THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
CHK'D
RJP
RJP
RJP
REVISED AS PER SEC COMMENTS DATED 03.06.2009 ON REVISED CT CALCULATION.
PG
BY
03.04.2009
25.06.2009
17.12.2009
DATE
NO.
D
B
REVISIONS
DRAWN
BY:- RJP
DATE:- 20.12.08
CHECKED
BY:- JA
DATE:- 22.12.08
OPRG. DEPT
BY
DATE:-
ENG'G. DEPT.
BY:-
DATE:-
CERTIFIED.
BY:-
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT DRAWING NO. SHEET NO. REV NO.
TO BE USED FOR
CONSTRUCTION OF 380kV CT SIZING CALCULATION
FOR ORDERING A T201 EE-086959 01 OF 50 D
MATERIALS UNTIL ABU-HADRIYAH 380/115kV BSP
CERTIFIED AND
DATED
KHURSANIYAH SAUDI ARABIA JOB ORDER NO. 3-083300.01 DWG.CONT.SHT. EE-086950
INDEX
1.2
1.3 DESIGN BASIS AND REFERENCES FOR CT CALCULATION 1
1.3 CT LEAD RESISTANCE CALCULATION 2
2.2 CT: 810 B1.C2 :- OHL FEEDER SET-1 PROTECTION (REL 531) 5
2.3 CT: 810 B1.C3 :- OHL FEEDER SET-2 PROTECTION (7SA522) 12
16
2.4 CT: 810 B1.C4 :- METERING 14
2.9 CT: 811 B1.C2 :- OHL FEEDER SET-1 PROTECTION (RED 670) 25
2.10 CT: 811 B1.C3 :- OHL FEEDER SET-2 PROTECTION (MiCOM P546) 31
2.14 CT: 811 B2.C2 :-OHL FEEDER SET-1 PROTECTION (REL 531) 36
2.21 CT: 812 B2.C2 :- OHL FEEDER SET-1 PROTECTION (REL 531) 41
(Refer Annexure-5) safe margin = 500 meter, Lead resistance calculated is,
= 3.76 x 0.5
= 1.88 ohms for 500 meters
CT CALCULATION:
2.1.1 CT Vk requirement:
For 2000 A
Vk Knee point voltage
IP = Nominal ( rated) CT primary Current = 2000 amps
T = Turn ratio = 1/2000
Is = Nominal ( rated) CT secondary Current = 1 amps
IF = Maximum short circuit current = 63000 amps
IF sec = CT Secondary short circuit current in Amps. = 31.5 amps
RCT = Internal CT secondary resistance = 3.1 ohms
RL = Lead Resistance =2 L x Rpkm / 1000 = 1.88 ohms
RL = Lead resistance of cable. = 1.88 Ohms
=For 6 sq.mm copper cable, RL= 0.00308 ohm/meter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)) RL = 1.88 ohms.
Consider length of cable = 500 meters.
RRAICA= Relay Burden (Refer Annexure-2, Sh. No. 6) = 0.15 VA
2 2
RRAICA= Relay resistance = RB / Is = (0.15/1 ) = 0.15 ohms
Note:
Maximum Relay burdens occur for 1ph-G fault when both phase & ground BFP O/C relay units are in series.
2x BFP Relay Fault Detectors = 0.30 Ohms
Total= 0.30 ohms Ground o/c relay [1ph-G loop]
0.15 ohms phase o/c relay [3ph]
BFP fault detectors come once main protection operates & initiate BFP. Worst case relay operation (fatest)
is ½ cycle & hence @ maximum peak during fully offset.
CT Requirement considering 20% margin.
General formulae:
Vkrequired > 1.2xOffset for DC x Ifsecondaryx (Connected burden)
Since CT rated knee point voltage is 3700V which is greater than 541.3 volts, CT is adequate.
Fault current calculation at the end of zone1 fault i.e 80% of line length:
For 44.485 Km line
Impedance calculated : (Rs+0.8R1) + j(Xs+0.8X1)
(Positive sequence) = (0.2+0.635) + j (3.48+11.32)
= 0.84+j14.8
ZT1 = 14.82 ohms
Phase fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x14.82
= 14800.04 Amps
Phase fault X/R = 14.82
0.835
= 17.75
Fault current calculation at the end of zone1 fault i.e 80% of line length:
For 44.485 Km line
Impedance calculated : (3Rs+0.8x2R1+R0) +
(Loop Impedance) j(3Xs+0.8x2X1+X0)
= 9.32+j69.12 ohms
ZT1 = 69.75 ohms
Earth fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x69.75
= 3145.62 Amps
Earth fault X/R = 69.12
9.32
= 7.42
3I0= = 9436.869326 Amps
2.2.6 CT Requirement : ( As per Annexure-1, Sh. No.20,21)
2
Eal > Ealreq = {I kmax x I sn} / Ipn x 0.5 x (RCT + RL + SR / Ir ) Equation-1
2
Eal > Ealreq = 2 x {Ikmax x I sn} / Ipn x (RCT + RL + SR / Ir ) Equation-2
2
Eal > Ealreq = 0.12 x f x Isn x(RCT + RL + SR / Ir ) Equation-3
2
Eal > Ealreq = (Imin sat x CT factor x Ir) / 100 x (RCT + RL + SR / Ir ) Equation-4
Where,
Ikmax = Maximum Primary fundamental frequency fault current for internal close-in faults (A)
Itfdb = Maximum Primary fundamental frequency fault current for external faults (A) that
passes through two CT's (A).
Here for one and half breaker scheme Ikmax is equal to Itfdb.
Ipn = The rated primary CT current (A)
Isn = The rated secondary CT current (A)
Ir = The rated current of the protection IED (A)
SR = The burden of IED 670 a current input channel (VA). SR = 0.25 VA/channel.
f= system frequeny in Hz.
Imin sat= Saturation detector min current ( 100 - 1000% Of Ir) and set at 500%
CT factor = set current scalling factor (0.4 - 1.0)
Itfdb = Maximum Primary fault current for external faults (A) = 63000 amps
I pn = Nominal ( rated) CT primary Current = 2000 amps
I sn = Nominal ( rated) CT secondary Current = 1 amps
RCT = CT secondary winding resistance = 3.1 ohms
RB = Burden of relay = 0.25 ohms
RL = Lead resistance of cable.
=For 6 sq.mm copper cable, RL= 3.08 ohm/kmeter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)) RL 1.88
Consider length of cable = 500 meters. 2RL = 3.76 ohms
Ir = Protection terminal rated Current = 1 amps
f = System Frequency = 60 Hz
Imin Sat= Sat saturation detector min current
2
Eal > Ealreq = {I kmax x I sn} / Ipn x 0.5 x (RCT + RL + SR / Ir ) Equation-1
As per REL 531 relay requirement, the factor 0.5( for Tc less than 120ms) is replaced with 0.53 & 0.54
for primary time constant of 200ms and 300ms respectively.
2
Eal > Ealreq = 2 x {Ikmax x I sn} / Ipn x (RCT + RL + SR / Ir ) Equation-2
As per REL 531 relay requirement, the factor 2 ( for Tc less than 120ms) is replaced with 2.32 & 2.5
for primary time constant of 200ms and 300ms respectively.
2
Eal > Ealreq = 0.12 x f x Isn x (RCT + RL + SR / Ir ) Equation-3
2
Ealreq = 0.12 x 50 x 1x(3.1+ 1.88 +0.27/1 ) = 31.4 volts
Eal > Ealreq = (Imin sat x CT factor x Ir) / 100 x (RCT + RL + SR / Ir 2 ) Equation-4
2
Ealreq = 500 x 1 x 1x(3.1+ 1.88 +0.27/1 ) = 26.2 volts
100
With 20% extra margin Ealreq = 31.4 volts
Since CT rated knee point voltage is 3700V which is greater than the required value,
the proposed CT is adequate.
The Voltage developed across the CT secondary for distance protection (21L) feature as per
ABB catalogue. (Refer Annexure-1 Sh. No. 22 )
Requirement -1
At 2000/1 A tap
Requirement -2
2
Eal > Ealreq = Ikzone1x 7 x (Isn / Ipn) x (RCT + RL + SR / Ir ) Equation-6
k' = 7 for primary time constant greater than 30 msec.
Ikzone1= Maximum primary fundamental fault current at the end of zone 1 reach.
Considering 80% of actual line length = 14800.04 Amps
(Refer above fault current calculation at the end of zone1 reach considering actual line length)
At 2000/1 A tap and with 20% extra margin
2
Ealreq = 14800 x 1.2 x 7 x ( 3.1+ 1.88 +0.27/1 ) = 442.58038 volts
2000
Since CT rated knee point voltage is 3700V which is greater than the required value,
the proposed CT is adequate.
2.3.1 CT Calculation
Where For 2000 amps
Vk = Knee point voltage of CT 3700 Volts
RB = Resistance of relay 7SA522 = 0.05 ohms
Rr = Relay resistance
RCT = CT secondary winding resistance = 3.1 ohms
RL = Lead resistance of cable.
For 6 sq.mm copper cable, RL= 3.08 ohm/kmeter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1)) RL = 1.88 ohms
Consider length of cable = 500 meters. 2RL= 3.76 ohms
IP = Nominal ( rated) CT primary Current = 2000 amps
IS = Nominal ( rated) CT secondary Current = 1 amps
ISCC max = Maximum short circuit current-Three phase = 63000 amps
VK CT knee point voltage specified = 3700 volts
X/R = System ratio = 17
If = Maximum value of through fault current for
stability ( multiple of Is) = I SCC max / IP = 31.50
( I f )x( X/R) = 535.5
Tp = Primary time constant, (L/R)
L/R = (X/(2x 3.14x f )/R
.= ( 17 / 2x 3.14x 60) x 1000 = 45.09 msec
Vk 1 > {Ktd(a)xIssc max(close-in fault)/1.3xIpn} x Isn x (RB + RCT +RL) For close-in fault
Vk 2 > {Ktd(b)xIssc max(zone-1 end fault)/1.3xIpn} x Isn x (RB + RCT +RL) For zone-1 end fault
Since CT rated knee point voltage is 3700V which is greater than the required value,
the proposed CT is adequate.
Protection : Metering
Core : CT: 810 B1.C4
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : 0.2
VA Burden 50 VA
Thermal rating factor 200%
Application : Metering
Burden Calculation (Refer Annexure-2)
a LCP
Ammeter 0.5 VA (Assumed)
b Revenue metering panel
ABB, ALPHA A3R 1E-04 VA ( Refer Annexure-1 Sh. No. 18 )
c Mosaic panel
Watt transducer, , AREVA, ISTAT300 1 VA ( Refer Annexure-1 Sh. No. 13 )
Var transducer, AREVA, ISTAT300 1 VA ( Refer Annexure-1 Sh. No. 13 )
Watt meter, PML ION6200 0.5 VA (Assumed)
Var meter PML ION6200 0.5 VA (Assumed)
d DSM 0.1 VA (Assumed)
Cabling loop (500 meters)
For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1));
Consider length of wire = 500 meters. RL = 2.812 Ohms
2RL = 5.624 VA
Total connected burden, PBC = 9.224 VA
Considering 25% safe margin, connected VA equals to= 11.53 VA
The total connected burden is less than the CT rated burden i.e 50VA. Hence the CT is adequate.
Protection : Spare
Core : CT: 810 F.C3
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap
CT excitation current at 3000A tap in mA Ie < 50
Thermal rating factor 200%
Application : Spare
NOTE:
Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)
are shown below.
2.6.1 CT Calculation
The setting voltage is determined by the following relationship. (Refer Annexure-1, Sh. No.11)
Vs > 1.2 x If x ( RCT + 2 x RL ) (20% additional margin is taken)
Where For 3000
IP = Nominal ( rated) CT primary Current 3000 amps
IS = Nominal ( rated) CT secondary Current 1 amps
IF = Maximum Fault Current = 63000 amps
If = CT secondary fault current = 21 amps
RCT = Internal CT secondary resistance 4.65 ohms
Hence, select a metrosil with setting range 25V- 325V and set at 275 volts.
= 273.167
This current is too small as compared to 63kA i.e 0.43% of 63kA.
It is observed that the primary operating current is less than 630A.
Hence, an external shunt resistor (Rsh) needs to be connected inorder to get a primary operating current 630A.
Select shunt resistor to get primary operating current of say 742 Amps.
Ip = { nIe+ Ir +IM+(Vs/Rsh)+IV}xT
= 742.0 Amps.
NOTE:
Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)
are shown below.
2.7.1 CT Requirement
Where For 3000 A
The setting voltage Vs shall be calculated in order to ensure the stability of the protection in
regard with the maximum through fault current If . The setting voltage is determined by the following eqn.
Vs > 211.932
Hence, select Vs same as Main-2 protection = 275 Vrms
Peak voltage = 388.91 Vpeak
Where
Vf = Maximum voltage in absence of saturation = 28547.6 volts
VPK = 1/2
( 2x5550x (28547.6- 5550)) = 15977.28 volts
= 15.98 kVolts
VPK is 15.98kV which is more than 3kV hence Metrosiles are required.
Metrosil requirement
For this relay Metrosil proposed by the manufacturer has the following parameters.
C = 900
β = 0.25
The current drawn by metrosil at relay setting voltage is given by formulae below.
Irms drawn= 0.52((√2xV')/C))1/β
where V' = voltage in (RMS Sine)
Metrosil recommended for 25-325V relay range @ 2kVrms
Irms drawn= 0.52x((√2x2000)/900)1/0.25
= 50.72 A rms
{(8x0.005)+0.2+0.018+0.003}x3000
= 783.2 Amps.
2.7.4 Determination of stabilising resistor Rsr: (Refer MCAG 14 Manual attached, Annex-1, Sh. No.10)
Relay circuit Voltage Vs = 275.00 Volts
Relay setting current, Is = 0.20 Amps
Relay burden at 275V setting is considered as 1VA,
Stabilising resistor required, Rsr = (Vs/Ir) - (Relay burden)/(Ir^2) Rs= = 1350.00 ohms
Select a resistor of range (0 -1500 ohms),0.31A continous,1.36A/3sec,1.8A/1sec as per MCAG 14 Manual.
Fault current calculation at the end of zone1 fault i.e 80% of line length:
1) For 50 Km line
Impedance calculated : (Rs+0.8R1) + j(Xs+0.8X1)
(Positive sequence) = (0.2+0.635) + j (3.48+12.5)
= 0.84+j16
ZT1 = 16.02 ohms
Phase fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x16.02
= 13693.21 Amps
Phase fault X/R = 15.98
0.835
= 19.14
Fault current calculation at the end of zone1 fault i.e 80% of line length:
1) For 50 Km line
Impedance calculated : (3Rs+0.8x2R1+R0) +
(Loop Impedance) j(3Xs+0.8x2X1+X0)
= 8.18+j72.5 ohms
ZT1 = 72.96 ohms
Earth fault current = Ph. Volt / Ph. Imp.
= 380000
Sqrt.(3)x72.96
= 3007.03 Amps
Earth fault X/R = 72.50
8.18
= 8.86
3I0= = 9021.097278 Amps
Voltage developed across CT as per ABB relay catalogue (Refer Annexure-1 Sh. No.2 )
At 2000/1 A tap
Considering 20% margin
2
Eal > Ealreq = {I kmax x I sn} / Ipn x (RCT + RL + SR / Ir ) Equation-1
At 2000/1 A tap
2
Eal > Ealreq = Itfdb x (Isn / Ipn) x (RCT + RL + SR / Ir ) Equation-3
Since CT rated knee point voltage is 3700V which is greater than the required value,
the proposed CT is adequate.
The Voltage developed across the CT secondary for distance protection (21L) feature as per
ABB catalogue. (Refer Annexure-1 Sh. No. 3 )
Requirement -1
At 2000/1 A tap
2
Eal > Ealreq = {I kmax x I sn} / Ipn x a x (RCT + RL + SR / Ir ) Equation-5
a' = 2 for primary time constant less than 50msec.
With 20% extra margin
Ealreq = 63000 x 1.2 x 2 x ( 3.1+ 1.88 + 0.26/1^2 ) = 538.3 volts
2000
Requirement -2
Vk1 > K xI n x (RB + RCT +RL) (equation -1) for through fault condition
Vk 2 > KRPA xIFZ1 x (1+X/R)x(RB + RCT +RL+Rr) (equation -2) for zone1 fault condition
Vk3 > Kmax x IFmax x (RB + RCT +RL+Rr) (equation -3) for close-up fault
Vk1 = Accuracy limiting voltage for line through fault condition in volts
Vk2 = Accuracy limiting voltage for end of zone 1 line fault in volts
Vk2 = Accuracy limiting voltage for close in fault in volts
IFZ1 = Maximum secondary fault current for end of zone 1 fault in amps.
For 50kM line length , primary fault current (A) calculated is equal to = 13693.21
Amps. Hence, CT secondary fault current = 13693.21
2000
= 6.85 Amps.
KRPA = Fixed dimensioning factor for zone 1 fault and always = 0.6 (Refer Annex-1, Sh. No. 7)
Kmax = Fixed dimensioning factor for close in fault and always = 1.4 (Refer Annex-1, Sh. No. 7)
RB = Relay burden
Where K is dimensioning factor and depends upon the maximum value of through fault current(as a multiple of In)
and primary system X/R ratio.
For three end current differential schemes relay set at Is1=20%, Is2=2In, K1=30% and K2=100%,
K' is calculated as below. (Refer Annex-1, Sh. No. 6)
For through fault condition the fault current and X/R calculated above are
IF = 11483.02 Amps. (Primary); X/R = 19.20
CT secondary fault currect calculated = 5.74
If x X/R = 110.24
If, If x X/R < 1000xIn,
K> 40 + 0.35 x (If x X/R)
K> 40 + 0.35x(110.24)
K> 78.584
As per AREVA relay catalogue, K > 78.584
Since, the CT rated knee point voltage is greater than the calculated value, the proposed CT is adequate.
Protection : Metering
Core : CT: 811 B1.C4
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : 0.2
VA Burden 50 VA
Thermal rating factor 200%
Application : Metering
Burden Calculation (Refer Annexure-2)
a LCP
Ammeter 0.5 VA (Assumed)
b Energy metering panel
NEXUS/1262 3.2 VA (Refer Annex-2, Sh. No. 8)
c Mosaic panel
Watt transducer, , AREVA, ISTAT300 1 VA (Refer Annex-2, Sh. No. 13)
Var transducer, AREVA, ISTAT300 1 VA (Refer Annex-2, Sh. No. 13)
Watt meter, PML ION6200 0.5 VA (Assumed)
Var meter PML ION6200 0.5 VA (Assumed)
d DSM 0.1 VA (Assumed)
Cabling loop (500 meters)
For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20ºC.
α at 20ºC = 0.004, RL at 75ºC = RL(1+α20(T2-T1));
Consider length of wire = 500 meters. RL = 2.812 Ohms
2RL = 5.624 VA
Total connected burden, PBC = 12.42 VA
Considering 25% safe margin, connected VA equals to= 15.53 VA
The total connected burden is less than the CT rated burden i.e 50VA. Hence the CT is adequate.
Protection : Metering
Core : CT: 811 B2.C4
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : 0.2
VA Burden 50 VA
Thermal rating factor 200%
Application : Metering
CT calculation same as CT: 810 B1.C4. Refer above CT: 810 B1.C4 for detailed calculation.
Protection : spare
Core : CT: 811 B2.C1
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap
CT excitation current at 3000A tap in mA Ie < 50
Thermal rating factor 200%
Application : spare
NOTE:
Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)
are shown below.
NOTE:
Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)
are shown below.
Protection : Spare
Core : CT: 812 F.C3
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : TPS
CT Secondary resistance at 75º C, RCT ohms < 4.65 Ohms at 3000A tap.
Knee point voltage, Vk Vk > 5550 V at 3000A tap
Application: Spare
Protection : Metering
Core : CT: 812 B2.C4
CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A
Class of Accuracy : 0.2
VA Burden 50 VA
Thermal rating factor 200%
Application : Metering
CT calculation same as CT: 811 B1.C4. Refer above CT: 811 B1.C4 for detailed calculation.
4 sq.mm copper cable resistance at 200C is 4.61 ohms/km.i.e Rdc at 200C = 4.61 ohm/km
Rdc at 75ºC = R20(1+α20(T2-T1)); α at 20ºC = 0.004,Where α= temperature co-efficient of resistance.
Core-1 Core-2
Calculation of VT burden :
Core-1 :
Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
FFR (98L) A811/A812 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
FFR (98) (Meas.) for set-1 protection RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
FFR (98) (Ref.) for set-2 protection RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
FFR (98) (Ref.) for Energy meter RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
Core-2:
Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
25MC/A811 KVAS100 1 0.02 0.02 (Annexure-2 Sh. No.10)
FFR (98) (Ref.) for set-1 protection RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
25AR / A811 FOR AF-2 KVAS100 1 0.02 0.02 (Annexure-2 Sh. No.10)
(27L2), Under voltage relay RAEDA1 3 4.4 13.2 (Annexure-2 Sh. No. 11)
Transducer Panel
Voltage transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No. 13)
Watt meter Watt transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No. 13)
Var meter Var transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No. 13)
Under voltage relay RAEDA1 1 4.4 4.4 (Annexure-2 Sh. No. 11)
FFR (98) (Meas.) for revenue meter RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
LCP
Under voltage relay RAEDA1 1 4.4 4.4 (Annexure-2 Sh. No. 11)
Since, the connected burden is less than 100VA,the provided VT burden is adequate.
Core-1 Core-2
Calculation of VT burden :
Core-1 :
Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
FFR 98-25AR/A811 FOR MAIN-2 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
Line set-1 protection REL 531 1 0.2 0.2 (Annexure-2 Sh. No.15)
FFR (98) (Ref.) for Energy meter RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
FFR (98L) (Ref.) for 25MC 810 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
Core-2:
Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
25MC/A811 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)
25AR / A811 FOR MAIN-2 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)
27-L2 Under voltage relay RAEDA1 3 4.4 13.2 (Annexure-2 Sh. No. 11)
Transducer Panel
Voltage transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No.13)
Watt meter Watt transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No.13)
Var meter Var transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No.13)
Under voltage relay RAEDA1 1 4.4 4.4 (Annexure-2 Sh. No. 11)
FFR (98) (Meas.) for revenue meter RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
LCP
FVS-U-
Under voltage relay 1 4.4 4.4 Assumed
DC12
Voltmeter PML 1 0.5 0.5 Assumed
Since, the connected burden is less than 100VA,the provided VT burden is adequate.
VT Details :
Core-1 Core-2
Calculation of VT burden :
Core-1 :
Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
FFR (98B1) (Meas.) 25AR/810 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
Considering 25% safety margin for any additional FFR relay required.
Core-2:
Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
25MC/A804 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)
Transducer panel
Voltage transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No.13)
LCC
Considering 25% safety margin for any additional FFR relay required.
Since, the connected burden is less than 100VA,the provided VT burden is adequate.
Core-1 Core-2
Calculation of VT burden :
Core-1 :
Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
FFR (98B2) (Meas.) 25AR/806 RXBA 4 1 2 2 (Annexure-2 Sh. No.9)
Considering 25% safety margin for any additional FFR relay required.
Core-2:
Total burden
Relays / Instruments Relay type Quantity Unit burden
(VA)
25MC/A806 RASC 1 0.25 0.25 (Annexure-2 Sh. No.17)
Transducer panel
Voltage transducer for SCADA ISTAT300 1 0.1 0.1 (Annexure-2 Sh. No.13)
LCC
Considering 25% safety margin for any additional FFR relay required.
Since, the connected burden is less than 100VA,the provided VT burden is adequate.
1. Applicable Standard
- IEC 60044-1, IEC 60044-6
2. Ratings
- Symmetric short circuit (Ith) : 63kA rms
- Dynamic short circuit (Idyn) : 163.8kA peak
- Continuous thermal current rating factor : 2.0
1) GCB A810
Specification Type
Location Current Ratio Adopted Class Ual Rct Ial Burden Kssc K Rb
TAP @75℃
<3.1Ω
Bus-1 1 3000-2500-2000-1500- 50BF/A810
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A
Side
<3.1Ω
2 3000-2500-2000-1500- AL-FADHILI
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A LINE-2 SET-2
3 3000-2500-2000-1500-
1250-1000-750/1A
2000/1A TPS >3700V <3.1 Ω <75mA - 31.5 12.63 6.2 CT-1
AL-FADHILI
LINE-2 SET-1
4 3000-2500-2000-1500- AL-FADHILI
2500/1A 0.2 SF<5 - - 50VA - - -
1250-1000-750/1A LINE-2 MET.
Bus-2 1 3000-2500-2000-1500-
1250-1000-750/1A
3000/1A TPS >5550V <4.65Ω <50mA - 21 18.95 9.3 CT-1 87B1/M1
Side
<4.65Ω
2 3000-2500-2000-1500- 87B1/M2
3000/1A TPS >5550V <50mA - 21 18.95 9.3 CT-1
1250-1000-750/1A
<4.65Ω
3 3000-2500-2000-1500- SPARE
3000/1A TPS >5550V <50mA - 21 18.95 9.3 CT-1
1250-1000-750/1A
NOTE:
1. CT-2 TYPE: Present design - 3000/1A Tap Rct<6.7ohm --- The CT is CT-2 type. If the CT will be used 2000/1A tap, Rct will be <4.65 ohm,
not <3.1ohm.
2. CT-1 TYPE: Present design - 2000/1A Tap Rct<3.1ohm --- The CT is CT-1 type. If the CT will be used 3000/1A tap, Rct will be <4.7ohm,
not <6.7ohm.
2) GCB A811
Specification Type
Location Current Ratio Adopted Class Ual Rct Ial Burden Kssc K Rb
TAP @75℃
<3.1Ω
Bus-1 1 3000-2500-2000-1500- 50BF/A811
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A
Side
<3.1Ω
2 3000-2500-2000-1500- MANIFA
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A LINE-2 SET-1
3 3000-2500-2000-1500-
1250-1000-750/1A
2000/1A TPS >3700V <3.1 Ω <75mA - 31.5 12.63 6.2 CT-1
MANIFA
LINE-2 SET-2
4 3000-2500-2000-1500- MANIFA
3000/1A 0.2 SF<5 - - 60VA - - -
1250-1000-750/1A LINE-2 MET.
Bus-2 1 3000-2500-2000-1500-
1250-1000-750/1A
3000/1A TPS >5550V Ω
<4.65 <50mA - 21 18.95 9.3 CT-1 SPARE
Side
<3.1Ω
2 3000-2500-2000-1500- AL-FADHILI
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A LINE-2 SET-1
3 3000-2500-2000-1500-
1250-1000-750/1A
2000/1A TPS >3700V <3.1 Ω <75mA - 31.5 12.63 6.2 CT-1
AL-FADHILI
LINE-2 SET-2
4 3000-2500-2000-1500- AL-FADHILI
2500/1A 0.2 SF<5 - - 50VA - - -
1250-1000-750/1A LINE-2 MET.
NOTE:
1. CT-2 TYPE: Present design - 3000/1A Tap Rct<6.7ohm --- The CT is CT-2 type. If the CT will be used 2000/1A tap, Rct will be <4.65 ohm,
not <3.1ohm.
2. CT-1 TYPE: Present design - 2000/1A Tap Rct<3.1ohm --- The CT is CT-1 type. If the CT will be used 3000/1A tap, Rct will be <4.7ohm,
not <6.7ohm.
3) GCB A812
Specification Type
Location Current Ratio Adopted Class Ual Rct Ial Burden Kssc K Rb
TAP @75 ℃
<4.65Ω
Bus-1 1 3000-2500-2000-1500- 87B2/M1
3000/1A TPS >5550V <50mA - 21 18.95 9.3 CT-1
1250-1000-750/1A
Side
<4.65Ω
2 3000-2500-2000-1500- 87B2/M2
3000/1A TPS >5550V <50mA - 21 18.95 9.3 CT-1
1250-1000-750/1A
<4.65Ω
3 3000-2500-2000-1500- SPARE
3000/1A TPS >5550V <50mA - 21 18.95 9.3 CT-1
1250-1000-750/1A
<3.1Ω
Bus-2 1 3000-2500-2000-1500- 50BF/A812
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A
Side
<3.1Ω
2 3000-2500-2000-1500- MANIFA
2000/1A TPS >3700V <75mA - 31.5 12.63 6.2 CT-1
1250-1000-750/1A LINE-2 SET-1
3 3000-2500-2000-1500-
1250-1000-750/1A
2000/1A TPS >3700V <3.1 Ω <75mA - 31.5 12.63 6.2 CT-1
MANIFA
LINE-2 SET-2
4 3000-2500-2000-1500- MANIFA
3000/1A 0.2 SF<5 - - 60VA - - -
1250-1000-750/1A LINE-2 MET.
NOTE:
1. CT-2 TYPE: Present design - 3000/1A Tap Rct<6.7ohm --- The CT is CT-2 type. If the CT will be used 2000/1A tap, Rct will be <4.65 ohm,
not <3.1ohm.
2. CT-1 TYPE: Present design - 2000/1A Tap Rct<3.1ohm --- The CT is CT-1 type. If the CT will be used 3000/1A tap, Rct will be <4.7ohm,
not <6.7ohm.
ANNEXURE-4A
380kV GIS DATA SCHEDULE FROM TOSHIBA
ANNEXURE-5
SUBSTATION ELECTRICAL LAYOUT-PLAN
PROJECT: ABU-HADRIYAH CONTRACT No.
ABU-HADRIYAH 380/115 kV BSP 3-083300.01
NOTE: CT LEAD LENGTH IS CONSIDERED AS 500 METERS ON CONSIDERABLY SAFER SIDE TO ACOUNT FOR ANY CIRCUIT
CHANGES IN FUTURE. HENCE, CT LEAD LENGTH IS ESTIMATED AS 500 METERS FOR ALL BAYS CT SIZING CALCULATION.
ANNEXURE-6
RELAYING & METERING ONE LINE DIAGRAM
ANNEXURE-7
LINE PARAMETERS
ANNEXURE-8
M&I METROSIL CATALOGUE
ANNEXURE-9
380kV CVT DATA SCHEDULE