∙ Revision :A
∙ Number of pages : 22
Daikin Europe N.V. Front Page EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 A 1
0 1 2 3 4 5 6 7 8 9
Page overview
Page Page Description Page Revision
0 Front Page A
1 Front Page A
2 Page Overview A
3 Notes -
4 Legend -
5 PCB interconnection diagram -
6 PCB I/O overview + fuses -
7 PCB changeable I/O overview -
8 Unit outlook -
9 Switchbox outlook (typical) -
15 Main power supply -
16 Trafo + PCB power supply A
20 Compressor & fan -
21 Circuit 1: control compressors -
22 Circuit 1: control fans -
30 Control circuit (DI 230V) -
31 Control circuit and EEV -
32 Circuit 1: sensors -
40 Fieldwiring DI, changeable DI -
41 Fieldwiring changeable AI/AO -
42 Fieldwiring DO,changeable DO -
43 Fieldwiring DO,changeable DO -
Daikin Europe N.V. Page Overview EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 A 2
0 1 2 3 4 5 6 7 8 9
Y1R, Y2R reversing valves are activated in cooling mode. DI: Digital input
DO: Digital output
AI: Analog input
AO: Analog output
Ch: Changeable (function can
be selected by the customer)
Description Unit name Drawing number Page
Daikin Europe N.V. Notes EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 3
0 1 2 3 4 5 6 7 8 9
Daikin Europe N.V. Legend EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 4
0 1 2 3 4 5 6 7 8 9
Std EKRUPG
1 1
HAP A4P HAP A4P HAP A5P
SUB SUB SUB
RS485
RS485
RS485
DC 24V
DC 24V
DC 24V
TERM TERM TERM
GND
GND
GND
S2A S2A S2A
+
X1M X1M X1M
-
ON OFF ON OFF ON OFF
3
V1C
ON DS1
TERM A11P
S2A
ON OFF
X52A X51A X88A OFF ADDRESS=1
ACS ACS
EKACPG HAP X89A
A71P *
A02P A01P
F1 HCP
DICN only
F2
ON DS1 for EWYQ
+
MODBUS RS485 080-100
- TERM
2 S3A
V2C X1M
HEP HDP ON OFF X88A OFF ADDRESS=2
HAP ACS
For S3A setting HAP X89A
see installation manual
A72P *
H1P
H2P shortcut on last
HAP * = EEV PCB (319)
HBP
ON
OFF S1A
ADDRESS=1
= DIPSWITCH
Daikin Europe N.V. PCB interconnection diagram EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 5
0 1 2 3 4 5 6 7 8 9
Daikin Europe N.V. PCB I/O overview + fuses EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 6
0 1 2 3 4 5 6 7 8 9
Daikin Europe N.V. PCB changeable I/O overview EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 7
0 1 2 3 4 5 6 7 8 9
M13F M14F
M15F M16F
MxxF
: Inverter controlled fan
SWITCHBOX
M11C M12C
EWAQ 80-100
EWYQ 80-100
Daikin Europe N.V. Unit outlook EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 8
0 1 2 3 4 5 6 7 8 9
A-A ( 1 : 2 )
X12Y
X16Y X13Y X10Y X17Y
A72P A71P
TR1
V1C
A13P
A11P
X19Y
A01P X11Y L=300
X15Y X14Y E7H X18Y
K13..16F X26Y/X27Y
F17B/F16B
K2P/K1P
F15B
K13..16S
TR1A
A4P
T1A
S1T
F14B
T1V
F9B
F6B
F8B
Earth Supply
K11M
K12M
K1A
<0
K3A
S1M
A A
Daikin Europe N.V. Switchbox outlook (typical) EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 9
0 1 2 3 4 5 6 7 8 9
L1C1 / 20.0
L2C1 / 20.0
L3C1 / 20.0
OPTC 2
L2C1./ 16.0 OPSC
L3C1./ 16.0
X26Y 1
X26Y 2
X26Y 3
1 3 5 1 3 5
11 11 OP10
F16B 14 F17B 14
I I I I I I
2 4 6 2 4 6 12
OP57
R1
Q1T 12
K3A
501 11 21.9 R2
/ 32.4
T1A U V W U V W
OPSP/OPTP/OPHP
TR1A 300A/5A M M
M1P 3˜
M2P 3˜
502 12 PE PE 0
/ 32.4
T1A
2
1 3 5 1 3 5 1 2
11 11
F16B 14 F17B 14
2 4 6
I I I I I I 2 4
S1M 2 4 6 2 4 6
1 3 5
S2M
1 3
1 3 5 1 3 5
K1P K2P
2 4 6 2 4 6
F1 F2 F3
X17Y 1 6 7 12 X17Y 4 3 10 9 F4 F5
U V W U V W
M1P M M2P M
3˜ 3˜
PE X17Y 9 PE
L1 L2 L3 PE PE
Power supply
Power supply 1˜50Hz 230V
3˜50Hz 400V
Daikin Europe N.V. Main power supply EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 15
0 1 2 3 4 5 6 7 8 9
15.2 /L2C1.
15.2 /L3C1.
1 3 5
F6B
I I I
2 4 6
OP57
62
60 11
/ 32.6
61 12 T1V
/ 32.6
T1V
400 VAC
1 5
TR1
32 33
31 34
230 VAC
63
F9B
I
X1A:3 X1A:1
F8B I
F1U 2
5A
SN
/ 30.0 t°
A11P S1T
SL
A11P / 30.0
66
F1U
X3A X2A:1 X2A:2
E7H
X18Y 1
X77A:3
X77A:1
X77A:3
X77A:1
E1 E1
A71P A72P
101
102
203
Daikin Europe N.V. Trafo + PCB power supply EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 A 16
0 1 2 3 4 5 6 7 8 9
15.2 / L1C1
15.2 / L2C1
15.2 / L3C1
1 3 5
F15B
I I I
325 2 4 6
1 3 5
5 L1 L2 L3
10
F14B 13 A13P
I I I K13F 11
31.2
2 4 6 14
326
8 U V W
13
K15F
14
328
1 3 5 1 3 5
K11M K12M
2 4 6 2 4 6 A11P
95 95
95 95
K14S K16S K13S 96 K15S
22.3 2 4 6 22.3 2 4 6 96 22.1 2 4 6 22.1 2 4 6 96
96
U1 V1 W1 U1 V1 W1 U1 V1 W1 U1 V1 W1
W2 U2 V2 W2 U2 V2 W2 U2 V2 W2 U2 V2
U V W U V W
M14F M M16F M M13F M M15F M
3˜ 3˜ 3˜ 3˜
M M
M11C 3~ M12C 3~ PE PE PE PE
Q11C Q12C
PE PE
X14Y 10 X14Y 22
Daikin Europe N.V. Compressor & fan EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 20
0 1 2 3 4 5 6 7 8 9
SL SL
102 102
16.1 / A11P A11P / 22.0
102 102
X2A X2A
SL 203 203 SL
16.2 / / 22.0
A11P 11
A11P
K1A
30.4 14
204
A11P A11P
X13A:1 X14A:2 X17A:2 X15A:7
21 21
K11M K12M K3R
K1R K2R K5R
22 22
212
105
106
107
213
X10Y 3 X10Y 6 X10Y 7 X12Y 6 X13Y 1
Q11C Q12C
L1 L1
A1 A1 A1
K11M K12M Y1R E11HC E12HC K3A
A2 A2 A2
N N
Only
for EWYQ
Daikin Europe N.V. Circuit 1: control compressors EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 21
0 1 2 3 4 5 6 7 8 9
SL
102 102
21.9 / A11P /
X2A
SL 203 203 SL
21.9 / / 43.2
A11P A11P
203
203
X27Y 2
122
A0
12
X72A:3 X72A:4
95 95
K15S K16S
12
20.8 96 20.5 96
111 121
A11P
X16A:3
111
116
121
323
324
K1*S K2*S K3*S K4R
/ 30.3 / 30.3 / 30.3
A11P A11P A11P
A11P
X19A:1 X19A:5 X20A:2 X16A:1
A13P 13
K7R K8R K9R
(0V) 2 (AIN+) 3 (AIN-) 4
13
X19A:3 X19A:7 X20A:1
X27Y 3
A1
K1P
220
220
222
222
A2
A1 A1 A1 A1
K13F K15F K14F K16F
A2 A2 A2 A2
OPSP/OPTP/OPSC/ X27Y 1
OPTC/OPHP
101
SN SN
101 101
21.9 / A11P A11P / 43.3
X2A X2A
Daikin Europe N.V. Circuit 1: control fans EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 22
0 1 2 3 4 5 6 7 8 9
A11P
SL
230
16.1 / A11P
X4A:1
F1U X10Y 10
S1PH P>
X10Y 11
239
X4A:3
DI 231
X5A:2
X12Y 3
14/M2
Q11C
11/M1
X12Y 4
232
X5A:1
DI 233
X6A:3
X13Y 3
14/M2
Q12C
11/M1
X13Y 4
234
X6A:1
DI 235
X7A:1
111 K1*S
/ 22.1
X7A:2 A11P
DI
X8A:1
116 K2*S
/ 22.2
X8A:3 A11P
DI
X9A:1
121 K3*S
/ 22.3
X9A:3 A11P
DI
X10A:3
A1
K1A
X10A:1 A2
DI
X11:1
SN 236
16.1 /
A11P X11A:2 11 14 21.1
Daikin Europe N.V. Control circuit (DI 230V) EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 30
0 1 2 3 4 5 6 7 8 9
A11P
DI DI DI RS485
X51A:1 X51A:2 X29A:4 X29A:3 X27A:1 X27A:2 X30A:1 X30A:2 X1B:1 X1B:2 X1B:3 X1B:4 X1B:5 X2B:1 X2B:3 X52A:1 X52A:2 X52A:3 X52A:4
244
245
301
302
303
304
OPIF
248
249
WHT
WHT
BLU
BLU
BLU
BLU
BLK
246
247
X16Y 5 6 X19Y 1 2 3 4
X18Y 3
A13P
301
302
303
304
A01P A4P
X1B:1 X1B:2 X1B:3 X1B:4 X1B:5 X2B:1 X2B:3 X1M:+ X1M:- X1M:24V X1M:GND
10 S1L
A13P
V1C 3 20.7 11
RS485
ALARM
313
314
*
315 *
316 319
A71P A72P
471
472
473
480
481
482
483
485
486
487
488
WHT
WHT
GRN
GRN
GRN
RED
RED
RED
BLK
BLK
BLK
M M M
Daikin Europe N.V. Control circuit and EEV EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 31
0 1 2 3 4 5 6 7 8 9
A11P A01P
AI AI AI AI AI AI AI AI AI AI AI
X33A:1 X33A:3 X34A:1 X34A:2 X35A:1 X35A:2 X36A:1 X36A:2 X37A:1 X37A:2 X38A:1 X38A:2 X39A:1 X39A:2 X40A:1 X40A:2 X41A:1 X41A:2 X66A:1 X66A:2 X67A:1 X67A:2
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
X16Y 7 8 1 2 3 4 X15Y 19 20 29 30 X15Y 25 26 27 28 X15Y 21 22 23 24 X15Y 31 32 33 34
R1T R2T R3T R14T R17T R16T R26T R15T R25T R18T R28T
-t° -t° -t° -t° -t° -t° -t° -t° -t° -t° -t°
A11P
AI AI AI AI
X42A:1 X42A:2 X42A:3 X42A:4 X43A:1 X43A:2 X43A:3 X43A:4 X44A:1 X44A:2 X44A:3 X44A:4 X45A:1 X45A:2 X45A:3 X45A:4
450
451
452
453
454
455
503
504
513
514
OP57
X15Y 13 14 15 X15Y 16 17 18
WHT
WHT
RED
RED
BLK
BLK
31 32 31 32
11 12 11 12
502
60
61
11 12 11 12
15.1 / / 15.1 16.3 / / 16.3
T1A T1A T1V T1V
Daikin Europe N.V. Circuit 1: sensors EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 32
0 1 2 3 4 5 6 7 8 9
A11P A01P
44
45
46
47
48
49
50
51
52
53
46 47 48 49 50 51 52 53
7
X27Y 7 44 X27Y 8 45
13 13 13 13
S1S S2S S3S S4S
14 14 14 14
13
K1P
22.7 14
Example: remote Example: remote
start/stop cool/heat
OBLIGATORY
X27Y 7 44 X27Y 8 45
OPTP/OPTC 7
OPSP/OPSC/OPHP
13 13
K1P K2P
22.7 14 43.3 14
OPSC/OPTC/OPSP/OPTP/OPHP
Daikin Europe N.V. Fieldwiring DI, changeable DI EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 40
0 1 2 3 4 5 6 7 8 9
A01P
71
72
73
74
75
76
77
78
79
80
81
90
91
70 71 72 76 77 78 79 80 81 90 91
73 74 75 73 74 75
8 8 + +
0 13 0
+ +
R8T to S5S to
-t° 0 0 14
to to 10VDC 20mA or 10V
- -
20mA 20mA
- -
Daikin Europe N.V. Fieldwiring changeable AI/AO EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 41
0 1 2 3 4 5 6 7 8 9
AC15: max.3A-230V Changeable DO: Maximum load: 2A-230VAC, Minimum load: 10mA-5VDC
A11P A11P
X22A:5 X24A:2
X22A:3
13 13
K11M K12M K12R K14R
14 14
X22A:1 X24A:1
3
Alarm NO Alarm NC
10
11
7
9
Default Software selection necessary
3 4 5 6 10 11
7 8 9 7 8 9
9 9
H11P H12P H2P
H1P H1P
Daikin Europe N.V. Fieldwiring DO,changeable DO EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 42
0 1 2 3 4 5 6 7 8 9
13
14
15
16
17
18
19
20
21
12 13 16 17 18 19 20 21
X27Y 4 X27Y 3
10 X27Y 6 14 X27Y 5 15 10 X27Y 6 14 X27Y 5 15
H5P H6P
H3P H4P
K1S
K1P
11
F17B K2P
14
X27Y 2 X27Y 1
External
SL SN Power
A11P A11P supply External External External
External 22.9 X2A (ex 24VAC Power Power Power
Power supply 22.9
or 230VAC) supply supply supply
(ex 24VAC (ex 24VAC (ex 24VAC (ex 24VAC
or 230VAC) Changeable DO3 Changeable DO3
or 230VAC) or 230VAC) or 230VAC)
(Default: 2nd pump) (no predefined function)
MODELS WITH OPTC/OPTP MODELS WITHOUT OPTC/OPTP
NOT FOR MODELS WITH
1 2 15.5
OPSC/OPTC/OPSP/OPTP/OPHP 3 4 15.5
5 6 15.5
13 14 40.2
Daikin Europe N.V. Fieldwiring DO,changeable DO EWAQ 80-100 EWYQ 80-100 OPIF 4TW57576-2 - 43