GSB Gradation

This document provides a test report for the grading of granular sub base material from a construction project. It includes information such as the project details, item description, location, quantities offered and inspected, sieve analysis results shown in a table with weights retained and percentages passing for each sieve size, and specification limits for comparison. The material was tested and found to meet the specifications, shown as the result of "Accepted".

Uploaded by

Gabriel Gabe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14K views1 page

GSB Gradation

This document provides a test report for the grading of granular sub base material from a construction project. It includes information such as the project details, item description, location, quantities offered and inspected, sieve analysis results shown in a table with weights retained and percentages passing for each sieve size, and specification limits for comparison. The material was tested and found to meet the specifications, shown as the result of "Accepted".

Uploaded by

Gabriel Gabe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd

Report No: 2

GRADING OF GRANULAR SUB BASE


TEST REPORT
Date: 16/01/2023

Project : Construction of General Civil


Customer : M/S TATA Power Solar Ltd. Work(GCW) at 4 GW Manufacturing Plant Project Code: UI/670065
Gangaikondan.
WO No & Amndt, If any.:
Manufacturer : PO No & Amndt, If any.:
Item Description: Identification No.
Location : Sub Location:
Package: Drg No & Rev No :
FQP No. & Rev No. RFIC No.

Layer : Date of sampling :


Total Quantity offered for inspection: Date of testing :
Total Quantity inspected & accepted: Total Weight (gm):
Total Quantity inspected & rejected:

Weight Cumulative
Sieve Size (mm) Cum. Wt. retained (gms) % Passing
retained (gms) % retained

75.00 0 0 0.0 0.0

53.00 0 0 0.0 100.0

26.50 1665 1665 16.7 83.4

4.75 1741 3406 34.1 65.9

0.075 1418 4824 48.2 51.8

Pan 176 5000 50.0 50.0


Specification Limits

Sieve Size
(mm)
Grade I Grade II Grade III Grade IV Grade V Grade VI

75.00 100 - 100

53.00 80 - 100 100 100 100 80 - 100 100

26.50 55 - 90 70 - 100 55 - 75 50-80 55 - 90 75 - 100

9.50 35 - 65 50 - 80 35 - 65 55 - 75

4.75 25 - 55 40 - 65 15-35 25 - 50 30 - 55
10 - 30
2.36 20 - 40 30 - 50 10 - 20 Oct-25
0.85 - - 2 - 10

0.425 10 -- 15 10 -- 15 0-5 0-8

0.075 <5 <5 <5 <5 0-3


Result: Accepted / Rejected

Signature of Sub-Contractor & Date Signature of TPL - FQE & Date Signature of Customer / Inspection Authority & Date
Format No.08.03.05-FMT-C-GSB-TR-001-R00

Date: 16/01/2023
Customer : M/S TATA Power Solar Ltd.
Project Code:  UI/670065
  
WO No & Amndt, If any.:
Manufacturer :
PO N