Professional Documents
Culture Documents
- CHECK LIST -
MARRIOTT FIRE PROTECTION & LIFE SAFETY
high rise BUILDING check list
Address: _________________________________________________________________________________
AIRPORT RESIDENTIAL AREA
City: _________________________
ACCRA State: _________________________ Zip: _________________________
Under Marriott Corporate guidelines, all fire protection systems and life safety features of the building
are required to be fully operational, comply with specifications, and be fully tested and accepted by
Marriott Corporate Fire Protection & Life Safety prior to admitting Marriott operations personnel or
general public to the building.
The final testing will include the sprinkler system, fire alarm system, emergency power and kitchen
hood suppression system where applicable. It is necessary that the installation of these systems is
complete, has received prior testing or adjustment, and is ready for full operational use, prior to the
witnessing of the final acceptance tests.
Testing will require the presence of representatives from the sprinkler and fire alarm companies.
Please have two fully charged portable radios available for use on site during test. The final test will
include the following:
System shall be flushed and pressure tested by contractor prior to Marriott testing.
All sprinkler devices connected to the fire alarm system will be tested. These devices
AUTOMATIC include water flow switches, tamper switches, and pressure switches/gauges (if
SPRINKLER installed) on all zones. The fire pump (if installed) must be tested and approved by
SYSTEM the authority having jurisdiction prior to Marriott testing. A representative of the
sprinkler contractor shall be present and prepared to test system.
The fire alarm system shall be clear from all troubles on the FACP and pre-tested
FIRE by the contractor prior to Marriott testing. Marriott will test all devices and ensure
ALARM proper zone/device indications and function on the alarm panel. A representative
SYSTEM of the fire alarm contractor shall be present and prepared to test system (including
canned smoke and pull station keys).
All power to the building will be turned off to test the emergency power system.
Emergency lighting illuminating the exit path, exit signs and lighting of the exit
EMERGENCY discharge to the public way will be checked as well as certain other public and back
POWER of house areas. Motor driven generator (if installed) must automatically activate
SYSTEM upon loss of power to operate all emergency systems as specified in the Marriott
International Design Guide.
Kitchen hood is protected by an UL 300 listed system that has been tested and
KITCHEN approved by the authority having jurisdiction prior to Marriott testing. A certified
SUPPRESSION installer must be present at the Marriott testing. The system will not be expelled
SYSTEM however the manual pull station test, shunt test for gas and electric under the hood,
(IF APPLICABLE) fire alarm interface and the detection test from the farthest link under the hood will
be tested.
Smoke The smoke exhaust system must have been tested and all exit signs are visible within
Control the test area in not more than 10 minutes from activation. In addition, smoke must
System not migrate out to any adjacent areas.
Note: The above systems represent only a portion of Marriott International’s Life Safety
Standards which must be implemented in accordance with the Marriott Hotel Design
Guide. Local codes will be enforced if more stringent than Marriott requirements.
LOCAL FIRE INSPECTIONS MUST BE COMPLETE WITH ALL DESCREPANCIES
CORRECTED BEFORE INSPECTION BY MARRIOTT FIRE PROTECTION. Attach and fax.
SPRINKLER SYSTEM:
1. System is zoned by floor. Each floor zone has a control valve assembly with a tamper switch and a
flow switch on every floor.
YES | NO
2. All floors are equipped with an inspector’s test (hard-piped to an express drain) at the remote end of each
sprinkler zone if not looped, per Module 14.
YES | NO
3. All sprinkler heads in occupied areas are quick response type and 155 to 165 °F.
YES | NO
4. The entire building is protected with an automatic sprinkler system including all mechanical and
electrical rooms, as well as all public and back of house storage closets.
YES | NO
6. All unheated areas subject to freezing are protected with a dry sprinkler system
(attic, garages, combustible canopies, etc.).
YES | NO
7. Sprinkler heads are installed in linen and trash chutes above the top opening, above the bottom
opening, and at alternating levels.
YES | NO N/A
8. Sprinkler heads in pool/whirlpool rooms and pool equipment rooms are corrosion proof type.
YES | NO
9. Sprinkler heads are located in guest bathrooms containing a combustible bathtub, surround or
whirlpool or where the room is greater than 55 sq.ft.
YES | NO
10. The air compressor for the dry system is tank mounted type. All wet sprinkler pipe is located in
heated space (40 °F or greater).
YES | NO (system is wet pipe only. No dry pipes are installed)
11. The dry system delivers water to the remote inspector’s test within 60 seconds of actuation of the
test valve.
YES | NO N/A
12. The inspector’s test for the dry system is located at the most remote end. Test valve must not be
located within a guestroom or attic space.
YES | NO (system is Wet type not dry type)
13. Mark all automatic sprinkler control valves, drain valves and test valves with permanently marked
weatherproof metal or rigid plastic identification signs. Signs must indicate the specific portion of the
building controlled by the valve.
YES | NO
14. The electric fire pump must annunciate the conditions “run”, “phase reversal” and “off line” at the
fire alarm control panel.
YES | NO Pump not yet Installed
15. The fire pump has been tested and accepted by the authority having jurisdiction.
ATTACH PUMP TEST DATA
YES | NO Pump not yet installed
16. Pressure gauges are installed on the inlet and outlet sides of each pressure-reducing valve.
YES | NO N/A
17. A permanent 3 inch drain is installed for testing the pressure reducing valves as required by NFPA 14.
YES | NO N/A
18. A permanent placard is installed at each pressure reducing valve showing the greatest fire
protection demand (flow and pressure) required at the valve outlet.
YES | NO N/A
19. A copy of a complete and satisfactory Contractor’s Material and Test Certificate for Aboveground
Piping is available with pressure reducing valve test data verifying that each pressure reducing valve
meets the greatest fire protection demand (flow and pressure) served by the pressure reducing valve.
YES | NO N/A
22. Sprinkler control valves have tamper switches monitored by the fire alarm control panel AND
valves in public view or access are chained and locked in the open position while valves in the back of
house behind locked doors or access panels are secured with plastic or wired seals.
YES | NO Not yet Installed
2. System type photoelectric smoke detectors (sensors) with sounder bases are installed in all
guestroom sleeping/living areas.
YES | NO
3. Guestroom system type smoke alarms will sound a local alarm within each guestroom, display an
audible/visual alarm at the fire alarm control panel (FACP), as well as display the guestroom number
at the FACP upon activation.
YES | NO ( This shall be programmed into the system after installation)
4. Multiple smoke detectors within a guestroom suite are interconnected. For example, if the smoke
detector sounds within the living area, the smoke detector located in the bedroom(s) must also sound.
YES | NO (This shall be programmed into the system after installation)
5. The guestroom smoke detectors DO NOT initiate the general fire alarm.
YES | NO (Dependent on programming of alarm panel)
6. Guest room smoke detectors are powered by the fire alarm control panel. A/C powered smoke
detectors are not acceptable.
YES | NO
7. Removal of a guest room smoke or carbon monoxide detector will initiate a trouble signal at the fire
alarm control panel.
YES | NO
8. Fire alarm speaker(s) are installed in all guestroom sleeping areas for general alarm notification
purposes. Hearing-impaired guestrooms must have a speaker/strobe in the sleeping area and a single
strobe in the bathroom. The strobe must be programmed to activate upon local and general alarm.
YES | NO (programming shall be done after installation is completed)
9. The fire alarm strobe located within all sleeping areas (pullout sofa is considered a sleeping surface)
of a hearing impaired room that is installed within 24 inches from the ceiling are 177 cd candela rated.
YES | NO ( To be installed)
10. A fire alarm speaker/strobe is located in all public areas, corridors and back of house common areas.
YES | NO
11. Carbon monoxide (CO) detectors are installed in ALL rooms containing fuel burning equipment,
appliances or fireplaces. CO detectors must provide a local alarm within the room and a supervisory
alarm at the fire alarm control panel
YES | NO N/A
12. All guest elevators are equipped with primary and secondary elevator recall. Ensure ground floor
elevator lobby smoke detector will recall the elevators to an alternate level.
YES | NO (Dependent on Programming of Fire Alarm Panel)
13. Area smoke detectors are installed in all public common areas for mechanical smoke exhaust
activation (lobby, public corridors, etc.).
YES | NO
(to be installed)
14. Magnetic door hold open devices are installed for all meeting room/ballroom entry doors serving
the public corridor. The magnetic door hold open devices must be monitored by the fire alarm control
panel and release upon general fire alarm with its associated zone.
YES | NO
15. A remote fire alarm annunciator panel is installed in an area monitored by a hotel associate at all
times (typically at the front reception desk or at PBX/AYS).
YES | NO
16. Weatherproof type fire alarm devices are installed in all unconditioned areas including the parking
garage, outdoor terraces, etc.
YES | NO
17. Ensure all fire alarm devices correspond with the permanent guestroom room number signage and
stair signage (Example: Level 10 Corridor Smoke Det by Rm 1010 or Level 10 Pull Station by Stair 1).
YES | NO (to be done after device installation)
18. The fire alarm installer has completed and signed the NFPA 72 Fire Alarm System Record of
Completion. ATTACH AND FAX.
YES | NO (Installation not yet completed)
FAILURE TO PROVIDE THE FOLLOWING WILL DICTATE A RETURN TRIP, TOTAL FIRE ALARM
RE-TEST AND A POSSIBLE DELAYED OPENING .
The FACP must disable audible appliances, visual strobes, and auxiliary function points for
testing purposes with the use of disconnect switches or single function key pads.
□ One switch/key should silence horns and strobes for general alarm. WHILE DISABLED,
The guestroom smoke alarms must sound as usual on local alarm and ADA/hearing
impaired rooms must have visible and audible on local alarm.
□ One switch should bypass the smoke control and stairwell pressurization fans.
*Please Note:
□ ADA/Hearing Impaired Guestroom Horns and Strobes will remain active for local activation
during testing.
1. Emergency lighting is installed throughout the entire hotel, including all back of house areas,
laundry, fire alarm control panel area, public restrooms, engineer’s office, telephone equipment room,
mechanical rooms, elevator room, fire pump and sprinkler room, administrative offices, meeting
rooms, and on the exterior side of all marked exit discharges.
YES | NO (to be done by electrical installer)
4. The emergency generator must annunciate the conditions “run” and “off line” at the fire alarm
control panel.
YES | NO (to be provided by electrical installer)
2. Activation of the hood system sends an alarm to the fire alarm control panel, drops an electric shunt
tripping breakers for all electric current under the hood, as well as trips the gas solenoid for all gas
fueled cooking appliances under the hood.
YES | NO (Not Installed)
3. Upon activation, the hood exhaust fan must continue to operate in a normal mode, hood make-
up air unit shuts off and the supply, return and exhaust fans in other areas remain in their normal
operating modes.
YES | NO (To be done after system installation)
LIFE SAFETY:
4. All exit stairwell doors are not locked from the stairwell side, (allowing re-entry back onto the
guestroom floor). However, the exit door at the bottom of the stairwell, which leads directly to the
exterior, may be locked from the exterior side as long as the door is equipped with panic hardware.
YES | NO
5. Guestroom entry doors are equipped with self-closers.
YES | NO
6. All doors in the means of egress that serve an area with an occupant load of 50 or more persons
swing out in the direction of egress (toward the corridor/outside).
YES | NO
7. A second remote exit is required for meeting room configurations where there are more than 50
occupants (350 sq. ft.) within an enclosed meeting space. A door in a partition leading to another
room is not considered an exit.
YES | NO
8. There is panic hardware on assembly occupancy doors where occupant loads are greater than 100
persons or 700 sq. ft.
YES | NO
10. The linen and trash chutes extend through the roof with sprinklers located at the top, bottom and
alternate floors. The terminal end of the chute has a fire rated door as do all access doors. Chutes
comply with NFPA 82.
YES | NO
11. There are no storage rooms or storage room doors which open directly into the stairwell.
YES | NO
2. Mechanical smoke exhaust is provided in all exit access and exit access corridors including
guestroom corridors.
YES | NO
3. The smoke exhaust system is activated by both area smoke detectors and water flow alarms-
independent from each other on guestroom floors.
YES | NO
4. On non-guestroom floors, the smoke exhaust system is activated by area smoke detectors only.
YES | NO
6. Manual fire alarm pull stations does not activate the smoke exhaust system.
YES | NO
7. A manual override is provided for the smoke exhaust and stair pressurization systems.
YES | NO
8. All smoke exhaust zones have been pre-tested with a theatrical smoke machine and able to exhaust
smoke out of the building so that all exit signs are visible within 10 minutes of activation from any
given point.
YES | NO
9. Upon activation of the smoke evacuation system the smoke does not migrate to adjacent smoke zones.
YES | NO
10. The mechanical pressurized stairwells will release the exit door hatch within 15 lbs., set the door
in motion within 30 lbs., and open the door to required width within 15 lbs. The stair pressurization
system must have a pressure difference across the barrier of not less than .05 in. water column.
YES | NO | N/A
When all items are complete, please sign and email this entire document, along with the required
attachments to Ronda Greenberg, at FLS@Marriott.com. To ensure receipt, contact Ronda
Greenberg at 301-380-5720.
I certify that the items above are complete, tested and ready for inspection by Marriott Fire Protection
& Life Safety. Failure of the Marriott Fire and Life Safety inspection may cause a delayed opening
and additional charges for re-inspection. (System Test will be done after completion of installation)
_________________________________________ _________________________________________
Printed Name Signed
_________________________________________ _________________________________________
Title Date
_________________________________________ _________________________________________
Email Phone
MFP 11/15/2018