Professional Documents
Culture Documents
Abstract—Transmission network voltage regulation through OLTC and FACTS controllers. This conventional approach to
coordinated automatic control of reactive powers is now becoming solving the network voltage control problem is now considered
a challenging objective for many utilities and system operators quite unsatisfactory because:
(ISO or TSO) to achieve significant improvements in the security,
quality, and efficiency of power system operation. This survey — dispatching units’ reactive power and scheduling
paper is concerned with application of Secondary and Tertiary plants’ high-side voltages are based on off-line fore-
Voltage Regulations (SVR and TVR), already operating in the casting: actual network operating conditions are often
Italian transmission network. The basic concepts behind SVR
and TVR and the related hierarchical control system are first different from their forecasted values and are quite
described in terms of system characteristics, main functions and unpredictable;
design requirements. Cost/benefit analysis and comparison with — voltage set-points coordination is often operated
alternative voltage control solutions are also provided in relation to through written requirements or requested by the
the influence of power system restructuring process on the voltage
system operator when strongly needed: untimely or
ancillary service. More details about control system apparatuses
and their field test results are provided in Part II. inadequate control actions may occur during most
dynamic phenomena.
Index Terms—Automatic control, coordinated voltage control,
multivariable hierarchical control, optimal reactive power flow, re- To improve voltage control in transmission grids, many ap-
active power, reactive power coordination, secondary and tertiary proaches have been applied in the past by utilities and system
voltage regulation, stability margins, transmission losses, voltage, operators and many projects have been developed around the
voltage ancillary service. world. In most cases, the approach adopted is limited to power
factor correction, by increasing the installed capacitors or re-
I. INTRODUCTION actor banks, requiring significant investment. Availability, in
some cases, of unit step-up transformers with OLTC offers an
Authorized licensed use limited to: TU Ilmenau. Downloaded on May 06,2022 at 06:37:56 UTC from IEEE Xplore. Restrictions apply.
1724 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 4, NOVEMBER 2004
extended at the national level. As a result of changes in the by generating units for dealing with emergency
organization of European utilities and the resulting energy conditions;
markets deregulation, hierarchical voltage control systems are — the transfer capability of power system is improved, in
increasingly being appreciated and reinforced. In fact, system terms of increased active power levels transmissible,
operators recognize that SVR and TVR permit both simpli- with reduced voltage instability and collapse risks;
fication of automatic control of overall transmission network — the efficiency of power system operation is enhanced,
voltages and recognition of the contributions of different par- in terms of minimization of active losses, reduction
ticipants to the voltage ancillary service. of reactive flows and better utilization of reactive
In North America, interest in SVR and TVR [10] or simpler resources;
power plant solutions, such as high-side voltage control, is — the controllability and measurability of voltage an-
growing. A wide area voltage control is under development at cillary service is simplified, in terms of definition of
BPA, based on the coordination of generator or load tripping, functional requirements and performance monitoring
reactive power switching, TCSC/SVC modulation, power plant criteria.
high-side voltage scheduling, and OLTC tap-changing [11].
SVR concepts are also under consideration in Brazil [12], II. BASIC SVR AND TVR CONCEPTS
where voltage control is proposed for critical distribution areas
too, based on a methodology providing a guideline for OLTC The basic concepts of SVR are summarized here to permit
assessment and coordination [13]. understanding of the proposed control system’s structure, per-
At the beginning of the new millennium, progress and trends formance and advantages:
in transmission network voltage control require major develop- a) the idea of automatic real-time control of hundreds of
ment and innovation through use of simple, effective, automatic transmission bus voltages is too complex, very critical,
control systems, managed and supervised directly by system not reliable and therefore unrealistic and uneconomical;
operators. The cost/benefit analyses strongly support this inno- b) the generating units’ reactive power is, obviously, the
vation [14]. Moreover, because voltage control is prevalently main resource already available in the field, low-cost and
a local problem, potential solutions must consider automatic simple to control for network voltage support;
coordination of local reactive power resources, primarily those c) a realistic simple voltage control system should consider
of generators and compensators but also shunt capacitors and the dominant buses only (a small amount), thus allowing
reactors, OLTCs, SVCs, and STATCOMs. For this reason, the a sub-optimal but feasible and reliable control solution;
goals (quality and security improvements in network opera- d) to more easily realize the dominant bus (pilot node) idea
tion) of voltage ancillary service can be pursued through a we call joint-buses those having high electrical coupling
decentralized voltage control system, by introducing local co- to form a “control area” with voltages close to each other;
ordination in each area/region of the power system. Such co- e) the control structure, based on the subdivision of the grid
ordination requires exchange of data and signals between the into control areas, automatically and, as much as possible,
regional dispatcher and local plants/substations: the more data independently regulates each area pilot node voltage;
are exchanged in real-time, on the basis of power system dy- f) the control resource is essentially based on the reactive
namics, the more the voltage control system can improve per- powers of the largest units in the area (control plants),
formance and effectiveness. The benefits of network voltage which mainly influence the local pilot node voltage.
control in terms of grid efficiency, on the other hand, are more The basic idea of TVR comes from the need to increase
strongly linked with inter-area coordination, requiring effective the system’s operating security and efficiency through
exchange of data and signals among regional dispatchers and centralized coordination of the decentralized SVR struc-
the central/national system operator. In particular, the exchange ture:
of measurements with the neighboring utilities (e.g., boundary g) the pilot nodes voltage set-points must be adequately
bus voltages and tie-line reactive flows), as well as the co- updated and coordinated with dynamics slower than
ordination of mutual control actions, are very important for SVR, considering the real condition of the overall grid
reducing system losses. The on-line and real-time monitoring and avoiding useless and conflicting inter-area control
of actual EHV control system performance also represents a efforts;
challenging opportunity for indubitable correct recognition of h) the pilot nodes voltage set-points can be computed and up-
power plants’ contributions to the voltage service [15], in the dated in real-time, considering the global control system
framework of energy sector liberalization and ancillary market structure and its real-time measurements;
competition. The main reasons supporting coordinated “auto- i) the pilot nodes voltage set-points have to be optimized
matic” real-time voltage regulation can therefore be summa- to minimize grid losses while still preserving control
rized as follows: margin.
— the quality of power system operation is improved, in It is necessary to point out that, notwithstanding the goal of
terms of reduced variation around the defined voltages minimizing control system complexity, the effort involved in
profile across the overall transmission network; achieving an effective control system is in any case considerable
— the security of power system operation is enhanced, when a large transmission network is involved, as confirmed
in terms of reactive power reserves kept available by past experience and existing applications. On one hand, a
Authorized licensed use limited to: TU Ilmenau. Downloaded on May 06,2022 at 06:37:56 UTC from IEEE Xplore. Restrictions apply.
CORSI et al.: COORDINATED AUTOMATIC VOLTAGE CONTROL OF THE ITALIAN TRANSMISSION GRID—PART I 1725
Authorized licensed use limited to: TU Ilmenau. Downloaded on May 06,2022 at 06:37:56 UTC from IEEE Xplore. Restrictions apply.
1726 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 4, NOVEMBER 2004
dynamic interaction between secondary control loops. With this the generators belonging to the “control area i” and having their
constraint, in fact, excessive reactive power exchanges among highest coefficient placed in the “pilot node i” row, as potential
adjacent control areas, determined by even slight differences “control plants i.” All potential plants with the highest product
between the pilot node voltages imposed by the regulating of sensitivity coefficient by rated reactive power capability are
system, are basically prevented. If network operational require- definitely assumed as “control plant i.”
ments condition pilot node selection by determining excessive These simple methods are not computationally heavy and
electrical coupling between control areas, the secondary control give satisfactory results, once some threshold values have been
law should de-couple the dynamic interactions between control refined, taking particular network characteristics into account.
loops. For instance, accepting a higher electrical coupling increases
The analytic procedure of selection of pilot nodes consists the number of pilot nodes but also requires more complex con-
of a successive reordering of the sensitivity matrix, expressing trol laws to deal with closed-loop interaction and dynamic insta-
the dependence of the whole grid’s bus voltages on reactive bility risks. Moreover, frequent reselection of pilot nodes, even
power injections, with primary voltage regulation operating. in the case of small network changes, is required. On the con-
The method assumes the load or generation bus, having the trary, excessively low electrical coupling reduces the number of
strongest short-circuit capacity, as the “pilot node 1.” All buses pilot nodes and significantly de-couples their control loops, but
with the highest coupling coefficient with “pilot node 1” are at the same time worsens voltage quality. Similarly, accepting
assumed belonging to “control area 1” and excluded from excessively low products of sensitivity coefficients by rated re-
subsequent pilot node choices. This procedure, progressively active powers increases the number of control plants and the
applied, identifies the other pilot nodes which are the strongest corresponding reserve margins, but could require more unnec-
of the remaining buses and therefore gradually weaker, until essary control infrastructures to permit the participation and co-
the procedure stops due to insufficient short-circuit capacity. ordination of small generators.
The choice of control plants is based on the simple criterion The subdivision of the whole system into control areas must
that they must operate in the control area and have the largest re- be robust and conservative, to prevent control system reconfig-
active power capability and the highest electrical coupling with uration from becoming too frequent in response to minor net-
the selected pilot node. Selection of control plants also permits work changes. Relevant structural changes, however, must be
advance recognition of control areas with consistent reactive analyzed to determine their impact on pilot nodes, control areas
power resources, as well as those where the reactive power re- and control plant selection, and to adequately re-tune regula-
serves are critical and pilot node voltage regulation could more tion parameters. Updated studies for selection of pilot nodes and
easily reach saturation. control power plants have resulted in the Italian power system
The analytic procedure for the choice of control plants re- (55 000 MW peak) subdivision into 18 control areas (see Fig. 3).
quires successive reorganization of the sensitivity matrix, ex- This plan involves the largest thermal and hydro power plants
pressing the dependence of the pilot node voltages on the re- connected to the 400/230 kV grids, for a total reactive power
active power injections by generators. The method assumes all capacity of about 20 000 MVAR.
Authorized licensed use limited to: TU Ilmenau. Downloaded on May 06,2022 at 06:37:56 UTC from IEEE Xplore. Restrictions apply.
CORSI et al.: COORDINATED AUTOMATIC VOLTAGE CONTROL OF THE ITALIAN TRANSMISSION GRID—PART I 1727
B. Control System Algorithms and Dynamics Design power control, EHV bus voltage regulation, pilot node voltage
regulation and pilot nodes voltage set-point optimization:
In the hierarchical voltage control system, the inner loop is • AVR closes the conventional unit voltage control loop,
typically faster than the outer one, in such a way as to achieve which is basically of the proportional-integral type. It is
substantial dynamic de-coupling between overlapped levels. In characterized by closed-loop dynamics dominated by a
other words, the time-decomposition criterion requires that the time constant of about 0.5 s.
dominant time constant of any external control loop be higher • Unit reactive power control within REPORT defines,
than the dominant time constants of all its internal loops. Such in closed-loop and real-time, the AVR voltage set-point
a criterion is applied to unit voltage regulation, unit reactive in the range between minimum and maximum
Authorized licensed use limited to: TU Ilmenau. Downloaded on May 06,2022 at 06:37:56 UTC from IEEE Xplore. Restrictions apply.
1728 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 4, NOVEMBER 2004
value , which obtains the unit reactive power pro- 5 min, and is the sensitivity matrix between area reactive
duction corresponding to its reference value levels and pilot node voltages
(5)
(1)
Relation (4) integrates the result of the TVR objective function
where is the regulator integral gain, tuned in such a minimization, which is based on the actual network state esti-
way that the closed loop has a dominant time constant of 5 mation and the forecasted optimal voltages and reactive powers
s. The fastest AVR dynamic responses, mainly required in plan
response to major local network perturbations, are then not
significantly affected by the reactive power loop. The ref-
erence value is obtained from the product of the re-
active power level by the unit capability limit ,
computed on-line according to the actual operating condi- (6)
tions of the electrical generator and cooling system where , are the vectors of pilot node voltages and
(2) area reactive power levels; , are the vectors of the
optimal forecasted pilot node voltages and area reactive power
• The reactive power level may be provided by the levels; , are weight matrices whose selection allows be-
local EHV bus-bar voltage regulator (REPORT in high- stowing a privilege on pilot node voltage differences, rather then
side voltage control) or by the pilot node voltage regulator on the effort of control area reactive power levels. The compro-
(RVR control). Both of them define, in closed-loop and mise reached by TVR, when the available optimal forecasted
real-time, the reactive level in the interval between plan does not fit the real situation, should properly consist in
its minimum and maximum value the achievement of the highest voltage plan consistent with real
, which achieves the EHV bus-bar or pilot node operating conditions, which minimize network losses as much
voltage corresponding to its reference value as is feasible. To achieve this result it is necessary to preserve
system controllability, even if close to the limits, in such a way
as to avoid the disastrous consequences of open-loop operation.
In this condition, in fact, the uncontrolled voltages determine
undesired heavy reactive power flows, which increase system
(3) losses and worsen the operation efficiency. TVR is therefore the
correct and necessary completion of the hierarchical automatic
where and are the regulator proportional and real-time voltage control system.
integral gains respectively, tuned in such a way that the
closed loop has minimum-phase and a dominant time con- C. Data Acquisition and Communication Design
stant of 50 s. The fastest contribution to the dynamic re- The dynamics of pilot node voltage control requires fast and
sponses is properly given by proportional correction. high resolution measurements, achievable with unconventional
• The pilot node voltage set-point may be provided voltage transducers, as well as negligible telecommunication
by the local daily trend (RVR automatic setting) or by delays. Being the dominant time constant of the voltage loop
the regional dispatcher operator (RVR manual setting) or of 50 s, but requiring the proportional correction of the control
voltage set-point optimization (TVR output). The latter law to contribute with rapid dynamics, the telecommunication
defines the most appropriate pilot node voltage set-points delay must be lower than 2 s. TVR can in principle accept longer
for secure/efficient operation, on the basis of an in- delays, as its dominant time constant is 5 min. As for LMC, the
tegral law of the optimal variations with respect only time requirement is related to its on-line version providing
to the present voltage values an updated optimal voltage reactive power plan with respect to
the forecasted one, computed the day before through the off-line
version. This happens when the TVR apparatus recognizes that
actual grid operating conditions are very different from the fore-
casted ones. The time delay for computing the new ORPF must
be marginal with respect to the system state estimation time (in
the order of 5 min or more).
Authorized licensed use limited to: TU Ilmenau. Downloaded on May 06,2022 at 06:37:56 UTC from IEEE Xplore. Restrictions apply.
CORSI et al.: COORDINATED AUTOMATIC VOLTAGE CONTROL OF THE ITALIAN TRANSMISSION GRID—PART I 1729
Fig. 4. Italian grid load ramps stability margins (dynamic evaluation): primary voltage regulation (continuous line), secondary voltage regulation (dotted line),
secondary and tertiary voltage regulation (dashed line).
Fig. 5. Italian grid load ramps stability margins (static evaluation): the dQgtot/dQctot voltage stability indicator represents the sensitivity of total reactive
production with respect to total reactive consumption.
The - trajectory reveals the expected stability improving ef- Such increased overall loadability is also demonstrated by
fect, in terms of both voltage profile and load margins (200 MW computing suitable off-line and on-line voltage stability indica-
and 300 MW margin are increased at Roma Nord and Roma Sud tors [20]. The study case, whose results are presented in Fig. 5,
buses respectively). concerns the overall Italian network and involves an increase in
Authorized licensed use limited to: TU Ilmenau. Downloaded on May 06,2022 at 06:37:56 UTC from IEEE Xplore. Restrictions apply.
1730 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 4, NOVEMBER 2004
Fig. 6. SVR and TVR: expected loss reduction in the overall italian grid.
load ramps at all the nodes. In this particular simulation very in such a way as to reduce overall system operation costs.
short-term reactive power re-dispatching by LMC has also been Many static analyzes conducted on the overall Italian network
simulated: TVR uses in fact four different optimal pilot node in recent years (see Fig. 6) have demonstrated that application
voltages and area reactive levels, computed at every 2000 MW of the multilevel control system for grid voltages and reactive
of total load increase. Due to the presence of SVR and TVR, the power regulation allows a reduction in transmission losses
largest amount of load margin increase achieved is 1500 MW for of about 4%–6%. Such a control system also achieves better
the overall Italian grid. service to the final user in terms of operation quality, security
and reliability.
E. Restoration Stability Improvement
In terms of security and repeatability, the execution of the V. COSTS-BENEFITS ANALYSIS OF THE CONTROL SYSTEM
voltage launch during restoration does in general represent a
relatively hazardous maneuver, whose risk margin remains, In order to analyze the costs-benefits [14] of the hierarchical
with the currently adopted common practice and control solu- voltage control system, let us consider a reference application
tions, beyond the full control of plant operators. In this context, involving 35 large power plants, 20 controlled grid stations,
the most effective power plant control solution is a multi- three regional dispatchers, and one national control center.
variable scheme [22], involving use of new under-excitation
limits or, better yet, a superimposed centralized reactive power A. Capital and Operational Costs
control. The objective is to reduce line extra voltages during Assuming an application lifetime of 25 years and a discount
energization, balancing the control efforts of all power plant rate minus inflation of 12%, the total yearly cost is about 4400
units while stabilizing generators’ under-excitation operation kEuro/year, which can easily be subdivided into capital costs
and preventing self-excitation wherever possible. Such a con- and operational costs. Capital costs, related to 50 REPORTs and
trol feature could easily be implemented by using the high-side 3 RVRs for the SVR, 1 TVR and 1 LMC for the NVR, total about
voltage regulator (REPORT), where it is easy to come up 18 000 kEuro, subdivided into:
with suitable adaptive control solutions, at both the reactive • studies, design, and software development: 5600 kEuro;
power control level and the high-side voltage regulation level. • apparatus manufacturing and testing: 6200 kEuro;
This solution could be based on proper real-time and on-line • installation, AVR modifications and tests: 6200 kEuro.
identification of the equivalent external reactance exhibited by
The yearly capital cost is then equal to 2580 kEuro/year. The
the islanded rather than interconnected network. This reactance
operational costs are related to maintenance and upgrading of
value is useful for correct selection of the most suitable control
tools, control apparatuses and telecommunication equipment
law at different stages in the restoration process. In this way,
(775 kEuro/year), as well as to voltage/reactive operation at
a power plant with centralized reactive power control is fully
regional dispatchers/national control center (1045 kEuro/year).
capable of maintaining the working point of the generating
units within the under-excitation region. At the same time it
B. Estimated Operational Benefits
represents the simplest way of decreasing manual coordination
problems during restoration, starting from the voltage launch A prudent value estimation of the achievable benefits gives a
maneuver up to the synchronization and re-closure of the yearly amount of about 14 250 kEuro/year, subdivided into:
network. 1) reduction up to 5% of the real losses in the power system,
by containing reactive power flows through better coordi-
F. Network Losses Reduction nation of reactive power resources;
The main objective of LMC is achievement of minimum 2) reduction of about 3%–5% in the duration of partial lack
losses in the grid, by optimizing the values of network voltages of loads feeding (for operational security reasons), due to
Authorized licensed use limited to: TU Ilmenau. Downloaded on May 06,2022 at 06:37:56 UTC from IEEE Xplore. Restrictions apply.
CORSI et al.: COORDINATED AUTOMATIC VOLTAGE CONTROL OF THE ITALIAN TRANSMISSION GRID—PART I 1731
TABLE I TABLE II
COSTS/BENEFITS DATA FOR THE HIERARCHICAL VOLTAGE CONTROL SYSTEM ESTIMATED YEARLY RATE COSTS OF NETWORK VOLTAGE CONTROL SYSTEMS
Authorized licensed use limited to: TU Ilmenau. Downloaded on May 06,2022 at 06:37:56 UTC from IEEE Xplore. Restrictions apply.
1732 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 19, NO. 4, NOVEMBER 2004
Authorized licensed use limited to: TU Ilmenau. Downloaded on May 06,2022 at 06:37:56 UTC from IEEE Xplore. Restrictions apply.