Professional Documents
Culture Documents
Sana’a University
Faculty of Engineering
Mechanical Engineering Department
Supervised by:
DR. ABDULJALIL AL-ABIDI
A Final Year Project Submitted in Partial Fulfillment for the Degree of Bachelor in
Mechanical Engineering Presented to the Department of Mechanical Engineering
at Sana’a University
September, 2019
Republic of Yemen
Sana’a University
Faculty of Engineering
Mechanical Engineering Department
Prepared by:
Supervised by:
DR. ABDULJALIL AL-ABIDI
A Final Year Project Submitted in Partial Fulfillment for the Degree of Bachelor in
Mechanical Engineering Presented to the Department of Mechanical Engineering
at Sana’a University
September, 2019
ABSTRACT
Heating, ventilation, and air conditioning (HVAC) system is designed to achieve the
environmental requirements of the comfort of occupants and a process. HVAC systems are
more used in different types of buildings such as industrial, commercial, residential and
institutional buildings.
HVAC systems for hospitals and health care facilities have special requirements
because of the inherent nature of their functions and the unique susceptibility of patients.
The design must provide a ventilation system that minimizes exposure hazards for health
care providers and provides a comfortable working environment. HVAC systems must also
provide ventilation that minimizes the hazard exposure of visitors.
Energy demand is increasing worldwide, and the Republic of Yemen is following this
trend. The Middle East and Northern Africa (MENA) region follows the worldwide trend
of a continuously increasing demand of both primary energy and electricity for cooling
purposes. Currently most of this energy demand is mainly covered by the use of fossil fuels
Consequently, conventional energy resources are getting depleted and more greenhouse
gas (GHG) emissions are emitted. Using renewable energy as a primary source in solar
cooling sector will help in decreasing the consumption of fossil fuel, thus, reducing GHG
emissions.
The objective of this project is to design the heating ventilation and air conditioning
system (HVAC) by absorption for a 1st floor commercial hospital which built in Sana’a
city with a total cooling coil load of 340.43KW (97.3 TR). The construction of duct work,
and piping network is done by using REVIT MEP software, and other program that aided
in manual method calculations such as duct sizer. The manual method is also utilized in
this research to estimate the cooling load, to size the duct work design, and to size piping
network. Also, a detailed select of the system equipment was done. For absorption HVAC
design system, the air-handling units (AHU) are installed with HEPA filters with a [1.5
m/s] velocity limit in the most important suite such as operation room, (ICU), (CCU), and
sterilization, to minimize infection, maintain staff comfort, and maintain patient comfort.
While Fan coil unit (FCU) are for the other spaces. The pressure drop in the piping network
is 1.695 bar. The pump (50-160/55) LOWARA is selected to overcome maximum head up
I
to 17.3m with 5.5 KW. The total aperture area of evacuated tubes collectors is 502 m2. The
chiller capacity is 369 KW.
II
ACKNOWLEDGEMENT
To our parents who have the white hearts that generously have given us whatever we need,
to those who suffered and have been devoted their life to see always in comfort. To our
supervisor, DR. Eng. ABDULJALIL AL-ABIDI, we would like to express my deepest
gratefulness for his enormous guidance and advice during the project, it was great
opportunity for us to do the project under his supervision for his wide experience and his
passion to share his knowledge with the others. We would like to thank all doctors in the
mechanical Engineering Department Sana’a University, who guide and support us during
five years.
III
DEDICATION
This work is dedicated to everyone supported us during the period of our study.
IV
Table of Contents
ABSTRACT............................................................................................................... I
ACKNOWLEDGEMENT ........................................................................................III
DEDICATION ......................................................................................................... IV
LIST OF TABLES .................................................................................................... X
LIST OF FIGURES ................................................................................................. XI
LIST OF ABBREVIATIONS ................................................................................ XIII
LIST OF SYMBOLS .............................................................................................. XV
CHAPTER ONE ........................................................................................................1
INTRODUCTION .....................................................................................................1
1.1 Background ................................................................................................................... 1
1.2 Problem Statement ........................................................................................................ 2
1.3 Objective ....................................................................................................................... 2
1.4 Scope and Limitation .................................................................................................... 3
1.5 Structure of the Research .............................................................................................. 3
CHAPTER TWO .......................................................................................................4
LITUREREVIEW............................................................................................................. 4
2.1 Overview of HVAC System by Absorption ................................................................. 4
2.2 Classification of HVAC systems .................................................................................. 4
2.3 Comfort ......................................................................................................................... 6
2.3.1 Comfort Conditioning ............................................................................................ 6
2.4.1 System selection guidelines ................................................................................... 7
2.5 HVAC system requirements ......................................................................................... 8
2.6 Central HVAC systems ............................................................................................... 10
2.7 Single zone .................................................................................................................. 12
2.8 Air-water systems ....................................................................................................... 14
2.8.1 Fan-coil units ........................................................................................................ 14
2.9 Hospitals ..................................................................................................................... 15
2.10 Sterile Spaces in Hospitals ........................................................................................ 16
2.10.1 Operating Suite ................................................................................................... 16
V
2.10.1.1Operating Room ........................................................................................... 16
2.10.1.2 Anesthesia Equipment Room ...................................................................... 18
2.10.1.3 Sterile Equipment Rooms ............................................................................ 19
2.10.2 Intensive Care Units ........................................................................................... 19
2.10.3 Central Sterile Services ...................................................................................... 22
2.10.4 Cardiac Care Unite ............................................................................................. 24
2.11 HVAC Design Parameters for Hospital Spaces ........................................................ 24
2.11.1 Temperature ....................................................................................................... 25
2.12.2 Relative Humidity .............................................................................................. 26
2.10.3 Filtration ............................................................................................................. 26
2.10.5 Pressurization ..................................................................................................... 29
2.10.5.1. Volumetric Flow Rate ................................................................................ 29
2.10.5.2 Room Differential Pressure ......................................................................... 30
2.10.6 Total and Fresh Air Changes .............................................................................. 30
2.11 Hospital and Laboratory Equipment ......................................................................... 30
2.12 Basic components of an HVAC system .................................................................... 31
2.12.1 Air filter .............................................................................................................. 31
2.12.1.1 Laminar Flow Unit ...................................................................................... 32
2.12.2 Supply and exhaust fan ...................................................................................... 34
2.12.3 Outdoor air intake............................................................................................... 35
2.12.4 Duct .................................................................................................................... 35
2.12.4.1 Duct components ......................................................................................... 35
2.12.4.2 Ducts can be classified according to their shapes into ................................ 36
2.12.4.3 Material of Air Ducts ................................................................................... 37
2.12.4.4 Duct insulation ............................................................................................. 37
2.12.4.5 Sound Attenuator ......................................................................................... 37
2.12.5 Terminal devices ................................................................................................ 38
2.12.5.1 Ceiling diffuser ............................................................................................ 38
2.12.5.2 Grilles and Registers .................................................................................... 38
2.12.6 Return air system ................................................................................................ 39
2.12.7 cooling coils ....................................................................................................... 39
VI
2.12.8 Fan-Coil Unit Systems ....................................................................................... 40
2.12.9 Air -Handling .................................................................................................. 42
2.12.10 Volume Control Damper .................................................................................. 42
2.12.11 CONDENSER .................................................................................................. 43
2.12.12 Control.............................................................................................................. 43
2.12.13 Water chiller ..................................................................................................... 44
2.12.14 Humidification and dehumidification equipment ............................................ 44
2.13 Piping System ........................................................................................................... 45
2.13.1 Type of Piping system ........................................................................................ 45
2.13.1.1 Closed system.................................................................................................. 45
2.13.1.2 Two-Pipe Direct Return System .................................................................. 46
2.13.2 Piping Material ................................................................................................... 47
2.13.3 Valves, Pipe Fittings and Accessories................................................................ 47
2.13.3.1 Gate Valves.................................................................................................. 48
2.13.3.2 Globe Valves ............................................................................................... 48
2.13.3.3 Check Valves ............................................................................................... 48
2.13.3.4 Pressure Relief Valves ................................................................................. 48
2.13.3.5 Butterfly Valves:.......................................................................................... 49
2.13.3.6 “Y” valve ..................................................................................................... 49
2.13.3.7 Balance Valves ............................................................................................ 49
2.13.4 Valve Connections and Ratings(joint) ............................................................... 50
2.13.4.1 Threaded ends .............................................................................................. 50
2.13.4.2 Flanged ends ................................................................................................ 50
2.13.4.3 Welded ends ................................................................................................ 50
2.13.4.4 Grooved ends ............................................................................................... 51
2.13.4.5 Soldered ends ............................................................................................... 51
2.13.5 Fitting ................................................................................................................. 51
2.13.6 Accessories ......................................................................................................... 52
2.13.6.1 Expansion tank ............................................................................................ 52
2.13.6.2 Air Separator................................................................................................ 52
2.13.6.3 Makeup Tank. .............................................................................................. 53
VII
2.13.6.4 Strainer......................................................................................................... 53
2.14 Water treatment ......................................................................................................... 53
2.15 Pump for HVAC system ........................................................................................... 54
2.16 Chilled water pipe insulation .................................................................................... 54
2.16.1 Economic thickness ............................................................................................ 55
12.17 Lithium Bromide-water Absorption Air-Conditioning System .............................. 55
2.18 Solar Thermal Collectors .......................................................................................... 57
2.18.1 Evacuated Tube Collectors................................................................................. 58
CHAPTER THREE ........................................................................................................ 59
METHODOLOGY ......................................................................................................... 59
3.1 Introduction ................................................................................................................. 59
3.2 Software program........................................................................................................ 59
3.2.1 REVIT MEP System Design Features ................................................................. 60
3.3 Flow Chart .................................................................................................................. 61
3.4 Building parameters .................................................................................................... 62
3.5 Sizing the HVAC System ........................................................................................... 63
3.5.1 Estimating Total Cooling Load ............................................................................ 63
3.5.1.1 Manual Method Sample................................................................................. 67
3.5.1.2 Technical method .............................................................................................. 68
3.5.2 Duct system Design.............................................................................................. 73
3.5.2.1 Duct Sizing Manually .................................................................................... 73
3.5.2.2Technical method for duct design .................................................................. 78
3.6 Ceiling diffuser ........................................................................................................... 79
3.7 Filters .......................................................................................................................... 80
3.8 Fan............................................................................................................................... 81
3.9 Air Handling Unit and Fan Coil Selection .................................................................. 83
3.10 Pipe sizing ................................................................................................................. 83
3.10.1 Manual Method .................................................................................................. 84
3.10.1.1 Valves and Fittings Losses .............................................................................. 85
3.10.3 Pump Sizing ....................................................................................................... 87
3.11 Chiller Absorption .................................................................................................... 88
VIII
CHAPTER FOUR........................................................................................................... 90
NUMERICAL RESULTS AND DISCUSSION ........................................................... 90
4.1 Introduction ................................................................................................................. 90
4.2 Manual method ........................................................................................................... 91
4.2.1 Cooling loads........................................................................................................ 91
4.2.2 Ductwork Summery Sample ................................................................................ 93
4.2.3 Piping Network Summary Sample ....................................................................... 94
4.2.4 Pump selection ......................................................................................................... 96
4.3 Technical method ........................................................................................................ 97
4.4 FCUs and AHUs Selection Summary ......................................................................... 99
4.4.1 Total Summary Parameters .................................................................................. 99
4.4.2 Rooftop Supply and Exhaust Fan Units Specification ....................................... 102
4.5 Supply, Return Diffuser, and Exhaust grille ............................................................. 105
4.6 Absorption chiller ..................................................................................................... 107
4.7 Solar Collector Characteristics ................................................................................. 108
CHAPTER 5 .................................................................................................................. 110
CONCLUSIONS AND RECOMMENDATIONS ...................................................... 110
REFERENCES.............................................................................................................. 111
APPENDIX A ................................................................................................................ 114
APPENDIX B ................................................................................................................ 116
IMPORTANT TABLES FOR CALCULTIONS ....................................................... 116
IX
LIST OF TABLES
X
LIST OF FIGURES
XI
Figure 3. 1: Duct sizer software calculation sample………………..………………........60
Figure 3. 2: Flow chart ...................................................................................................... 61
Figure 3. 3: shown view for (OP-Z1) from rivet program ................................................ 67
Figure 3. 4: Determination of Economic Thickness of Insulation .................................... 77
Figure 3. 5: Filter Pressure Drop versus Air Velocity ...................................................... 81
Figure 3. 6: Friction Loss for Water in Commercial Steel Pipe (Schedule 40) ................ 84
Figure 3. 7: shows head pump………………………………………………………….87
Figure 4. 1: Layout of operation room 1 (OP-Z1) ductwork ............................................ 93
Figure 4. 2: Selected fan performance chart ................................................................... 104
XII
LIST OF ABBREVIATIONS
XIII
SR Static Regain
XIV
LIST OF SYMBOLS
XV
Qglass Heat gain due to solar transmission through the glass [W]
V Volume [m3].
XVI
CHAPTER ONE
INTRODUCTION
1.1 Background
Solar cooling technologies were developed and deployed for practical use since the
1970s. Larger absorption machines (larger than 50 kW) have already reached a significant
market and track record in non-solar applications. In particular, smaller systems are still at
the earlier stage of development. Any thermal cooling system is comprised of several
important elements. One such element is the heat rejection system, which is bigger for
thermal cooling systems than for compression systems and which requires specific
considerations especially in hot climate regions, where heat rejection to the environment is
more difficult to achieve. Another important element is a storage system for thermal energy
to provide cooling in periods without sunshine, given that solar irradiation varies
throughout the year and fluctuates within individual days. An alternative is a back-up
supply of thermal energy via a gas burner, but as the deployment of fossil fuel power
backup system negatively affects the greenhouse gas (GHG) emission profile of the system,
a storage system is preferred wherever feasible [1].
Solar radiation as a sustainable energy resource is one of the most available forms of
energy on the earth surface which could reduce the fossil fuel consumption and CO2
emission to the atmosphere. Solar cooling is a possible technological alternative to
conventional air conditioning systems that has recently attracted a growing interest. A solar
assisted absorption cooling system as a sustainable solution for cooling systems could
provide both heating and cooling of a building. Since the solar energy is available for only
a fraction of the day and its availability depends on several factors such as latitude and sky
clearness [2].
The design of HVAC systems for health care facilities is a unique and challenging art
and science demanding specialized experience and knowledge of the character of these
1
high stakes facilities, the sensitivity and vulnerability of their populations, and the complex
interactions of the HVAC system with the other architectural and engineering elements that
make up the building. The design process requires familiarity with a specialized and
diverse set of criteria, regulations, codes, and design standards, and the ability to weigh
their application in the face of an owner’s economic limitations associated with the
business of health care (addressed in detail in Chapter 9). This manual describes best
practices for the design of HVAC systems for health care facilities. It is not intended as a
code document, and readers should consider that even best practices, unless codified, may
be rejected by the building owner[3].
1.3 Objective
The main aim of this research is to design an HVAC system for a USTH 1st floor in
Sana’a. Other objectives of this study can be stated as following:
1- To estimate the cooling load of the 1st floor of the USTH.
2-To construct the duct work and piping network by using REVIT MEP.
3- To determine the main HVAC system components sizing.
4- To determine the total aperture area of the solar collectors.
2
1.4 Scope and Limitation
The scope of the study will be limited to:
1. The study will consider a health care facility.
2. This study will be limited to the summer (from April to September) climate of Yemen
represented by Sana'a city.
3
CHAPTER TWO
LITUREREVIEW
This chapter represents an overview of HVAC system by absorption. Also, the chapter
outlines the classification of HVAC systems, the types of HVAC systems and their uses.
the accessories of the system and an overview of the absorption cycle.
Temperature, Fulfilling any or all of the design Fulfilling any or all of the design
humidity, Parameters parameters
4
and space pressure
requirements
Capacity • Considering HVAC diversity factors to • Maximum capacity is required for
requirements reduce the installed equipment capacity. each equipment
• Significant first cost and operating cost • Equipment sizing diversity is
limited
Redundancy Standby equipment is accommodated for No backup or standby equipment
troubleshooting and maintenance
Operating cost • More significant energy efficient primary • Less energy efficient primary
equipment equipment
• A proposed operating system which • Various energy peaks due to
saves operating cost occupants’
preference
• Higher operating cost
Maintenance cost Accessible to the equipment room for Accessible to equipment to be
maintenance and saving equipment located in the
in excellent condition, which saves basement or the living space.
maintenance cost However, it is
difficult for roof location due to bad
weather
Reliability Central system equipment can be an Reliable equipment, although the
attractive benefit when considering its long estimated
service life equipment service life may be less
5
Flexibility Selecting standby equipment to provide an Placed in numerous locations to be
alternative source of HVAC or backup more
Flexible
2.3 Comfort
Comfort is a highly subjective word, reflecting sensations which vary greatly from one
individual to another. Comfort can be defined only in general or statistical terms. Research
by ASHRAE over many years has identified the major factors contributing to comfort:
temperature, relative humidity, air movement, and radiant effects. Attempts have been
made to combine these factors to obtain a single-number index called the effective
temperature1 or comfort index. The type and quantity of clothing and the level of activity
also affect comfort, but these factors vary so greatly that they cannot be quantified.
Typically, the air system is designed to control temperature always and humidity
sometimes. Good control of air movement (from supply grilles and diffusers) is also needed
to improve the comfort index. Most people do not like a draft (local air velocity over about
100ft/min), but in some hot industrial environments, a high rate of airflow at the
workstation may be necessary.
Radiant effects are often beyond the control of the HVAC designer but should be taken
into account in the HVAC design. Typical radiant effects are caused by windows (cold in
winter, hot when exposed to the- sun), by lighting fixtures (especially incandescent), and
by cross-radiation among people in large groups [ 5].
6
to thermal stress that may hinder the body’s ability to properly regulate body heat, interfere
with rest, and be psychologically harmful. At the same time, a health care provider stressed
by an uncomfortable environment may not function at peak performance levels.
Patients clothed in a simple gown in an examination room, for example, or orthopedic
surgical staff heavily garbed in scrub suits during an hours-long, complex, and stressful
procedure, require special room temperature and humidity levels and controls. Similarly,
room airflow patterns and air change rates influence thermal comfort. For these reasons,
health care codes and criteria establish specific requirements for space temperature, relative
humidity, and total air change rates [3].
7
Building conditions New or existing building or space, Location, Orientation, Architecture, Climate and
shading, Configuration
Construction, and Codes and standards
8
The rooms should consider the size of the installation and removal of fan shafts and
coils, the replacement, and maintenance. The size of fans depends on the required air
flow rate to condition the building, and it can be centralized or localized based on the
availability, location, and cost. It is preferable to have easy access to outdoor air.
d. Vertical shaft: provide space for air distribution and water pipe distribution. The air
distribution contains HVAC supply air, exhaust air, and return air ductwork. Pipe
distribution includes chilled water, condenser water, and condenser return.
e. Equipment access: the equipment room must allow the movement of large, heavy
equipment during the installation, replacement, and maintenance. Air distribution
considers ductwork that delivers the conditioned air to the desired area in a direct, quiet,
and economical way as possible. Air distribution includes air terminal unit such as
grilles and diffusers to deliver supply air into a space at low velocity; fan-powered
terminal units, which uses an integral fan to ensure the supply air to the space; variable
air volume terminal units, which deliver variable amount of air into the space and air-
water induction terminal units, which contains a coil in the induction air stream. All the
ductwork and piping should be insulated to prevent heat loss and save building energy.
It is also recommended that buildings should have enough ceiling spaces to host
ductwork in the suspended ceiling and floor slab, and can be used as a return air plenum
to reduce the return ductwork. The piping system is used to deliver cooled water to and
from HVAC equipment in a direct, quiet and affordable way. Piping systems can be
divided into two parts: the piping in the central plant equipment room and the delivery
piping. HVAC piping should be insulated based on existing code criteria [8].
9
Heating Equipment
Cooling Equipment
Primary Equipment
Air Delivery Equipment
Equipment Rooms
HVAC Facilities
Vertical Shaft
HVAC System Space Requirements
Requirements Fan Rooms
Equipment Access
Ductwork
System Piping
10
Single zone
Multizone
All air systems
Dual duct
Terminal reheat
11
Figure 2. 3: Equipment arrangement for central HVAC system.
12
Figure 2. 4: Water-air HVAC system for single zone.
In a single zone all-air HVAC system, one control device such as thermostat located in the
zone controls the operation of the system, as shown in Figure 2.4. Control may be either
modulating or on–off to meet the required thermal load of the single zone. This can be
achieved by adjusting the output of cooling source within the unit. Movements of
occupants affect the thermal load of the building, which results in dividing the building
into several single zones to provide the required environmental condition. This can be
observed in larger residences, where two (or more) single zone systems may be used to
provide thermal zoning. In low-rise apartments, each apartment unit may be conditioned
by a separate single zone system. Many sizeable single story buildings such as
supermarkets, discount stores, can be effectively conditioned by a series of single zone
systems. Large office buildings are sometimes conditioned by a series of separate single
zone systems.
13
2.8 Air-water systems
Air-water systems are introduced as a hybrid system to combine both advantages of
all-air and all-water systems [10]. The volume of the combined is reduced, and the outdoor
ventilation is produced to properly condition the desired zone. The water medium is
responsible for carrying the thermal load in a building by 80–90% through heating and
cooling water, while air medium conditions the remainder. There are two main types: fan-
coil units and induction units.
Figure 2. 5: Air-water HVAC system using fan coil units with 4-pipes configuration.
14
2.9 Hospitals
Hospitals are always interesting and challenging for the HVAC designer because of the
wide variety of environmental conditions required in various departments. For example,
the operating suite with heavily-clothed staff, working under hot lights requires a design
temperature of about 65 to 70_F, with the relative humidity held to a range between 50 and
60 percent, and a high percentage of outside air when the suite is in use. To achieve the
clean conditions needed, the supply air must be filtered through high-efficiency filters,
preferably at or near the discharge into the room, and a high airflow rate is needed. These
requirements all have a rational basis in research; 50 to 55 percent relative humidity (RH)
is the value at which bacteria propagate least readily. Public health authorities prescribe
most of these criteria.
Some authorities are allowing reduction of airflow and some recirculation when the
operating rooms are not in use. Nurseries do not require high airflow rates but do require
about 55 percent RH. Offices, public areas, cafeterias, shops, and other support areas have
similar criteria to other types of buildings. Air is often not recirculated from patients’
rooms, so individual fan-coil units are common, combined with a small central ventilation
system which provides makeup air for exhaust. There are criteria for air-pressure
relationships between occupancies to keep air moving from high-quality to lower-quality
environment[5].
15
4- Ensuring enough conditioned makeup air to maintain the specified positive
pressurization.
2.10.1.1Operating Room
An operating room is the space where the surgical procedures take place and this space
requires high levels of hygiene since the infection risk is high. Because of this reason,
operating room personnel wear protective garments such as gloves, shoe covers, masks,
caps etc. Since operating rooms are one of the most important rooms in operating suite in
terms of patient health, a lot more information and standards on ventilation and air
conditioning systems for operating rooms can be found in literature compared to the other
components of an operating suite.
16
Figure 2. 6: View from operating room (Source: West Walley Hospital 2005)
The operating rooms are classified into groups according to their hygiene need and the
types of surgical procedures that are executed in the room. As can be seen from the Table
2.3 most of the references classify the operating rooms according to the type of the surgical
procedure. ASHRAE and AIA divide the operating rooms into three groups as Class A, B
and C. Class A operating room serves for minor operations that are performed under local,
topical or regional anesthesia without preoperative sedation. Intravenous, spinal and
epidural operations are excluded and these methods are appropriate for Class B and C
rooms. Class B room provides minor or major surgical procedures performed in
conjunction with oral, parenteral or intravenous sedation or under analgesic or dissociative
drugs. Class C rooms are suitable for major surgical procedures that require general
anesthesia or regional block anesthesia and support of vital bodily functions [16].
Table 2.3 shows characteristics typically desired in different types of operating rooms.
As indicated, orthopedic and cardiac operating room surgeons frequently request very low
temperatures, often as low as 15.6°C [3].
17
Table 2. 3: Typical Operating Room (OR) Requirements
Several factors complicate unoccupied setback in the OR suite, including the following:
• Maintenance of positive pressurization using supply and return air control device
(most older systems will not have return control)
• Maintenance of adequate ventilation to exhaust fumes from off-hour cleaning
• Control strategies for override (light switch, occupancy sensor, time clock, etc.)
• Rapid transition from unoccupied- to occupied-air-changes while maintaining
desired temperature and humidity, there are two basic mechanisms for maintaining
pressurization: (1) fixed offset between supply and return/exhaust airflows, and (2)
maintenance of a measured pressure differential (usually at least 30% of design
flow) [3].
18
2.10.1.3 Sterile Equipment Rooms
Sterile equipment room holds the sterile instruments and medical supplies that are used
during surgical procedures. The level of hygiene in sterile equipment rooms must be equal
or higher than the operating room. These spaces must be positively pressurized with respect
to the neighboring spaces. The direction of airflow must be outwards even it is adjacent to
an operating room. By this way it is ensured to minimize the contamination level in the
room and the risk of contamination of sterile equipment is reduced. Used equipment are
collected and stored in soiled equipment rooms. Disposable and reusable equipment are
separated and reusable equipment are sent for cleaning and sterilization. This room must
be kept under negative pressure with respect to the adjacent spaces in order to keep the
airborne contaminants in the room.
19
Figure 2. 7: Intensive Care Unit
(Source: JSP Health Network 2003)
As higher room temperatures are suggested for newborn intensive care units, when
compared to the other types. Generally, 30-60% or relative humidity ratio is suggested to
be maintained in the units. In addition, higher relative humidity ratios are needed in burn
intensive care units to prevent the excessive drying of the tissues[16].
Another point that needs to be emphasized is the requirement that is suggested by
ASHRAE’s design manual is that, according to this reference, laminar air flow must be
maintained in burn intensive care units [16].
Isolation Rooms
The purpose of an isolation rooms is to protect health care workers, other patients and
visitors from exposure to any airborne infectious agents. To control the transfer of
microorganisms via air, isolation rooms must be implemented. Two types of isolation
rooms exist; negative pressure room (or airborne infection isolation room) and positive
pressure room (or protective environment room)[16].
20
Both types of rooms aim to control air flow and reduce the number of airborne infectious
agents to a level that ensures infection of other person is unlikely. The implementation aim
of these rooms is to protect the immunosuppressed patients from the environmental
infectious sources. High or very high levels of hygiene are required for protective
environment rooms.
21
2.10.3 Central Sterile Services
Central sterile services department cleans and prepares instruments and equipment for
use in surgical procedures, delivery, emergency care and related areas. This department in
the hospital is responsible from various duties. These responsibilities can be listed as
follows.
• Cleanup of surgical case carts; separation of trash, linens and instruments.
• Decontamination of instruments and washing of carts.
• Cleaning of instruments including ultrasonic cleaning, soaking and processing
through a washer/sterilizer.
• Assembly of instrument sets and supplies for surgical packs and packaging.
• Sterilization of packs, labeling and storage.
• Preparation of case carts or sets of packs for scheduled and emergency procedures
• Delivery of case carts or sets of packs to the served departments.
• Receipt and stocking of supplies and linens to be used in packs.
• Inventory control and administration [16]. Central sterile services department is
responsible in some cases for the delivery of sterile equipment to the served departments.
The level of hygiene in sterile equipment storages in central sterile services department
must be equal or higher than the operating room. These spaces must be positively
pressurized with respect to the neighboring spaces. The soiled equipment work areas in
this department must be kept under negative pressurization. Sterilization of medical
instruments is important to maintaining patient health and preventing the spread of diseases
in a hospital. Instrument sterilization can be provided by local electric self-generating
sterilizers or, more commonly, by high- or medium-pressure steam plants, although many
modern sterilizers do not use plant steam in direct contact with instruments. Steam
sterilizers require high-quality steam, 97% quality or better, to prevent excess moisture
from wetting packs or instruments. Sterilization requires that instruments be exposed to
steam at a temperature of 250°F [121°C] or higher for a length of time, so steam pressures
of 50 to 80 psi [345 to 552 kPa] are required. Sterilization is more effective with saturated
steam than superheated steam, so it is important for the designer to minimize superheated
steam. Excessive superheat may result if the sterilizer jacket is maintained at a higher
temperature than the chamber or if there is excessive pressure reduction before the sterilizer
22
connection. Steam condensate comes in direct contact with medical devices during the
sterilizing process is considered contaminated and is not returned for reuse [3].
Figure 2. 8: View from central sterile services department sterile storage area
(Source: WA Country Health Service 2002)
Not all of the studied references have commented on the filtration stages for supply air
except VDI, DIN and ASHRAE standards. Although there is not a concrete comment about
the filtration stages in most of the references, the same level of filtration that is used for the
operating rooms can be implemented since the same level of hygiene is needed. For the
case of the differential pressure of the room, all reviewed references agree on the positive
pressurization of sterilized equipment areas. The soiled equipment room should be
maintained under negative pressure.
23
2.10.4 Cardiac Care Unite
24
2.11.1 Temperature
Room temperature directly affects the thermal comfort of both hospital staff and
patients. Especially, the staff wearing protective garments working under highly radiant
lighting can be affected easily in terms of thermal comfort. This uncomfortable feeling
affects the concentration; consequently, the result of the activity being held in the room can
be affected negatively. The thermal comfort feelings of surgeons working under lighting
and in protective garments are different from other operating room personnel. Surgeons
generally feel more comfortable at lower temperatures while nurses and anesthesia
specialists feel comfortable at higher temperatures. Generally, temperatures between 24-
26ºC are suitable for the thermal comfort of patient while temperatures below 21ºC increase
the risk of hypothermia. However, the thermal comfort of surgical staff is greatly reduced
with the room temperatures higher than 23ºC [17]. Not only the thermal comfort is taken
into account to determine design temperature, but the activity being held in the room must
also be considered. Especially in operating rooms, the type of operation must be defined
since different types of operations require different room temperatures. Some examples are
[16].
• 32ºC with a low relative humidity level found beneficial for treating certain kinds of
arthritis.
• High relative humidity with 32ºC is used for burn patients.
• Room temperature around 30ºC is used for pediatric surgery.
• For cardiac surgery, room temperature is set about 15-16ºC and raised up to
temperatures around 25ºC
• Room temperature around 15-16ºC is used for transplant operations. Since the room
temperature depends on the type of operation, the temperature must be individually
controlled for each operating and delivery room. (American Institute of Architects
2006). In spaces where the health of the patients is more important than the thermal
comfort, room temperature must be specified in a range in which the growth of the
microorganisms are affected and/or the immunity system of the patients are not
affected, negatively [16].
25
2.12.2 Relative Humidity
Like the room temperature, the relative humidity ratio is a factor affecting the thermal
comfort of both patients and hospital staff. A high level of relative humidity is a common
thermal disturbance, especially when combined with low room temperature. Consequently,
the concentration of staff may be adversely affected by this disturbance. Humidity control
during cooling of the air is very important to prevent this adverse effect. As in temperature,
relative humidity level of the room must not act as a potent risk for the patient’s health.
Previous studies have shown that average values or relative humidity between 40% and
70% are not suitable for microbial growth. In addition to this fact, low levels of relative
humidity results with the drying or the mucous coating on special tissues in the upper and
lower respiratory tracts which causes the particles in the air to be breathed deeply into the
lungs (American Society of Heating Refrigerating and Air-Conditioning Engineers 2003).
Other effect of relative humidity ratio of room air is on the patient’s wounds. Low relative
humidity ratio results with excessive drying of the wound, especially in surgeries. High
relative humidity ratio is needed during eye surgeries or tissue transplant operations for
burn wounds where the drying of the wound is not desired. For example, up to 95% relative
humidity is used for burn patients. In some cases, low relative humidity levels may be
required, such conditions can be experienced in treatment of arthritis, where the relative
humidity level are maintained at around 35% [16].
2.10.3 Filtration
A sterile space in a hospital is generally closed environments. The fresh air need of this
space is provided by mechanical ventilation system. In order to prevent the increment of
particle concentration in a space, the supply air must be filtered appropriately. It is reported
that the microorganisms are transported by the particles suspended in the air; therefore, an
increase in the particle concentration would result with an increase in the microorganism
concentration. The particles present in the supply air is not the only source of particle
concentration. Along with the particles transported into a sterile space by supply air,
articles are also generated in space by the activities. These particles may also carry
microorganisms. The microorganisms that are present in the air may be bacteria, viruses or
originate from molds. The bacteria which are highly infectious and transported via air or
air-water mixture are Mycobacterium tuberculosis and Legionella pneumophila
26
(Legionnaire’s disease). Varicella (chicken pox/shingles), Rubella (German measles), and
Rubella (regular measles) are the examples or viral infections that are transported by air. It
is proved that some molds like Aspergilli’s can be fatal to advanced leukemia, bone marrow
transplant and other seriously immunosuppressed patients. Previous studies have shown
that 99.9% of all bacteria present in a hospital are removed by 90-95% efficient filters. The
main reason of this is that the bacteria exist in colony-forming units that are larger than 1
mm. The use of high efficiency particulate air (HEPA) filters having filtering efficiencies
of 99.97% in certain areas is recommended. It is proved that many of the airborne viruses
are in sub-micron size, thus, there is no exact method to eliminate 100% of the viable
viruses from air even HEPA and/or ultra-low penetration (ULPA) filters offers the greatest
efficiency. Implementing ultraviolet (UV) lights or chemicals to inactivate the viable
viruses are not proven effective [16].
2.10.4 Air Velocity and Air Distribution
The velocity of air in a sterile space is important due to its influence on the comfort
feeling along with the other effects such as drying of the wounds, especially in surgical
site. There are two types of air distribution profiles for a sterile space which are laminar
and turbulent flow. The velocity of air is a significant factor for air distribution. Turbulent
air distribution is generally used in older operating rooms and in other sterile spaces in an
operating suite such as post-operation or sterile equipment rooms. The particles that are
present in the operating room are considered to be distributed homogeneously for this kind
of air distribution profile (Figure 2.20). Conventionally ventilated operating rooms are
generally used for general surgeries which do not require high level of hygiene. It is
recommended to use laminar flow operation rooms for surgeries requiring high level of
hygiene [16].
27
In laminar flow rooms, a clean space is created in the room and the flow profile prevents
the contaminant from entering this clean space from outside. In this kind of room, the
filtered air with low particle concentration is supplied above the patient and/or the
personnel, and the air flows down to floor level and is exhausted by low level registers
(Figure 2.21). Since the velocity of the air is low, the supply air temperature must always
be 1-2ºK lower than the room temperature in order to provide the flow of the air down to
floor. Supplying cold air above the personnel may reduce the thermal comfort. Also it is
shown that if the operating room staff lacks in required precautions for infection control,
the air moving from the staff to the patient transfers skin squamae’s and particles from the
head of the staff (Owers, James and Bannister 2004). Horizontal laminar flow rooms are
recommended to overcome these problems of vertical laminar flows but it is almost
impossible to protect the horizontal laminar flow of the air because of the medical
equipment, movement of staff…. etc[18].
28
air from above the patient bed and exhaust from the region near the door [16]. Using low
level exhaust is beneficial in operating rooms because of the precipitation of waste
anesthetic gases. It is more effective by low level exhaust to remove these waste gases [17].
2.10.5 Pressurization
The aim of the pressurization is to protect the cleanliness of room air from the
contaminants that may enter from the neighboring spaces. Since most of the airborne
viruses are in sub-micron size, filtration is not a perfect method to effectively eliminate the
viable particles. Therefore, the best practice to prevent airborne viable particles to spread
is achieved by pressurization. The air can flow from a space to the neighboring spaces
through the openings of the room. The pressure difference between these spaces is the main
factor to specify the flow between them. Positive pressurization means an outwards flow
from the room while negative pressurization refers to an inwards flow. The flow direction
of air between the spaces must be determined by comparing the cleanliness levels of
neighboring rooms. Air must flow from a space with high level of hygienic need to a lower
one. This required air flow can be maintained by the openings of the room like door
perimeters. Furthermore, the transfer grilles with preset spring-loaded dampers can be
employed to maintain required pressure difference. Thus, the excess of supply or exhaust
air can flow from/to the space and the rooms are maintained under a constant pressure even
the doors are kept closed for a long period. In literature, there are two methods to maintain
required air flow, thus the pressurization. These are discussed under relevant headings. It
is not important how the pressure relation between the spaces is maintained, the designed
airflow between the room must be provided 24-hours a day. The ventilation system serving
to these rooms must be operated all day long. For conservation of energy, the systems can
be operated at reduced air flow rates when the rooms are not used.
29
pressurization. The disadvantage of this method is when the doors of the room are kept
close for a long period; the pressure of the room would become too high/low which would
make high amount of air flow between the rooms at high velocities when the doors are
opened. When the doors are closed, a noise may be generated due to high velocity of air
flow through door perimeter.
30
office equipment because medical equipment is much more varied in type and in
application. Some heat gain testing has been done, but the equipment included represents
only a small sample of the type of equipment that may be encountered. Equipment in
laboratories is similar to medical equipment in that it varies significantly from space to
space. heat gain from equipment, which may range from 50 to 270 W/m2 in highly
automated laboratories. Computers, printers, copiers, etc., can generate very significant
heat gains, sometimes greater than all other gains combined [19].
31
Figure 2. 12: HEPA filter (Source: AAF International 2008)
A HEPA filter is located in a HEPA filter box which consists of ductwork connection,
plenum, seals, tightening mechanism and diffuser. Since the HEPA filter box is a terminal
unit and it is located in the sterile space, it must be made of hygienic materials. The diffuser
may be square or swirl. The types of these diffusers are shown in Figure 2.23. The type of
the selected diffuser depends on the geometrical parameters of space. The turbulent flow
is achieved when a HEPA filter box is used. It is assumed that the contamination in the air
is homogeneous when the clean air is supplied by the HEPA filter boxes.
Figure 2. 13: Swirl and square diffusers and HEPA filter boxes
[Source: ANIL, Mobedi and Özerdem 2007]
32
laminar air flow must cover the patient, surgery team and the sterile instruments used
during surgery (Kenter 2007). A laminar flow unit consists of ductwork connection, HEPA
filter and filter housings, plenum box and laminator. Similar to the HEPA filter boxes, a
laminar air flow unit must be made of proper materials since it is a terminal unit. It is in
the sterile space and directly supplies clean air to the space.
The new trend in the operating room ventilation is to protect both the patient, surgery
team and the sterile instruments used during the operation. Therefore, the area under the
laminar flow unit is enlarged. Moreover, the operations such as total hip replacement or
other types of orthopedic surgeries require high sterile conditions. In order to attain the
required hygiene level, high ventilation rates are implemented. In order to increase air flow
rate in the operating room, laminar air flow units with recirculation air have been
developed. This kind of laminar flow units contains additional fans and filters with
minimum class F7. The return air extracted from the room flows through filter mounted in
the unit and it is mixed with the fresh air supplied by the air handling unit. A laminar flow
unit assisted with recirculation air is shown in Figure 2.14 schematically.
Figure 2. 14: Schematic view of a laminar air flow unit with recirculation air [source:
ANIL, Mobedi and Özerdem 2007]
33
2.12.2 Supply and exhaust fan
A fan is the prime mover of an air system or ventilation system. It moves the air and
provides continuous airflow so that the conditioned air, space air, exhaust air, or outdoor
air can be transported from one location to another through air ducts or other air passages.
Two types of fans are widely used in air conditioning and ventilation systems: centrifugal
fans and axial fans (Fig. 2.15). Fans can be mounted individually as ventilating equipment
to provide outdoor air or air movement inside a building. They can also transport air
containing dust particles or material from one place to another via air duct systems. In air
conditioning systems, fans are often installed in air-handling units, packaged units, or other
air conditioning equipment [20].
34
2.12.3 Outdoor air intake
Designers must carefully consider the location of the outdoor air intake for an AHU.
Intakes must not be located near potential contaminant sources, such as boiler and
generator stacks, laboratory exhaust vents, plumbing vents, cooling towers, ambulance
waiting and vehicle parking areas, loading docks, and helipads [20].
2.12.4 Duct
The outcome of the duct design process will be a duct system (supply and return plenums ducts,
fittings) that:
• Provides conditioned air to all room equal heating or cooling loads.
• is sealed to provide proper air flow and to prevent air contaminant entering.
• Minimizes duct air temperature gains or losses between the supply, return duct and
ambient air.
Typical air temperatures for HVAC applications are 4 to 50°C. Because of the more
moderate temperature ranges associated with HVAC applications, there is a wide range of
insulation materials available.
35
2.12.4.2 Ducts can be classified according to their shapes into
(a) rectangular duct.
For the space available between the structural beam and the ceiling in a building,
rectangular ducts have the greatest cross-sectional area. They are less rigid than round ducts
and are more easily fabricated on-site. The joints of rectangular ducts have a comparatively
greater percentage of air leakage than factory-fabricated spiral-seamed round ducts and flat
oval ducts, as well as fiberglass ducts. Rectangular ducts are usually used in low-pressure
systems.
Figure 2. 17: Various types of air duct: (a) rectangular duct; (b) flexible duct.
(sources: HANDBOOK OF AIR CONDITIONING AND REFRIGERATION Shan K.
Wang).
36
2.12.4.3 Material of Air Ducts
When a designer chooses the shape (round, rectangular, or flat oval duct) or material
(galvanized sheet, aluminum, fiberglass, or other materials) of an air duct, the choices
depend mainly on the space available, noise, cost, local customs and union agreements,
experience, quality, and the requirements of the project.
37
Figure 2. 19: Sound traps or duct silencers source osama khaiadah handbook.
38
and registers usually have adjustable louvers and are available in single or double
deflection models.
Lint grilles (Figure 2.20) are used at the exhaust registers of the operating room. The
aim of their use is to prevent the clogging of the exhaust ductwork system with lint that
originates from the gowns and other fabric used during operating. A lint grille is a cleanable
stainless- steel mesh filter [27].
39
Standard tube diameters used are 3/8”, 1/2” and 5/8”. In aluminum finned designs, fins are
coated with epoxy, providing high corrosion resistance.
40
Figure 2. 22: Horizontal Fan-Coil Unit.
41
2.12.9 Air -Handling
An air-handling unit (AHU) is the primary equipment in an air system of a central hydronic
system; it handles and conditions the air and distributes it to various conditioned spaces. In an
AHU, the required amounts of outdoor air and recirculating air are often mixed and conditioned.
The temperature of the discharge air is then maintained within predetermined limits by means
of control systems. After that, the conditioned supply air is provided with motive force and is
distributed to various conditioned spaces through ductwork and space diffusion devices. Many
air-handling units are modular so that they have the flexibility to add components as required.
An AHU basically consists of an outdoor air intake and mixing box section, a fan section
including a supply fan and a fan motor, a coil section with a water cooling coil, a filter section,
and a control section. A return or relief fan, a heating coil, a precooling coil, and a humidifier
may also be included depending on the application as shown in the Figure 2.24 [20].
Figure 2. 24: A typical AHU with unhoused plug/plenum return fan (source [20]).
42
Figure 2. 25: Volume Control Damper
2.12.11 CONDENSER
the condenser in a refrigeration system is a heat exchanger that rejects all the heat from the
system. This heat consists of heat absorbed by the evaporator plus the heat from the energy input
to the compressor. The compressor discharges hot, high-pressure refrigerant gas into the
condenser, which rejects heat from the gas to some cooler medium. Thus, the cool refrigerant
condenses back to the liquid state and drains from the condenser to continue in the refrigeration
cycle. Condensers may be classified by their cooling medium as (l) water-cooled, (2) air-cooled,
(3) evaporative (air- and water-cooled), and (4) refrigerant-cooled (cascade systems) [22].
2.12.12 Control
The purpose of a control system on an HVAC plant is to:
1. Provide automatic operation, i.e. avoid the cost of attendant labor or for where control is
too complex for manual operation.
2. Maintain the controlled conditions closer than could be achieved by manual operation.
3. Provide maximum efficiency and economy of operation.
4. Ensure safe operation at all times [23].
The control system will consist of a loop, with detector (sensor), controller and controlled
device. The communication between these parts of the loop will be electric, pneumatic or
mechanical (see Figure2.26)
43
Figure 2. 26: Basic control loop
[source: Refrigeration and Air-Conditioning Third edition A. R. Trott and T. Welch]
44
dehumidifiers have been used to control humidity in this application. While the separable units
are not always as efficient as central systems, their low first cost and the ability to serve a single
zone make them appropriate in many circumstances.
45
Figure 2. 28: Closed-loop of piping system. [source: carrier]
46
Figure 2. 29: Two-Pipe Direct Return System. [source: carrier]
47
2.13.3.1 Gate Valves
The disk of a gate valve is in the shape of a “gate” or wedge, as shown in Fig.2.30a. When
the wedge is raised at the open position, a gate valve does not add much flow resistance. The
wedge can be either a solid wedge, which is most commonly used, or a split wedge, in which
two disk halves being forced outward fit tightly against the body seat. Gate valves are used
either fully opened or closed, an on/off arrangement. They are often used as isolating valves for
pieces of equipment or key components, such as control valves, for service during maintenance
and repair.
48
Figure 2. 30: Types of valves. (a) Gate valve; (b) Globe valve; (c) Check valve, swing check.
[source: Handbook of HVAC Shan K. Wang]
2.13.3.5 Butterfly Valves: A butterfly valve has a thin rotating disk. Like a ball or plug
valve, it varies within a quarter-turn from fully open to fully closed. a butterfly valve exhibits
low flow resistance when it is fully opened. The difference between a butterfly valve used for
control purposes and a hand-operated butterfly valve is that the former has an actuator and can
be operated automatically. Butterfly valves are lightweight, easy to operate and install, and
lower in cost than gate valves. They are primarily used as fully open or fully closed, but they
may be used for throttling purposes. Butterfly valves are gaining in popularity, especially in
large pipes.
49
(d) (e)
(i) (k)
Figure 2. 31: Types of valves. (d) Ball valve; (e) Plug valve; (i) Y valve; (k) Butterfly Valves.
[source: Water Piping and Pumps system by Career]
50
2.13.4.4 Grooved ends
These connections use circumferential grooves in which a rubber gasket fits and are enclosed
by iron couplings. Butterfly valves are often connected with grooved ends.
(a) (b)
(c)
Figure 2. 32: (a) Soldered Joint; (b) Weld and Threaded Joint; (c) Groove Joint.
[source: Water Piping and Pumps system by Career ]
2.13.5 Fitting
Numerous fittings are available such as 90 and 45-degree elbows, tees, concentric reducers,
eccentric reducers, flanges, etc. as shown in Figure (2.33) [25].
Figure 2. 33: Example of various pipe weld fittings [source: Water Piping and Pumps system
by Career ]
51
2.13.6 Accessories
Figure 2. 35: Air Separator. [source: Water Piping and Pumps system by Career ]
52
2.13.6.3 Makeup Tank.
Make up tank as shown in figure 2.36 is a component of the cooling system that allows
additional coolant to be added to the system as needed [25].
2.13.6.4 Strainer
The strainer is used to prevent construction debris from entering the equipment during
initial start-up and to catch any small debris that may be circulating through the system
during normal operation or servicing as shown in figure 2.37 [25].
Figure 2. 37: Y Strainer. [source: Water Piping and Pumps system by Career ]
53
2.15 Pump for HVAC system
Pump is the heart of HVAC system figure 2.38. The centrifugal pump has long been the
workhorse of HVAC systems, supporting the operation of chillers, and hydronic distribution
systems and while practically every other component in an HVAC system has been greatly
modified to meet ever changing requirements for efficiency and reliability, centrifugal pump
shape not changed very much. Manufacturers have made significant improvements in impeller
designs, construction materials, bearing and seal designs, and couplings. But these changes have
been more evolutionary than revolutionary [24].
54
• Non-polar polymer base with high water and moisture resistance.
• Universal smoke and flammability proof standards.
• Flexibility for quick and easy installation.
2.16.1 Economic thickness
Economics can be used to (1) select the optimum insulation thickness (Table 2.11) for a
specific insulation, or (2) evaluate two or more insulation materials for least cost for a given
level of thermal performance. In either case, economic considerations determine the most cost-
effective solution for insulating over a specific period. Life-cycle costing considers the initial
cost of the insulation system plus the ongoing value of energy savings over the expected service
lifetime. The economic thickness is defined as the thickness that minimizes the total life-cycle
cost [19].
Figure2.39 shows installed costs for a multilayer application. The slope of the curves is
discontinuous and increases with the number of layers because labor and material costs increase
more rapidly as thickness increases. Figure 2.39 shows curves of total cost of operation,
insulation costs, and lost energy costs. Point A on the total cost curve corresponds to the
economic insulation thickness [19].
55
solution. This system is safer and has more COP than ammonia-water system especially when
used in air conditioning. In such a system it would be better to combine evaporator and absorber
in the same shell, likewise, generator and condenser have to be put together in the same shell
since pressures in this system are very low (under barometric pressure) and can be lost easily.
In this research, using water-LiBr solution since it is very efficient especially in air conditioning
operations. The absorbing substance is LiBr-water solution and the refrigerant is the water.
LiBr-water solution is very suitable and efficient in air conditioning processes more than NH3 -
water solution due to high evaporation temperature which LiBr absorption system is being
worked on.
Their studies show that the LiBr/ water systems have higher COP than systems with other
working fluids. Li and Sumathy (Li and Sumathy, 2000) characterized the main
disadvantages of Ammonia/ Water system as follows:
1.The coefficient of performance for the Ammonia/ Water system is lower than for
Li-Br/ Water.
2.LiBr/ Water absorption units require lower generator inlet temperature (60-88℃)
than Ammonia/ water units (90-180℃).
3.There is limitations on utilizing ammonia- water units because of the hazards associated
with the use of ammonia.
4.The Ammonia/ water absorption system requires higher pressure and hence higher
pumping power.
5.A rectifier is required in this system to separate ammonia and water vapor at the
generator outlet.
For these reasons the lithium bromide-water system is considered to be better suited for this
solar absorption system [30].
Figure 2. 40: Schematic of a single-effect absorption chiller [(adopted from [Estiot (2009):
Development of Plate Heat Exchangers as Main Components of an Absorption Chiller, by
Thomas Hasenöhrl]
56
2.18 Solar Thermal Collectors
Figure 2.41 shows the four different types of solar hot water collectors. The type of collector
chosen for a certain application depends mainly on the required operating temperature and the
given ambient temperature range. Due to the design and simplicity of design each type has a
maximum temperature that they are best suited to provide
• Unglazed EPDM (Ethylene Propylene Diene Monomer) collector, below 90 °F (32 °C).
• Flat plate, below 160 °F (71 °C).
• Evacuated tube, up to 350 °F (177 °C).
• Parabolic trough, up to 570 °F (299 °C).
In this research chosen heat pipe evacuated tubes solar collector because of the following:
1) Its high performance.
2) Plug and Play heat pipe system for easy transport, installation and maintenance (changing
broken tubes).
3) When one tube or more are broken down, the system doesn’t stop.
4) Use of non-toxic heat pipe transfer liquid.
5) High quality and long lasting components (corrosion resistant materials).
6) Excellent insulation properties (>50mm thick rock wool).
7) Environmentally friendly through the use of non-polluting, recyclable materials.
8) Corrosion resistant manifold header pipe (copper).
9) Suitable for open or closed flow operation.
10) Accepts a standard sized temperature sensor.
11) Compact frame that could be packed with the manifold.
12) Adjustable width frame to allow for varying installation surfaces.
13) Quick and simple tube attachment system – permitting easy removal of any one tube.
14) Compact manifold size.
15) No leakage [28].
57
2.18.1 Evacuated Tube Collectors
Conventional simple flat-plate solar collectors were developed for use in sunny and warm
climates. Their benefits however are greatly reduced when conditions become unfavorable
during cold, cloudy and windy days. Furthermore, weathering influences such as condensation
and moisture will cause early deterioration of internal materials resulting in reduced
performance and system failure. Evacuated tube collector (ETC) as shown in Figure 2.42,
operate differently than the other collectors available on the market. Their thermal losses to the
environment are extremely low. Convective heat losses can be reduced by evacuating the space
around the absorber surface. A high quality vacuum layer around the tube prevents heat loss
when the outside air is colder than the tube. The tube captures the energy and keeps it inside
like a thermos flask. This means that they work well in cold weather without losing energy. The
tubes have a round surface which means that the sun’s radiation is not reflected away when the
sun is not directly above the collector. These solar collectors consist of a heat pipe inside a
vacuum-sealed tube. In this type of vacuum collector, the absorber strip is located in an
evacuated and pressure proof glass tube. Several single tubes, serially interconnected, or tubes
connected to each other via manifold, make up the solar collector [31].
58
CHAPTER THREE
METHODOLOGY
3.1 Introduction
This chapter discusses the basic methodology of calculating the cooling load, using manual
method and technical method (Revit program) which will be used. Pressure drop across the air
streams terminals that are calculating, to get overall view about this point pressure drop across
air streams ducts will be discussed, the total static pressure drop is given in the form of required
fanning power necessary to overcome the pressure drop.
The proper components sizing of the system is a very complex problem which includes both
predictable components such as pipe size and other components performance characteristics and
unpredictable components such as weather data.
The accurate calculation of cooling loads is essential to provide a sound bridge between
fundamental building design decisions and an operating building. If loads are substantially
underestimated, occupants and users will likely be cold [1].
Cooling load is the rate of heat energy must be removed from a space in order to maintain
the space at a given inside design condition. Cooling load calculation is the estimated of heat
gain from solar effect, occupants, lighting, equipment, etc.
59
3.2.1 REVIT MEP System Design Features
Estimates design cooling loads for commercial buildings in order to determine required sizes
for air conditioning system components. Ultimately, the program provides information needed
for selecting and specifying equipment. Specifically, the program performs the following tasks:
• Calculates design cooling loads for spaces, zones, and coils in the air conditioning
system.
• Determines required airflow rates for spaces, zones and the system.
• Sizes cooling coils.
• Sizes air circulation fans.
• Sizes chillers.
Also, DUCT SIZER software is used in this research. By knowing the flow rate of a
space, and recommended velocity using DUCT SIZER to calculate the losses and duct
size as shown in figure 3.1.
60
3.3 Flow Chart
The flowchart shown below shows the summary of the design procedures in figure 3.2.
Methodology
Manual&Technical
Estimating
Total Cooling
Loads
Duct
System
Design
Water
Piping
System
Design
Standard&cataloged Selection
Pump Selection
AHUs&FCUs
Selection
FANs Selection
Chiller Selection
Evacuated Tube
Selection
61
3.4 Building parameters
The downward table 3.1 indicates the indoor and outdoor conditions in Sana’a city
according to ASHRAE meteorological weather data of Sana'a, see appendix A Table (A.1).
Table 3. 1: General Project Data
Outside Condition according to ASHARE meteorological
weather data of Sana'a
Region middle east
Location Yemen
City Sana’a
Latitude 15.5° N
Longitude 44.2° E
Elevation above sea level (m) 2206 m
Dry bulb(db) temperature (0c) 30.2°C
wet bulb(wb) temperature (0c) 17°C
Summer daily temperature range (k) 12.9°K
62
3.5 Sizing the HVAC System
There are two methods to size the HVAC system that the research included; manual method,
and technical method by the software’s in section 3.2 for one space as a sample.
Numerous cooling load calculation procedures are available to the designer. Most of the
procedures are based upon ASHRAE research and publications, with simplifications and
adjustments sometimes incorporated for specific applications.
Loads for small envelope-load-dominated buildings are often manually calculated using a
single design-day peak hour with the addition of a safety factor when selecting equipment.
Loads for large, multi-zoned buildings are almost universally calculated using computer
programs.
Sizing a HVAC system is by determining all the cooling loads.
The total thermal resistance for the heat transfer from the air on one side of a composite wall
to the air on other side, as obtained from given as follows:
𝑛
1 𝑥𝑗
𝑅𝑡ℎ = = 𝑅𝑖 + ∑ + 𝑅𝑜 (3.2)
𝑈𝑤 𝑘𝑗
𝑗=1
Where:
j: 1,2, …, Xi: Width of Layer(mm), Ri: inside thermal resistance (K.m2/W), Ro: outside
thermal resistance(K.m2/W), Kj: thermal conductivity of section (W/m. K).
63
1-Heat Gain Due to Solar Effects through Building
Conduction through the roof, exterior walls, windows, skylights, ceiling, interior walls, and
floor, as well as the solar radiation through the windows and skylights, all contributes only
sensible heat to the space. The estimated Heat Gain Due to Solar effects through building is
given by:
𝐷𝑅
𝑇𝑜𝑚 = 𝑇𝑜 − (3.3)
2
Where:
Qsolar: Heat gain due to solar effects through building(W), U: Overall heat transfer coefficient
for Wall and Glass as shown in Appendix b table B.11 for glass,{CLTD: Cooling Load
Temperature Difference (℃), LM: Latitude correction factor which are obtained from Appendix
B Table (B.1,2)} respectively, K: Color adjustment factor 0.83 for medium color and 1 for
windows, Ti is the indoor design temperature, To,m is the outdoor design temperature(℃), f: Attic
or roof fan factor, it is 1 for no fan roof.
Solar radiation often represents a major cooling load and is highly variable with time and
orientation. Careful analysis of heat gains through windows, skylights, and glazed doors is
imperative. The estimated Heat Gain Due to Solar Transmission through Glass is given by:
Where:
Qglass: Heat gain due to solar transmission through the glass (w), {SHG: Solar heat gain factor
(W/m2), SC: Shading coefficient W/m2. K, CLF: The cooling load factor which are obtained
from Appendix B Table (B.3,4,5)} respectively, A: The area of glass (m2).
The heat gain from the light is taken for every meter square according ASHREA, and can be
estimated by equation:
𝑊
𝑄𝑙𝑖𝑔ℎ𝑡 = 𝑄 (𝑚2 ) 𝐴 (3.7)
64
Where:
Qlight: Heat gain due to light, Q = light power (w/m2), A = area of zone (m2).
Heat gain from people is depended on the activity of peoples, athletes in a gymnasium release
eight times the amount of heat released by a seated audience.
Equations 3.5 – 3.7 are used to find heat gain due to occupants:
Where:
Qoccup: total heat from occupant(W), QSH: Sensible heat gains from occupant (W), QLH: Latent
heat gains from occupant (W), {N: Number of people, SHG: Sensible heat gain W/person, LHG:
Latent heat gain is W/person, CLF: Cooling load factor for people which are obtained from
Appendix B Table (B.6,7,9)} respectively.
Hospital and laboratory equipment items are major sources of sensible and latent heat gains
in conditioned spaces. Equipment in laboratories is similar to medical equipment in that it varies
significantly from space to space. heat gain from equipment, which may range from 50 to 270
W/m2 in highly automated laboratories [4], and more laboratory equipment which are obtained
from Appendix B Table (B.13). To find heat gain due to equipment by equation:
Where:
Q equip: Heat gain of equipment, A: Area of zone(m2), Q: Heat gain from equipment (W/m2).
Medical equipment of 110W/m2 will be considered in our research.
65
6. Heat gain due to infiltration
The total heat load due to infiltration consists of two parts: (a) Sensible heat load and (b)
Latent heat load. Sensible heat is the heat which raises the temperature of the moisture air. The
latent heat is associated with the evaporation or condensation of water vapor at the same
temperature.
The sensible heat load Qs,f , due to infiltration is given by the following equation.
Or,
The total heat load Qt,f , due to infiltration is given by the equation
__
QL,f = Qt,f 𝑄𝑠𝑓 (3.14)
Where:
mf is the mass flow rate of infiltration outside air, Cp: Specific heat of air constant equal 1005
kg
J/kg, 𝜌° is the Specific density of air constant which is 1.143 (m3), Vf: is the Volumetric
flow rate of infiltrated air, Vf= No. of ACH*Room volume (m3 /s), 𝑇𝑖 and TO are the inside and
outside temperatures of infiltration air, respectively, hi and ho are the inside and outside
enthalpies of infiltration air which are obtained from the psychometric chart at the given inside
and outside conditions, respectively. The infiltration rate per unit length of crack for different
types of windows and doors under different wind velocities.
The outdoor air ventilation load does not have a direct impact on the conditioned space
(except when provided via open windows), but it does impose a load on the HVAC equipment.
The amount of ventilation depends upon the occupancy and function of each space. Also the
load of ventilation could be the ACH load of the space or room for example the ACH of the
operation room in hospital from 12-20 [3]., and more Ventilation Design Parameters which are
66
obtained from Appendix B Table (B.10) [3]. The Heat gain due to ventilation is given by the
equation:
SHR=Qs/Qt (3.15.a)
Then hi can be obtained from the psychometric chart at the inside conditions, after that ms
estimated from equation (3.15.b), and determine the cooling coil by equation (3.15.c)
Qt=ms*(hi-hs) (3.15.b)
Where:
hi and ho are the inside and outside enthalpies of ventilation air which are obtained from the
psychometric chart at the given inside and outside conditions, respectively.
67
Table 3. 2: Data needed for manual method
Outside design condition: 30.20 C Db, 40% RH.
Inside design condition: 210C Db and 50% RH.
Overall heat transfer coefficient for walls U=1.787 w/m2 C which is obtained from equation
(3.1)
Overall heat transfer coefficient for Aluminum Windows U=5.097w/m2 C as shown in table
3.4.
Occupancy: 5m2/person=8 people with sensible heat gain 82.1 W/person, and latent heat gain
79.1W/person as shown in appendix B
Lights: 17 W/m2 of floor area.
Equipment: 100 W/m2.
68
2-The building is sketched up.
69
4-The spaces gathered in a zone.
70
5-Insert the space parameters according to ashrae standard.
71
7- From the icon of Heating and Cooling Loads insert the building parameters such as building
type, location, and the rest of them as shown in figure below.
8- Insert the location weather and site such as city, latitude, and longitude. Which are obtained
from the REVIT library.
72
9- Insert the weather data, according to meteorological weather data of Sana’a city. Then
insert calculate to get the results in a form of report.
73
3. Determine the duct diameter of the duct from the friction chart in figure3.3. Or the following
equation can be used to determine the diameter:
𝜋
𝑉𝑠̇ = 4 𝑑 2 (3.18)
74
Another manual method to design the main supply duct by using (Duct Sizer software) which
aided to obtain the duct size. By knowing the main duct supply velocity air (5 m /s) and flow
rate (405.4 liter/second), the program gives the dimensions of main duct as shown in the Figure
3.4. similarly, the next branches ducts can be obtained
The dimensionless coefficient C is used for fluid resistance, because this coefficient has the
same value in dynamically similar streams (i.e., streams with geometrically similar stretches,
equal Reynolds numbers, and equal values of other criteria necessary for dynamic similarity).
The fluid resistance coefficient represents the ratio of total pressure loss to velocity pressure at
the referenced cross section. The pressure loss in the straight duct can be obtained from the
equation
Where:
L= the length of the straight duct, ∆P/m=pressure lose per meter which has obtained from the
chart in figure3.3.
Fittings are classified as either constant flow, such as an elbow or transition, or as divided
flow, such as a wye or tee.
The pressure drop for fitting is obtained from the equation
Where:
75
Δp: is pressure drop per meter (Pa), ρ: Density of air (kg/m3), C: local dimensionless loss factor
for any fitting, V: air velocity(m/s). The local dimensionless loss factor can be obtained from
ASHRAE Tables in Appendix C
The total pressure drop is the sum of the two equations 3.20.a, and 3.20.b.
• Size fan supply ducts by either the equal friction (EF) or static regain (SR) method. The
duct velocity anywhere in the system should not exceed the velocity listed in in appendix
B Table B.16.
• Size ducts downstream of terminal boxes, toilet exhaust ducts, and other low-pressure
systems using the equal friction method with a friction rate in the range from 0.4 to 1.6
Pa/m such that the duct velocity in the duct anywhere in the system does not exceed the
values as shown in appendix B Table B.15. Use Table B.18 as a guide to select the design
friction rate [19].
• Diffuser runouts should be full size, except for runouts in the critical path or a runout length
greater than about 4.5 m: these runouts should be at least 2 m of flexible-duct full size, and the
remainder’s size determined by the design method [19].
Duct insulation
Insulation thicknesses in these standards are minimum values; economic and thermal
considerations may justify higher insulation levels. Additional insulation, vapor retarders, or
both may be required to limit vapor transmission and condensation.
Economic Thickness
Economics can be used to (1) select the optimum insulation thickness for a specific
insulation, or (2) evaluate two or more insulation materials for least cost for a given level of
thermal performance. In either case, economic considerations determine the most cost-effective
solution for insulating over a specific period. Figure 3.4 shows installed costs for a multilayer
application. The slope of the curves is discontinuous and increases with the number of layers
because labor and material costs increase more rapidly as thickness increases.
76
Figure 3. 4: Determination of Economic Thickness of Insulation
[source Ashrae fundamentals 2017 SI]
Thermal insulation is commonly used to reduce energy consumption of HVAC systems and
equipment. Minimum insulation levels for ductwork is often dictated by energy codes, many of
which are based on ASHRAE Standards 90.1 and 90.2. In many cases, it may be cost-effective
to go beyond the minimum levels dictated by energy codes. Thicknesses greater than the
optimum economic thickness may be required for other technical reasons such as condensation
control, personnel protection, or noise control. as shown in appendix B Table B.17,18. contain
minimum insulation levels for ducts, excerpted from ANSI/ASHRAE Standard 90.1-201
77
For below-ambient systems, condensation control is often the overriding design objective.
The design problem is best addressed as two separate issues: (1) avoiding surface
condensation on the outer surface of the insulation system and (2) minimizing or managing
water vapor intrusion. To illustrate, Table 3.10 shows insulation thicknesses required to
prevent condensation on the exterior surface of a hypothetical insulated tank containing a
liquid held at 4°C in a mechanical room with a temperature of 27°C. Note that, at high
relative humidifies, the thickness required to prevent surface condensation increases
dramatically, and becomes impractical above 90% rh as shown in appendix B Table B.19.
78
3- Tap the duct layout to obtain the size of the duct according to the flow rate, and
friction(pa/m), which is determined from the duct sizer software method.
79
1. Supply airflow rate per diffuser which is given by air conditioning system design to
be.
3. Required noise criteria (NC) for the hospital rooms as shown in appendix B table
B.20.
4. Pressure drop through the diffuser which can be obtained from the used diffuser
catalogs in this research.
Note: all the above parameters must meet the catalogs according to ASHRAE cods for
Health care facilities.
3.7 Filters
Many of the spaces in a health care facility require a higher level of filtration than is
provided by a pre-filter alone. The FGI Guidelines, for example, recommend a filtration
level of MERV 14 for all patient care areas, whether in clinics or in full-service hospitals.
Some codes require HEPA filtration for inpatient applications, especially where patients
are particularly vulnerable to infection, such as protective isolation rooms for
immunocompromised patients and orthopedic operating rooms. Designers must provide
(and require in contract documents) adequate space for replacing filters. All filters should
be provided with a differential pressure indicating manometer, mounted on the AHU, to
indicate when replacement is required [3].
To ensure adequate airflow throughout the range (from clean to dirty) of filter
resistance, designers should use the filter manufacturer’s recommended final resistance
when calculating fan pressure requirements. If no final resistance recommendation is
available, a value of 1.4 in. of water [350 Pa] is recommended for MERV 13 to 15 filters.
Be aware that when filters are clean, resulting in system resistance lower than the fan
selection point, the fan motor must be adequately sized to accommodate the higher power
requirements at that operating condition. One advantage of using variable-speed drives on
fans is that fan speed can be increased as filters begin to load so the AHU maintains a
80
constant airflow. Figure 3.5 shows a typical relationship of pressure drop versus air velocity
for a MERV 14 filter [3].
3.8 Fan
Selection of a fan for a given type of air system or mechanical ventilating system
actually is done in two stages: selection of fan type and determination of fan size.
Before the selection, the following conditions must be clarified:
1. Setting (in a commercial building to handle clean air at room temperature, or an
industrial setting to handle dirty air)
81
2. Special requirements (such as high-temperature operation or spark-resistant
construction)
3. Function (supply fan or a return fan in an air-handling unit, or supply or exhaust fan
in a ventilating system)
4. Characteristics of the air system (constant volume or variable air volume)
5. Room NC curve
6. Approximate annual operating hours
7. Unit cost of energy at the specific location.
During selection, the following factors should be considered:
• Pressure-volume flow operating characteristics. Selecting a fan to provide the
required volume flow rate and total pressure loss for the longest run of supply and
return ducts, including the pressure drop for all fittings, filters, exit air diffusers,
cooling coils, ..etc [20].
When all above parameters are determined, the fan is selected from fan performance
tables or graphs supplied by the fan manufacturers, such as that shown in catalogs
[6].
• Fan capacity modulation. A variable-air-volume system operates at a reduced
volume flow rate during part-load operation. Effective and economical fan capacity
modulation is an important factor that affects the operation of an air system.
• Fan efficiency. Fan efficiency is closely related to the energy consumption of an air
system. Fans should be selected so that they can operate at high efficiency during as
much of their operation time as possible.
• Sound power level. Most commercial and public buildings and many industrial
applications need a quiet indoor environment. Fans are the major source of noise in
an air system. Usually, the higher the fan total efficiency, the lower the sound power
level of the selected fan. A fan with a low sound power level and sound power level
at high frequencies is preferable. High-frequency sound is more easily attenuated
than low frequency sound.
• Airflow direction. In many applications, a straight-through or in-line flow occupies
less space and simplifies layout.
82
• Initial cost. The initial cost of the fan modulation device, sound attenuator(s), and
space occupied by a particular type of fan, in addition to the cost of the fan itself,
should be considered [21].
Where:
V=the volumetric air flow rate(m3/s), ∆P=the fan pressure drop, 𝜂=the motor efficiency
[21].
Where:
𝑄𝑐𝑐 = cooling coil load (kw), 𝐶𝑝 = the specific heat water whose value can be taken to
equal to (4.186 k J/ kg °C), 𝑇𝑖𝑛 = Entering chilled water temperature (7°C), 𝑇𝑜𝑢𝑡 = Leaving
chilled water temperature (12°C) [21].
83
the chilled water from the chiller to the AHUs, and FCUs. For calculating pipe dimensions
and fittings, the manual method and programing method are used.
Figure 3. 6: Friction Loss for Water in Commercial Steel Pipe (Schedule 40)
(source: The 2017 ASHRAE Handbook—Fundamentals SI).
84
Or, calculating main pipe diameter by using manual method, select the velocity of cold
water in the main pipe V= (1.11) m/s, by equation
Q = V × A (3.20)
Where:
Q = water flow rate (l/s), V = velocity of cold water in the main pipe, A = area of
water pipe (m2).
𝑉2 𝑉2
∆𝑃 = 𝐾𝜌 𝑜𝑟 ∆ℎ = 𝐾 (3 .21)
2 2𝑔
where
K = geometry- and size-dependent loss coefficient (Tables C.4-8. in appendix C) and 𝜌 =
𝑉2
density of fluid = 1000 kg/m3 for water at temperatures below 120°C, = velocity
2𝑔
head (m)[19].
∆𝑃
∆𝑃𝑡 = ∑( 𝑚 × 𝐿𝑆𝑡𝑟𝑎𝑖𝑔ℎ𝑡 + ∆𝑃Valves and fittings ) (3.22)
85
1-Construct the piping network, fitting, and pipe accessories.
86
3.10.3 Pump Sizing
After the piping system has been laid out, and the total pressure loss, or head, for the
pumps is calculated, the selection of pumps can be made. In this research, concentrate on
centrifugal pump designs which are the most common types used in comfort air
conditioning.
The choice of the pump is according to total pressure drop around the fluid circuit or
total head actual and the water flow rate.
Capacity (water flow rate) is the amount of liquid that can be pumped, given in term of
gallons per minute (g.p.m).
Head (hd) is an energy unit that is usually expressed in feet or meter of the liquid being
pumped (total head). The total head consist of discharge head is the head at the pump
discharge, a pump discharge gauge would indicate total discharge head and Suction head
is the head indicated on a pressure gauge at the pump suction as shown in the figure (3.7).
87
𝑓𝑠∗∆𝑃 ∗𝑄
𝑡
hp = 1000∗𝜂∗746 (hp) (3.24)
Where:
Q = the water flow rate (L/s or gpm), 𝜂 = pump efficiency %, fs= factor of safety will be
considered in our research, pump efficiency = 75 % and factor of safety =1.1.
Since:
∆𝑃 = 𝜌𝑔𝐻 (3.25)
𝜌 = water density (kg/m3) =1.2kg/m3, 𝑔 = gravity (9.81N), 𝐻= actual total head (m).
88
𝑸𝒈
𝑨𝑪 = (3.27)
𝛈𝐬𝐨𝐥𝐚𝐫 𝐈𝐦𝐚𝐱
Where:
Ac = total collector area [𝑚2 ], η solar = efficiency of solar system (the efficiency of solar
system is taken as 0.6 for design purpose), and Imax= maximum daily solar radiation
[W/𝑚2 ]. (Imax in the equation above means the system is designed to meet the load on the
sunniest day of the year, which eliminates excess capacity and optimizes economic
performance) [33].
𝑨𝒕
𝑨𝒕 = 𝒏𝑨𝒄 → 𝒏 = (𝟑. 𝟐𝟖)
𝑨𝒄
89
CHAPTER FOUR
4.1 Introduction
This chapter represents the numerical results and data output from calculations and
REVIT model simulation as detailed in the methodology chapter for the proposed HVAC
system. The data is then analyzed and presented in the form of tables and figures. Table
4.1 shows the summaries of the HVAC system sizing.
Table 4. 1: The summaries of the HVAC system sizing
Building summery
Area 1,970 m²
Volume 5,418.69 m³
AHUs 201.962 KW
FCUs 113.732 KW
Item Result
Qe 369KW
Qg 473.1KW
90
Qs 333.2KW
Ac 5O4.9m2
Ag 792m2
Number of collector 180
Number of tubes 5400
Total 705.73
91
The heat gain due to solar transmission through glass is given by equation (3.4). As
shown in table 4.3, QTranssmssion = 679.722W.
Table 4. 3:Result of Heat gain due to solar transmission through the glass
As we state in chapter 3, the heat gain due to light is given by equation (3.5). Lights: 17
W/m2 of floor area then 𝐐𝐥𝐢𝐠𝐡𝐭 = 595 W
To estimate the heat gain due to occupants, must determine (i) QSH= Sensible heat gains
from occupant (W), and(i) QLH= Latent heat gains from occupant (W). Equations (3.5 –
37) are used to find heat gain due to occupants as a result 𝐐𝐨𝐜𝐜𝐮𝐩. = 𝟒𝟎𝟐. 𝟐𝟗 + 𝟓𝟓𝟑. 𝟕 =
𝟗𝟓𝟔 𝐖
According to equation (3.9) that has been used to estimate the heat gain from equipment,
we determined that 𝑸𝒆𝒒𝒖𝒊𝒑 = 𝟑𝟓𝟎𝟎 𝑾.
The total heat gain for the room is given by equation (3.10).
𝐐𝐭𝐨𝐭𝐚𝐥 = 𝟕𝟎𝟓. 𝟕𝟑 + 𝟔𝟕𝟗. 𝟕𝟐𝟐 + 𝟓𝟔𝟎 + 𝟗𝟓𝟔 + 𝟑𝟓𝟎𝟎 + 𝟐𝟕. 𝟔 = 𝟔𝟒𝟐𝟗. 𝟎𝟒𝟐 𝐖
92
Table 4. 4: Summary of cooling loads of the sample(OP-Z1) .
Item Cooling loads (𝑾)
Q solar 705.73
QTranssmssion 679.722
Q light 560
Q occup 956
Q equip 3500
Qinf 27.6
Q total 6429.042
Qsensible 6012.752
SHR 0.93
Qcoil 16430
93
Table 4. 5: Sample Ductwork Summery
Duct Air NO. of Duct size Velocity Duct Fitting Duct Total
element flow element (mmXmm) (m/s) length loss pressure pressure
(L/s) (m) coefficient loss drop
(Pa/m) (Pa)
Duct 405.4 1 350X350 3.46 0.378 ــــــــــ 8.182 3.093
Elbow 405.4 3 350X350 3.46 ــــــــــــ 1.2 ــــــــــــــ 25.857
Diffuser 405.4 1 ـــــــــــــــ 3.46 ـــــــــــ ــــــــــــ ــــــــــ 8
A.H.U. 405.4 1 ــــــــــــــــــ 3.46 ــــــــــ ــــــــــ ــــــــــ 32
TOTAL 68.95
94
Elbow 0.38 5 ــــــــــ ــــــــــ 377.0555
Sect 6 Pipe 40 1.02 0.75 ــــــــــ ــــــــــ 1.02 200 204
Tee 0.23 1 ــــــــــ ــــــــــ 64.6875
Sect 7 Pipe 32 0.82 0.78 ــــــــــ ــــــــــ 15.26 260 3967.6
Tee 0.25 1 ــــــــــ ــــــــــ 76.05
Sect 8 Pipe 25 0.49 0.8 ــــــــــ ــــــــــ 6.9944 370 2587.928
Elbow 0.43 6 ــــــــــ ــــــــــ 825.6
Valve 13 2 ــــــــــ ــــــــــ 8320
Sect 9 Pipe 25 0.49 0.8 ــــــــــ ــــــــــ 6.9944 370 2587.928
Elbow 0.43 6 ــــــــــ ــــــــــ 825.6
Valve 13 2 ــــــــــ ــــــــــ 8320
Sect 10 Pipe 32 0.82 0.78 ــــــــــ ــــــــــ 15.26 260 3967.6
Tee 0.25 1 ــــــــــ ــــــــــ 76.05
Sect 11 Pipe 40 1.02 0.75 ــــــــــ ــــــــــ 1.02 200 204
Tee 0.23 1 ــــــــــ ــــــــــ 64.6875
Sect 12 Pipe 50 1.37 0.63 ــــــــــ ــــــــــ 40.66 100 4066
Tee 0.2 1 ــــــــــ ــــــــــ 39.69
Elbow 0.38 5 ــــــــــ ــــــــــ 377.0555
Sect 13 Pipe 100 9.51 1.2 ــــــــــ ــــــــــ 4.233 140 592.62
Tee 0.15 1 ــــــــــ ــــــــــ 108
Sect 14 Pipe 125 13.36 1.2 ــــــــــ ــــــــــ 1.4 100 140
Tee 0.15 1 ــــــــــ ــــــــــ 108
Sect 15 Pipe 125 15.4 1.13 ــــــــــ ــــــــــ 2.1 110 231
Tee 0.15 1 ــــــــــ ــــــــــ 95.7675
sect 16 Pipe 125 16.7 1.2 ــــــــــ ــــــــــ 4.297 130 558.61
Elbow 0.31 6 ــــــــــ ــــــــــ 1339.2
Tee 0.15 1 ــــــــــ ــــــــــ 108
Valve 6.25 3 ــــــــــ ــــــــــ 13500
F.C.U. 40000
Chiller 54900
Total 169519.62
95
4.2.4 Pump selection
after calculating size and losses of pipes the total quantity of the chilled water needed for
the cooling coils in all AHUs and FCUs is 16.7 L/s.
from table 4.6 the pressure drop in the critical path of pipes is 1.69 bar.
Pump specifications:
96
4.3 Technical method
Revit calculations output of cooling loads for the operation room 1 (OP-Z1) is shown
in the Table 4.7 below.
Table 4. 7: Zone summary -op-z1
Zone Summary - OP-Z1
Area (m²) 35
Cooling Setpoint 21 °C
From manual method, the total heat gain for the operation room 1 (OP-Z1) is16430 W.
The total heat gain from REVIT report for this room is 15485W. The difference between
the two results is due to defining the thermal resistance for the used materials of the wall,
roof, and windows in ERVIT program. In addition, the sources of constants used in the
equations of manual method are not the same. The results of programing method are more
accurately because the program is performing analysis for every element of whole building.
The manual method takes all the loads at the same time (collecting them accumulatively).
Whereas the programing method takes the time of acting load for example, the program
does not account the lights in the mid. The REVIT output total cooling coil loads for all
the spaces are labeled in the Table 4.8
97
Table 4. 8: All spaces cooling coil load
Space name Total Coil Load (kW) Maximum Supply air (L/s)
Break 1 2.861 137.3
Break 2 2.951 141
Break 3 2.846 137.1
Break 4 2.834 136.3
Break 5 3.008 143.4
Cath zone 6.171 242.439
Dressing NR STR 4.659 244.3
Fixing NR STR 4.25 128
Hall Near OP 11.823 356.9
Hall with stair 8.545 302
Monitoring 9.967 309.6
OP-Z1 15.485 405.4
OP-Z2 12.23 423.5
OP-Z3 13.847 414.1
OP-Z4 7.689 344.9
OP-Z5 18.195 616.7
I.C.U 23.996 1189.9
CATH Heart Zone 23.996 1021.1
Dirt unit 10.929 431.1896
PR-ZONE 2 13.523 439.1
PREP-R-OP 4.865 243.4
Recovery zone 9.831 314.1
Replacing dressing zone 6.831 321
Replacing NR CATH 7.284 347.3
Replacing zone 11.052 396.5
Service + electric 4.011 162
Sterilization 37.33 1225.6
Store 1-OP 2.876 111.5
Store 2-OP 2.479 103.2
Store NR break 5.839 279.3
Sub NR STR 2.654 113
Subway 01 4.089 159.1
Subway 02 9.621 470.1
Subway 03 10.204 400.7
TOTAL 340.432 12912.3
98
4.4 FCUs and AHUs Selection Summary
In this section FCU and AHU, selection summary will be provided.
99
Table 4.10 shows the summary of AHU parameters. We can note from the table that
AHU09 Load, and ventilation has the largest value. That’s because of the large space area.
Taking into account other influencing parameters such as the high temperature glassware
washers/autoclaves for sterilization, chemical hoods, water filtration systems, and
refrigerators and/or freezers. Also Sterilization requires that instruments be exposed to
steam at a temperature of 250°F [121°C] or higher for a length of time. Excessive superheat
may result if the sterilizer jacket is maintained at a higher temperature than the chamber or
if there is excessive pressure reduction before the sterilizer connection. [3] the space
construction which is exposed to the solar radiations through its windows also causes
increasing the conditioned air. The total cooling coil will be 201962 W.
Here the method to select FCU from FCU YGFC catalog, according to the cooling coil and
the flow rate as a sample FCU01 has 8688W lays close to Model 3Rows10 with nominal
cooling capacity of 9.07KW. So the rest of them can be obtained.
The AHU11with 22043W lays close to the AHU 2Row section with cooling mode of
22.8 KW. The rest of the AHUs also can be gotten according to their cooling loads.
100
Table 4. 10: Summary of AHU parameters
A.H.U. Spaces Q(W) V(L/s) mw(L/s)
101
4.4.2 Rooftop Supply and Exhaust Fan Units Specification
Table 4.11 are representing the actual values of the flow rates, pressure drops, also the
standard values of them which obtained from the Revit software.
Table 4. 11: The actual and standard values of the flow rates, pressure drops of the
rooftop fan units
Roof top fan units Actual Actua Model standard flow Standard
3
flow l rate (m /s) Pressure drop
rate Press (Pa)
(m3/s) ure
drop
(Pa)
Mechanical supply air (1) 1.056 123.64 MUB 042450 EC-A2-k 1.41 250
Mechanical supply air (2) 1.08 314.67 MUB 042450 EC-A2 1.75 560
Mechanical supply air (3) 1.9274 334.62 MUB 062560 EC-A2 3 540
Mechanical supply air (4) 3.04 772.7 MUB 062630 D4-A2 3.89 790
IE2
Mechanical supply air (5) 0.9795 116.3 MUB 042450 EC-A2 1.75 600
Mechanical supply air (6) 1.1859 342 MUB 042450 EC-A2 1.75 430
Mechanical exhaust air (1) 2.8107 349 MUB 062630 D4-A2 3.63 660
IE2
Mechanical exhaust air (2) 1.9485 255.5 MUB 062560 EC-A2 3 500
Mechanical exhaust air (3) 1.7505 276 MUB 062560 EC-A2 3 550
102
The MUB-EC fans are driven by EC-external rotor motors. These are energy
savingmotors with high efficiency. Fans specifications are gotten from systemair catalog
show inTable4.12 . Table 4. 12: Fan specifications
FAN MODEL FLOW (m3/s) ∆P (Pa)
Mechanical supply air (4) MUB 062630 D4-A2 IE2 3.89 790
Mechanical exhaust air (1) MUB 062630 D4-A2 IE2 3.63 660
Also, it can be seen that the system characteristics (flow rate, pressure loose) lay very close
from setting number4, so this fan dose not satisfies the needs to overcome the pressure
losses. So move to the air flow rate 1.41 (m3/s) which is selected from technical data Table
4.13 MUB 042 450EC-A-2K. Then selected fans performance chart case (B) is shown in
Figure4.3. It can be seen from that graph that there are four different settings. Also, it can
be seen that the system characteristics (flow rate, pressure losses) lay very close from
setting number 2, so this fan satisfies the needs to overcome the pressure losses. By using
this method, the rest of fans can be obtained from the fan catalogs as labeled above in the
preceding table.
103
Table 4. 13: technical data for fans
A B
104
4.5 Supply, Return Diffuser, and Exhaust grille
Table 4.14 is representing a summary of 600X600 diffusers where they are installed in
the large spaces, 450X450 are installed in the small spaces, while the grills are installed in
the operations rooms,
The way to select the 4 Way Square Diffuser- model 4WS from the catalog is shown
below, according to the flow rate and the throw distance.
105
The exhaust grilles also can be obtained according to the flow rate as shown in next
table
106
4.6 Absorption chiller
According to the total cooling load of the whole 1st floor of USTH that has been
estimated by using the Revit software program which is equal to 340.435KW. So from the
catalog can select Lithium bromide absorption chiller Single effects steam type hot water
inlet /outlet 80-95 0C respectively, with cooling capacity 369KW closes to the required
capacity.
107
Table 4. 15: Absorption chiller specifications
Item Specifications
Required cooling capacity in kilowatt 369 kW
Entering and Leaving chilled water temperature 7-12 0C
Entering and Leaving cooling water temperature 32-40 0C
Entering and Leaving hot water temperature 80-95 0C
Design ambient temperature 35 0C
108
Apricus solar collectors use high efficiency twin-glass evacuated tubes. They are ideal for
cold regions and high temperature applications. The collector performance parameters and
its technical specifications are given in the Table 4.16.
Table 4. 16: Technical specifications of the collector
Apricus AP-30 collector specifications
109
CHAPTER 5
CONCLUSIONS AND RECOMMENDATIONS
This research investigates the potential of selecting an absorption HVAC for the 1st floor
of USTH, Sana’a. Many software computer program have been used in calculating,
designing the ductwork construction, and piping network. Also, the manual method has
been used to compare the results. The total cooling loads of the 1st floor of USTH is
340.43KW (97.3 TR), and total air flow rate is 12912.3 L/s.
The system includes two types of unites which are selected according to the cooling coil
load and the flow rate, eleven AHUs are installed in the most critical spaces such as ICU,
CCU, operations rooms, and sterilization room with total cooling coil load of 201962 W.
While the fourteen FCUs are installed in the other spaces such as the break zones, dressing
room, and the corridors with total cooling coil of 113732 W.
The design includes some points which are studied such as ductwork design with total
area of 1927m2 the duct material used is galvanized steel, the rooftop unites comprises of
six supply fans with total flow rate 13.89L/s, three exhaust fans with 9.63L/s, selection of
diffusers and grills according to the flow rate were done from catalogs. The system will
operate with 100 % capacity in the pipeline network a ANIS SCH 40 steel type was used
because it can handle the high pressure and therefore it has long life and using the maps
the diameters and pressure drop were calculated in the critical path which is equal to 1.69
bar. Selection of water pump (50-160/55) LOWARA is achieved to overcome maximum
head up to 17.3m. The absorption chiller with cooling capacity of 369 KW is selected from
carrier company.
Regarding the analysis presented in this research it can be concluded that solar energy
systems are efficient, cost effective, and friendlier to the environment. The reduction of
GHGs pollution is the main advantage of utilizing solar energy. Therefore, solar cooling
energy systems should be employed whenever possible in order to achieve a sustainable
future.
110
REFERENCES
[1] Solar Cooling for Industry and Commerce (SCIC) Study on the Solar Cooling Potential
in Jordan
[2] Laleh Hosseini August 2011 Design and Analysis of a Solar Assisted Absorption
Cooling System Integrated with Latent Heat Storage.
[3] HVAC Design Manual for Hospitals and Clinics Second Edition.
[4] Khalid Alshibani, (May 2013), “Yemen's Second National Communication under the
United Nations Framework Convention on Climate Change”.
[5] Roger W. Haines, C. Lewis Wilson - HVAC Systems Design Handbook (2003,
McGraw-Hill Professional)
[6] ASHRAE Handbook. HVAC Systems and Equipment. Atlanta, GA: American Society
of Heating, Refrigerating, and Air Conditioning Engineers; 1996. pp. 1-10
[7] American Society of Heating, Refrigerating & Air-Conditioning Engineers. Heating,
Ventilating, and Air-Conditioning: Systems and Equipment: 2000 ASHRAE Handbook:
Inch-Pound. Amer Society of Heating; 2000
[8] Sugarman SC. HVAC Fundamentals. 2nd ed. CRC Press, The Fairmont Press, Inc.;
2005
[9] American Society of Heating, Refrigerating & Air-Conditioning Engineers. ASHRAE
Handbook. Fundamentals: SI edA. mer Society of HeatingA, tlanta, GA; 2009
[10] Haines RW, Myers ME. HVAC Systems Design Handbook. McGraw-Hill Education;
2010
[11] ASHRAE Handbook. Fundamentals. Atlanta: American Society of Heating,
Refrigerating and Air Conditioning Engineers; 2001. p. 111
[12] Mumma SA. Ceiling panel cooling systems. ASHRAE Journal. 2001;43(11):28
[13] Brumbaugh JE. Audel HVAC Fundamentals: Volume 1: Heating Systems, Furnaces,
and Boilers. Vol. 17. Canada: John Wiley & Sons, Wiley Publishing, Inc.; 2004
[14] From HVAC fundamentals/Samuel C. Sugarman pdf50 reference
[15] Deutsches Institut für Normung 1999 March, American Institute of Architects 2006,
American Society of Heating Refrigerating and Air-Conditioning Engineers 2003
111
[16] American Institute of Architects 2006 and American Society of Heating Refrigerating
and Air-Conditioning Engineers 2003).
[17] (Melhado, Hensen and Loomans, Literature Review of Staff Thermal Comfort and
Patient “Thermal Risks” in Operating Rooms 2006).
[18] (Melhado, Hensen and Loomans, Review of Ventilation Systems in Operating Rooms
in View of Infection Control 2006
[19] (The 2017 ASHRAE Handbook—Fundamentals SI).
[20] HANDBOOK OF AIR CONDITIONING AND REFRIGERATION Shan K. Wang
[21] Heating and air conditioning for residential buildings fifth edition, by Mohammad A.
Alsaad and Mahmoud A. Hammad)
[22] The 2016 ASHRAE Handbook—HVAC Systems and Equipment
[23] Refrigeration and Air-Conditioning Third edition A. R. Trott and T. Welch)
[24] STUDY OF PERFORMANCE OF AN AIR CONDITIONING SYSTEM AND
COOLING LOAD CALCULATION BY USING DEVELOPED SOFTWARE FOR A
BUILDING ByKhandakar Mozammel Hossan
[25] Water Piping and Pumps system, by Company Carrier
[26] R. Z. Wang, T. S. Ge, C. J. Chen, Q. Ma, and Z. Q. Xiong, "Solar sorption cooling
systems for residential applications: Options and guidelines," International Journal of
Refrigeration, vol. 32, pp. 638-660, 2009.
[27] X. Q. Zhai, M. Qu, Y. Li, and R. Z. Wang, "A review for research and new design
options of solar absorption cooling systems," Renewable and Sustainable Energy Reviews,
vol. 15, pp. 4416-4423, 12// 2011.
[28] A Thesis Submitted to the Graduate School of Engineering and Sciences of İzmir
Institute of Technology in Partial Fulfillment of the Requirements for the Degree of
MASTER OF SCIENCE in Mechanical Engineering by Orkun Baki ANIL December 2008
İZMİR
[29]US Army Corps of Engineering, (2011), “Central Solar Hot Water Systems Design
Guide”.]:
[29] UNDP, “Yemen-Prospects of Solar Energy in Yemen”. Policy Note, January 2014
112
[30] Design and Analysis of a Solar Assisted Absorption Cooling System Integrated with
Latent Heat Storage, August 2011
[31] Owura Kofi Amoabeng, (2012), BSc. Mechanical Engineering, “Assessing The
Feasibility of a Solar Water Heating System Based on Performance and Economic
Analysis”.
[32] Gravely. B, (2012), “Optimal Design in Solar Hot Water Systems”. Certified Solar
Thermal Installer, North American Board of Certified Energy Practitioners
[33] Andy Walker, PhD PE, (2013),"Solar Energy Technologies and Project Delivery for
Buildings". John Wiley & Sons, Inc., Hoboken, New Jersey.
113
APPENDIX A
SANA’A WEATHER DATA
12 3.8 5.0 -18.0 1.0 16.1 -14.8 1.3 17.6 7.5 20.5 7.1 20.1 1.0 220
6 12.9 30.2 12.6 29.9 12.5 29.2 12.4 16.6 22.3 16.1 22.0 15.7 22.0 5.0 40
15.0 14.0 18.3 14.2 13.2 18.4 13.7 12.9 18.4 55.7 22.3 54.0 22.2 52.4 22.0 18.9
8.2 7.2 6.3 DB N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
WB -3.6 17.8 1.8 0.7 -4.8 18.3 -5.9 18.8 -6.9 19.2 -8.1 19.7
Wind WSAvg 2.5 2.1 2.2 2.4 2.4 2.7 2.8 2.9 2.8 2.7 2.4 2.1 2.0
PrecAvg 194 2 6 21 43 18 11 30 45 4 8 2 2
Precipitation PrecMax 466 45 91 107 161 155 81 102 174 31 166 19 18
PrecMin 73 0 0 0 0 0 0 0 0 0 0 0 0
114
PrecStd 95 8 16 28 35 29 19 27 36 7 28 5 4
DB 26.2 28.4 28.9 28.9 30.0 31.2 31.2 30.2 29.9 26.1 25.7 25.1
0.4%
MCWB 10.0 11.7 11.6 12.1 12.1 12.9 13.1 13.4 12.8 10.4 10.6 10.6
DB 25.1 27.1 27.8 28.0 29.0 30.2 30.8 29.7 28.9 25.2 24.5 24.0
Monthly Design Dry Bulb and 2% MCWB 9.5 10.8 11.5 11.7 11.8 12.4 12.9 13.3 12.3 10.1 10.6 10.2
Mean Coincident Wet Bulb
Temperatures DB 24.1 26.1 26.8 27.1 28.2 29.9 30.0 29.0 28.0 24.8 23.8 23.1
5%
MCWB 9.7 10.4 11.2 11.6 11.8 12.2 12.6 13.2 12.0 10.0 10.5 9.7
DB 23.1 24.9 25.8 26.1 27.6 29.1 29.1 28.1 27.1 23.9 22.8 22.0
10%
MCWB 9.7 10.5 11.2 11.7 11.7 11.7 12.7 13.3 11.7 9.8 10.2 9.1
WB 13.5 14.2 15.7 16.2 16.7 16.2 17.4 17.2 15.9 14.7 14.0 13.9
0.4%
MCDB 20.9 22.9 22.9 22.0 21.2 23.3 22.6 22.7 22.9 19.1 18.5 22.2
WB 12.3 13.3 14.8 15.5 15.7 15.3 16.6 16.6 15.2 13.5 12.8 13.1
Monthly Design Wet Bulb and 2% MCDB 20.4 21.8 21.8 21.5 21.6 24.0 22.4 22.2 22.7 18.8 19.8 20.6
Mean Coincident Dry Bulb
Temperatures WB 11.7 12.6 14.1 14.8 15.2 14.6 15.9 16.1 14.4 12.0 12.0 12.1
5%
MCDB 20.2 21.5 21.4 21.0 21.3 24.0 22.2 21.6 22.5 21.5 20.0 19.6
WB 10.9 11.9 13.4 14.3 14.5 14.0 15.4 15.7 13.7 10.7 11.3 11.0
10%
MCDB 20.0 21.3 21.0 20.7 21.1 23.8 22.4 21.6 22.6 22.6 20.5 19.4
MDBR 17.1 16.9 15.3 13.8 13.1 12.9 12.1 12.3 13.1 14.1 15.3 17.1
MCDBR 18.0 17.7 16.4 14.8 13.8 13.6 13.0 13.0 13.3 14.6 16.1 17.5
Mean Daily Temperature 5% DB
MCWBR 7.9 7.2 6.5 5.8 5.3 5.3 4.4 4.2 5.1 6.2 7.1 8.0
Range
MCDBR 15.8 16.2 14.1 13.3 12.7 13.0 12.1 12.4 12.7 11.9 14.1 14.9
5% WB
MCWBR 7.2 6.7 5.3 5.0 4.6 5.4 4.2 4.0 5.1 6.2 7.1 8.0
taub 0.332 0.367 0.434 0.452 0.482 0.572 0.647 0.610 0.499 0.375 0.353 0.332
taud 2.383 2.253 2.046 2.013 1.913 1.677 1.581 1.655 1.859 2.207 2.287 2.366
Clear Sky Solar Irradiance
Ebn,noon 961 938 882 861 823 744 692 726 812 917 929 950
Edn,noon 116 138 174 181 197 246 272 255 207 142 126 115
RadAvg 5.62 6.25 6.72 6.89 7.05 6.76 5.83 5.93 6.51 6.54 5.78 5.48
All-Sky Solar Radiation
RadStd 0.17 0.25 0.34 0.29 0.32 0.34 0.26 0.29 0.20 0.20 0.18 0.21
115
APPENDIX B
IMPORTANT TABLES FOR CALCULTIONS
Table B.1 Cooling Load Temperature Difference(CLTD), for convection heat gain rate
for glass windows
Table B .1
CLTDs for glass (From ASHRAE, 1989, with permission.)
The units are degrees fahrenheit; to convert to kelvins, multiply by 5 / 9
Solar
time,
h CLTD, °F
1 1
2 0
3 -1
4 -2
5 -2
6 -2
7 -2
8 0
9 2
10 4
11 7
12 9
13 12
14 13
15 14
16 14
17 13
18 12
19 10
20 8
21 6
22 4
23 3
24 2
116
Table B.2 Latitude-Month correction factor LM, values as applied to flat roofs and walls.
Table B.2
CLTD correction for latitude and months, applied to walls and roofs. (From ASHRAE, 1989, with
permission.)
The units are degrees fahrenheit; to convert to kelvins, multiply by 5 / 9
NE / SE /
Lat. Month N NW E/W SW S HOR
16 Dec -4 -8 -4 4 13 -9
Jan / Nov -4 -7 -4 4 12 -7
Feb / Oct -3 -5 -2 2 7 -4
Mar / Sep -3 -2 -1 0 0 -1
Apr / Aug -1 -1 -1 -3 -6 0
May / Jul 4 3 -1 -5 -7 0
Jun 6 4 -1 -6 0 -7
Table B.3 Solar heat gain rate SHG, for sunlit glass windows (W/m2 ), for latitude angle
of 16 0N.
Table B.3
Maximum solar heat gain factor SHG, for sun lighted
glass, north latitudes. (From ASHRAE, 1989, with permission.)
The units are Btu / ( h ft2 ); to convert to W/m2, multiply by 3.155
16°
117
Table B.4 Shading coefficient SC (W/m2. K), for glass windows with interior shading.
Table B.4
Shading coefficient SC and solar transmissivity t for several
conventional glazing types, for winter and summer conditions
(From ASHRAE, 1989, with permission.)
Nominal thickness
Type of glazing SC
of each pane
mm in Winter Summer
Single Glazing
Clear 3 1/8 0.86 1 1
6 1/4 0.78 0.94 0.95
10 3/8 0.72 0.9 0.92
13 1/2 0.67 0.87 0.88
Double glazing
Clear out, clear in 3 1/8 0.71 0.88 0.88
6 1/4 0.61 0.81 0.82
Heat-absorbing out, clear in 6 1/4 0.36 0.55 0.58
Table B.5 The cooling load factor CLF, for glass windows with interior shading
118
Table B.6 Cooling load factor due to occupants (CLF), for sensible heat gain rate.
119
Table B.8 Instantaneous heat gain rate due to occupants in units of wattes per person
120
TABLE B.9 Inside flim resistance Ri, for different material type and heat directions.
TABLE B.10 Outside film resistance Ro, for different material type and wind speeds
121
TABLE B.11 Values of overall heat transfer coefficient Ug, for glass windows, W/m2.k
TABLE B.12 Lighting Power Densities Using the Building Area Method
(source: ANSI/ASHRAE STANDARD 90.1-1999)
122
Table B.13 Laboratory Equipment
(Source: The 2017 ASHRAE Handbook—Fundamentals SI).
123
Table B.15 Ventilation Design Parameters
(source: HVAC Design Manual for Hospitals and Clinics Second Edition).
124
Table B.17 Guide for Selecting Low-Pressure System Friction Rate
Table B.18 : Minimum Duct Insulation R-Value,a Cooling and Heating Only Supply
Ducts and Return Ducts
125
Table B.19: Minimum Duct Insulation R-Value,a Combined Heating and Cooling Supply
Ducts and Return Ducts
126
Table B.21: FGI Limits for background Noise [source: HVAC DESIGN MANUAL FOR
HOSPITALS AND CLINICS 2nd edition]
127