You are on page 1of 78

Project On

[Electrical Wiring Installation of a Single Flat In a Multi-Storied Building]


Course Code : EEE 300
Course Name : Electrical Services Design
Semester & Year:
Fall-2023

Name of Student Name of Instructor


Shahanul Islam Md. Abdur Rahman
2021-2-80-013 Lecturer, Dept. of EEE
Fall-2023
A RESIDENTIAL BUILDING WILL BE ELECTRIFIED WITH C.T.S. WIRING. THE DETAILS OF THE FITTINGS
REQUIRED ARE GIVEN BELOW. WE HAVE TO CALCULATE THE APPROXIMATE COST OF THE WIRING SYSTEM

SERIAL FOOTCANDLE EXHASTED AC PLUG POINT


ROOM SIZE FAN PLUG POINT
NO NEEDED FAN

1 Bedroom 1 13ft × 12 ft 6.50321 1 -


2 Bedroom 2 12 ft × 12 ft 6.50321 1 - 1 Iron

3 Bedroom 3 12 ft × 12 ft 6.50321 1 - 1 pc
4 M Bedroom 13ft × 12 ft 6.50321 1 - 1 AC
5 Kitchen 6 ft × 10 ft 18.5806 - 1 1 Blender Machine
6 Living Room 13 ft × 10 ft 13.9355 1 - 1 TV/ Router 1
7 Dining Room 10’-5” × 10 ft 13.9355 1 - 1 fridge
8 Toilet 1 5ft × 7 ft 9.2903 - 1 1 Geyser

9 Toilet 2 5ft × 7 ft 9.2903 - 1


10 Varanda 1 3’-5” × 12 ft 6.50321 -
11 Varanda 2 3’-5” × 12 ft 6.50321 - -
REQUIRED STANDARD ILLUMINANCE (LUX) AND FOOT CANDLE VALUES FOR
RESIDENTIAL BUILDINGS:

SERIAL FOOTCANDLE
ROOM SIZE LUX
NO NEEDED

1 Bedroom 1 13ft × 12 ft 6.50321 70


2 Bedroom 2 12 ft × 12 ft 6.50321 70
3 Bedroom 3 12 ft × 12 ft 6.50321 70
4 M Bedroom 13ft × 12 ft 6.50321 70
5 Kitchen 6 ft × 10 ft 18.5806 200
6 Living Room 13 ft × 10 ft 13.9355 150
7 Dining Room 10’-5” × 10 ft 13.9355 150
8 Toilet 1 5ft × 7 ft 9.2903 100
9 Toilet 2 5ft × 7 ft 9.2903 100
10 Varanda 1 3’-5” × 12 ft 6.50321 70
11 Varanda 2 3’-5” × 12 ft 6.50321 70
Plan With Furniture
Arrangement
LIGHT/FAN/PLUG POSITION: FOR EVERY FUNCTION

1'-0"

1'-0"
Exhast Fan position from celling Ac & Water Heater Plug Pt. & Light Position From
Ceiling

3'-0"
Light Position For Toilet From Ceiling

6'-0"
Switchboard & TV Plug Pt. Position From Ceiling

Plug Pt. Position For Kitchen,From Ground


5'-0"

2'-0"
Plug Pt. Position From Ground
D.B POSITION:
METER POSITION FOR EVERY FUNCTION

Meter Position From Ceiling = 4f LIGHT/FAN/PLUG POSITION: D.B Position From Ceiling = 4 ft
FOR EVERY FUNCTION

Ac & Water Heater Plug Pt. & Light Position From Ceiling = 1 ft

Switchboard & TV Plug Pt. Position From Ceiling = 6 ft.

Plug Pt. Position From Ground = 2 ft

Plug Pt. Position For Kitchen From Ground = 5 ft

Light Position For Toilet From Ceiling = 3 ft

Exhaust Fan Position From Ceiling = 1 ft


ASSUMPTIONS

Collected From The GOV.BD.BNBC


 Utilization factor = 0.75
PC 200W
 Depreciation factor = 0.8
LED TV 120W
 Illumination AC 1300W
Iron 1000W
 Lumen per watt = 95 lumen
Lamp 30W
 The switchboards are 4 feet above the ground.
Washing Machine 350W
 Building height 10 feet Refrigerator 250W
 Conduit and wire calculation with 5 % extra quantity. Geyser 1200W
Aquarium 100W
The estimation for the building where the temperature
Fan 60W
will not cross the range of 30
Exhaust fan 50W
Degree to 40 degree Celsius.
Induction cooker 2000W
Load calculation with 25% additional load Router 9W
Blender Machine 300W
LIGHT CALCULATION
NUMBER OF LIGHT CALCULATION

BEDROOM 1 BEDROOM 2
Total lumens required =
13×12×6.50321
0.75×0.8
≅ 1690.83 lumens Total lumens required =
12×12×6.50321
0.75×0.8
≅ 1560.77 lumens
Power required =
1690.83
95
≅ 17.798 ≅ 18 Watt Power required =
1560.77
95
≅ 16.429 ≅ 18 Watt
So, we can use 1 light of 18 W to fullfil the criteria. So, we can use 1 light of 18 W to fullfil the criteria.

So total power = (1×18) = 18 W So total power = (1×18) = 18 W

BEDROOM 3 MASTER BEDROOM


Total lumens required =
12×12×6.50321
0.75×0.8
≅ 1560.77lumens Total lumens required =
13×12×6.50321
≅ 1690.83 lumens
0.75×0.8

Power required =
1560.77
95
≅ 16.429 ≅ 18 Watt Power required =
1690.83
95
≅ 17.798 ≅ 18 Watt
So, we can use 1 light of 18 W to fullfil the criteria. So, we can use 1 light of 18 W to fullfil the criteria.

So total power = (1×18) = 18 W So total power = (1×18) = 18 W


LIVING ROOM NUMBER OF LIGHT CALCULATION
DINING ROOM
Total lumens required =
13×10×13.9355
0.75×0.8
≅ 3019.35 lumens Total lumens required =
10.5×10×13.9355
0.75×0.8
≅ 2438.71 lumens
Power required =
3019.35
95
≅ 31.782 ≅ 35 Watt Power required =
2438.71
95
≅ 25.670 ≅ 25 Watt
So, we can use 2 lights, one of 20W and another of 15 W to So, we can use 1 light of 25 W to fullfil the criteria.
fulfil the criteria
So total power = (1×25) = 25 W
So total power = (1×15)+(1×20)= 35 W

KITCHEN TOILET 1
Total lumens required =
6×10×18.5806
0.75×0.8
≅ 1858.06 lumens Total lumens required =
5×7×9.2903
0.75×0.8
≅ 650.321 lumens
Power required =
1858.06
95
≅ 19.558 ≅ 20 Watt Power required =
650.321
95
≅ 6.845 ≅ 6 Watt
So, we can use 1 light of 20 W to fullfil the criteria. So, we can use 1 light of 6 W to fullfil the criteria.

So total power = (1×20) = 20 W So total power = (1×6) = 6 W

Light Calculation
TOILET 2 NUMBER OF LIGHT CALCULATION
VARANDA 1
Total lumens required =
5×7×9.2903
0.75×0.8
≅ 650.321 lumens Total lumens required =
3.5×12×6.50321
0.75×0.8
≅ 455.224 lumens
Power required =
650.321
95
≅ 6.845 ≅ 6 Watt Power required =
455.224
95
≅ 4.791 ≅ 6 Watt
So, we can use 1 light of 6 W to fullfil the criteria. So, we can use 1 light of 6 W to fullfil the criteria.

So total power = (1×6) = 6 W So total power = (1×6) = 6W

HT CALCULATION
VARANDA 2
Total lumens required =
3.5×12×6.50321
0.75×0.8
≅ 455.224 lumens
Power required =
455.224
95
≅ 4.791 ≅ 6 Watt
So, we can use 1 light of 6 W to fullfil the criteria.

So total power = (1×6) = 6W

Light Calculation
Symnolls
CF CF

S.B
S.B
PC
S.B

B.S

B.S
PLAN WITH LIGHT FAN PLUG CF
FAN

ARRAGMENT
S.B S.B

S.B
S.B
CF CF CF
TV

LIGHT

S.B S.B
CONDUIT CALCULATION
CF CF

S.B
S.B

S.B

B.S

B.S
PLAN WITH MAIN CONDUIT
CF

ARRAGMENT S.B S.B

S.B
S.B
CF CF CF

S.B S.B

Conduit Calculation
CF CF

S.B
S.B

S.B

B.S

B.S
PLAN WITH SUB CONDUIT
CF

ARRAGMENT S.B S.B

S.B
S.B
CF CF CF

S.B S.B

Conduit Calculation
CF CF

S.B
S.B

S.B

B.S
DETAILED PLAN WITH

B.S
LIGHT/ FAN/ PLUG, MAIN CF

CONDUIT, AND SUB-


CONDUIT
S.B S.B

ARRANGMENT

S.B
S.B
CF CF CF

S.B S.B

Conduit Calculation
CF CF

S.B
S.B

5"

8"
S.B

B.S
6'-3"

9"
3'-2"
8"

B.S
DETAILED PLAN WITH MAIN

16'-4"
CF

9'-10"
3'-2"

CONDUIT MEASUREMENT

4'-8"
3'-4"

1'-3"
S.B S.B

6'-0" 10'-0" 11'-6"

1'-6"
2'-8"
S.B
3'-7"
Light 1

S.B
CF CF CF

13'-2"

11'-6''

9'-7''
P2
Light 1
Light 2
P1

S.B S.B

9'' 11''

Conduit Calculation
4''

2'-3" 1'-3'' 1'-8''


5'-9"

2'-6''
5'-4''
CF
2'-2'' CF

S.B
S.B

5"

8"
S.B 10''

B.S
6'-3"

9"
5" 3'-2"

5'-9"
8" 5'-6''

6'-2''
10'-7"

5"
2'-9'' 4'-10"

B.S
16'-4"
DETAILED PLAN WITH CF

9'-10"
3'-2"
2'-9''

3'-6''
MEASUREMENT 3'-4"

1'-3"
S.B S.B

6'-0" 10'-0" 11'-6"

1'-6"
2'-8"
5'-8"

S.B
3'-7"
4'-2" 5'-8"

3'-4"
Light 1

S.B
5'-9"

13'-2"
CF CF CF

11'-6''
4'-0"

9'-7''
P2

3"
Light 2

9'-6"
Light 1

7''

4'-6''
P1

2'-4"
S.B S.B

9'' 11'' 6'


5' 9'-2"

Conduit Calculation
FROM MAIN METER TO DISTRIBUTION BOX

Distribution Box / Sub-Circuit Box /


From Meter To 19'- 6'’
Circuit Breaker Box

FROM DISTRIBUTION BOX TO EVERY SWITCHBOARD AND AC/GEYSER


Bedroom 1 16'-0'’
Bedroom 2 27'-0"
Bedroom 3 9'-10"
Master Bedroom 8'-8"
Kitchen 6'-5"
Every
Distribution Living Room 13'-7"
From To Switchboard And
Box Dining Room 13'-0"
AC
Toilet 1 6'-0"
Toilet 2 15'-10"
Varanda 1 19'-11"
Varanda 2 16'-6"

Conduit Length Calculation


FROM DISTRIBUTION BOX TO EVERY SWITCHBOARD AND AC/GEYSER
AC 1 28'-0"
Geyser 1 2'-3"

Every
Distribution
From To Switchboard And
Box Total 183 ft
AC

Conduit Length Calculation


BEDROOM 1

L1 6'-9"
Every
From SwitchBoard To (Light/Fan/Plug) F1 11'-8"
Total 18'-5" ft

BEDROOM 2

L1 9'-6"
From SwitchBoard To Every
(Light/Fan/Plug) F1 5'-9"

P1 13'-9"
Total 29 ft

Conduit Length Calculation


BEDROOM 3

L1 7'-2"
From SwitchBoard To Every
(Light/Fan/Plug) F1 11'-4"

P1 13'-6"
Total 32 ft

MASTER BEDROOM

L1 10'-4"
From SwitchBoard To Every
(Light/Fan/Plug) F1 5'-8"

Total 16 ft

Conduit Length Calculation


LIVING ROOM

L1 11'
From SwitchBoard To Every
(Light/Fan/Plug) L2 10'-6"

F1 10'-2"

P1 6'-7"
P2 6'-3"
Total 44'-6"

DINING ROOM

L1 7'-10"
From SwitchBoard To Every
(Light/Fan/Plug) F1 13'-5"

P1 8'-5"
Total 29'-8"

Conduit Length Calculation


KITCHEN

L1 11'-5"
From SwitchBoard To Every
(Light/Fan/Plug) EF1 3'

P1 6'-3"
Total 20'-8"

TOILET 1

L1 7'-8''
From SwitchBoard To Every
(Light/Fan/Plug) EF1 10'-4"

Total 18 ft

Conduit Length Calculation


TOILET 2

L1 10'-2"
From SwitchBoard To Every
(Light/Fan/Plug) EF1 5'-10"

Total 16 ft

VARANDA 1

Every
From SwitchBoard To L1 11'
(Light/Fan/Plug)

Total 11ft

Conduit Length Calculation


VARANDA 2

Every
From SwitchBoard To L1 12'
(Light/Fan/Plug)

Total 12 ft

DIS-LINE FOR TV

Every
From Outside Area To TV 23'-8"
TV

Total 23'-8"

INTERNET SERVICE PROVIDER LINE

From Outside Area To Router Plug L1 12'-4"

Total 12'-4"

Conduit Length Calculation


TOTAL CONDUIT NEEDED

Distribution Box / Sub-Circuit Box /Circuit Breaker Box 19'- 6'’

From Distribution Box To Every Switchboard And AC/Geyser 183'

Conduit From switchboard to Every/Light/Fan/Plug 247'-3"

Internet Service Provider Line 23'-8"

Dis-Line For TV 12'-4"

TOTAL 485'-9"

By Increasing 5% Total Conduit Needed = 510 ft

Conduit Length Calculation


LOAD CALCULATION
TOTAL LOAD OF DIFFERENT SECTION

Total Load of Bedroom 1 : Total Load of Bedroom 2 :


Lights + Fan Lights + Fan + Iron
18 W+60W 18 W+60W+1000 W
= 78 W = 1078W

Total Load of Bedroom 3 : Total Load of Master Bedroom (Without AC) :


Lights + Fan + PC Lights + Fan
18 W+60W+200 W 18 W+60W
= 278 W = 78 W

Load Calculation
Total Load of Living Room : Total Load of Dining Room:
Light1 +Light2 + Fan+ TV + Router Lights + Fan + Fridge
20W+ 15W+60W+120+9 25 W+60W+250 W
= 224 W = 335W

Total Load of Kitchen : Total Load of Toilet 1 (without Geyser):


Lights + E Fan + Blender Machine Lights + E Fan
20W+50W+300 W 6 W+50W
= 370W = 56 W

Load Calculation
Total Load of Toilet 2 : Total Load of Varanda 1:
Lights + E Fan Lights
6W+50W 6W
= 56 W

Total Load of AC( Master Bedroom )


Total Load of Varanda 2:
1300W
Lights
6W
Total Load of Geyser( Toilet 1)
1200W

Load Calculation
TOTAL LOAD
Bedroom 1 78W
Bedroom 2 1078W

Bedroom 3 278 W

Master Bedroom 78 W
Kitchen 370W
Living Room 224 W
Dining Room 335W
Toilet 1 56W
Toilet 2 56W

Varanda 1 6W
Varanda 2 6W

AC 1300W
Geyser 1200W

TOTAL 5065 W

By Increasing 25% Total Conduit Needed = 6332W


Load Calculation
CABLE SELECTION
METER TO DISTRIBUTION BOX:

So the total load of Building is about 6332 W and Supply voltage is 220V and temperature is 30-40 degree.
Wire length ( meter to distribution) = (19'- 6") × 2 = 39ft

Total Power 6332


Total current needed = = 28.78 Amp
Supply Voltage 220

Now select the size of cable for load current of 28.78 Amp which is 7/0.044 (34A).
Current rating for 35°C = 34 × 0.97 = 32.98 Amp

5.7 ×19.6 28.78


Actual Voltage Drop =
100
× 34
= 0.94 V

Allowable voltage drop = 5.5 V

So, suitable cable size is 7/0.044 (34A)

Cable Selection
DISTRIBUTION BOX TO BEDROOM 1 SWITCHBOARD :

Wire length = 16×2=32ft

Total Power 78
Total current needed = = 0.355 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.355 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 16 0.355
Actual Voltage Drop =
100
× 11
= 0.072V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO BEDROOM 2 SWITCHBOARD :

Wire length = 27×2=54 ft

Total Power 1078


Total current needed = = 4.9 Amp
Supply Voltage 220

Now select the size of cable for load current of 4.9 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 27 4.9
Actual Voltage Drop =
100
× 11
= 1.68V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO BEDROOM 3 SWITCHBOARD :

Wire length = 9'-10"×2=19'-8" ft

Total Power 278


Total current needed = = 1.26 Amp
Supply Voltage 220

Now select the size of cable for load current of 1.26 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 ×9.10 1.26
Actual Voltage Drop =
100
× 11
= 0.14V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO MASTER BEDROOM SWITCHBOARD :

Wire length = 8'-8" ×2=17"-4"ft

Total Power 78
Total current needed = = 0.355 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.355 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 8.8 0.355
Actual Voltage Drop =
100
× 11
= 0.039V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO KITCHEN SWITCHBOARD :

Wire length = 6'-5"×2=12"-10" ft

Total Power 370


Total current needed = = 1.68 Amp
Supply Voltage 220

Now select the size of cable for load current of 1.68 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 6.5 1.68
Actual Voltage Drop =
100
× 11
= 0.13V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO LIVING ROOM SWITCHBOARD :

Wire length = 13'-7"×2=27'-2" ft

Total Power 224


Total current needed = = 1.12 Amp
Supply Voltage 220

Now select the size of cable for load current of 1.12 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 ×13.7 1.12
Actual Voltage Drop =
100
× 11
= 0.19V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO DINING ROOM SWITCHBOARD :

Wire length = 13'×2=26 ft

Total Power 335


Total current needed = = 1.52 Amp
Supply Voltage 220

Now select the size of cable for load current of 1.52 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 13. 1.52
Actual Voltage Drop =
100
× 11
= 0.25V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO TOILET 1 SWITCHBOARD :

Wire length = 6'×2=12 ft

Total Power 56
Total current needed = = 0.25 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.25 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 6 0.25
Actual Voltage Drop =
100
× 11
= 0.01V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO TOILET 2 SWITCHBOARD :

Wire length = 15'-10"×2=31'-8" ft

Total Power 56
Total current needed = = 0.25 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.25 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 15.10 0.25
Actual Voltage Drop =
100
× 11
= 0.04V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO VARANDA 1 SWITCHBOARD :

Wire length = 19'-11"×2=39'-10"ft

Total Power 6
Total current needed = = 0.027 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.027 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 19.11 0.027
Actual Voltage Drop =
100
× 11
= 0.006V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO VARANDA 2 SWITCHBOARD :

Wire length = 16'-6"×2=33 ft

Total Power 6
Total current needed = = 0.027 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.027 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 16.6 0.027
Actual Voltage Drop =
100
× 11
= 0.005V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO AC SWITCHBOARD :

Wire length = 28×2=56 ft

Total Power 1300


Total current needed = = 5.90 Amp
Supply Voltage 220

Now select the size of cable for load current of 5.90 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 28 5.90
Actual Voltage Drop =
100
× 11
= 2.10V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
DISTRIBUTION BOX TO GEYSER SWITCHBOARD :

Wire length = 2'-3"×2=4'-6" ft

Total Power 1200


Total current needed = = 5.45 Amp
Supply Voltage 220

Now select the size of cable for load current of 5.45 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 2.3 5.45
Actual Voltage Drop =
100
× 11
= 0.15V

Allowable voltage drop = 5.5 V

So, suitable cable size is 1/0.044 (11A)

Cable Selection
CABLE SELECTION SWITCH BOARD TO PLUG POINT
PLUG-1 BEDROOM 2 :

Wire length = 13'-9"×2=27'-6" ft

Total Power 1000 (Iron)


Total current needed = = 4.54 Amp
Supply Voltage 220

Now select the size of cable for load current of 4.54Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 13.9 4.54
Actual Voltage Drop =
100
× 11
= 0.80 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
PLUG-1 BEDROOM 3 :

Wire length = 13'-6"×2=27 ft

Total Power 200 (PC)


Total current needed = = 0.89 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.89Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 13.6 0.89
Actual Voltage Drop =
100
× 11
= 0.15 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
PLUG-1 LIVING ROOM :

Wire length = 6'-3"×2=12'-6" ft

Total Power 9 (ROUTER)


Total current needed = = 0.04 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.04 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 6.3 0.04
Actual Voltage Drop =
100
× 11
= 0.003 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
PLUG-2 LIVING ROOM :

Wire length = 6'-7"×2=13'-2" ft

Total Power 120 (TV)


Total current needed = = 0.54 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.54 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 6.7 0.54
Actual Voltage Drop =
100
× 11
= 0.04 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
PLUG-1 DINING ROOM :

Wire length = 8'-3"×2=16'-6" ft

Total Power 250 (Fridge)


Total current needed = = 1.136 Amp
Supply Voltage 220

Now select the size of cable for load current of 1.136 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 8.3 1.136
Actual Voltage Drop =
100
× 11
= 0.12 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
PLUG-1 KITCHEN :

Wire length = 6'-3"×2=12'-6" ft

Total Power 300 (Blender )


Total current needed = = 1.36 Amp
Supply Voltage 220

Now select the size of cable for load current of 1.36 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 6.3 1.36
Actual Voltage Drop =
100
× 11
= 0.10 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
CABLE SELECTION SWITCHBOARD TO APPLIANCE
BEDROOM 1 SWITCHBOARD TO LIGHT-1

Wire length = 6'-9"×2=13'-6" ft

Total Power 18
Total current needed = = 0.08 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.08 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 6.9 0.08
Actual Voltage Drop =
100
× 11
= 0.007 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
BEDROOM 1 SWITCHBOARD TO FAN-1

Wire length = 11'-8"×2=23'-4" ft

Total Power 60
Total current needed = = 0.27 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.27 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 11.8 0.27
Actual Voltage Drop =
100
× 11
= 0.04 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
BEDROOM 2 SWITCHBOARD TO LIGHT-1

Wire length = 9'-6"×2=19 ft

Total Power 18
Total current needed = = 0.08 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.08 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 9.6 0.08
Actual Voltage Drop =
100
× 11
= 0.004 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
BEDROOM 2 SWITCHBOARD TO FAN-1

Wire length = 5'-9"×2=11'-6" ft

Total Power 60
Total current needed = = 0.27 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.27 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 5.9 0.27
Actual Voltage Drop =
100
× 11
= 0.009 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
BEDROOM 3 SWITCHBOARD TO LIGHT-1

Wire length = 7'-2"×2=14'-4" ft

Total Power 18
Total current needed = = 0.08 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.08 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 7.2 0.08
Actual Voltage Drop =
100
× 11
=0.0033 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
BEDROOM 3 SWITCHBOARD TO FAN-1

Wire length = 11'-4"×2=22'-8" ft

Total Power 60
Total current needed = = 0.27 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.27 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 11.4 0.27
Actual Voltage Drop =
100
× 11
= 0.017 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
MASTER BEDROOM 3 SWITCHBOARD TO LIGHT-1

Wire length = 10'-4"×2=20'-8" ft

Total Power 18
Total current needed = = 0.08 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.08 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 10.4 0.08
Actual Voltage Drop =
100
× 11
= 0.004 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
MASTER BEDROOM 2 SWITCHBOARD TO FAN-1

Wire length = 5'-8"×2=11'-4" ft

Total Power 60
Total current needed = = 0.27 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.27 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 5.8 0.27
Actual Voltage Drop =
100
× 11
= 0.009 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
KITCHEN SWITCHBOARD TO LIGHT-1

Wire length = 11'-5"×2=22'-10" ft

Total Power 20
Total current needed = = 0.09 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.09 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 11.5 0.09
Actual Voltage Drop =
100
× 11
= 0.01 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
KITCHEN SWITCHBOARD TO E-FAN-1

Wire length = 3×2=6 ft

Total Power 50
Total current needed = = 0.22 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.22 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 3 0.22
Actual Voltage Drop =
100
× 11
= 0.008 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
LIVING ROOM SWITCHBOARD TO LIGHT-1

Wire length = 11×2=22 ft

Total Power 20
Total current needed = = 0.09 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.09 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 11 0.09
Actual Voltage Drop =
100
× 11
= 0.01 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
LIVING ROOM SWITCHBOARD TO LIGHT-2

Wire length = 10'-6"×2=21 ft

Total Power 15
Total current needed = = 0.06 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.06 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 10.6 0.06
Actual Voltage Drop =
100
× 11
= 0.008 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
LIVING ROOM SWITCHBOARD TO FAN-1

Wire length = 10'-2"×2=20'-4"ft

Total Power 60
Total current needed = = 0.27 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.27 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 10.2 0.27
Actual Voltage Drop =
100
× 11
= 0.035 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
DINING ROOM SWITCHBOARD TO LIGHT-1

Wire length = 7'-10"×2=15'-8" ft

Total Power 25
Total current needed = = 0.11 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.11 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 7.6 0.11
Actual Voltage Drop =
100
× 11
= 0.009 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
DINING ROOM SWITCHBOARD TO FAN-1

Wire length = 13'-5"×2=26'-10"ft

Total Power 60
Total current needed = = 0.27 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.27 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 13.5 0.27
Actual Voltage Drop =
100
× 11
= 0.046 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
TILET 1 SWITCHBOARD TO LIGHT-1

Wire length = 7'-8"×2=15'-4" ft

Total Power 6
Total current needed = = 0.027 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.027 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 7.8 0.027
Actual Voltage Drop =
100
× 11
= 0.002 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
TILET 1 SWITCHBOARD TO E FAN -1

Wire length = 10'-4"×2=20'-8" ft

Total Power 50
Total current needed = = 0.22 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.22 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 10.4 0.22
Actual Voltage Drop =
100
× 11
= 0.029 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
TILET 2 SWITCHBOARD TO LIGHT-1

Wire length = 10'-2"×2=20'-4" ft

Total Power 6
Total current needed = = 0.027 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.027 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 10.2 0.027
Actual Voltage Drop =
100
× 11
= 0.003 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
TILET 2 SWITCHBOARD TO E FAN -1

Wire length = 5'-10"×2=11'-8" ft

Total Power 50
Total current needed = = 0.22 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.22 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 5.10 0.22
Actual Voltage Drop =
100
× 11
= 0.001 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
VARANDA 1 SWITCHBOARD TO LIGHT-1

Wire length = 11×2=22 ft

Total Power 6
Total current needed = = 0.027 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.027 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 11 0.027
Actual Voltage Drop =
100
× 11
= 0.003 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
VARANDA 2 SWITCHBOARD TO LIGHT-1

Wire length =12×2=24 ft

Total Power 6
Total current needed = = 0.027 Amp
Supply Voltage 220

Now select the size of cable for load current of 0.027 Amp which is 1/0.044 (11A).
Current rating for 35°C = 11 × 0.97 = 10.67 Amp

14 × 12 0.027
Actual Voltage Drop =
100
× 11
= 0.003 V

220× 1.25
Allowable voltage drop = = 2.75 V
100
So, suitable cable size is 1/0.044 (11A)

Cable Selection
TOTAL WIRE CALCULATION

Cable 7/0.044 (34A) = 39 feet


Increasing after 5% , total Cable 7/0.044(34A) needed = 40.95 feet

Cable 1/.044(11A) = 861 feet


Increasing after 5% , total Cable 1/.044 (11A) needed = 904.05 feet

To connect all the device with earth total earthling cable needed = 945 feet
So, the total wire needed to complete this C.T.S wiring = 1890 feet

Apart from this,


we need Coaxial cable (for Dis-line) = 23'-8" feet
we need twisted pair cable (for ISP-line) = 12'-4" feet