SITE TESTING Page 1 of 4
SCHEDULE Revision 1
WARNING
The use of equipment out of calibration is strictly prohibited. Prior to the
commencement of any activity on this STS, confirmation that all requiring
calibration carries a current calibration label.
General
Use test equipment capable of producing a good waveform to simulate the measured quantities of
current/voltage/frequency over the range of the transducer/instrument under test.
Where possible, tests should include as much of the secondary wiring as practical. Conjunctive tests from the CT/VT
secondary side through to the indicating device are preferable
Test procedure
Meters
Inject values to check the accuracy of meters at Full Scale and, as near as possible, mid scale. Observe also the 'zero'
condition with no injection to the meter
Transducers
Before checking the accuracy of transducers apply nominal input quantities and allow the unit to 'soak' for 5
minutes. For transducers with 4 to 20mA output or similar, check at maximum and at minimum. For 'positive and
negative' output transducers, e.g. -1mA 0 +1mA check accuracy at the extremes of range and at zero
MW Transducer serial No