
33 33 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
34 34 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
35 35 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
36 36 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
37 37 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
38 38 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
39 39 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
40 40 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
41 41 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
42 42 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
43 43 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
44 44 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
45 45 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
46 46 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
47 47 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
48 48 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
49 49 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
50 50 NORTH 0.00 0 0.00 10 1 0.00 0.00
SOUTH 0.00 0 0.00 10 1 0.00 0.00
EAST 0.00 0 0.00 10 1 0.00 0.00
WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH EAST 0.00 0 0.00 10 1 0.00 0.00
SOUTH WEST 0.00 0 0.00 10 1 0.00 0.00
NORTH WEST 0.00 0 0.00 10 1 0.00 0.00
Glass Load Summary-Direction wise

Glass Load in
Direction TR
Area(sq.m) (Btu/Hr)
NORTH 0 0 0.00 Equipment cost/TR 45000 Rs
SOUTH 0 0 0.00 Operating cost/TR/Hr 6 Rs
EAST 0 0 0.00 Number Hrs/Day 16 Rs
WEST 0 0 0.00 Number Days/Year 360 Rs
NORTH EAST 0 0 0.00 Maintanance Cost/year/TR 1000 Rs
SOUTH EAST 0 0 0.00
SOUTH WEST 0 0 0.00
NORTH WEST 0 0 0.00
TOTAL 0 0 0.00

Glass Load Summary-Glass Type wise

Solar U-Value in North in South in East in West in North East South East South West North West in Total Glass GlassCost in Equip.cost in First Cost Opera+Maintenance cost in
Glass Type Glass Code TR Rs/Sq.m
Factor W/sq.m K Btu/hr Btu/hr Btu/hr Btu/hr in Btu/hr in Btu/hr in Btu/hr Btu/hr Area(sq.m) Lakhs Lakhs in Lakhs Lakhs

DGU ST 408 1 0.1 2.1 0 0 0 0 0 0 0 0 0 0.00 3295 0.00 0.00 0.00 0.00
Ref Green 2 0.36 6 0 0 0 0 0 0 0 0 0 0.00 1330 0.00 0.00 0.00 0.00
ST 408 3 0.16 4 0 0 0 0 0 0 0 0 0 0.00 2134 0.00 0.00 0.00 0.00
DGU Green 4 0.26 3.273 0 0 0 0 0 0 0 0 0 0.00 2470 0.00 0.00 0.00 0.00
green laminate 5 0.33 6.29 0 0 0 0 0 0 0 0 0 0.00 2509 0.00 0.00 0.00 0.00
DGU skyblue 6 0.29 2.8 0 0 0 0 0 0 0 0 0 0.00 2533 0.00 0.00 0.00 0.00
ST Blue 7 0.33 5.2 0 0 0 0 0 0 0 0 0 0.00 2027 0.00 0.00 0.00 0.00
DGU ST blue 8 0.24 2.2 0 0 0 0 0 0 0 0 0 0.00 3230 0.00 0.00 0.00 0.00
low e 9 0.4 1.8 0 0 0 0 0 0 0 0 0 0.00 2723 0.00 0.00 0.00 0.00
Ordinary Glass 6mm 10 0.82 5.7 0 0 0 0 0 0 0 0 0 0.00 400 0.00 0.00 0.00 0.00
Ordinary Plain Glass-DG 11 0.72 2.8 0 0 0 0 0 0 0 0 0 0.00 1400 0.00 0.00 0.00 0.00
Deep Blue 12 0.15 1.2 0 0 0 0 0 0 0 0 0 0.00 4440 0.00 0.00 0.00 0.00
Ultra Marine 13 0.26 1.2 0 0 0 0 0 0 0 0 0 0.00 4380 0.00 0.00 0.00 0.00
Marine Blue 14 0.18 1.3 0 0 0 0 0 0 0 0 0 0.00 4560 0.00 0.00 0.00 0.00
SGG Climailit 15 0.24 2.76 0 0 0 0 0 0 0 0 0 0.00 3707 0.00 0.00 0.00 0.00
Tinted Glass 16 0.34 2.8 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
0 17 0.2 2 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
0 18 0.3 3 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
0 19 0.4 4 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Sapphire Blue - Reflectasol 20 0.39 6.3 0 0 0 0 0 0 0 0 0 0.00 720 0.00 0.00 0.00 0.00
Blue Ray - Antelio Plus - ST 767 21 0.48 6.2 0 0 0 0 0 0 0 0 0 0.00 850 0.00 0.00 0.00 0.00
Blue Single Glazing (6mm)
Titanium Blue - Cool Lite - STB 120 22 0.33 5.8 0 0 0 0 0 0 0 0 0 0.00 1150 0.00 0.00 0.00 0.00
Royale Blue - Cool Lite - STB 136 23 0.43 5.9 0 0 0 0 0 0 0 0 0 0.00 1150 0.00 0.00 0.00 0.00
Sapphire Blue - Reflectasol 24 0.28 3.2 0 0 0 0 0 0 0 0 0 0.00 1970 0.00 0.00 0.00 0.00
Blue Ray - Antelio Plus - ST 767 25 0.37 3.2 0 0 0 0 0 0 0 0 0 0.00 2100 0.00 0.00 0.00 0.00
Double Glazed Unit (6mm with Coating Face 2-12mm Titanium Blue - Cool Lite - STB 120 26 0.24 3 0 0 0 0 0 0 0 0 0 0.00 2400 0.00 0.00 0.00 0.00
Air Gap - Inner - 6mm Clear Glass) Royale Blue - Cool Lite - STB 136 27 0.34 3.1 0 0 0 0 0 0 0 0 0 0.00 2400 0.00 0.00 0.00 0.00
Satin Blue - Planitherm - PLT TB 28 0.35 1.98 0 0 0 0 0 0 0 0 0 0.00 2300 0.00 0.00 0.00 0.00
Misty Blue - Nano- KT 755 29 0.25 2 0 0 0 0 0 0 0 0 0 0.00 2750 0.00 0.00 0.00 0.00
Sapphire Blue - Reflectasol 30 0.21 2 0 0 0 0 0 0 0 0 0 0.00 2570 0.00 0.00 0.00 0.00
Blue Ray - Antelio Plus - ST 767 31 0.3 2 0 0 0 0 0 0 0 0 0 0.00 2700 0.00 0.00 0.00 0.00
Double Glazed Unit (Outer: 6mm with Coating Face Titanium Blue - Cool Lite - STB 120 32 0.19 2 0 0 0 0 0 0 0 0 0 0.00 3000 0.00 0.00 0.00 0.00
2-12mm Air Gap - Inner - 6mm Planitherm Total(Low
Royale Blue - Cool Lite - STB 136 33 0.28 2 0 0 0 0 0 0 0 0 0 0.00 3000 0.00 0.00 0.00 0.00
E Coating on Face 3 )
Satin Blue - Planitherm - PLT TB 34 0.33 1.85 0 0 0 0 0 0 0 0 0 0.00 2900 0.00 0.00 0.00 0.00
Misty Blue - Nano- KT 755 35 0.24 1.86 0 0 0 0 0 0 0 0 0 0.00 3350 0.00 0.00 0.00 0.00
Green - Reflectasol 36 0.37 6.33 0 0 0 0 0 0 0 0 0 0.00 660 0.00 0.00 0.00 0.00
Emerald Glaze - Antelio Plus - ST 467 37 0.47 6.19 0 0 0 0 0 0 0 0 0 0.00 800 0.00 0.00 0.00 0.00
Single Glazed Unit (6mm, Coating Face 2)
Deep Green - Cool Lite - ST 408 38 0.16 4.05 0 0 0 0 0 0 0 0 0 0.00 1250 0.00 0.00 0.00 0.00
Aquamarine - Cool Lite - ST 420 39 0.28 5.85 0 0 0 0 0 0 0 0 0 0.00 1250 0.00 0.00 0.00 0.00
Green - Reflectasol 40 0.26 3.3 0 0 0 0 0 0 0 0 0 0.00 1910 0.00 0.00 0.00 0.00
Emerald Glaze - Antelio Plus - ST 467 41 0.37 3.2 0 0 0 0 0 0 0 0 0 0.00 2050 0.00 0.00 0.00 0.00
Double Glazed Unit (Outer: 6mm, with Coating Face Deep Green - Cool Lite - ST 408 42 0.1 2.12 0 0 0 0 0 0 0 0 0 0.00 2500 0.00 0.00 0.00 0.00
2-12mm Air Gap - Inner - 6mm Clear Glass) Aquamarine - Cool Lite - ST 420 43 0.18 3.08 0 0 0 0 0 0 0 0 0 0.00 2500 0.00 0.00 0.00 0.00
Mint Green - Planitherm - PLT TG 44 0.36 1.97 0 0 0 0 0 0 0 0 0 0.00 2350 0.00 0.00 0.00 0.00
Double Glazed Unit (Outer: 6mm, with Coating Face
2-12mm Air Gap - Inner - 6mm Clear Glass)

Olive - Nano - KT 455 45 0.25 2.1 0 0 0 0 0 0 0 0 0 0.00 2750 0.00 0.00 0.00 0.00
Green - Reflectasol 46 0.19 2 0 0 0 0 0 0 0 0 0 0.00 1910 0.00 0.00 0.00 0.00
Emerald Glaze - Antelio Plus - ST 467 47 0.31 2 0 0 0 0 0 0 0 0 0 0.00 2650 0.00 0.00 0.00 0.00
Double Glazed Unit (Outer: 6mm, with Coating Face Deep Green - Cool Lite - ST 408 48 0.09 1.88 0 0 0 0 0 0 0 0 0 0.00 3100 0.00 0.00 0.00 0.00
2-12mm Air Gap - Inner - 6mm Planitherm Total (Low
Aquamarine - Cool Lite - ST 420 49 0.14 1.98 0 0 0 0 0 0 0 0 0 0.00 3100 0.00 0.00 0.00 0.00
E Coating on Face 3)
Mint Green - Planitherm - PLT TG 50 0.35 1.84 0 0 0 0 0 0 0 0 0 0.00 2950 0.00 0.00 0.00 0.00
Olive - Nano - KT 455 51 0.24 1.7 0 0 0 0 0 0 0 0 0 0.00 3350 0.00 0.00 0.00 0.00
Blue Green- Antelio Plus - ST 450 52 0.41 6.28 0 0 0 0 0 0 0 0 0 0.00 1150 0.00 0.00 0.00 0.00
Single Glazed Unit (6mm, Coating Face 2)
Turquoise - Cool-Lite ST 436 53 0.35 6.16 0 0 0 0 0 0 0 0 0 0.00 1250 0.00 0.00 0.00 0.00
Blue Green- Antelio Plus - ST 450 54 0.3 3.25 0 0 0 0 0 0 0 0 0 0.00 2400 0.00 0.00 0.00 0.00
Double Glazed Unit (Outer : 6mm, with Coating Face
2 - 12mm Air Gap - Inner : 6mm Clear Glass)
Turquoise - Cool-Lite ST 436 55 0.25 3.21 0 0 0 0 0 0 0 0 0 0.00 2500 0.00 0.00 0.00 0.00
Double Glazed Unit (Outer : 6mm, with Coating Face Blue Green- Antelio Plus - ST 450 56 0.25 2 0 0 0 0 0 0 0 0 0 0.00 3000 0.00 0.00 0.00 0.00
2 - 12mm Air Gap - Inner : 6mm Planitherm Total(Low
E Coating on Face 3)) Turquoise - Cool-Lite ST 436 57 0.2 1.99 0 0 0 0 0 0 0 0 0 0.00 3100 0.00 0.00 0.00 0.00
Bronze - Reflectasol 58 0.45 6.27 0 0 0 0 0 0 0 0 0 0.00 660 0.00 0.00 0.00 0.00
Dark Grey - Reflectasol 59 0.37 6.4 0 0 0 0 0 0 0 0 0 0.00 660 0.00 0.00 0.00 0.00
Single Glazed Unit (6mm, Coating Face 2)
Platinum - Cool Lite - ST 108 60 0.15 3.86 0 0 0 0 0 0 0 0 0 0.00 1150 0.00 0.00 0.00 0.00
Sterling Silver - Cool Lite - ST 120 61 0.3 5.7 0 0 0 0 0 0 0 0 0 0.00 1150 0.00 0.00 0.00 0.00
Bronze - Reflectasol 62 0.34 3.27 0 0 0 0 0 0 0 0 0 0.00 1910 0.00 0.00 0.00 0.00
Double Glazed Unit (Outer: 6mm, with Coating Face Dark Grey - Reflectasol 63 0.25 3.3 0 0 0 0 0 0 0 0 0 0.00 1910 0.00 0.00 0.00 0.00
2-12mm Air Gap - Inner - 6mm Clear Glass) Platinum - Cool Lite - ST 108 64 0.1 2.1 0 0 0 0 0 0 0 0 0 0.00 2400 0.00 0.00 0.00 0.00
Sterling Silver - Cool Lite - ST 120 65 0.22 3 0 0 0 0 0 0 0 0 0 0.00 2400 0.00 0.00 0.00 0.00
Bronze - Reflectasol 66 0.24 2 0 0 0 0 0 0 0 0 0 0.00 2510 0.00 0.00 0.00 0.00
Double Glazed Unit (Outer: 6mm, with Coating Face Dark Grey - Reflectasol 67 0.17 2 0 0 0 0 0 0 0 0 0 0.00 2510 0.00 0.00 0.00 0.00
2-12mm Air Gap - Inner - 6mm Planitherm Total (Low
Platinum - Cool Lite - ST 108 68 0.1 1.85 0 0 0 0 0 0 0 0 0 0.00 3000 0.00 0.00 0.00 0.00
E Coating on Face 3)
Sterling Silver - Cool Lite - ST 120 69 0.18 1.98 0 0 0 0 0 0 0 0 0 0.00 3000 0.00 0.00 0.00 0.00
Classic Clear 70 0.55 5.7 0 0 0 0 0 0 0 0 0 0.00 832 0.00 0.00 0.00 0.00
Classic Bronze 71 0.45 5.7 0 0 0 0 0 0 0 0 0 0.00 845 0.00 0.00 0.00 0.00
Stopsol Classic Grey 72 0.43 6.34 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Classic Green 73 0.39 6.38 0 0 0 0 0 0 0 0 0 0.00 908 0.00 0.00 0.00 0.00
Stopsol Classic Dark Blue 74 0.39 6.38 0 0 0 0 0 0 0 0 0 0.00 1145 0.00 0.00 0.00 0.00
Stopsol Silver Light Priva Blue 75 0.35 6.44 0 0 0 0 0 0 0 0 0 0.00 1023 0.00 0.00 0.00 0.00
Stopsol Classic Pink 76 0.54 6.12 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
STOPSOL reflective coated glass (6mm)
Stopsol Supersilver Clear 77 0.69 5.77 0 0 0 0 0 0 0 0 0 0.00 640 0.00 0.00 0.00 0.00
Stopsol Supersilver Grey 78 0.51 6.24 0 0 0 0 0 0 0 0 0 0.00 848 0.00 0.00 0.00 0.00
Stopsol Supersilver Green 79 0.47 6.25 0 0 0 0 0 0 0 0 0 0.00 732 0.00 0.00 0.00 0.00
Stopsol SupersilverLight Green 80 0.5 5.7 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Supersilver Dark Blue 81 0.47 6.27 0 0 0 0 0 0 0 0 0 0.00 805 0.00 0.00 0.00 0.00
Stopsol Supersilver Ice Blue 82 0.54 6.15 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Supersilver Pink 83 0.67 5.94 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Classic Clear 84 0.46 3.18 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Classic Bronze 85 0.34 3.28 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Classic Grey 86 0.32 3.29 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Classic Green 87 0.28 3.3 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Classic Dark Blue 88 0.29 3.3 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Silver Light Priva Blue 89 0.23 3.33 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
THERMOBEL with STOPSOL reflective coated glass Stopsol Classic Pink 90 0.45 3.03 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
(6-12-6mm) Stopsol Supersilver Clear 91 0.62 3.1 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Supersilver Grey 92 0.4 3.25 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Supersilver Green 93 0.38 3.25 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol SupersilverLight Green 94 0.4 3.09 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Supersilver Dark Blue 95 0.38 3.26 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Supersilver Ice Blue 96 0.45 3.22 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Supersilver Pink 97 0.58 2.97 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Classic Clear 98 0.32 1.4 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Classic Bronze 99 0.22 1.45 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Classic Grey 100 0.2 1.46 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Classic Green 101 0.2 1.47 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Classic Dark Blue 102 0.19 1.47 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Silver Light Priva Blue 103 0.18 1.51 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
THERMOPLUS with STOPSOL reflective coated Stopsol Classic Pink 104 0.35 1.52 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
glass and LOW - E Glass #3 (6-12-6mm) Stopsol Supersilver Clear 105 0.47 1.38 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Supersilver Grey 106 0.28 1.43 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Supersilver Green 107 0.29 1.43 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol SupersilverLight Green 108 0.33 1.43 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
THERMOPLUS with STOPSOL reflective coated
glass and LOW - E Glass #3 (6-12-6mm)

Stopsol Supersilver Dark Blue 109 0.28 1.44 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Supersilver Ice Blue 110 0.35 1.45 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Stopsol Supersilver Pink 111 0.49 1.5 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Eclipse Advantage Clear 112 0.6192 3.00934 0 0 0 0 0 0 0 0 0 0.00 850 0.00 0.00 0.00 0.00
Eclipse Advantage Grey 113 0.4128 3.00934 0 0 0 0 0 0 0 0 0 0.00 850 0.00 0.00 0.00 0.00
Pilkington Eclipse Advantage Reflective Low E- Eclipse Advantage Bronze 114 0.4558 3.00934 0 0 0 0 0 0 0 0 0 0.00 850 0.00 0.00 0.00 0.00
Glass Outer Lite (#2 Surface) Eclipse Advantage Blue Green 115 0.4558 3.00934 0 0 0 0 0 0 0 0 0 0.00 950 0.00 0.00 0.00 0.00
Eclipse Advantage Ever Green 116 0.3698 3.00934 0 0 0 0 0 0 0 0 0 0.00 1025 0.00 0.00 0.00 0.00
Eclipse Advantage Artic Blue 117 0.3612 3.00934 0 0 0 0 0 0 0 0 0 0.00 1025 0.00 0.00 0.00 0.00
Eclipse Advantage Clear 118 0.5418 1.9873 0 0 0 0 0 0 0 0 0 0.00 1600 0.00 0.00 0.00 0.00
Eclipse Advantage Grey 119 0.3354 1.9873 0 0 0 0 0 0 0 0 0 0.00 1600 0.00 0.00 0.00 0.00
Pilkington Eclipse Advantage Reflective Low E- Eclipse Advantage Bronze 120 0.3784 1.9873 0 0 0 0 0 0 0 0 0 0.00 1600 0.00 0.00 0.00 0.00
Glass Outer Lite (#2 Surface) and Clear Float Glass
Eclipse Advantage Blue Green 121 0.3784 1.9873 0 0 0 0 0 0 0 0 0 0.00 1700 0.00 0.00 0.00 0.00
Inner Lite
Eclipse Advantage Ever Green 122 0.2838 1.9873 0 0 0 0 0 0 0 0 0 0.00 1775 0.00 0.00 0.00 0.00
Eclipse Advantage Artic Blue 123 0.2838 1.9873 0 0 0 0 0 0 0 0 0 0.00 1775 0.00 0.00 0.00 0.00
Eclipse Advantage Clear 124 0.516 1.7034 0 0 0 0 0 0 0 0 0 0.00 2250 0.00 0.00 0.00 0.00
Eclipse Advantage Grey 125 0.3096 1.7034 0 0 0 0 0 0 0 0 0 0.00 2250 0.00 0.00 0.00 0.00
Pilkington Eclipse Advantage Reflective Low E- Eclipse Advantage Bronze 126 0.3526 1.7034 0 0 0 0 0 0 0 0 0 0.00 2250 0.00 0.00 0.00 0.00
Glass Outer Lite (#2 Surface) and Energy Advantage
Eclipse Advantage Blue Green 127 0.3526 1.7034 0 0 0 0 0 0 0 0 0 0.00 2350 0.00 0.00 0.00 0.00
Low-E Glass Inner Lite (#3 Surface)
Eclipse Advantage Ever Green 128 0.2666 1.7034 0 0 0 0 0 0 0 0 0 0.00 2425 0.00 0.00 0.00 0.00
Eclipse Advantage Artic Blue 129 0.2666 1.7034 0 0 0 0 0 0 0 0 0 0.00 2425 0.00 0.00 0.00 0.00
0 130 0 0 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
0 131 0 0 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
0 132 0 0 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
0 133 0 0 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
0 134 0 0 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
0 135 0 0 0 0 0 0 0 0 0 0 0 0.00 0 0.00 0.00 0.00 0.00
Number of
Sl No Room Direction Area (sq.ft) Load (btu/Hr) TR similar TR Area
rooms
1 Departmental store NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 160 978 0.08 1 0.08 160
SOUTH EAST 1644 14792 1.23 1 1.23 1644
SOUTH WEST 817 6176 0.51 1 0.51 817
NORTH WEST 1937 9063 0.76 1 0.76 1937
2 2 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
3 3 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
4 4 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
5 5 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
6 6 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
7 7 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
8 8 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
9 9 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
10 10 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
11 11 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
12 12 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
13 13 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
14 14 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
15 15 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
16 16 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
17 17 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
18 18 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
19 19 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
20 20 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
21 21 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
22 22 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
23 23 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
24 24 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
25 25 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
26 26 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
27 27 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
28 28 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
29 29 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
30 30 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
31 31 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
32 32 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
33 33 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
34 34 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
35 35 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
36 36 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
37 37 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
38 38 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
39 39 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
40 40 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
41 41 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
42 42 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
43 43 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
44 44 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
45 45 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
46 46 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
47 47 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
48 48 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
49 49 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
50 50 NORTH 0 0 0.00 1 0.00 0
SOUTH 0 0 0.00 1 0.00 0
EAST 0 0 0.00 1 0.00 0
WEST 0 0 0.00 1 0.00 0
NORTH EAST 0 0 0.00 1 0.00 0
SOUTH EAST 0 0 0.00 1 0.00 0
SOUTH WEST 0 0 0.00 1 0.00 0
NORTH WEST 0 0 0.00 1 0.00 0
Wall Load Summary-Direction wise

Direction Wall Area( sq.ft) Load (btu/Hr) TR


NORTH 0 0 0.00
SOUTH 0 0 0.00
EAST 0 0 0.00
WEST 0 0 0.00
NORTH EAST 160 978 0.09
SOUTH EAST 1644 14792 1.39
SOUTH WEST 817 6176 0.58
NORTH WEST 1937 9063 0.85
Total 4556.75314 31008.5001288 2.90704689