Professional Documents
Culture Documents
Annunciator System....
• Membrane type built in push buttons. 7) Audible Output : Potential free relay contact
terminals at back side for external
• Choice of two different window sizes. alarm.
Site Selectable Features 8) Relay Contact Rating : 5Amps at 230 V AC.
• Four operating sequences. 9) Max. Op. Amb. Temp. : 60oC
• NO / NC fault contacts selection for each window. 10) Window Size : Refer Manual
• Trip or Non-Trip Audible Alarm selection for each window. 11) Viewing Area : Refer Manual
Optional Features 12) Legends/Inscriptions : Laser Printout on butter paper.
• DC / AC fail Annunciation facility.
• Potential free NO contacts for each window. *Please clearly mention at the time of ordering.
• RS 485 Communication port with MODBUS protocol.
• Ring back (“R” seq) / first up (F1,F2,F3) Operating sequence.
• Self supervision Annunciator healthy condition or Annunciator fail
Relay Contacts. Model Dimensions & Weight Details :
• Man / Unmanned (Sleep Mode) facility.
SR. OVERALL DIMENSIONS
MODEL (H x L x D) CUT OUT WEIGHT
NO.
Scope Supply :- 1 1D 144 x 72 x 210mm 720 gm.
138 x 68mm +1/ -0
Alan Offers to supply its micro controller based Annunciation System 2 2D 144 x 144 x 210mm 138 x 138mm +1/ -0 1000 gm.
MLD-02 series as in isolated system to be installed in a Suitable
3 3D 144 x 216 x 210mm 138 x 210mm +1/ -0 1360 gm.
Control cubicle.
4 4D 144 x 288 x 210mm 138 x 282mm +1/ -0 1770 gm.
1) Mounting clamps - 1D-2D = 2 nos.
5 5D 144 x 360 x 210mm 138 x 354mm +1/ -0 1800 gm.
3D-4D = 4 nos.
6 6D 144 x 432 x 210mm 138 x 426mm +1/ -0 2000 gm.
5D-6D = 6 nos. for panel flush Mounting.
2) User’s manual (may be supplied with consignment or will be
sent to the user/buyer separately). Customer can download
from website.
2
Standard Operating Sequence :- Installation And Commissioning :-
The MLD-02 series annunciator systems are programmed to 1. Check for physical damage to the pack
Operate as per following operating sequences confirming to ISA 2. Check for physical damage to the unit
Standards. Other sequences/non standard sequences are given
as per customer’s requirement. 3. Check number of points / windows, legends, Input Supply
marking on unit as per purchase order details.
Sequence : Manual Reset “M” 4. Check all accessories such as mounting clamps, Operating
manual. Also the optional accessories such as Hooter , Buzzer,
Field Faul Push Buttons Facia Audio Bell etc.
Condition Condition Operation (Window) Alarm 5. Connect input supply as per mentioned on the unit.
Normal Open --------- OFF OFF 6. Fault inputs are adjusted internally as per requirement for NO
--------- Flashing or NC fault contacts.
Abnormal Close ON
-------- 7. Switch “ON” the supply to the unit after ensuring its
Close Silence Flashing OFF connections are as per wiring diagram. Initially do not connect
-------- Close Accept Steady ON OFF anything to the fault input terminals. If the fault inputs are
Close Reset Steady ON OFF selected for NC type contacts, then the corresponding
windows will start flashing and the alarm contacts will close. If
------- Open Reset OFF OFF the fault inputs are selected for “NO” type contacts, only watch
dog LED will flash. By pressing “Operational Test “push button
Sequence : Manual Reset + Repeat Alarm “N” window will start flashing and the Alarm contacts will close.
8. Now check the operating sequence as per the individual
Field Faul Push Buttons Facia Audio sequence chart as shown in the following pages. Push Button
Condition Condition Operation (Window) Alarm Details.
Normal Open --------- OFF OFF TEST : Operation Test AKN : Accept / Acknowledge
Abnormal Close --------- Flashing ON MUTE : Silence RST : Reset
-------- --------- Silence Flashing OFF 9. Now initiate individual faults by either shorting the fault input
terminals or by dip switch selection on doing so every
Close Reset Flashing ON corresponding window should flash and audio should get ON.
-------- -------- Silence Flashing OFF Proceed further as per sequence selected.
-------- Accept Steady ON OFF 10. To change the legends ,remove the window cover From front
------- side, gently by using screw driver as shown in the Fig.1 on
Open Reset OFF OFF Pg.4
11. Then use mounting clamps provided with the unit to Mount the
Sequence : Self Reset or Auto Reset “S” unit on the control panel.
Field Faul Push Facia Audio 12. Connect the NO type push buttons externally if Required
Condition Condition Buttons (Window) Alarm 13. Connect various fault contact cables to the input terminals of
Open --------- the unit
Normal OFF OFF
---------
14. Connect the input supply wires and switch on the supply
Abnormal Close Flashing ON
15. Now check the functioning of the unit by pressing “Operational
-------- -------- Silence Flashing OFF test”, “Silence”, “Accept” and “Reset” push buttons
-------- Close Accept Steady ON OFF sequentially.
-------- Open --------- OFF OFF 16. Now the unit is ready for operation.
3
Maintenance instructions :-
BU
C HH
TR OLZ
IP
Co
Le lou
Wi ge rA
nd Mil nt cry
ow ky / In lic
Be wh scr
zel ite ipti
Ac on
ryli
c
Notch for
Bazzel Removal
Step.1 Step.2 Step.3 Step.4 Fig-1
3 4 11 12 2 6 10 14 All
Windows No
Consult Alan
Steady
5 6 13 14 3 7 11 15 ON
Yes
7 8 15 16 4 8 12 16
Initiate Reset Command Assumption
NO - Fault Contacts
16pt. Small Window 16pt. Big Window All
A Configurations B Configurations No Manual Reset (M) seq.
Windows
Off Note: -
The numbering system is shown for 16pt. Models (small & big ) for AKN = MUTE + AKN.
Reference. All other models can be referred from this fig. Yes (i.e. When Unit is Acknowledged Mute
operation will also take place.)
End Fig-3
Drawing / illustrations
OFF ON Sequence Settings :-
F1
NC F2
To selection one sequence from S3, S4 keep
F3 corresponding switch in on position.
ON =NC , OFF = NO
F4
F1
NO/NC SELECTION
F5 SEQUENCE
F6 S1 - SELECTION F2 Fault
SELECTION Facia
F7 Inputs
F8 S3 S4 OFF ASCII Block
F1
OFF OFF M ON RTU Fn
F2
F3 ON OFF N S2 - SELECTION
F4
F5 OFF ON S OFF Slave
F6
NO F7
ON ON F ON Master Mute
F8
Accept Push Button Control Audible Block
F9
G1 No/ Nc Selection :-
F10 Control Card
Reset
F11
F12
To select type of fault contacts for particular Test Group
I1
ON =G1 , OFF = G2
GROUP SELECTION
4
1D to 6D Dimensional & Panel Cutout Details
1D 2D 3D
72 144
68 138 216
210
144
144
144
138
138
138
4D 5D
288 360
282 354
144
144
138
138
6D
432 426
144
138
How to parallel more than One Annunciators in Panel (MLD-02)
Vertical Configuration Horizontal Configuration
C
A A A
138 138
front Panel
138
Model Dimensions & Cut out Detail (All Dimensions are in mm)
RS + RS + RS +
FOUT = First out sequence Terminal
FOUT FOUT FOUT
SYNC = Flashing Synchronisation Terminal
SYNC SYNC SYNC
5
Connection Diagram :-
C
F1
Notes :-
.
F2
F3
F4
- External potential free fault contacts.
F5
F6 F - Fault input contact.
F7 C - Common points fault input contact.
F8
F9
TEST - Operation test push button.
F10 MUTE - Silence push button.
F11 AKN - Accept push button.
F12
F13
RST - Reset push button.
F14 RLY-1 - Normal Hooter Contact/Group-1 contact.
F15
F16
RLY-2 - Normal Hooter Contact/Group-2 contact.
F17 RLY-3 - Optional Relay
F18
F19 A) Ring back hooter Relay with grouping
F20 facility or
F21
F22
B) Supervisory Relay or
F23
C) Any other function (optional)
F24
TEST
MUTE This is diagram for maximum fault inputs Fn, n = 24
AKN
RST
C
I1
RLY-1 External terminal connection diagram for
C1
I2
max 24 point MLD-02 series
RLY-2 C2
~/+ VE Lug size :- 2.5 sq mm
~/- VE Fig-5
External relay connection diagram for supply fail Stand by Power Source Connection :-
Annunciator function
Any type of same normal voltage & standby voltage or different
normal voltage & standby voltage within the range of ANN Changeover relay assembly
90V to 270 V AC/DC WINDOW
effecting switch over to standby
power source is external to the
Partial terminal strip annunciator ( unit 1 ) annunciator
- AC
~ / +VE ~ / -VE I1 C1 ~
~
To next unit ‘ C1 ’ -
(Terminal) VE
230 V AC/110V AC
24 V DC 24 V AC/ 50Hz.
COIL P1 P2 P3 P4 + DC 48 V DC 48 V AC/ 50Hz.
POWER
- SUPPLY
COIL NO NC NO NC NO NC NO NC Fig-6
NOTE :-
Annunciator failure contact
1) R1 external 4 CO plug in type relay with base.
(Coil Voltage must be same as normal supply- p1)
I4 This normally open supervisory contact
2) P1- Normal Supply.
C4 closes when ever annunciator fail.
3) P2 Stand by supply.
4) NO ring back hooter operation when normal supply P1 fails.
5) Relay contacts shown in de-energised condition. Fig-11
6
Safety Instructions and Recommendations
User’s Guide
User guide for Annunciator Equipment. This Manual gives necessary information for correct technical, installation, operation & Maintenance of the
equipment.
Kindly preserve this Manual for entire equipment life.
The following conventions and words used in have specific meanings.
Indicates loss of life personnel injury if Indicates Equipment damage can result, Indicates preliminary action to be taken.
proper care is not taken if proper precautions are not followed.
Indicates mandatory actions Indicates personnel to read the manual Indicates personnel to read the manual
to be taken / followed. before working on the equipment. before maintenance of the equipment.
Warning Labels - warning labels have been pasted on equipment, which indicate the safety and hazards precautions to avoid the problems.
CE Mark
Read and Understand Operator’s
on the Manual Before Using
this Equipment
Personnel Safety
Don’t operate the equipment without If any faults occur during the operation, stop
understanding the Installation, Operation and the equipment immediately and eliminate the
Maintenance manual thoroughly. fault.
Lighting :
Before shifting the equipment disconnect all wires, cables from the equipment ,which are connected externally.
Failure to do this could cause the load to shift and slip.
7
Declaration of Conformity
This Product complies with the directive of the Council of the European Communities on the approximation of the laws
of the member states relating to electromagnetic compatibility (EMC Council Directive 89 / 336 EC ) and concerning
electrical equipments for application within specific voltage limits (Low Voltage Directives 73 / 23 / EC).
The conformity has been proved by tests performed according to the Council Directive in agreement with the generic
standards EN 61010-1, EN 61000-6-2 & EN 61000-6-4 for the EMC Directive.
The device is designed and manufacturered for application in industrial environment.
Study the safety as well as operating instructions carefully before starting the equipment. Do not start the equipment
unless you are well acquainted with the operating parts. Ensure that all the systems of the equipment are properly
connected. If all the systems found smoothly working, run the equipment for some time without any load.
Alan is responsible for the safety, reliability and performance of the Annunciator (MLD - 02 Series) only is all the
Manufacturer’s following Conditions have been met.
Responsibility 1) Installation and setup Procedures in this manual are followed.
2) Assembly, Operation, Readjustment, Modifications or repairs are carried out by the person authorised by Alan.
Model Coding
Model Coding
D C E V X Y Z
Note :-
Optional Features In 1D size enclosure, number of ‘B’ size windows will be
A = AC Fail maximum 4 and ‘S’ size Windows will be maximum 8.
Z 0 = without AC Fail
External PCB mounted Repeat Relays card will be
D = DC Fail given for Annunciator with Repeat Relays model.
Y 0 = without DC Fail
R = with Repeat Relay Enclosure Max No. Of Small Max No. Of Big
X Type
0 = without any of above features ‘S’ size window ‘B’ size window
Push Buttons 1 = 1D 8 4
P = Built in push Buttons ( Big ) 2 = 2D 16 8
V S = Built in membrane push Buttons ( Small ) 3 = 3D 24 12
0 = without Built in push Buttons 4 = 4D Not applicable 16
Small Window 5 = 5D Not applicable 20
0S = NIL 6 = 6D Not applicable 24
1S = Small window
E For more than 24 windows, use parellel Annunciator
combination. Kindly refer more than one Annunciator
24S = 24 Small window parellel combination diagram.
Big Window
0B = NIL
1B = Big window
C
24B = 24 Big window
Enclosure
1 MLD = 1D
2 MLD = 2D
3 MLD = 3D
D 4 MLD = 4D
5 MLD = 5D
6 MLD = 6D
Manufactured by :
www.alanindia.net