You are on page 1of 1

No.

: 4236 /01/2020/I
Date: 18/03/2020
INSPECTION CERTIFICATE
Client : ASSIUT OIL REFINING CO.
One Electric overhead crane
Type : MISIA Capacity : 5 TON
Equipment to be inspected :
Unit : ‫ورشة البلوف والطلمبات‬
Code : CR5
Date & place of inspection : 17 /03 /2020 – at client’s works – Assiut.
Type of test : - Visual inspection - loading & stability tests
Applicable references : - BS 7121-2-7

1- VISUAL INSPECTION 2- MOTIONS CHECKS


Item Result Item Result Motion Direction Limit Brake
switch
General view OK Electrical OK Hoisting Lifting OK OK
cables Lowering OK OK
Wire rope / OK Alarm -- Cross Right OK OK
Chain (visually) devices travel Left OK OK
Hook OK Control unit OK Long Fwd OK OK
Beams OK Greasing OK travel Bwd OK OK
3- DYNAMIC TEST
Applied load (ton) Time (min.) Motions Limit switches Brake
Up /down Accepted Accepted
4600 15 Right / left Accepted Accepted
Fwd / Bwd Accepted Accepted
4- STATIC TEST
Applied load Time (min.) Vertical deflection (mm) Test satisfactory
(ton) Theoretical Measured
4600 15 ------- ------ Accepted
Conclusion:
Based on our inspection findings the crane in this condition was found satisfactory for lifting
rated load, the crane will due for re-inspected on 16/03/2021, or after any major repairs.
****************************
INSPECTED BY HEAD OF INSPECTION SECTOR
Eng. / Ahmed Mustafa Mohamed