You are on page 1of 2

Blokset

Low Voltage Switchboard for High Dependability







• •
-

• ·1

I

• •
•L __._,

Sc~fleider
CF Electric
Busbars

IP ≤ 42
Flat copper busbars
Values given for copper tin:
a) Standard architecture

Profile Cross-section /ph Outside ambient temperature (°C)


35 40 45 50
1b x 60 x 5 (1) 900 850 800 750
2b x 60 x 5 (1) 1550 1500 1400 1300
1b x 80 x5 1150 1100 1050 1000
1b x 100 x 5 1250 1200 1100 1050
1b x 125 x 5 1600 1500 1400 1300
2b x 80 x 5 1850 1800 1700 1600
2b x 100 x 5 2250 2100 2000 1900
2b x 125 x 5 2700 2500 2400 2200
3b x 100 x 5 2850 2700 2600 2400
3b x 125 x 5 3400 3250 3050 2850
4b x 100 x 5 3450 3300 3100 2900
4b x 125 x 5 4000 3750 3550 3350
5b x 100 x 5 (2) 3650 3500 3400 3100
5b x 125 x 5 4300 4100 3850 3600
2 x 3b x 100 x 5 5300 5050 4800 4500
2 x 4b x 100 x 5 6200 5900 5650 5300
2 x 5b x 100 x 5 6500 6500 6100 5700

(1) As an option, busbar 63 x 5 can be used.


(2) This solution is not optimized, better to use 4 x 125 x 5.

b) Double front architecture

Profile Cross-section /ph Outside ambient temperature (°C)


35 40 45 50
(2b + 2b) x 60 x 5 (3) 3100 3000 2800 2600
(2b + 2b) x 80 x 5 3700 3600 3400 3200
(2b + 2b) x 100 x 5 4500 4200 4000 3800
(3b + 3b) x 100 x 5 5300 5050 4800 4500
(4b + 4b) x 100 x 5 6200 5900 5650 5300
(5b + 5b) x 100 x 5 6500 6500 6100 5700

(3) For NW12, 16 and 20, the minimum cross-section to be maintained is 2 x 2b x 60 x 5.