SITRANS P, Series DS III

7MF4*.33-...

Transmitters for Pressure, Differential Pressure and Flow, Filling Level,


Absolute pressure from differential pressure series, absolute pressure from
pressure series, series DS III

Instruction Manual

SITRANS P, Series DS III


A5E00047092-01 1
SITRANS P, Series DS III
2 A5E00047092-01
Table of Contents

General Information ..................................................................................................... 7

1 Technical description ............................................................................................... 11

1.1 Application Range ...................................................................................................... 11


1.1.1 Pressure ..................................................................................................................... 12
1.1.2 Differential pressure and flow ..................................................................................... 12
1.1.3 Filling level .................................................................................................................. 13
1.1.4 Absolute pressure ....................................................................................................... 13
1.2 Design and functional principle ................................................................................... 14
1.2.1 Design ........................................................................................................................ 14
1.2.2 Mode of operation ....................................................................................................... 17
1.2.2.1 Mode of operation of the electronics .......................................................................... 17
1.2.2.2 Pressure ..................................................................................................................... 19
1.2.2.3 Differential pressure and flow ..................................................................................... 19
1.2.2.4 Filling level .................................................................................................................. 20
1.2.2.5 Absolute pressure from the differential pressure series ............................................. 20
1.2.2.6 Absolute pressure from the pressure series ............................................................... 21

2 System integration ................................................................................................... 23

2.1 System configurations ................................................................................................ 23


2.2 SIMATIC PDM ............................................................................................................ 24

3 Local operation and display .................................................................................... 25

3.1 General operating instructions .................................................................................... 25


3.1.1 Digital display ............................................................................................................. 26
3.1.2 Measured value representation .................................................................................. 26
3.1.3 Unit display/bargraph .................................................................................................. 27
3.1.4 Error signaling ............................................................................................................ 28
3.1.5 Signal range ............................................................................................................... 28
3.1.6 Mode display .............................................................................................................. 29
3.2 Operation with the keyboard ....................................................................................... 29
3.2.1 Cancel keyboard disable and write protection ............................................................ 31

SITRANS P, Series DS III


A5E00047092-01 3
3.2.2 Set/adjust start of scale, full scale .............................................................................. 31
3.2.2.1 Theoretical relationships ............................................................................................. 31
3.2.2.2 Practical application .................................................................................................... 34
3.2.3 Electric damping ......................................................................................................... 35
3.2.4 Blind setting of start of scale and full scale ................................................................. 35
3.2.4.1 Theoretical relationships ............................................................................................. 35
3.2.4.2 Practical application .................................................................................................... 36
3.2.5 Zero adjustment (position correction) ......................................................................... 37
3.2.6 Current transmitter ...................................................................................................... 38
3.2.7 Failure current ............................................................................................................ 38
3.2.8 Key and/or function disable ........................................................................................ 39
3.2.9 Flow measurement (only differential pressure) .......................................................... 40
3.2.10 Measured value display .............................................................................................. 42
3.2.11 Selection of unit of pressure ....................................................................................... 42

4 Local operation without display or with activated keylock .................................. 45

4.1 Set start of scale, full scale ......................................................................................... 45

5 Functions/Operation by HART ................................................................................ 47

5.1 Measuring point data .................................................................................................. 47


5.2 Measuring operation ................................................................................................... 48
5.3 Setting start of scale, full scale ................................................................................... 48
5.4 Blind setting of start of scale and full scale ................................................................. 48
5.5 Zero adjustment (position correction) ......................................................................... 48
5.6 Electric damping ......................................................................................................... 49
5.7 Fast measured value acquisition (fast response mode) ............................................. 49
5.8 Current transmitter ...................................................................................................... 49
5.9 Fault current ............................................................................................................... 49
5.10 Setting the current limits ............................................................................................. 50
5.11 Disabling of input keys and write protection ............................................................... 51
5.12 Measured value display .............................................................................................. 51
5.13 Selection of unit of pressure ....................................................................................... 51
5.14 Display/bargraph ........................................................................................................ 52
5.15 Sensor adjustment ...................................................................................................... 52
5.15.1 Trimming the lower sensor adjustment point .............................................................. 52
5.15.2 Trimming the upper sensor adjustment point ............................................................. 53
5.16 Current transmitter adjustment ................................................................................... 53
5.17 Factory calibration ...................................................................................................... 55
5.18 Static configuration data ............................................................................................. 55
5.19 Flow measurement (only differential pressure) .......................................................... 55
5.20 Diagnostic functions ................................................................................................... 56
5.20.1 Operating hours counter ............................................................................................. 56
5.20.2 Calibration timer/service timer .................................................................................... 56
5.20.3 Slave pointer ............................................................................................................... 57
5.20.4 Limit value components .............................................................................................. 58
5.20.4.1 Monitoring the current saturation ................................................................................ 58
5.21 Simulation ................................................................................................................... 59
5.21.1 Simulation as a fixed value ......................................................................................... 60
5.21.2 Simulation with a ramp function .................................................................................. 60
5.22 Relationships .............................................................................................................. 61

SITRANS P, Series DS III


4 A5E00047092-01
6 Modular design ......................................................................................................... 61

6.1 Practical application .................................................................................................... 62


6.1.1 Exchanging the electronics ......................................................................................... 62

7 Installation ................................................................................................................. 63

7.1 Installation (except filling level) ................................................................................... 63


7.1.1 Mounting without mounting bracket ............................................................................ 64
7.1.2 Mounting with mounting bracket ................................................................................. 64
7.2 Mounting ”filling level” ................................................................................................. 66
7.2.1 Installation .................................................................................................................. 66
7.2.2 Connecting the low pressure line ............................................................................... 66
7.3 Rotating the measuring cell in relation to the housing ................................................ 68
7.4 Electrical Connection .................................................................................................. 70
7.4.1 Connection to screw terminals ................................................................................... 71
7.4.2 Connection with plug .................................................................................................. 72
7.5 Turn digital display ...................................................................................................... 73

8 Commissioning ......................................................................................................... 75

8.1 Pressure, absolute pressure from differential pressure


series and absolute pressure from pressure series .................................................... 76
8.1.1 Measuring gases ........................................................................................................ 77
8.1.2 Measuring vapor and liquid ........................................................................................ 78
8.2 Differential pressure and flow ..................................................................................... 79
8.2.1 Measuring gases ........................................................................................................ 80
8.2.2 Measuring liquids ........................................................................................................ 81
8.2.3 Measuring vapor ......................................................................................................... 82

9 Technical Data .......................................................................................................... 83

9.1 Measuring spans and overload limits ......................................................................... 88


9.1.1 Pressure ..................................................................................................................... 88
9.1.2 Differential pressure and flow ..................................................................................... 88
9.1.3 Absolute pressure from the pressure series ............................................................... 89
9.1.4 Absolute pressure from the differential pressure series ............................................. 89
9.1.5 Filling level .................................................................................................................. 89
9.2 Dimensions ................................................................................................................. 90

10 Care and maintenance ............................................................................................. 95

11 Ordering data ............................................................................................................ 97

12 Certificates .............................................................................................................. 111

12.1 EC Declaration of Conformity ................................................................................... 112

13 Index ........................................................................................................................ 113

14 Appendix ................................................................................................................. 115

SITRANS P, Series DS III


A5E00047092-01 5
SITRANS P, Series DS III
6 A5E00047092-01
General Information

Warning

means that failure to take the necessary safety precautions may lead to death,
serious injury and/or considerable material damage.
Caution!

means that failure to take the necessary safety precautions can lead to minor
injury and/or material damage.

+
Note

is an important information about the product itself, the handling of the product or
that part of the manual to which special attention is to be drawn.

SITRANS P, Series DS III


is a Siemens trademark.

The other names in this manual may be tradenames. If used by third parties for own purposes, this could
violate owner’s rights.

SITRANS P, Series DS III


A5E00047092-01 7
+
Note

Dear customer,

You have purchased a modular device in which you can exchange the electronics.
In the event of an exchange, please observe the instructions enclosed with the
component to be exchanged.

For reasons of clarity the manual does not contain detailed information about all
types of products and cannot take into account every conceivable case of
installation, operation or maintenance.

If you require further information or should problems occur which are not sufficiently
explained in the manual, you can consult your local Siemens branch to obtain the
necessary information.

May we also draw your attention to the fact that the contents of the manual are not
part of a previous or existing agreement, approval or legal relationship or an
amendment thereof. All obligations of the Siemens AG result from the contract of
purchase which also contains the full and solely valid warranty agreement. These
contractual warranty conditions are neither extended nor restricted by the contents
of the manual.

The contents reflect the technical state at the time of going to print. They are subject
to technical modifications in the course of further development.

Qualified Personnel

are persons familiar with the installation, assembly, commissioning and operation of
the product and who have the appropriate qualifications for their activities such as:

• training or instruction or authorization to operate and maintain devices/systems


according to the standard of safety technology for electrical circuits, high
pressures and corrosive media.
• training or instruction according to the standards of safety engineering in the care
and use of suitable safety equipment.
• training in first aid

SITRANS P, Series DS III


8 A5E00047092-01
Warning!
This device may only be assembled and operated after qualified personnel has
ensured, by providing suitable power supplies, that no hazardous voltages can get
into the device in normal operation or in the event of a failure of the system or parts
thereof.

Explosion-proof devices may only be opened when the power is off (to be
observed especially in Chapter 6 and Chapter 7).

Intrinsically safe devices lose their license as soon as they are operated on circuits
which do not meet the requirements of the EC test certificate (to be observed
especially in Chapter 7).

The device may be operated with high pressure and corrosive media. Therefore
serious injuries and/or considerable material damage cannot be ruled out in the
event of improper handling of the device.

The perfect and safe operation of this equipment is conditional upon proper
transport, proper storage, installation and assembly as well as on careful operation
and commissioning.

The equipment may only be used for the purposes specified in this instruction
manual.

All modifications to the device require the express approval of the manufacturer.

Caution!

Modules which are sensitive to electrostatic charge may be destroyed by voltages


which are far below the human level of perception. These voltages occur already
when you touch a component or electrical connections of a module without first
discharging yourself electrostatically. The damage incurred by a module as a
result of an overvoltage is not usually immediately perceptible but only becomes
noticeable after a long time in operation.

SITRANS P, Series DS III


A5E00047092-01 9
SITRANS P, Series DS III
10 A5E00047092-01
7HFKQLFDOGHVFULSWLRQ


+
1RWH

The transmitter must warm up for about 5 minutes after switching on the power in
order to obtain stable measured values.

 $SSOLFDWLRQ5DQJH

The SITRANS P, Series DS III transmitter measures the pressure, the differential
pressure, the absolute pressure or the filling level of non-corrosive and corrosive
gases, vapors and liquids depending on the version. The output signal is a load-
independent direct current of 4 to 20 mA.

Transmitters with intrinsic safety and explosion-proof degrees of protection can be


used in areas where there is an explosion hazard (zone 1). The devices have EC test
certification and fulfil the appropriate harmonized European standards of CENELEC.

The transmitters are available with remote seals of different designs for special
applications, e.g. measuring high viscous substances.

The transmitter can be parameterized locally with three input keys or externally via
HART. The following table describes the basic parameters. Other parameters are
accessible via HART for special applications.

SITRANS P, Series DS III


A5E00047090-01 11
Technical description

Table 1 Basic parameters

Parameter Parameterization Parameterization


by input keys by HART

Start of scale yes yes

Full scale yes yes

Electric damping yes yes

Blind setting of start of scale yes yes

Blind setting of full scale yes yes

Zero adjustment (position correction) yes yes

Current transmitter yes yes

Fault current yes yes

Keyboard disable and write protection yes yes, except cancel


write protection

Type of unit, unit yes yes

Characteristic (lin., squ.) yes * yes *

* differential pressure only

You will find a description of the listed parameters in Chapter 3 and Chapter 5

1.1.1 Pressure

This version of the device measures the pressure of non-corrosive and corrosive
gases, vapors and liquids. Measuring spans between 0.01 mbar and 400 bar are
possible.

1.1.2 Differential pressure and flow

This version of the device is used to measure

• the differential pressure, e.g. the active pressure,


• of a small positive or negative excess pressure,
• of the flow q ~ ∆p (together with a flow control valve)
• of non-corrosive and corrosive gases, vapors and liquids.

Measuring spans between 1 mbar and 30 bar are possible.

SITRANS P, Series DS III


12 A5E00047092-01
Technical description

1.1.3 Filling level

This version of the device with mounting flange measures the filling level of non-
corrosive and corrosive liquids in open and closed containers. Measuring spans
between 25 mbar and 5 bar are possible. The nominal diameter of the mounting
flange is DN 80 or DN100 or 3 or 4 inch.

In the filling level measurement on an open container the low pressure connection of
the measuring cell remains open (measurement ”compared to atmospheric”), in the
measurement on a closed container this connection is usually connected to the
vessel to compensate the static pressure.

The wetted parts are made of different materials (see Chapter 9) according to the
required corrosion resistance.

1.1.4 Absolute pressure

This version of the device measures the pressure of non-corrosive and corrosive
gases, vapors and liquids.

There are two series: one ”differential pressure” series and one ”pressure” series.
The ”differential pressure series” is characterized by a high overload capacity.

Measuring spans between 8.3 mbar and 30 bar are possible.

SITRANS P, Series DS III


A5E00047092-01 13
Technical description

1.2 Design and functional principle

The SITRANS P, Series DS III transmitter is ready for operation immediately after
installation (Chapter 7). The settable measuring span corresponds to the
specification on the rating plate (see Figure 1). If a customized setting is made at the
factor, the start of scale and full scale are specified on the measuring point plate.

If necessary, the parameters can also be changed during commissioning (Chapter


9) by simple operating procedures.

1.2.1 Design

The device consists of different components depending on what the customer has
specified in the order. The possible variants are listed in Chapter 11.

The rating plate (Figure 1 and 1, Figure 3) with the order number is on the side of
the housing. You can determine the optional constructional details and the possible
measuring range (physical properties of the built-in sensor element) with the
specified number and specifications in Chapter 11.

1 Order number (MLFB number)


2 Serial number

1
2

Figure 1 Example of a rating plate

SITRANS P, Series DS III


14 A5E00047092-01
7HFKQLFDOGHVFULSWLRQ

Opposite it is the license plate (Figure 2 and 4 Figure 4). This contains information
about the hardware and firmware versions among other things.

FW xx.yy.zz HW:xx.yy.zz

Compatibility mark
Product version connection board
Product version measuring cell
FW version
Document revision
Device type

Figure 2 Example of a license plate

The electronics housing is made of diecast aluminum or stainless steel precision


casting. There is an unscrewable, round cover on the front and rear. The front cover
(4, Figure 3) can be designed as a window in order to be able to read measured
values directly from the digital display. The inlet (2, Figure 3) to the electrical
connection box is located on the side, either left or right. The opening which is not
used is sealed by a blanking plug (e.g. 5, Figure 4). The PE conductor terminal
(2, Figure 4) is mounted at the front of the housing.

The electrical connection box is accessible for power supply and screen when
the rear cover (1, Figure 4) is removed. The bottom part of the housing contains
the measuring cell with process connection (8, Figure 3). This is secured turning by
a locking screw (7, Figure 3). The modular concept of the SITRANS P, Series DS III
allows the measuring cell and electronics to be exchanged as required. The set
paramter data are retained. The procedure for exchanging the electronics is
explained in Chapter 6.

At the top of the housing you can see a plastic cover (3, Figure 3) which can be
opened. The input keyboard is beneath this.

SITRANS P, Series DS III


A5E00047090-01 15
Technical description

1 Rating plate
3
2 Inlet with cable gland
3 Plastic access cover
to the input keys
4 Unscrewable cover, optional with window
5 Digital display
2
6 Measuring point plate
7 Locking screw
8 Process connection 4

1 5

Figure 3 Front view of the device Transmitter SITRANS P, Series DS III, pressure series

1 Unscrewable
cover for access to
electrical connection
box
2 PE conductor
connection
3 Alternative 1 Electrical connection box
measuring point plate 5
4 License plate
5 Blanking plug

2
4 3

Figure 4 Rear view of device Transmitter SITRANS P, Series DS III, pressure series

SITRANS P, Series DS III


16 A5E00047092-01
Technical description

1.2.2 Mode of operation

This chapter describes how the transmitter operates and what protection and safety
measures you need to observe. First of all the electronics are described on a
functional diagram level, then the sensors used for the individual measuring modes
in the various device versions.

The process variable to be measured is referred to generally in the sections which


follow as the input variable.

1.2.2.1 Mode of operation of the electronics

The sensor signal is amplified by an instrument amplifier (2) and converted into a
digital signal in an analog-digital converter (3). This is evaluated in a microprocessor,
its linearity and temperature behavior corrected and converted into the 4-20 mA
output current in a digital-analog converter (5). A diode circuit (10) provides reverse
polarity protection. An external display (voltage drop < 0.5 V) can also be connected
here. The measuring cell-specific data of the electronics and the data for transmitter
parameterization are stored in two non-volatile memories (6).

You can parameterize the transmitter directly at the measuring point with the three
input keys (8) and view measuring results, error messages and modes of operation
on the digital display (9). The HART modem (7) enables parameterization by a
protocol according to HART specifications.

SITRANS P, Series DS III


A5E00047092-01 17
Technical description

8 9

2 3 4 5 10

A mc D IA , UH
D A

HART modem
7
EEPROM

EEPROM
1 Sensor Electr.
Cell

1 Sensor of the measuring cell


2 Instrument amplifier
3 Analog-digital converter
4 Microcontroller
5 Digital-analog converter
6 Two non-volatile memories in the measuring cell and in the electronics
7 HART modem
8 Three input keys (local operation)
9 Digital display
10 Connection for external ammeter
IA Output current
UH Power supply

Figure 5 Principle representation of the transmitter SITRANS P, Series DS III, electronics

SITRANS P, Series DS III


18 A5E00047092-01
Technical description

1.2.2.2 Pressure

The pressure pe is fed in through the process connection (3, Figure 6) of the
measuring cell (2). It is passed further through the seal diaphragm (4) and the filling
liquid (5) to the silicon pressure sensor (6) and its measuring diaphragm flexes as a
result. Four piezo-resistors in bridge circuit doped in the measuring diaphragm
change their resistance as a result. The change in resistance causes a bridge output
voltage proportional to the input pressure.

The transmitters with measuring spans ≤ 63 bar measure the input pressure
compared with atmospheric, those with measuring spans ≥ 160 bar compared with a
vacuum.

1 Reference pressure
2 Measuring cell
3 Process connection
4 Seal diaphragm 1
5 Filling liquid
6
6 Silicon pressure sensor
pe Input variable pressure 5 2

4
3
pe

Figure 6 Pressure measuring cell, functional diagram

1.2.2.3 Differential pressure and flow

The differential pressure is transmitted via the seal diaphragms (7, Figure 7) and the
filling liquid to the silicon pressure sensor (5). On exceeding the measuring limits, the
overload diaphragm (6) flexes until one of the seal diaphragms (7) comes into
contact with the body of the measuring cell (4) and protects the silicon pressure
sensor (5) against overloading. The seal diaphragm is deflected by the resulting
differential pressure. Four piezo-resistors in bridge circuit doped in the measuring
diaphragm change their resistance as a result. The change in resistance causes a
bridge output voltage proportional to the differential pressure.

1 Input pressure P +
2 Process flange
3 O-ring
9
4 Body of the measuring cell
5 Silicon pressure sensor 8 1
7 2
6 Overload diaphragm
7 Seal diaphragm
8 Filling liquid 6 5 4 3
9 Input pressure P-

Figure 7 Measuring cell for differential pressure and flow, functional diagram

SITRANS P, Series DS III


A5E00047092-01 19
Technical description

1.2.2.4 Filling level

The input pressure (hydrostatic pressure) acts through the seal diaphragm (10,
Figure 8) at the mounting flange hydraulically on the measuring cell. The differential
pressure applied at the measuring cell is transmitted via the seal diaphragms (6) and
the filling liquid (7) to the silicon pressure sensor (3). On exceeding the measuring
limits, the overload diaphragm (5) is deflected until one of the seal diaphragms (6)
comes into contact with the body of the measuring cell (4) and protects the silicon
pressure sensor (3) against overloading. The measuring diaphragm is flexed by the
differential pressure. Four piezo-resistors in bridge circuit doped in the measuring
diaphragm change their resistance as a result. The change in resistance causes a
bridge output voltage proportional to the differential pressure.

1 Process flange
2 O-ring
8 9
3 Silicon pressure sensor
4 Body of the measuring cell
5 Overload diaphragm
6 Seal diaphragm at the measuring cell
7 Filling liquid of the measuring cell 7
10
8 Capillary tube with filling liquid of the 6
mounting flange
9 Flange with tube
10 Seal diaphragm at the mounting 5 3 4 2 1
flange

Figure 8 Measuring cell for filling level, functional diagram

1.2.2.5 Absolute pressure from the differential pressure series

The absolute pressure is transmitted via the seal diaphragm (6, Figure 9) and the
filling liquid (7) to the silicon pressure sensor (3). On exceeding the measuring limits,
the overload diaphragm (5) is deflected until the seal diaphragm (6) comes into
contact with the body of the measuring cell (4) and protects the silicon pressure
sensor (3) against overloading. The pressure difference between the input pressure
(pe) and the reference pressure (8) on the low pressure side of the measuring cell
flexes the measuring diaphragm. Four piezo-resistors in bridge circuit doped in the
measuring diaphragm change their resistance as a result. The change in resistance
causes a bridge output voltage proportional to the absolute pressure.

1 Process flange
2 Seal diaphragm at the measuring Pe
cell 8
3 O-ring 1
7
4 Body of the measuring cell
2
5 Silicon pressure sensor
6 Overload diaphragm
7 Filling liquid of the measuring cell 6 5 4 3
8 Reference pressure
pe Input variable pressure

Figure 9 Measuring cell for absolute pressure, functional diagram

SITRANS P, Series DS III


20 A5E00047092-01
Technical description

1.2.2.6 Absolute pressure from the pressure series

The pressure is transmitted via the seal diaphragm (3, Figure 10) and the filling liquid
(4) to the absolute pressure sensor (5) and flexes its measuring diaphragm. Four
piezo-resistors in bridge circuit doped in the measuring diaphragm change their
resistance as a result. The change in resistance causes a bridge output voltage
proportional to the input pressure.

1 Measuring cell
2 Pressure connection
3 Seal diaphragm
4 Oil filling
5 Absolute pressure sensor 5
pe Input variable pressure 1
4

3
2
pe

Figure 10 Measuring cell for absolute pressure from pressure series, functional diagram

SITRANS P, Series DS III


A5E00047092-01 21
Technical description

SITRANS P, Series DS III


22 A5E00047092-01
System integration
2
2.1 System configurations

The SITRANS P, Series DS III transmitter can be used in a number of system


configurations. as a stand-alone version, supplied with the necessary power and as
part of a complex system environment e.g. SIMATIC S7.

All basic settings (see Table 3) can be made directly on the device with three
input keys. The full scope of communication is available via HART (online
parameterization).

Communication via the HART interface can take place optionally with:

• HART Communicator
• HART modem with following PC/laptop on which suitable software such as
SIMATIC PDM is available
• a HART-capable control system (e.g. SIMATIC S7 with ET 200M)

SITRANS P, Series DS III


A5E00047092-01 23
System integration

S7 400

ET 200M
SIMATIC PDM

Control system

or

. . .
. . .
+ A +
- -
Load
SITRANS P Power supply
transmitter,
series DS III

HART HART PC/laptop with


communi- modem RS-232-C Simatic PDM
cator or

Figure 11 Possible system configurations

2.2 SIMATIC PDM

SIMATIC PDM is a software package for configuring, parameterizing,


commissioning, diagnosing and maintaining SITRANS P, Series DS III and other
process devices.

SIMATIC PDM contains a simple process monitoring of the process values, alarms
and status signals of the device.

There are two versions which run under Windows NT or Windows 95/98.

• SIMATIC PDM (stand-alone)


• SIMATIC PDM Integrated

Further information on request.

SITRANS P, Series DS III


24 A5E00047092-01
Local operation and display
3
3.1 General operating instructions

You operate the device with the keys [M], [↑] and [↓] (Figure 16). These are
accessible when you loosen the two screws of the protective cover (3, Figure 3) and
lift it up. The cover must be closed again after operation.

The device is normally in the measured value display mode. You can then select an
option with the [M] key and change a value with [↑] and [↓]. You accept the selected
option or changed value by pressing the [M] key again. Exceptions to this procedure
are described in the explanations of the individual device functions.

It generally applies that:

• If more than 2 minutes have passed since last pressing a key, the setting is saved
and the measured value display is returned to automatically.
• Numerical values are always set from the least significant digit still displayed. In
the case of an overflow in the key repetition mode it switches to the next
significant digit and only this continues to be counted. This procedure serves for
fast rough setting over a wide numeric range. For fine setting you have to release
the desired key ([↑] or [↓]) and press it again. Exceeding of the upper or lower
measured value limits are shown on the display with ↑ or ↓
• The keylock must be released for keyboard operation.
• When you operate the transmitter locally, write accesses via HART are refused
during this time – it is possible to read data, e.g. measured values, at any time.

SITRANS P, Series DS III


A5E00047092-01 25
Local operation and display

3.1.1 Digital display

A plug-in standard display is used for local display of the measured value (1,
Figure 12) with unit (2), sign (6), status (5, 7) and mode (4). The root sign (3) is used
for the device variants ”differential pressure and flow”. Active communication,
e.g. with a HART Communicator, is displayed by flashing of the communication
indicator (8).

1 Measured value 
2 Unit/bargraph
3 Root display (flow) 
4 Mode/key disable
5 Lower current limit reached 
6 Sign for measured value

7 Upper current limit reached
8 Communication indicator 

  

Figure 12 Structure of the digital display

3.1.2 Measured value representation

In the measured value representation, the current output by the transmitter, the
percentage pressure value related to the set range or the measured value in a
selectable physical unit are shown depending on the customer setting.

Status display

Table 2 Meaning of the arrow indicators

Operating mode (7, Figure 12) (5, Figure 12)

Mode 2 (set MA*) on exceeding the upper on dropping below the lower
current limit value current limit value

Mode 3 (set ME*) on exceeding the upper on dropping below the lower
current limit value current limit value

Mode 4 (set damping) on exceeding the upper on dropping below the lower
damping value damping value

Mode 5 (set MA blind) on exceeding the upper on dropping below the lower
sensor limit sensor limit

Mode 6 (set ME blind) on exceeding the upper on dropping below the lower
sensor limit sensor limit

SITRANS P, Series DS III


26 A5E00047092-01
Local operation and display

Table 2 Meaning of the arrow indicators (contd.)

Operating mode (7, Figure 12) (5, Figure 12)

Mode 7 (position on exceeding the max. span


correction) by more than 5 %

Mode 12 (root application on exceeding the root on dropping below the root
point) application point of 15 % application point of 5 %

Keyboard operation if the span to be set if the span to be set


(mode 2, 3, 5, 6) becomes greater than the becomes smaller than the
maximum span minimum span

Normal operation Current exceeds the upper Current drops below the
saturation limit Pressure lower saturation limit.
exceeds the upper sensor Pressure drops below the
limit lower sensor limit.

* MA = start of scale, ME = full scale

Communication indicator

HART communication active.

3.1.3 Unit display/bargraph

The unit display consists of five 14-segment fields to represent the type of unit as a
percentage, physical unit or current value. A bargraph which represents the percentage
pressure value in the range from 0 to 100% can be displayed alternately with the unit. The
”bargraph” function is switched off in the standard setting.

or

Figure 13 Examples of measured value display in ”Unit” and ”Bargraph” display types.

SITRANS P, Series DS III


A5E00047092-01 27
Local operation and display

3.1.4 Error signaling

If hardware or software errors occur in the transmitter, the ”Error” message appears
in the measured value display.

A message text runs through the unit display indicating the type of error. This
diagnostic information is also available via HART.

Figure 14 Error message, example ”Senso(r)”

3.1.5 Signal range

The output signal is divided into defined areas (Figure 18).

The transmitter converts the measured pressure into an output current which is
normally in the range from 4 mA (start of scale) to 20 mA (full scale).

Measured values below and above the range limits are displayed correctly when the
measuring limits are exceeded. The ”UNDER” message or ”OVER” message for the
selected unit appears alternately in place of the bargraph. The possible overflow
range can be set via HART. If the upper or lower range limits are exceeded, the
output current remains constant. "↑" or "↓" appears on the digital display.

+
Note

The setting of the overflow range and fault current range can be selected freely by
HART (see Chapter 5, ”Functions/Operation by HART”). Useful setting possibilities
are shown in Figure 24.

SITRANS P, Series DS III


28 A5E00047092-01
Local operation and display

3.1.6 Mode display

The currently selected mode is shown in the mode display. In the following example
(Figure 15) a damping of 0.2 s has been set in mode 4.

Figure 15 Example of a mode display

3.2 Operation with the keyboard

The transmitter can be parameterized locally with the keyboard (Figure 16). You can
select and execute all the functions described in the Table 3 with settable modes
(M-key). These are available in an extended scope of functions via HART (see
Chapter 5).

3 4 5

1
SPAN

1)
M
ZERO

Symbols for
input keys
(see flange)
1 Digital display
2 Connecting plug
for digital display
3 Mode key
4 Increment key
5 Decrement key 2

1) Keyboard operation without display see Chapter 4

Figure 16 Position of the keyboard (three input keys) and digital display

SITRANS P, Series DS III


A5E00047092-01 29
Local operation and display

Table 3 Summary of operating functions with keys


Function Mode Key function Display, explanations Chap.

M 1) [↑] [↓] [↑] and [↓]


Measured value Output current in mA or % or input 3.2.10
pressure in unit of pressure
Error display Error, if transmitter disturbed 3.2.7
Moving text indicating reason for
disturbance
Start of scale 2 Current Current Set to 4 mA Output current in mA 3.2.2
greater smaller
Full scale 3 Current Current Set to 20 mA Output current in mA 3.2.2
greater smaller
Electric damping 4 Damping Damping Time constant T63 in s 3.2.3
greater smaller Parameter range: 0,0...100,0
Start of scale 5 Pressure Pressure Set to start of Start of scale in the selected unit of 3.2.4
”Blind setting” greater smaller scale 0 pressure
Full scale 6 Pressure Pressure Set to upper Full scale in the selected unit of 3.2.4
”Blind setting” greater smaller measuring pressure
limit
Zero adjustment 7 -- -- Execute Vent transmitter (pressure, 3.2.5
(position differential pressure, flow, filling level)
correction) 2) or evacuate (absolute pressure,
< 0.1 ‰ of the measuring span)
(start of scale remains unaffected)
measured value in unit of pressure
Current 8 Current Current Switch on Const. output current in mA 3.2.6
transmitter greater smaller 3.6 - 4.0 - 12.0 - 20.0 or 22.8
switch off by [M]-key
Output current in 9 Change between the two -- Selected output current 3.2.7
the event of an values Possible: fault current limits set by
error user
Keys and/or 10 Change between the five -- 0 = none 3.2.8
function disable functions LA = all disabled
LO = all disabled except start of scale
LS = all disabled except start of scale
and full scale
L = write protection
Operation by HART not possible.
Characteristic, 11 Change between the three -- lin = linear 3.2.9
differential functions srlin = square rooting (linear up to
pressure only application point)
sroff = square rooting (switched off
up to application point)
Application point 12 greater smaller -- Parameter range 5 to 15 % flow 3.2.9
of the square
rooting
characteristic,
differential
pressure only
Measured value 13 Select from three possibilities Unit of pressure (input value) or 3.2.10
display output current in mA or %
Unit of pressure 14 Select according to Figure 23 Technical units of pressure 3.2.11

1) Change mode by pressing the [M] key


2) ATTENTION: The start of scale is in a vacuum in absolute pressure transmitters! The Zero
adjustment in ventilated transmitters leads to misadjustments!

The operations of the device necessary for parameterization are described in detail
in Chapter 3.2.2, pg. 31 to Chapter 3.2.11, pg. 42.
SITRANS P, Series DS III
30 A5E00047092-01
Local operation and display

3.2.1 Cancel keyboard disable and write protection

You can cancel a set keyboard disable (LA, LO, LS) or a write protection for HART
(L) with the input keys. To do this, press the [M] key for 5 s.

Another keyboard disable (LL) is possible in HART (see Table 6; pg. 51)

3.2.2 Set/adjust start of scale, full scale

You can set or adjust the start of scale and full scale with the input keys. Modes 2
and 3 from Table 3 are available for this. This allows implementation of rising or
falling characteristics.

3.2.2.1 Theoretical relationships

Setting

In setting, a desired start of scale and/or a desired full scale is assigned to the
standard current values (4 mA/20 mA). Prerequirements: Two reference pressures
(pr1, pr2) provided by the process or generated by a pressure transmitter. After
setting, the measuring span specified on the measuring point plate may no longer
match the setting.

A turn-down up to a maximum 1:100 (span ratio = r, turn down) can be reached


depending on the series and measuring range.

+
Note

The measuring span is not changed by setting the start of scale. By setting the full
scale the start of scale remains unchanged, you should therefore set the start of
scale first, then the full scale.

The relationship between the measured pressure and the generated output current
is linear (exception: square rooting characteristic in differential pressure
transmitters). You can calculate the output current with the following equation
(Figure 17).

I = output current
p = pressure p - MA
I= * 16 mA + 4 mA
MA = start of scale
ME - MA
ME = full scale

Figure 17 Equation for calculating the current

SITRANS P, Series DS III


A5E00047092-01 31
Local operation and display

0 16 bar

A Initial situation 4 20 mA

0 2 16 bar

B Set start of scale 4 18 20 mA

0 2 11 14 16 bar

4 16 20 mA
C Set full scale

D Calculate output current I=


11 bar - 2 bar
* 16 mA + 4 mA = 16 mA
14 bar - 2 bar

Figure 18 Example, set start of scale and full scale, calculate output current

Explanations to the example (Figure 18):

A: Given a transmitter with a measuring span of 0 to 16 bar. Set to a measuring


span of 2 to 14 bar.
B: Apply 2 bar process pressure. Set the device to mode 2 with the mode key [M].
The display shows the set mode at the bottom left. Set the start of scale by
pressing the [↑] and [↓] keys on the value for about two seconds. An output
current of 4 mA is then generated at 2 bar input pressure.
C: Apply 14 bar process pressure. Set the device to mode 3 with the mode key [M].
The full scale is set by pressing the [↑] and [↓] keys on the value for about 2
seconds. An output current of 20 mA is then generated at 14 bar input pressure.
D: You can calculate the output current for any input pressure with the specified
equation (Figure 17).

Adjusting

When adjusting, you can assign the start of scale and/or the full scale to any desired
current value using one reference pressure. This function is particularly suitable if the
pressures necessary for start of scale and full scale are unavailable. After adjusting,
the measuring range specified on the measuring point plate may no longer match the
setting.

Requirements: Applied pressure (reference pressure), the set start of scale and full
scale are known.

SITRANS P, Series DS III


32 A5E00047092-01
/RFDORSHUDWLRQDQGGLVSOD\

Using the following equation (Figure 19) you can calculate the current to be adjusted
for the desired start of scale and full scale.

1)
current to be
set at MA nom pref - MAnom
I= * 16 mA + 4 mA
MEact - MAact

1)
current to be p ref - MA nom
set at ME nom I= * 16 mA + 4 mA
ME nom- MAnom

I = output current MEact = old full scale


p = applied reference pressure MAact = old start of scale
ref
MEnom = new full scale
MA nom = new start of scale

1)
To calculate the output currents when seting start of scale and full scale, the reference pressure must
be selected so that a value between 4 and 20 mA is obtained for the current.

Figure 19 Equations for calculating current (set start of scale, full scale)

p
0 ref 11 16 bar
$Initial situation
4 15 20

MAact MAnom MEact


0 2 11 16 bar
%Calculate start of scale
4 set 13 18

MAact MAnom MEnom


0 2 11 14 16 bar
&Calculate full scale
4 set 16 20

Figure 20 Example, set start of scale and full scale

Explanations to the example (Figure 20):

A: Given a transmitter with a measuring span of 0 to 16 bar. Adjust to a measuring


span of 2 to 14 bar. A reference pressure of 11 bar is available.
B: Set the device to mode 2 with the [M] key. Using the equations (Figure 19) first
calculate the current to be adjusted for the desired start of scale (2 bar) at the
applied reference pressure and then adjust it with the [↑] or [↓] (13 mA) keys.
C: Set the device to mode 3 with the [M] key. Using the equations (Figure 19) first
calculate the current to be adjusted for the desired full scale (14 bar) at the
applied reference pressure and then adjust it with the [↑] or [↓] (16 mA) keys.

SITRANS P, Series DS III


A5E00047090-01 33
Local operation and display

3.2.2.2 Practical application

Set start of scale and full scale

The device sets the output current for the start of scale to 4 mA and the full scale to
20 mA when the input keys are pressed according to the following instructions.

• This is how to set the start of scale:


− Apply reference pressure
− Set mode 2
− Set start of scale to 4 mA with [↑] and [↓]
− Save with [M]
• This is how to set the full scale:
− Apply reference pressure
− Set mode 3
− Set full scale to 20 mA with [↑] and [↓]
− Save with [M]

Set start of scale and full scale

If the output current is not set but adjusted continuously, you have to calculate the
currents to be adjusted mathematically (Chapter 3.2.2.1, pg. 31). It is possible to
make an adjustment for the start of scale, the full scale or both values one after the
other.

Warning!
Only certified ammeters may be used in intrinsically safe circuits.

The housing cover may not be unscrewed from ”explosion-proof” transmitters type
in hazardous areas.

• This is how to set the start of scale:


− Apply reference pressure
− Set mode 2
− Set the output current of the start of scale with [↑] or [↓]
− Save with [M]
• This is how to set the full scale:
− Apply reference pressure
− Set mode 3
− Set the output current of the full scale with [↑] or [↓]
− Save with [M]

SITRANS P, Series DS III


34 A5E00047092-01
Local operation and display

3.2.3 Electric damping

You can set the time constant of the electric damping in steps of 0.1 s between 0 and
100 s with the input keyboard. This damping acts additionally to the device-internal
basic damping.

• This is how you set the electric damping:


− Set mode 4
− Set the desired damping with [↑] and [↓]
− Save with [M]

3.2.4 Blind setting of start of scale and full scale

In modes 5 and 6 you can set/adjust the start of scale/full scale with the input keys
and without applying pressure. It is also possible to change between rising and falling
characteristics here.

3.2.4.1 Theoretical relationships

First select the desired physical unit. Then you can set/adjust two pressure values
with the [↑] and [↓] keys and save them in the device. These theoretical pressure
values are assigned to the standard current values 4 mA and 20 mA. After adjusting,
the measuring span specified on the measuring point plate may no longer match the
setting.

A turn-down up to a maximum 1:100 (span ratio = r, turn down) can be reached


depending on the series and measuring range.

The relationship between the measured pressure and the generated output current
is linear (exception: square rooting characteristic in differential pressure
transmitters).

SITRANS P, Series DS III


A5E00047092-01 35
Local operation and display

AInitial situation 0 16 bar

4 20

MA act MA nom MEact


0 2 16 bar
B Blind adjustment of start of scale
4 set 18

MA act MA nom MEnom


0 2 14 16 bar
C Blind adjustment of full scale
4 set 20

Figure 21 Example, Adjusting start of scale and full scale without pressure applied

Explanations to the example (Figure 21):

A: Given a transmitter with a measuring span of 0 to 16 bar Adjust it to a measuring


span of 2 to 14 bar without applying pressure.
B: Set the device to mode 5 with the mode key [M]. Set the start of scale to 2 bar by
pressing the [↑] and [↓] keys. If 2 bar input pressure are applied later, an output
current of 4 mA is generated.
C: Set the device to mode 6 with the mode key [M]. Set the full scale to 14 bar by
pressing the [↑] or [↓] keys. If 14 bar input pressure are applied later, an output
current of 20 mA is generated.

3.2.4.2 Practical application

Set start of scale and full scale (blind)

The device sets the start of scale to the lower and the full scale to the upper sensor
limit when you operate the keys as follows:

• This is how to set the start of scale (blind):


− Set mode 5
− Press [↑] and [↓] simultaneously and hold for 2 s. The start of scale is set to
the lower sensor limit.
• This is how to set the full scale (blind):
− Set mode 6
− Press [↑] and [↓] simultaneously and hold for 2 s. The full scale is set to the
upper sensor limit.

SITRANS P, Series DS III


36 A5E00047092-01
Local operation and display

Adjusting start of scale and full scale (blind):

If the pressure for the start of scale and full scale is not to be set but adjusted
continuously, you have to operate the keys as follows:

• This is how to adjust the start of scale (blind):


− Set mode 5
− Adjust the pressure value of the start of scale with [↑] or [↓]
− Save with [M]
• This is how to adjust the full scale (blind):
− Set mode 6
− Adjust the pressure value of the full scale with [↑] or [↓]
− Save with [M]

3.2.5 Zero adjustment (position correction)

You can correct the zero error resulting from the installation position with a zero
adjustment. To do this, ventilate the device (pressure, differential pressure, flow,
filling level) or evacuate it (absolute pressure, <0.1‰ of the measuring span). Then
correct the existing offset so that the value 0 bar appears in the display.

+
Note

The settings of start of scale and full scale remain the same. Correction is possible
by calling the factory setting via HART.

Caution!

The start of scale is in a vacuum in absolute pressure transmitters! The zero


adjustment in ventilated transmitters leads to misadjustments!

• This is how to set the zero adjustment:


− Vent transmitter (pressure, differential pressure, flow, filling level) or evacuate
(absolute pressure, <0.1‰ of the measuring span)
− Set mode 7
− Set zero with [↑] and [↓]
− Save with [M]

SITRANS P, Series DS III


A5E00047092-01 37
Local operation and display

3.2.6 Current transmitter

You can switch the transmitter to constant current mode with the [M] key. In this case
the current no longer corresponds to the process variable. The following output
currents can be set independently of the input pressure. Intermediate values can also
be set via HART (see Chapter 5.8, pg. 49).

• 3.6 mA
• 4.0 mA
• 12.0 mA
• 20.0 mA
• 22.8 mA

You cancel the current transmitter function again with the [M] key.

• This is how to set the constant current:


− Set mode 8
− Activate constant current with [↑] and [↓] simultaneously
− Activate constant current with [↑] or [↓]
− Turn off constant current with [M]
− Exit constant current mode with [M]

3.2.7 Failure current

In mode 9, select whether the upper or lower fault current is to be output in the event
of a fault or an alarm. The default is the lower fault current. The value of the upper
and lower current can be altered via HART (see Chapter 5.9, pg. 49). Here the
default values are 3.6 mA and 22.8 mA.

• This is how to set the fault current:


− Set mode 9
− Select the fault current with [↑] and [↓]
− Save fault current with [M]

Fault currents can be caused by:

• HW/FW alarm (see also Chapter 5.9, pg. 49)


• Diagnostic alarm (see also Chapter 5.20, pg. 56)
• Sensor break

SITRANS P, Series DS III


38 A5E00047092-01
Local operation and display

3.2.8 Key and/or function disable

In mode 10 you can disable several functions which are generally possible with
keyboard operation. In addition you can activate a write protection to protect the
saved parameters. The following settings are possible:

Table 4 Meaning of the mode displays

Symbol Explanations

0 No disable

LA Input keys disabled, operation via HART possible. Input key function ”Release
keyboard disable” (see Chapter 3.2.1, pg. 31)

LO Input keys partly disabled, only start of scale can be set (see Chapter 4),
operation via HART possible. Input key function ”Release keyboard disable”
(see Chapter 3.2.1, pg. 31)

LS Input keys partly displayed, only start of scale and full scale can be set
(see Chapter 4), operation via HART possible. Input key function ”Release
keyboard disable” (see Chapter 3.2.1, pg. 31)

L Write protection, operation by HART not possible. Input key function ”Release
write protection” (see Chapter 3.2.1, pg. 31)

If the disable modes LS or LO are active, the keyboard operation works as described
in Chapter 4. Another keyboard disable (LL) is possible in HART (see Table 6; pg. 51)

+
Note

If the LO or LS disable is selected, it is recommended to select the measured


value display ”Current” in ”mA” or ”%” first in mode 13. Otherwise a change in the
output variable is not detected when pressing the [↑] and [↓] key

• This is how you set the key disable and write protection:
− Set mode 10
− Select the disable mode with [↑] and [↓]
− Save disable mode with [M]

+
Note

When delivered with a blanking cover, the disable mode LS is active, i.e. only zero
and span can be changed. If you operate the device permanently with a blanking
cover, make sure the disable mode LS remains set.

SITRANS P, Series DS III


A5E00047092-01 39
/RFDORSHUDWLRQDQGGLVSOD\

 )ORZPHDVXUHPHQW RQO\GLIIHUHQWLDOSUHVVXUH

You can select the characteristic of the output current as follows:

• linear (proportional to the differential pressure)


• square rooting (proportional to the flow)

Below the application point of the square rooting characteristic the output current can
either be output linearly or switched off (see Figure 22).

• This is how to set the characteristic:


− Set mode 11
− Select the characteristic type with [↑] and [↓]
− Save with [M]
• This is how to set the root application point:
− Set mode 12
− Select the application point between 5 and 15 % with [↑] and [↓]
− Save with [M]

+
1RWH

Mode 12 cannot be selected when the "linear" measuring mode 11 is set.

If the input pressure is selected as a display in mode 13 and the square rooting
characteristic in mode 11, the differential pressure corresponding to the flow and
the root sign are displayed.

SITRANS P, Series DS III


40 A5E00047090-01
Local operation and display

Output [%]

square rooting

square rooting

application
setting range point
for application
point
pressure-linear pressure-
linear

srlin

square rooting

Pressure [%]

application
point

sroff

Figure 22 Application point of the square rooting characteristic

SITRANS P, Series DS III


A5E00047092-01 41
Local operation and display

3.2.10 Measured value display

In mode 13 you can set one of three display types with the input keys.

• Display in mA
• Display in % (of the set measuring range)
• Display in a unit of pressure (selectable in mode 14)

• This is how to set the unit type:


− Set mode 13
− Select the unit type with [↑] and [↓]
− Save with [M]

3.2.11 Selection of unit of pressure

In mode 14 you can select a desired unit of pressure for the display from a list with
the input keys (see also Figure 23). The unit of pressure set via HART is not
influenced by this (see Chapter 5.13, pg. 51).

• This is how to set the unit of pressure:


− Set mode 14
− Select the unit of pressure with [↑] and [↓]
− Save with [M]

If the display capacity of the digital display is exceeded, ”9.9.9.9.9” appears in the
display.

In the measuring mode the selected unit is only visible in the display if you have
selected a unit of pressure display in mode 13. Otherwise ”mA” or ”%” is displayed.

SITRANS P, Series DS III


42 A5E00047092-01
Local operation and display

bar

mbar

mm water column (20 °C/68 °F)

inch water column (20 °C/68 °F)

feet water column (20 °C/68 °F)

mm mercury column

inch mercury column

psi

Pa

KPa

MPa

g/cm2

kg/cm2

Torr

ATM

inch water column (4 °C/39.2 °F)

mm water column (4 °C/39.2 °F)

Calculated and displayed according to the dimension


set with HART

Figure 23 Parameterizable physical units and their representation on the digital display.

SITRANS P, Series DS III


A5E00047092-01 43
Local operation and display

SITRANS P, Series DS III


44 A5E00047092-01
Local operation without display
or with activated keylock 4
If the digital display has been removed or the keyboard is locked or partially locked
(as-delivered state in devices with a cover without window, see also Chapter 3.2.8,
pg. 39), restricted operation with the keyboard is still possible. In addition to the
”Cancel keyboard disable and write protection” function with the [M]-key (see also
Chapter 3.2.1, pg. 31), you can also set or adjust the start of scale and full scale. The
different modes can no longer be selected.

4.1 Set start of scale, full scale

The differences between set and adjust start of scale/full scale have already been
described in Chapter 3.2.2.1, pg. 31. The same conditions and mathematical
relationships apply as for operating the display.

The SITRANS P, Series DS III transmitter sets the output current for the start of
scale to 4 mA and the full scale to 20 mA when the input keys are pressed according
to the following instructions. An ammeter is not required.

• This is how to set the start of scale:


− Apply reference pressure corresponding to the start of scale
− Press [↑] and [↓] simultaneously so that the start of scale is set to 4 mA and
saved
• This is how to set the full scale:
− Apply reference pressure corresponding to the full scale
− Press and hold [M]
− Press [↑] and [↓] simultaneously in addition so that the full scale is set to 20 mA
and saved

If the output current is not set but adjusted continuously, you have to calculate the
currents to be adjusted mathematically (Chapter 3.2.2.1, pg. 31). It is possible to
make an adjustment for the start of scale, the full scale or both values one after the
other.

SITRANS P, Series DS III


A5E00047092-01 45
Local operation without display or with activated keylock

Warning!

Only certified ammeters may be used in intrinsically safe circuits.

The housing cover may not be unscrewed from ”explosion-proof” transmitters in


hazardous areas.

1. Clean the casing so that no dirt can penetrate


2. Unscrew the cover from the electrical connection box (Figure 4).
3. Connect the DC ammeter to the test plug (Figure 39)

• This is how to set the start of scale:


− Apply reference pressure
− Set the output current of the start of scale with [↑] or [↓]
− The set output current is saved automatically when you release the key
• This is how to set the full scale:
− Apply reference pressure
− Press and hold [M]
− Set the output current of the full scale with [↑] or [↓]
− The set output current is saved automatically when you release the key

SITRANS P, Series DS III


46 A5E00047092-01
Functions/Operation by HART
5
For operation via HART it is necessary to use a HART Communicator (see the
foldout in the appendix) or a PC software such as SIMATIC PDM. Please consult the
appropriate operating instructions or online help to find out how to operate this tool.
The full scope of functions of the SITRANS P, Series DS III is available via the HART
communication.

5.1 Measuring point data

Information about the measuring point, date etc. can be stored in freely writable
fields.

Table 5 Measuring point data

Field Explanations

Measuring position descriptor eight characters

Date Day:Month:Year

Description 16 characters

Message 32 characters

Serial number Integer number

SITRANS P, Series DS III


A5E00047092-01 47
Functions/Operation by HART

5.2 Measuring operation

In measuring operation the process variables pressure and temperature are


provided as digital information via the HART interface. The HART communication is
signaled using the communication character (see Figure 12).

See Chapter 3.1.1, pg. 26 for further information about the measured value display.

5.3 Setting start of scale, full scale

You can set start of scale and full scale via HART. You can implement rising or falling
characteristics with this function (see also Chapter 3.2.2, pg. 31).

The pressure unit can be set independently for the display and the HART
communication.

5.4 Blind setting of start of scale and full scale

The start of scale and full scale can be set without applying a reference pressure.
Both values are freely selectable within the sensor limits. The maximum turn down is
1:100 depending on the series and measuring range.

5.5 Zero adjustment (position correction)

You can correct the zero error resulting from the installation position with a zero
adjustment. To do this, ventilate the device (pressure, differential pressure, flow,
filling level) or evacuate it (absolute pressure, <0.1 ‰ of the measuring span).

Caution!

The start of scale is in a vacuum in absolute pressure transmitters! The zero


adjustment in ventilated transmitters leads to misadjustments!

SITRANS P, Series DS III


48 A5E00047092-01
Functions/Operation by HART

+
Note
The useful measuring range is reduced by the pre-pressure. Example: At a pre-
pressure of 100 mbar the useful measuring range of a 1 bar transmitter is reduced
to 0 to 0.9 bar.

5.6 Electric damping

You can adjust the time constant of the electric damping within a range of 0 to 100 s.

5.7 Fast measured value acquisition (fast response mode)

This mode is designed exclusively for special applications such as fast acquisition of
pressure jumps, e. g. pressure drop in the event of a burst pipe. Here, the internal
measured value acquisition is accelerated at the cost of accuracy. You get an
increased low-frequency noise of the measured value. For this reason, good
accuracy can only be achieved when setting to maximum measuring span.

5.8 Current transmitter

The transmitter can be switched to constant current operation for test purposes. In
this case the current no longer corresponds to the process variable. A ”C” appears
in the mode indicator of the digital display.

5.9 Fault current

With this function you can adjust the value of the lower (< 4 mA) and upper (> 20 mA)
fault current (Figure 24). Both indicate a hardware/firmware error, a sensor break or
reaching an alarm limit (diagnostic alarm). In this case "Error" appears in the digital
display (see Chapter 3.1.4, pg. 28). You can obtain a detailed list from SIMATIC PDM
or the HART Communicator.

SITRANS P, Series DS III


A5E00047092-01 49
Functions/Operation by HART

5.10 Setting the current limits

The value of the upper and lower fault current and the upper and lower limit of the
linear modulation range are freely selectable within the given limits of the current
modulation range (see Figure 24).

The specified accuracy of the current output signal only applies within the current
limits 4 to 20 mA.

IA
[mA] über HART programmierbarer oberer Fehleranzeigebereich
5.
23
22.8
20.5
20
7. 3.
1.
2. 6. 4.
4.0
3.84

3.6
3.55

0% 100 % p [%]
measuring range

1 linear modulation range


2. lower limit of the modulation range (default value)
3. upper limit of the modulation range (default value)
4. lower fault current value (default value)
5. upper fault current value (default value)
6. recommended setting range for lower fault current range and
lower modulation range limit
7. recommended setting range for upper fault current range and
upper modulation range limit

Figure 24 Current limits

SITRANS P, Series DS III


50 A5E00047092-01
Functions/Operation by HART

5.11 Disabling of input keys and write protection

With this function you can disable the input keys or activate a write protection to
protect the saved parameters. The following settings are possible:

Table 6 Input key disable and write protection

Device Explanations
display

No disable

LA Input keys disabled, operation via HART possible

LO Input keys partly disabled, only start of scale can be set, operation via
HART possible

LS Input keys partly disabled, only start of scale and full scale can be set,
operation via HART possible

L Write protection, operation via HART no longer possible, input key


function only ”Cancel write protection” (see Chapter 3.2.1, pg. 31)

LL Input keys fully disabled. The disable can only be released via HART

For operating the device keyboard with activated write protection see also Chapter
3.2.8, pg. 39

5.12 Measured value display

You can set one of three types of units for the device display with this function:

• Display in ”mA”
• Display in ”%” (of the set measuring range)
• Display in a unit of pressure, e.g. ”bar”, ”mbar”, ”Pa” etc.

5.13 Selection of unit of pressure

With this function you can select a desired unit of pressure (see also Figure 23) from
a list of defined units.

The unit of pressure can be set independently for the display and the HART
communication. You can couple the setting of both units optionally.

SITRANS P, Series DS III


A5E00047092-01 51
Functions/Operation by HART

5.14 Display/bargraph

Here you can switch on the ”Bargraph” function which is displayed in alternation with
the unit display. The ”bargraph” factory setting is ”off”.

5.15 Sensor adjustment

With the sensor adjustment it is possible to set the characteristic of the transmitter at
two adjustment points. The results are then correct measured values at the
adjustment points. The adjustment points are freely selectable within the nominal
range.

Devices not turned down at the factory are adjusted at 0 bar of the upper nominal
range limit, devices turned down at the factory at the lower and upper limit of the set
measuring range.

Application examples:

1. The typical measured value of a not turned down device (e.g. 63 bar) is 50 bar.
In order to achieve the greatest possible accuracy for this value you can make
the upper sensor adjustment at 50 bar.
2. A 63 bar transmitter is turned down to 4 to 7 bar. You achieve the greatest
possible accuracy when you select the lower sensor adjustment point at 4 bar
and the upper one at 7 bar.

+
Note

Pressure transmitters must always be sufficiently accurate.

5.15.1 Trimming the lower sensor adjustment point

The pressure at which the lower sensor adjustment is to be made is applied to the
transmitter. With SIMATIC PDM or the HART Communicator you instruct the
transmitter to accept this pressure. This represents an offset shift of the characteristic
(1., Figure 25).

SITRANS P, Series DS III


52 A5E00047092-01
Functions/Operation by HART

5.15.2 Trimming the upper sensor adjustment point

The pressure at which the upper sensor adjustment is to be made is applied to the
transmitter. With SIMATIC PDM or the HART Communicator you instruct the
transmitter to accept this pressure. This corrects the characteristic slope (2., Figure
25). The lower sensor adjustment point is not affected. The upper adjustment point
must be greater than the lower adjustment point.

measured
pressure

1.: A
2.: B
B: Parallel shift
C: Change in slope
B

1.
2. C

lower adjustment upper adjustment preset pressure


point point
A: Output characteristic
B: Characteristic after lower sensor adjustment
C: Characteristic after upper sensor adjustment

Figure 25 Sensor adjustment

5.16 Current transmitter adjustment

You can adjust the current output by the transmitter independently of the pressure
measuring circuit. This function is suitable for compensating inaccuracies in the
operating sequence following the transmitter.

Application example:

The current should be measured as a voltage drop from 1 to 5 V at a resistance of


250 Ω +/− 5 %. To compensate the tolerance of the resistor, set the current
transmitter so that the voltage drop at 4 mA is exactly 1 V and at 20 mA exactly 5 V.

SITRANS P, Series DS III


A5E00047092-01 53
Functions/Operation by HART

+
Note

A used multimeter must always be sufficiently accurate.

1. Adjustment at 4 mA:
Instruct the transmitter to output 4 mA under menu item Current transmitter
adjustment. Read the measured value from the ammeter and enter it for example
via SIMATIC PDM. The transmitter uses this value for offset correction of the
current.
2. Adjustment at 20 mA:
Instruct the transmitter to output 20 mA under menu item Current transmitter
adjustment. Read the measured value from the ammeter and enter it for example
via SIMATIC PDM. The transmitter uses this value for slope correction of the
current. This does not alter the value for 4 mA.

Measured
current I 1.: A B: Parallel shift
A
2.: B C: Change in slope
1.
B
2. C
I2

I1

4 mA 20 mA Nominal
current I
A: Output characteristic
B: Characteristic after current transmitter adjustment 4 mA
C: Characteristic after current transmitter adjustment 20 mA

Figure 26 Current transmitter adjustment

SITRANS P, Series DS III


54 A5E00047092-01
Functions/Operation by HART

5.17 Factory calibration

You can return the transmitter to its original state with the factory calibration. You can
select the scope of the recovered parameters in a menu with SIMATIC PDM or the
HART Communicator in four steps:

1. Cancelation of the current adjustment


2. Cancelation of the sensor zero adjustment (position correction)
3. Cancelation of the pressure corrections (zero adjustment and sensor
adjustment)
4. Cancelation of all parameters relevant to measured value processing such as
start of scale, full scale, electric damping, display unit, current adjustment, zero
adjustment (position correction), sensor adjustment, measuring speed, alarm
current limits, alarm setting, overflow ranges of the current.

5.18 Static configuration data

Under another menu item in the appropriate operating program you can read and
write a series of sensor-specific material data. These values are not contained in the
”Factory calibration” function, i.e. changes in the device remain permanently stored.

List of adjustable material parameters: flange type, flange material, vent valve
material, remote seal type, filling medium, O-ring material, remote seal, seal
diaphragm material, number of remote seals, sensor filling medium, sensor seal
diaphragm material, transmitter version, housing material, tube length, process
connection, electrical connection, process flange screw material, position vent valve.

5.19 Flow measurement (only differential pressure)

You can select the characteristic of the output current via HART for the ”differential
pressure and flow” device as follows:

• linear (proportional to the differential pressure)


• square rooting (proportional to the flow)

The application point of the square rooting can then be selected between 5 and 15 %
(see also Figure 22).

SITRANS P, Series DS III


A5E00047092-01 55
Functions/Operation by HART

5.20 Diagnostic functions

Communication with the HART interface enables activation and evaluation of


numerous diagnostic functions from a central control station or locally. The
simulation of pressure and temperature measured values is possible in addition to
calibration/service timers, slave pointers and limit value monitoring components.

The diagnostic concept of the SITRANS P, Series DS III is conceived such that a
(diagnostic) warning and a (diagnostic) alarm can be parameterized for diagnostic
functions which serve for monitoring limit values (e.g. monitoring of current
saturation).

• Diagnostic warning: The device transmits the diagnostic event that has
occurred via HART. The current output value remains unaffected. The moving
text ”Diagnostic Warning” appears in the display alternately with the unit.
• Diagnostic alarm: The device goes into the fault current state. The messages
”ERROR” and as a moving text ”Diagnostic Warning” or ”Diagnostic Alarm”
appear in the display. The diagnostric event is provided additionally via HART.

The standard setting for all warnings and alarms is off. You can set either only the
diagnostic warning or diagnostic alarm and warning optionally. To do this use the
HART Communicator or SIMATIC PDM. See the foldout for operation of the HART
Communicator in the appendix or the help functions of the SIMATIC PDM software
for the necessary steps.

5.20.1 Operating hours counter

Operating hours counters for the electronics and the sensor can be read out via
HART (PDM or Communicator). The counters are activated the first time the
transmitter is started. If the device is disconnected from ist power supply the counter
readings are stored automatically in the non-volatile memories. It can therefore
access the latest counter readings the next time it is restarted. The operating hours
counters cannot be reset.

5.20.2 Calibration timer/service timer

You can wind up a two-stage timer to ensure regular calibration of the electronics and
for service work on the sensor. A calibration or service warning appears after a first
time expires. On expiry of a second time set as a time difference, a diagnostic alarm
is signaled and a fault current is output (see also Chapter 5.9, pg. 49).

SITRANS P, Series DS III


56 A5E00047092-01
Functions/Operation by HART

You must acknowledge the warnings and alarms to perform the calibration work.
Then you can reset the timers and switch off the monitoring function. The calibration
intervals for the electronics are given by the following equation:

(necessary accuracy - probable total error)


Calibration interval = -----------------------------------------------------------------------------------------------------
stability/month

5.20.3 Slave pointer

This device offers three pairs of slave pointers with which you can monitor three
measuring variables pressure, sensor temperature and electronics temperature for
negative and positive peak values. Per measured value a resettable slave pointer
saves the maximum and minimum peak values long-term in the two non-volatile
memories. The values are then reavailable after restarting the device. The slave
pointers are also updated during a simulation (see Chapter 5.21, pg. 59).

Upper slave pointer value


rve
cu
re
ssu
Pre

Lower slave pointer value

Figure 27 Principle representation of slave pointers with pressure as an example

SITRANS P, Series DS III


A5E00047092-01 57
Functions/Operation by HART

5.20.4 Limit value components

The diagnostic functions of this device offer you the possibility of monitoring
measured values in parameterizable limits and having their violation reported by a
warning (via HART communication) or a fault current (analog) of a superior level.

5.20.4.1 Monitoring the current saturation

You can monitor the current output in the saturation range with a simple limit value
component. This component is parameterized and activated via HART (PDM or
Communicator). For this you have to parameterize two times. The first of these
determines how long the current output may be in saturation (reponse time) before
an alarm is triggered and the device outputs its set fault current. The second time
(hold time) determines the duration of the alarm.

In the first example (Figure 28) the response time begins at time t1 when the current
reaches the parameterized saturation limit for the first time. At t2 the response time
ends and the hold time begins. The alarm is canceled immediately when the
parameterized hold time has already expired (t3) and the current does not drop back
below the saturation limit before this.

In the second example the duration of current saturation is shorter than the response
time (t1, t2). In this case the device does not go into the ”fault current” state.

In the third example the current only drops below the lower saturation limit for a short
time. The fault current is not switched off until the end of the hold time (t3).

I [mA]
Fault current

20.5 mA

3.8 mA
I [mA]
pmax

pmin

Response Time [s]


Response Response
time time time
Min. Hold time Min. Hold time
t1 t2 t3 t1 t2 t1 t2 t3
Example 1 Example 2 Example 3

Figure 28 Three examples for saturation monitoring

SITRANS P, Series DS III


58 A5E00047092-01
Functions/Operation by HART

5.21 Simulation

With the ”Simulation” diagnostic function you can receive and process (simulated)
measuring data locally or in a central station without an applied process pressure or
temperature value. You can therefore run individual processes ”cold” and thus
simulate process states. In addition you can check the line from the control station to
the individual transmitters by applying simulation values.

The value to be simulated can be preset as a fixed value or in the form of a ramp
function. The simulation of pressure and temperature values is handled identically in
parameterization and function so that only the general simulation methods ”fixed
value” and ”ramp function” are explained below.

For security reasons all the simulation data are only kept in the RAM. This means
any simulation which may be activated is switched off when the device is restarted.
You can simulate the pressure and both temperature values. You must note that
changing the temperatures by simulation has no effect on the measured pressure
value.

Measure
Sensor A
P

Sensor Process value


D
T 4..20 mA

Sensor A
T electr .
D
µC

Values P Fixed value

Comm..
Values HART HART
T Sensor
Ramp
Values
T electr .

I
Constant
Simulate

Figure 29 Principle circuit diagram simulation

SITRANS P, Series DS III


A5E00047092-01 59
Functions/Operation by HART

5.21.1 Simulation as a fixed value

Under consideration of the physical unit you can parameterize a fixed simulation
value for all three possible simulation lines. You can simulate the pressure and both
temperature values simultaneously. As long as the pressure simulation is switched
on, the transmitter does not react to changes in the process pressure. The current
output value is set according to the pressure default. Simulation of the temperature
values has no influence on the current output. It can only be observed through the
HART communication interface.

5.21.2 Simulation with a ramp function

As a second possibility you can also parameterize a ramp function in addition to the
settable fixed values for all three simulation lines. A settable start and end value
determines the respective limits between which the simulation values move with a
rising and falling tendency. The step width can also be calculated with the settable
number of steps. The rise speed of the ramp is determined by the duration of the
individual ramp steps.

(end value - start value)


Step width = ---------------------------------------------------------
number of steps

The current output follows the simulated values in the pressure simulation.

SITRANS P, Series DS III


60 A5E00047092-01
Modular design
6

+
Note

Dear customer,

You have purchased a modular device in which you can exchange the electronics.
In the event of an exchange, please observe the instructions enclosed with the
component to be exchanged.

6.1 Relationships

The two single components measuring cell and electronics both have a non-volatile
memory (EEPROM). Each contains a data structure which is permanently assigned
to the measuring cell or the electronics. Measuring cell data (e. g.: measuring range,
measuring cell material, oil filling etc.) are stored in the measuring cell’s EEPROM.
Data of the electronics (e.g.: turn-down, electric damping etc.) are in the electronics’s
EEPROM. This ensures that the data relevant to the remaining component are
retained when the electronics are exchanged.

Before replacing components you can set, via HART, whether the common
measuring range settings are to be taken from the measuring cell or the electronics
after the exchange or whether standard parameters should be set. The measuring
accuracy in the specified measuring limits (with turn-down 1:1) may be reduced by
factor 2 under unfavorable conditions. The ”factory calibration” mode (see Chapter
5.17, pg. 55) can no longer be used after an exchange.

In the course of further development, extended functions may be implemented in the


measuring cell or electronics. This is identified by a changed firmware version (FW).
The firmware version has no influence on the exchangeability. However, the scope
of functions is restricted to the function of the respective older component.

SITRANS P, Series DS III


A5E00047092-01 61
Modular design

If the combination of certain firmware versions of the measuring cell and the
electronics is not possible for technical reasons, the device detects this and goes into
the ”fault current” state. This information is also provided via th HART interface.

6.2 Practical application

Warning!

This work may only be performed by qualified personnel!

6.2.1 Exchanging the electronics

To exchange the electronics, you must:

1. remove the cover and the digital display (1 and 2, Figure 30) behind it
2. unscrew the two threaded bolts (3) holding the electronics (4) in place,
3. remove the cast electronic block carefully from the housing (6),
4. pull off the measuring cell board (5) which connects the measuring cell (7) to the
electronics and plug it to the new electronics,
5. assemble the individual parts in reverse order.

6 5 4 3 2 1

1 cover with window (optional)


2 digital display
3 threaded bolt
4 electronics
5 measuring cell board
6 housing
7 measuring cell

Figure 30 Device assembly

SITRANS P, Series DS III


62 A5E00047092-01
Installation
7
The installation cases described below are typical examples. Different types of
installation may be possible depending on the system configuration.

7.1 Installation (except filling level)

The transmitter can be arranged above or below the pressure tapping point.

When measuring gases we recommend installing the transmitter above the pressure
tapping point and laying the pressure line with a constant downward gradient to the
pressure tapping point so that condensation which forms can drain into the main line
and the measured value is not falsified (recommended installation see Chapter 8.1,
pg. 77).

When measuring vapors and liquids the transmitter should be installed below the
pressure tapping point and the pressure line should have a constant upward gradient
so that gas entrapped in the main line can escape (recommended installation see
Chapter 8.1, pg. 78).

The installation point should be easily accessible, if possible in the vicinity of the
measuring point and should not be exposed to strong vibration. The permissible
ambient temperature limits (see Chapter 9 for further information) may not be
exceeded. Protect the transmitter from direct radiation of heat.

The desired operating data must be compared with the values specified on the
device’s rating plate before installation.

The housing may only be opened for maintenance, local operation or electrical
installation.

SITRANS P, Series DS III


A5E00047092-01 63
Installation

Warning!
All modifications or extensions to the devices require the manufacturer’s
permission.

Suitable tools must be used for connecting the transmitter on the pressure side. Do
not rotate on the housing!

Observe the installation instructions on the housing!

7.1.1 Mounting without mounting bracket

The transmitter may be mounted directly at the process connection.

7.1.2 Mounting with mounting bracket

The mounting bracket is fastened

• to a wall or a mounting rack with two screws


or
• with a pipe bracket to a horizontal or vertical mounting pipe (Ø 50 to 60 mm)

The transmitter is fixed to the mounting bracket with two screws (enclosed).

Figure 31 Mounting the SITRANS P, Series DS III transmitter with mounting bracket

SITRANS P, Series DS III


64 A5E00047092-01
Installation

Figure 32 Mounting the SITRANS P, Series DS III transmitter with mounting bracket
(example differential pressure, horizontal active pressure lines)

Figure 33 Mounting the SITRANS P, Series DS III transmitter with mounting bracket
(example differential pressure, vertical active pressure lines)

SITRANS P, Series DS III


A5E00047092-01 65
Installation

7.2 Mounting ”filling level”

7.2.1 Installation

Before installing, check whether the transmitter satisfies the operating conditions
(material, sensor length, measuring span).

The installation location must be easily accessible and free from vibration. The
permissible ambient temperatures may not be exceeded. Protect the transmitter
from heat radiation, rapid temperature fluctuations, heavy soiling and mechanical
damage.

The height at which the container flange for mounting the transmitter (measuring
point) must be chosen so that the lowest liquid level to be measured is always above
the flange or at its top edge.

1. Screw the flange of the transmitter (dimensions Figure 49) after fitting a seal
(e.g. flat sealing ring DIN 2690) to the counterflange of the vessel (seal and
screws are not included in the delivery). The seal must be central and may not
restrict the mobility of the flanges seal diaphragm at any point.
2. Observe the installation position!

7.2.2 Connecting the low pressure line

No line is necessary when measuring on the open container Figure 34 because the
low pressure chamber is connected to the atmosphere. The open connecting pipe
should point downwards to prevent dirt getting in.

Start of scale pMA = ρ · g · HU


Full scale pME = ρ · g · HO
Full scale

∆pMA start of scale to be set


∆pME full scale
to be set
HU start of scale
Ho r
HO full scale Start of scale
g local acceleration
due to gravity
Hu
ρ density of the medium in
the container
+

Figure 34 Measuring setup on the open container

SITRANS P, Series DS III


66 A5E00047092-01
Installation

When measuring on the closed container without or with only slight condensation
(Figure 35) the low pressure line remains unfilled. The line must be laid so that no
condensate sacks can form, you may have to install a condensation vessel.

start of scale ∆pMA = ρ · g · HU


Static
full scale ∆pME = ρ · g · HO pressure gas-filled low
pressure line
∆pMA start of scale to be set
∆pME full scale to be set Maximum level
HU start of scale
HO full scale
g local acceleration Full scale

due to gravity
ρ density of the medium
Start of scale
in the vessel
Ho

Hu r

transmitter
reference line

Figure 35 Measuring set up on the closed container (no or only slight condensation escape)

When measuring on the closed container with strong condensation formation


(Figure 36), the low pressure line must be filled (usually with medium condensate)
and a calibration vessel must be installed. The device can be shut off for example by
a double valve manifold 7MF9001-2.

SITRANS P, Series DS III


A5E00047092-01 67
Installation

start of scale ∆pMA = g · (HU · ρ - HV · ρ‘)


Static
full scale ∆pME = g · (HO · ρ - HV · ρ‘) pressure constant
level of
comparison
∆pMA start of scale to be set
∆pME full scale to be set Maximum level
HU start of scale
HO full scale
Full scale liquid-filled
HV outlet spacing
low pressure line
g local acceleration due to gravity
ρ density of the medium in the
Start of scale Hv
vessel r'
Ho
ρ‘ density of the liquid in the
low pressure return line Hu r
corresponds to the prevailing
temperature there

transmitter
reference line

Figure 36 Measuring setup on the closed container (strong condensation formation)

The process connection on the low pressure side is a female thread 1/4 -18 NPT or
an oval flange.

The line for the low pressure must be made of 12 mm x 1.5 mm seamless steel pipe.
See Figure 35 and Figure 36 for shutoff valves.

7.3 Rotating the measuring cell in relation to the housing

If necessary, you can rotate the electronics housing in relation to the measuring cell
in the SITRANS P, Series DS III transmitter so that the digital display (in housing
covers with a window) is visible and access to the input keys and the current
connection for an external measuring instrument is possible.

Only a limited rotation is permitted! The range of rotation (3, Figure 37) is marked at
the base of the electronics housing, there is an orientation mark (4) on the neck of
the measuring cell which must stay within the marked area when rotating.

1. Loosen the locking screw ((2), hexagon socket head 2.5 mm).
2. Rotate the electronics housing in relation to the measuring cell (only within the
marked area)
3. Tighten the locking screw (torque: 3.4 to 3.6 Nm).

SITRANS P, Series DS III


68 A5E00047092-01
Installation

Figure 37 Range of rotation of the measuring cell (in pressure and absolute pressure
transmitters of the pressure series)

Figure 38 Range of rotation of the measuring cell (in differential pressure and flow and
absolute pressure transmitters from the differential pressure and filling level series

+
Note

The range of rotation must be observed, otherwise destruction of the electrical


connections of the measuring cell cannot be ruled out.

SITRANS P, Series DS III


A5E00047092-01 69
Installation

7.4 Electrical Connection

Warning!
The pertinent regulations must be observed for electrical installation, in explosion
risk areas in particular:

- the directive governing electrical installations in hazardous areas (Elex V)


- the regulation for erecting electrical installations in hazardous areas
(VDE 0165) and
- the EC Type Examination Certificate

Check whether the available power supply matches the EC type examination
certificate specified on the rating plate. Sealing caps in the cable inlets should be
replaced by suitable screwed glands or blanking plugs which must be certified for
explosion-proof transmitters!

The transmitter should be powered from a power source with SELV (safety extra-low
voltage). If other power sources are used, we recommend grounding the transmitter
housing at the PE connection. The screen terminal in the connection box (Figure 39)
must be connected internally to the PE connection.

+
Note

When laying the connecting cable (max. 2.5 mm2 cross section)/signal cable,
always:

- Lay cable separately from cable with voltages > 60 V


- Use cables with twisted wires
- Avoid the vicinity of large electrical installations or use screened cables
- Full HART specifications only apply with screened cables.

For error-free communication at least one load of 230 Ω must be available in the
signal circuit (see Figure 39). A load is already built into the device when using feed
isolators for SMART transmitters, e.g. Siemens 7NG4021.

SITRANS P, Series DS III


70 A5E00047092-01
Installation

7.4.1 Connection to screw terminals

Connect the transmitter as follows:

1. Unscrew the cover of the connection box (marked ”FIELD TERMINALS” on the
housing).
2. Insert the connecting cable through the cable gland.
3. Connect the wires to the ”+” and ”-” terminals (Figure 39) and observe the
polarity!
4. Connect the screen to the screen screw if necessary.
5. Screw on the housing cover.

-
2
1 230 W bis 1100 W (HART communicator)
230 W bis 500 W (HART modem and PC/laptop)

5
6

1 Screen plate
2 Power supply
3 Screws for fastening the terminal strip
4 Terminals
5 Test plug for DC ammeter or connection facility for external display
6 Cover catch
7 PE conductor connection

Figure 39 Electrical connection, schematic diagram

Warning!

In explosion-proof transmitters the housing cover must be screwed on tightly and


secured with the cover catch.

SITRANS P, Series DS III


A5E00047092-01 71
Installation

+
Note

The power supply connection is voltage-free. The device does not need to be
earthed. If you want to earth these lines, however, we recommend that you earth
the negative pole.

7.4.2 Connection with plug

(not for ”explosion-proof” degree of protection)

The contact parts for the coupling socket are enclosed packed in a bag.

1. Push the sleeve and screwed gland onto the cable.


2. Insulate the cable ends approx. 8 mm.
3. Crimp or solder the contact parts to the cable ends.
4. Assemble the coupling socket.

!IA output current


UH power supply

1 = -UH
2 = -UH  
3 = screen
  

 

 $
,

8
+

Figure 40 Connect with plug (Han 7D / Han 8U)

For error-free communication at least one load of 230 Ω must be available in the
signal circuit (see Figure 39). A load is already built into the device when using feed
isolators for SMART transmitters, e.g. Siemens 7NG4021.

SITRANS P, Series DS III


72 A5E00047092-01
Installation

7.5 Turn digital display

If the device cannot be operated in a vertical position you can turn the digital display
to make it easier to read. To do this, proceed as follows:

1. Unscrew the cover from the electronics housing.


2. Unscrew the digital display. Depending on the position of the transmitter you can
screw it back in four different positions (rotated by ±90° or ±180° possible).
3. Screw on the housing cover.

SITRANS P, Series DS III


A5E00047092-01 73
Installation

SITRANS P, Series DS III


74 A5E00047092-01
Commissioning
8
The operating data must match the values specified on the rating plate. The
transmitter is in operation when the power supply is switched on.

Warning!

Only certified ammeters may be used in intrinsically safe circuits.

The housing cover may not be unscrewed from ”explosion-proof” transmitters in


hazardous areas. Please observe the appendix in Chapter 12 if the transmitter is
to be used as category 1/2 equipment.

+
Note

- The explosion protection of the transmitter depends particularly on the


tightness of the measuring cell diaphragms (wall thickness Σ 0.025 mm). For
this reason the transmitter may only be used for those combustible gases and
liquids for which the diaphragms are sufficiently resistant to chemicals and
corrosion. The appropriate remote seals may have to be installed.
- The transmitters must be included in the recurrent pressure testing of the
container and the pipeline.
- The following applies for equipment with protection type ”intrinsically safe” and
”pressurized” (EEx ia + EEx d): The inapplicable protection type must be
permanently deleted from the rating plate before commissioning.
- The ”intrinsically safe” protection type is no longer effective in the case of
improper feeding.

The following commissioning cases are typical examples. Different arrangements


may be advisable depending on the system configuration.

SITRANS P, Series DS III


A5E00047092-01 75
Commissioning

8.1 Pressure, absolute pressure from differential pressure


series and absolute pressure from pressure series

Warning!
Wrong or improper operation of the valves Figure 41 may result in serious injury or
considerable material damage.

Make sure the process connection is sitting firm and tight. When using a male
thread G ½ A and installing in zone 0, a flat metal seal e.g. DIN 16258 must be
used. The width of the seal (material strength) must be at least 3 mm.

SITRANS P, Series DS III


76 A5E00047092-01
Commissioning

8.1.1 Measuring gases

Operate the shutoff fittings in the following order:

Initial position: all valves closed

1. Open the shutoff valve Figure 41, 2B).


2. Apply pressure corresponding to the start of scale through the test connection of
the shutoff fitting (2) to the transmitter.
3. Check the start of scale and correct it if necessary.
4. Close the shutoff valve (2B).
5. Open the shutoff valve (4) on the pressure tap.
6. Open the shutoff valve (2A).

1
4

2A 2B 2

3
1
4

2A 2B 2

Transmitter above the pressure tapping point Transmitter below the pressure tapping point
(normal arrangement) (exception)

1 Transmitter
2 Shutoff fitting
A shutoff valve to the process
B shutoff valve for test connection or venting screw
3 Pressure pipe
4 Shutoff valve
5 Shutoff valve (optional)
6 Condensation vessel (optional)
7 Drain valve

Figure 41 Measuring gases

SITRANS P, Series DS III


A5E00047092-01 77
Commissioning

8.1.2 Measuring vapor and liquid

Operate the shutoff fittings in the following order:

Initial position: all valves closed

1. Open the shutoff valve (Figure 42, 2B).


2. Apply pressure corresponding to the start of scale through the test connection of
the shutoff fitting (2) to the transmitter.
3. Check the start of scale and correct it if necessary.
4. Close the shutoff valve (2B).
5. Open the shutoff valve (4) on the pressure tap.
6. Open the shutoff valve (2A).





$ % 

11 Transmitter
2 Shutoff fitting
A shutoff valve to the process
B shutoff valve for test connection or venting screw
3 Pressure pipe
4 Shutoff valve
5 Drain valve
6 Compensation vessel (for vapor only)

Figure 42 Measuring vapor

SITRANS P, Series DS III


78 A5E00047092-01
Commissioning

8.2 Differential pressure and flow

Warning!
- If the vent valve and/or the sealing screw are missing or are not tight enough
and/or

- if the valves are operated wrongly or improperly,


serious injury or considerable material damage may result.

In the case of hot media the individual operating steps must be performed in rapid
succession. Otherwise the valves and the transmitter may be heated up
impermissibly leading to damage.

SITRANS P, Series DS III


A5E00047092-01 79
Commissioning

8.2.1 Measuring gases

Operate the shutoff fittings in the following order:

Initial position: all valves closed

1. Open both shutoff valves (5) at the pressure taps.


2. Open the compensation valve (2).
3. Open the active pressure valve (3A or 3B).
4. Check and correct zero (4 mA) if necessary at start of scale 0 mbar.
5. Close the compensation valve (2).
6. Open the other active pressure valve (3B or 3A).

1 5B 5A
- + - +

2
10

3B 3A
1
4 - + 4
4 4
2
5B 5A
- +
3B 3A
10

9 9
7B 7A

Transmitter above the active pressure Transmitter below the active pressure transmitter
transmitter (normal arrangement) (exception)

1 Transmitter
2 Compensation valve
3 Active pressure valves
4 Active pressure lines
5 Shutoff valves
7 Blowout valves
9 Condensation vessels (optional)
10 Active pressure transmitters

Figure 43 Measuring gases

SITRANS P, Series DS III


80 A5E00047092-01
Commissioning

8.2.2 Measuring liquids

Operate the shutoff fittings in the following order:


Initial position: all valves closed

1. Open both shutoff valves (5) at the pressure taps.


2. Open the compensation valve (2).
3. In the transmitter below the active pressure transmitter open both blowout
valves (7) one after the other, in the transmitter above the active pressure
transmitter open both vent valves (8) slightly until air-free liquid emerges.
4. Close both blowout valves (7) or vent valves (8).
5. Open the active pressure valve (3A) and the vent valve at the high pressure
chamber of the transmitter (1) slightly until air-free liquid emerges.
6. Close the vent valve.
7. Open the vent valve at the low pressure chamber of the transmitter (1) slightly
until air-free liquid emerges.
8. Close the active pressure valve (2).
9. Open the active pressure valve (3B) slightly until air-free liquid emerges, then
close it.
10. Close the vent valve at the low pressure chamber (1).
11. Open the active pressure valve (3A) by 1/2 turns.
12. Check and correct zero (4 mA) if necessary at start of scale 0 bar.
13. Close the compensation valve (2).
14. Open the active pressure valves (3A or 3B) fully.
- +
8 8
5B 5A
12 12
10

4 3B 3A 4
2

- + 4 3B 3A 4
7B 1 7A 2

- +
1 Transmitter
7B 1 7A
2 Compensation valve
3 Active pressure valves
4 Active pressure lines
5 Shutoff valves - +
7 Blowout valves
10 Active pressure transmitters
5B 10 5A
12 Gas collectors (optional)
Transmitter above the active pressure Transmitter below the active pressure transmitter
transmitter (normal arrangement) (exception)
Figure 44 Measuring liquids

SITRANS P, Series DS III


A5E00047092-01 81
Commissioning

8.2.3 Measuring vapor

Operate the shutoff fittings in the following order:

Initial position: all valves closed

1. Open both shutoff valves Figure 45, 5 at the pressure taps.


2. Open the compensation valve (2).
3. Wait until the vapor in the active pressure lines (4) and in the compensation
vessels (13) has condensed.
4. Open the active pressure valve (3A) and the vent valve at the high pressure
chamber of the transmitter (1) slightly until air-free condensate emerges.
5. Close the vent valve.
6. Open the vent valve at the low pressure chamber of the transmitter (1) slightly
until air-free condensate emerges.
7. Close the active pressure valve (3A).
8. Open the active pressure valve (3B) slightly until air-free condensate emerges,
then close it.
9. Close the vent valve at the low pressure chamber (1).
10. Open the active pressure valve (3A) by 1/2 turns.
11. Check and correct zero (4 mA) if necessary at start of scale 0 bar.
12. Close the compensation valve (2).
13. Open the active pressure valves (3A and 3B) fully.
1 Transmitter
- +
2 Compensation valve
13 13
3 Active pressure valves
4 Active pressure lines
5 Shutoff valves 5B 10 14 5A
7 Blowout valves 4 4
10 Active pressure transmitters
13 Compensation vessels 3B 3A
14 Insulation
2

- +
7B 1 7A

Figure 45 Measuring vapor

Caution!
The measuring result is only error-free when the active pressure lines (4) contain
equally high condensate columns of equal temperature. Zero adjustment must be
repeated if these conditions are satisfied.
If the compensation valve (2) is opened when the shutoff valves (5) and active
pressure valves (3) are open simultaneously, the transmitter (1) may be damaged
by flowing vapors!

SITRANS P, Series DS III


82 A5E00047092-01
7HFKQLFDO'DWD


SITRANS P, Series DS III


A5E00047090-01 83
Technical data: SITRANS P DS III

Device type: Pressure Differential pressure Absolute pressure Filling level


7MF4033 7MF4433 / 7MF4533 Pressure series 7MF4233 Diff. pressure series 7MF4333 7MF4633

Application range see page 11


Function see page17

84
Meas. principle piezoresistive
Input
Meas. var. Pressure Diff. pressure and flow Absolute pressure Filling level
Meas. Range
 Span (cont. adjustable) 0.01 to 400 bar 8.3 mbar to 30 bar 8.3 mbar to 160 bar 25 mbar to 5 bar
Nominal pressure PN 32 1 mbar to 20 mbar
Nominal pressure PN 160 1 mbar to 30 bar
Nominal pressure PN 420 2,5 mbar to 30 bar
 Lower meas. Limit -100% of max span -100% of max span
- 30 bar measuring cell -33 % of max span
- Meas. cell with silicone oil filling 30 mbar (absolute) 30 mbar (absolute) 0 mbar (absolute) or 30 mbar (abs) dep. on
remote seal
- Meas. cell with inert filling liquid
for process temp. -20 °C < ϑ < 60 °C 30 mbar (absolute)
for process temp. +60 °C < ϑ < 100 °C 30 mbar(abs) + 20 mbar(abs) · (ϑ - 60 °C)
°C
(maximum +85°C for 30 bar meas. cell)
 Upper meas. limit +100 % of maximum span, (maximum 160 bar in oxygen measurement and inert filling liquid 160 bar) +100% of max span
 Start of scale (cont. adjustable) between the measuring limits
Output
Output signal 4 to 20 mA
 Lower limit (cont. adjustable) 3.55 mA, factory set to 3.84 mA
 Upper limit (cont. adjustable) 23.0 mA, factory set 20.5 mA or optionally 22.0 mA
 Ripple (without HART communication) Ipp ≤ 0.5% of maximum output current
 Electric damping
- adjustable time constants (T 66) 0 to 100 s, in steps of 0.1 s, factory set to 0.1 s
 Current transmitter adjustable 3.55 bis 23 mA
 Failure signal adjustable 3.55 bis 23 mA
Load
 without HART communication RB ≤ (UH - 10.5 V) / 0.023 A in Ω, UH: power supply in V

 with HART communication RB = 230 to 500 Ω (HART-Communicator) or RB = 1100 Ω (HART-Communicator)


Characteristic linear rising or falling
or square rooting rising
Measuring accuracy
Reference conditions Rising characteristic, start of scale 0 bar, seal diaphragm stainless steel, ( for filling level mounting flange without tube ), silicone oil filling and room temp. ( 25 °C )
r = maximum span / set span = span ratio
Meas. error (limit point setting, including
hysteresis an repetitive accuracy)
 linear characteristic
r ≤ 10 ≤ 0.1 % ≤ 0.15 %
10 < r ≤ 30 ≤ 0.2 % ≤ 0.3 %
30 < r ≤100 ≤ (0.005 · r + 0.05) % ≤ (0.0075 · r + 0.075)%
 Square rooting characteristic
Flow > 50% ≤ 0.1 % at r ≤ 10
≤ 0.2 % at 10 < r ≤ 30
Flow 25 to 50% ≤ 0.2 % at r ≤ 10
≤ 0.4 % at 10 < r ≤ 30
 Repetitive accuracy contained in measuring error

SITRANS P, Series DS III


A5E00047090-01
7HFKQLFDO'DWD

 Hysteresis contained in measuring error


about 0.2 s, about 0.3 s with
Transient time (T63, without el. damping) about 0.2 s about 0.2 s
20 and 60 mbar meas. cell
Technical data: SITRANS P DS III

Device type: Pressure Differential pressure Absolute pressure Filling level


7MF4033 7MF4433 / 7MF4533 Pressure series 7MF4233 Diff. pressure series 7MF4333 7MF4633
Long-term drift every 12 months ≤ ( 0.1 · r) % ≤ (0.2 · r) % ≤ ( 0.1 ,· r) %
20 mbar meas. cell: ≤ ( 0.2 · r) %

Influence of ambient temperature


1)
 at -10 to +60 °C ≤ (0.1 · r + 0.2) %
2)
250 mbar meas. cell ≤ (0.5 · r + 0.2 )%

A5E00047090-01
2)
600 mbar meas. cell ≤ (0.3 · r + 0.2 )%
7HFKQLFDO'DWD

2)
1,600 and 5,000 mbar meas. cell ≤ (0.25 · r + 0.2 )%
1) 2)
double value with 20mbar 0.4 inst. of 0.2 at 10 < r ≤ 30
meas. cell

SITRANS P, Series DS III


1)
 at -40 to -10 °C and +60 to +85 °C ≤ (0.1 · r + 0.15) % / 10 K
250 mbar meas. cell ≤ (0.25 · r + 0.15 3) ) % / 10 K
600 mbar meas. cell ≤ (0.15 · r + 0.15 3) ) % / 10 K
3)
1,600 and 5,000 mbar meas. cell ≤ (0.12 · r + 0.15 ) % / 10 K
1) 3)
double value with 20mbar 0.3 inst. of 0.15 at 10 < r ≤ 30
meas. cell
Influence of static pressure

 on start of scale ≤ ( 0.15 · r ) % per 100 bar

20 mbar meas. cell ≤ (0.15 · r) % per 32 bar

250 mbar meas. cell (0.3 · r) % per nom. Pressure


600 mbar meas. cell (0.15 · r) % per nom. Pressure
1,600 and 5,000 mbar meas. cell (0.1 · r) % per nom. Pressure
 on the span ≤ 0.2% per 100 bar (0.1 · r) % per nom. Pressure
20 mbar meas. cell ≤ 0.2% per 32 bar
Influence of installation position ≤ 0.05 mbar per 10° angle ≤ 0.7 mbar per 10° angle ≤ 0.05 mbar per 10° angle ≤ 0.7 mbar per 10° angle depending on the filling liquid
in the mounting flange
Influence of power supply 0.005 % per 1 V change in voltage
Operating conditions
Installation conditions
Process connection vertically Process connection vertically
 Installation note any any determined by flange
downwards downwards
Ambient conditions
 Ambient temperature (in hazardous
zones note temperature class)
Meas. cell
- Meas. cell with sil. oil fill. -40 to +85 °C
Span 30 bar at PN 420 -20 to +85 °C
- Meas. cell with inert filling liquid -20 to +85 °C
- Digital display -30 to +85 °C
 Ambient temperature limit see ambient temperature
 Storage temperature -30 to +85 °C
 Cimate class
- Condens. permissible
 Degree of protection (EN 60 529) IP 65
 EMC
- Spurious emission EN 50 081-1
- Interference resistance EN 50 082-2 and NAMUR NE 21

85
Process conditions
 Process temperature
- Meas. cell with sil. oil fill. -40 to +100 °C
Span 30 bar at PN 420 -20 to +85 °C
Technical data: SITRANS P DS III

Device type: Pressure Differential pressure Absolute pressure Filling level


7MF4033 7MF4433 / 7MF4533 Pressure series 7MF4233 Diff. pressure series 7MF4333 7MF4633

- Meas. cell with inert filling liquid -20 bis +100 °C

86
Span 30 bar -20 to +85°C -20 to +85°C
 Process temperature limit see process temperature
 Process pressure limit see chapter 9.2. Nominal pressure (PN) see chapter 9.2. Nominal pressure (PN)
Constructional design
Weight (without options) about 1.5 kg about 4 kg about 1.5 kg about 4.5 kg
Transmitter with mounting flange without tube DIN: about 11 to 13 kg
ANSI: about 11 to 18 kg
Dimensions see fig. 45 see fig. 47 see fig. 47 see fig. 46 see fig. 48
Material
 Material of wetted parts
- Connection shank Stainless st., M.-No. 1.4401 or Stainless st., M.-No. 1.4401 or
Hastelloy C4, M.- No. 2.4610 Hastelloy C4, M.- No. 2.4610
- Oval flange Stainless st., M.-No. 1.4401 Stainless st., M.-No. 1.4401
- Seal diaphragm Stainless steel, M.-No. 1.4404
or Hastelloy C276, M.- No. 2.4819
Monel, M.-No. 2.4360 Monel, M.-No. 2.4360
Tantalum or gold Tantalum or gold
- Process flanges and sealing screw Stainless st., M.-No. 1.4408, Stainless st., M.-No. 1.4408,
Hasteloy C4, M.-No. 2.4610 or Hasteloy C4, M.-No. 2.4610 or
Monel, M.-No. 2.4360 Monel, M.-No. 2.4360
- O- Ring FPM (Viton) or optionally: FPM (Viton) or optionally:
PTFE, FEP, FFPM and NBR PTFE, FEP, FFPM and NBR
Seal material (O-ring) for mounting flange
in the process flanges
for standard applications FPM (Viton)
for vacuum applications copper
- High pressure side
Seal diaphragm at mounting flange Stainless st., M.-No. 1.4571,
Monel 400 M.-No. 2.4360,
Hastelloy B2 M.-No. 2.4617,
Hastelloy C276, M.-No. 2.4819,
Hastelloy C4, M.-No. 2.4610,
Tantalum, PTFE, ECTFE
Sealing face smooth DIN 2526, Form D or
ANSI B16.5 RF for stainless st.
M.-No. 1.4571, DIN 2526 Form E
or ANSI B16.5 RSFS for
other materials.
- Low pressure side
Seal diaphragm Stainless steel M.- No 1.4404
Process flanges and sealing screw Stainless steel M.- No 1.4408
Connection shank Stainless steel M.- No 1.4401
O- ring FPM (Viton)
 Material of non-wetted parts
- Electronics housing Low copper diecast aluminium GD-ALSi 12, polyester-based varnish or stainless steel precision casting, stainless steel rating plate
- Process flange screws steel, galvanized, yellowed steel, galvanized, yellowed
chromed or stainless steel chromed or stainless steel
- Mounting bracket (optional) steel, galvanized and yellow-chromed or stainless steel

SITRANS P, Series DS III


A5E00047090-01
7HFKQLFDO'DWD

Meas. cell filling silicone oil filling or inert liquid (maximum pressure 160 bar for oxygen measurement) Silicone oil
Filling liquid mounting flange Silicone oil or different
version
Technical data: SITRANS P DS III

Device type: Pressure Differential pressure Absolute pressure Filling level


7MF4033 7MF4433 / 7MF4533 Pressure series 7MF4233 Diff. pressure series 7MF4333 7MF4633
Process connection Connection shank G½A Female thread 1/4 - 18 NPT and Connection shank G½A Female thread 1/4 - 18 NPT and
DIN 16 288, female thread Flange connection DIN DIN 16 288, female thread Flange connection DIN
½ -14NPT or oval flange 19213 with mounting thread ½ -14NPT or oval flange 19213 with mounting thread
maximum range 160 bar maximum range 160 bar
with mounting thread M10 / M10 (PN 160) with mounting thread M10 / M10 or 7/16 - 20 UNF

A5E00047090-01
7HFKQLFDO'DWD

M12 or 7/16 -20 UNF M12 or 7/16 -20 UNF M12 or 7/16 -20 UNF
High pressure side DIN and ANSI flange
Low pressure side Female thread 1/4 - 18 NPT and

SITRANS P, Series DS III


Flange connection DIN
19213 with mounting thread
M10 or 7/16 - 20 UNF
Electrical connection Screw terminals, cable inlet or screwed gland Pg 13.5 (adapter), M20 x 1.5 or ½ - 14 NPT, or Han 7D/Han 8U plug
Display and user interface
Input keys 3 for local programming directly on the device
Digital display installed, cover with window (optional)
Power supply (UH)
Terminal voltage at the transmitter DC 10.5V to 45V or
DC 10.5V to 30 V in intrinsically safe operation
Ripple Upp ≤ 0.2 V (47 to 125 Hz)
Noise Ueff ≤ 1.2 mV (0.5 to 10 kHz)
Certificates and licenses The specifications in the official EC test certificate and the applicable supplements are exclusively valid
CENELEC DIN EN 50 014: 1997, EN 50 020: 1994 and EN 50 284: 1999
 Intrinsic safety Ex II 1/2 G EEx ia IIC T4 / T5 / T6
- EC test certificate TÜV 99 ATEX 1494
- Max. ambient temperature +85 °C temperature class T4, +70 °C temperature class T5, +60 °C temperature class T6
- Connection to certified intrinsically safe Ui = 30 V, Ii = 100 mA, Pi = 750 mW Ri = 300 Ω
circuits with the maximum values
- Active internal inductance Li = 1 mH
- Active internal capacitance Ci = 6 nF
 Explosion proof planned
- Certificate of conformity planned
- Max. ambient temperature planned
 Ex-tested zone 2n planned
- Registration number planned
FMRC (Factory Mutual Research Corp.) planned
 Intrinsic safety and explosion-proof planned
 Explosion-proof planned
 Dust-ignition proof planned
 Intrinsically safe planned
 Entity parameters planned
CSA (Certificate of Compliance) planned
Communication
Load when connecting a
 HART Communicators 230 to 1100 Ohm
 HART-Modems 230 to 500 Ohm

87
Line 2-wire screened: ≤ 3.0 km multi-wire screened: ≤ 1.5 km
Protocol HART, Version 5.x
PC/Laptop requirements IBM-compatible, RAM > 32 Mbytes, Hard disk > 70 Mbytes, RS 232 interface, VGA graphics
Software for PC/Laptop WINDOWS 95 / 98 / NT 4.0 and SIMATIC PDM
7HFKQLFDO'DWD

 0HDVXULQJVSDQVDQGRYHUORDGOLPLWV

 3UHVVXUH

0HDVXULQJVSDQ 3URFHVVSUHVVXUH
FRQWLQXRXVO\DGMXVWDEOH OLPLWV
/RZHU 8SSHU
0.01 to 1 bar = 1 to 100.0 kPa -1 bar 6 bar
0.04 to 4 bar = 4 to 400.0 kPa -1 bar 10 bar
0.16 to 16 bar = 16 kPa to 1.6 MPa -1 bar 32 bar
0.63 to 63 bar = 63 kPa to 6.3 MPa -1 bar 100 bar
1.60 to 160 bar = 160 kPa to 16.0 MPa -1 bar 250 bar1)
4.00 to 400 bar1) = 400 kPa to 40.0 MPa1) -1 bar 600 bar1)
1) for oxygen measurement max. 160 bar

 'LIIHUHQWLDOSUHVVXUHDQGIORZ

1RPLQDOSUHVVXUH 0HDVXULQJVSDQ
FRQWLQXRXVO\DGMXVWDEOH
PN 324) 1.0 to 20 mbar = 0.10 to 2 kPa
PN 160 1.0 to 60 mbar = 0.10 to 6 kPa
PN 160 2.5 to 250 mbar = 0.25 to 25 kPa
or 6.0 to 600 mbar = 0.60 to 60 kPa
PN 4201)2)3) 1.6 to 1600 mbar = 1.60 to 160 kPa
50.0 to 5000 mbar = 5.00 to 500 kPa
300.0 to 30000 mbar = 30.00 to 3000 kPa
1) for oxygen measurement max. 160 bar
2) measuring cell filling only silicone oil
3) With process flange screw of stainless steel only PN 315
4) not suitable for remote seal mounting

SITRANS P, Series DS III


88 A5E00047090-01
Technical Data

9.1.3 Absolute pressure from the pressure series

Measuring span Process


continuously adjustable pressure limit
8.3 to 250 mbar = 0.83 to 25.0 kPa 6 bar
43.3 to 1300 mbar = 4.33 to 130.0 kPa 10 bar
166.6 to 5000 mbar = 16.60 to 500.0 kPa 30 bar
1000 to 30000 mbar = 100.00 to 3000.0 kPa 100 bar

+
Note on 250 mbar cell

See below.

9.1.4 Absolute pressure from the differential pressure series

Measuring span Process


continuously adjustable pressure limit
8.3 to 250 mbar = 0.83 to 25.0 kPa 32 bar
43.3 to 1300 mbar = 43.33 to 160.0 kPa 32 bar
166.6 to 5000 mbar = 16.60 to 500.0 kPa 32 bar
1000 to 30000 mbar = 100.00 to 3000.0 kPa 160 bar
5300 to 160000 mbar = 530.00 to 16000.0 kPa 250 bar*

* 160 bar at process connection M10.

+
Note on 250 mbar cell

This measuring cell is designed for operation within the measuring limits 0 mbar
(absolute) to 250 mbar (absolute). When storing under normal ambient pressure of
about 1000 mbar (absolute), the measuring cell is in the overload state. An
overload error may occur in this. The overload error disappears in operation within
the measuring limits. Then the transmitter operates again within its specification,
the start of scale may have to be readjusted.

In pressure measurements with repeated exceeding of the measuring limits (e.g.


batch processes with transitions between vacuum and ventilation) a measuring
cell with a maximum range of 1300 mbar should be selected to avoid overloading.

9.1.5 Filling level

Measuring span Nominal pressure


continuously adjustable
25 to 250 mbar = 2.50 to 25.0 kPa PN 16 or PN 40
25 to 600 mbar = 2.50 to 60.0 kPa
53 to 1600 mbar = 5.30 to 160.0 kPa
160 to 5000 mbar = 16.00 to 500.0 kPa

SITRANS P, Series DS III


A5E00047092-01 89
Technical Data

9.2 Dimensions

15 138 55 10
30 *
50 28 6 2
0

20

50
80

3 3

117

171
5 4

237
68
1

120

36.5
72

123

* for Pg 13,5 with adapter 7

105

1 Process connection, ½ – 14 NPT, 4 Connection side


Connection shank G½A or oval flange 5 Electronics side, digital display
2 Blanking plug (greater length for cover with window)
3 Electrical Connection: 6 Protective cap over keys
Screwed gland Pg 13.5 (adapter) 7 Mounting bracket (optional)
Screwed gland M20 x 1.5 or
Screwed gland ½ - 14 NPT or
Han 7D/Han 8 U plug

Figure 46 SITRANS P, Series DS III transmitter for pressure and absolute pressure from the pressure
series

SITRANS P, Series DS III


90 A5E00047092-01
Technical Data

15 138 * 100
30 **
50 7 3

20

50
80

198
6 5 9

261
10

1 8

2
134

11

72 * 161 for series DS with PROFIBUS-PA


105 ** 45 for Pg 13,5 with adapter 68
120

1 Process connection ¼ - 18 NPT 5


Connection side
for absolute pressure (+) side 6
Electronics side, digital display
2 Mounting thread M10, M12 or 7/16 - 20 UNF (greater length for cover with window)
3 Dummy plug 7 Protective cover over keys
4 Electrical Connection: 8 Sealing screw
Screwed gland Pg 13.5 (adapter) 9 Side vent for measuring liquid
M20 x 1.5 or ½ - 14 NPT or 10 Side vent for measuring gas (supplement H02)
Han 7D/Han 8 U plug 11 Mounting bracket (optional)

Figure 47 SITRANS P, Series DS III transmitter for differential pressure and flow as well as absolute
pressure from the differential pressure series

SITRANS P, Series DS III


A5E00047092-01 91
Technical Data

1 Process connection of low pressure side ¼ – 18 NPT 10 Blanking plug (only for Pg 13.5 and Han 7D)
2 Mounting thread M10 or 7/16 -20 UNF 11 Protective cover over keyboard
3 Connection side 12 Electrical Connection:
4 Electronics side, digital display Cable gland Pg 13.51, 2
(greater length for cover with window) M20 x 1.52 or ½ – 14 NPT or
5 Sealing screws Han 7D plug1, 2

1 not for ”explosion-proof” degree of protection


2 Not in FM exp/CSA exp degree of protection

Figure 48 SITRANS P, Series DS III transmitter for differential pressure and flow, order option H03 (half
flanges)

A special half flange is available for better reading of the SITRANS P, Series DS III
transmitter’s digital display. It is a particular advantage when mounting the
transmitter on a valve manifold with vertical active pressure lines.

SITRANS P, Series DS III


92 A5E00047092-01
Technical Data

210 *
185
10
7
0

3
4

165
L
2

8
41.3

d4
d5

D
k
4 1 54 108

nxd2
b
f

7
6
5

* 225 for Pg 13,5 with adapter


** Dimensions in brackets for (92)**
series DS with PROFIBUS-PA 69 69
82
(105)**

1 Process connection of low pressure side ¼ – 18 NPT 5 Connection side


2 Mounting thread M10, M12 or 7/16 -20 UNF 6 Electronics side, digital display
3 Blanking plug (greater length for cover with window)
4 Electrical Connection: 7 Protective cover over keyboard
Cable gland Pg 13.5 (with adapter) 8 Sealing screw with valve
M20 x 1.5 or ½ -14 NPT or
Han 7D/Han 8 U plug

Figure 49 SITRANS P, Series DS III transmitter for filling level

SITRANS P, Series DS III


A5E00047092-01 93
Technical Data

SITRANS P, Series DS III


94 A5E00047092-01
Care and maintenance
10
Check the device’s start of scale from time to time.

In the event of a fault decide:

• whether the internal self-test has detected a fault, e.g. sensor break, HW/FW
error etc.
Displays:
- digital display: display ”ERROR” and moving error text
- analog output: factory setting Failure current 3.6 mA or 22.8 mA
or depending on the parameterization
- HART: detailed error list for display in the HART Communicator
or SIMATIC PDM
• serious hardware error the processor is not working
Displays:
- digital display: no defined display
- analog output: failure current < 3.6 mA

In the event of a fault you can exchange the electronics as described in Chapter 6
under consideration of the warnings.

SITRANS P, Series DS III


A5E00047092-01 95
Care and maintenance

SITRANS P, Series DS III


96 A5E00047092-01
Ordering data
11

SITRANS P, Series DS III


A5E00047092-01 97
SITRANS P transmitter for pressure

Product description Order no.


SITRANS P transmitter for pressure 7MF4033-
Two-wire technology, series DS III -
Measuring cell filling Measuring cell cleaning
Silicone oil normal 1
Inert grease-free 3
Span
0.01 to 1 bar B
0.04 to 4 bar C
0.16 to 16 bar D
0.63 to 63 bar E
1.6 to 160 bar F
4.0 to 400 bar G
Material of wetted parts
Seal diaphragm Connection shank
Stainless steel Stainless steel A
Hastelloy Stainless steel B
Hastelloy Hastelloy C
Version for diaphragm remote seal Y 0
Process connection
Connection shank G1/2 A 0
Female thread 1/2-14 NPT 1
Oval flange and connection shank, stainless steel,
max. span: 160 bar
- Mounting thread 7/16-20 UNF 2
- Mounting thread M10 3
Material of non-wetted parts
Housing diecast aluminum 0
Housing stainless steel precision casting 3
Vesion
Standard version 1
International version (in preparation)
English plate description and documentation
in 5 languages on CD 2
Explosion protection
without explosion protection A
with explosion protection (CENELEC)
- Degree of protection "Intrinsic safety" (EEx ia) B
- Degree of protection "Explosion-proof" (EEx d) 1) D
- Degree of prot. "Intr. Safety and ex.-proof" (EEx ia + EEx d) 1) P
Application in Zone 2 n (TÜV) E
with explosion protection (FM + CSA)
- intrinsic safe und explosion proof (is + ep) 1) N C
Electrical connection / cable inlet
Screwed gland PG 13.5 2) (Adapter) A
Female thread M 20 x 1.5 B
Female thread 1/2-14 NPT C
Han 7D plug 2) D
Housing cover / display
without window (digital display covered, setting: mA) 1
with window (digital display, visible, setting: mA) 6
with window (digital display visible, setting: acc. to spec,
short spec. Y21 necessary) 7
1) 2)
Without cable screwed gland Not in connection with "ex-proof" protection
Scope of delivery:
Transmitter as ordered, 1 brief instructions (Leporello)

Ordering example:
Position line: 7MF4033-1EA00-1AA5-Z
B-line: A01+Y01+Y21
C-line: Y01: 10 ... 20 bar
C-line: Y21+D100+D36: bar

SITRANS P, Series DS III


98 A5E00047092-01
SITRANS P transmitter for pressure

Other versions
Add "-Z" to order no. and add short spec.. 7MF4033 - . . . . . - . . . . - Z
Transmitter with mounting bracket of
- steel A01
- stainless steel A02
Han 7D plug (metal, gray) A30
Han 8U plug (instead of Han 7D) A31
Labeling of rating plate (instead of German)
- English B11
- French B12
- Spanish B13
- Italian B14
Manufacturer test certificate M acc. to DIN 55 350, part 18, and
acc. to ISO 8402 C11
Acceptance test certificate B acc. to DIN 50 049 / EN 10 204-3.1 B C12
Works certificate acc. to DIN 50 049-2.2 / EN 10 204-2.2 C14
Esetting upper output signal limit to 22.0 mA D05
Acid gas version acc. to NACE
Only in connection with Hastelloy seal diaphragm D07
IP 68 (not in connection with Han 7D/Han 8U plug,
Cable screwed gland Pg 13.5 and measuring cells < 63 bar) D12
Application in zone 0 (basic device EEx ia) E02
Oxygen application (in oxygen measurement and
inert filling liquid max. 160 bar) E10
Range to be set, specify in clear text:
Y01: ... to ... mbar, bar, kPa, MPa, ... (maximum 27 characters) Y01
Measuring point number / description
(max. 16 characters) specify in clear text:
Y15:................ Y15
Meas. point message (max. 27 characters) specify in clear text:
Y16:........................... Y16
Setting digital display, specify in clear text
Y21: mbar, bar, kPa, MPa, ... Y21
Other factory pre-settings than "Y01", "Y21" und "D05" are not possible.

SITRANS P, Series DS III


A5E00047092-01 99
SITRANS P transmitter for absolute pressure
from pressure series
Product description Order no.

SITRANS P transmitter for absolute pressure


from pressure transmitter series, 7MF4233-
two-wire technology, serie DS III -
Meas. cell filling Meas. cell cleaning
Silicone oil normal 1
Inert grease-free 3
Span
8.3 to 250 mbar D
43 to 1.300 mbar F
160 to 5.000 mbar G
1.000 to 30.000 mbar H
Material of the wetted parts)
Seal diaphragm Parts of meas. cell
Stainless steel Stainless steel A
Stainless steel Hastelloy B
Hastelloy Hastelloy C
Version for diaphragm remote seal 1) Y 0
Process connection
Connection shank G 1/2 A 0
Female thread 1/2-14 NPT 1
Oval flange and connection shank stainless steel
- Mounting thread 7/16-20 UNF, max. span 160 bar 2
Oval flange and connection shank stainless steel
- Mounting thread M10, max. span 160 bar 3
Material of the non-wetted parts
Housing diecast aluminum 0
Housing stainless steel precision casting 3
Version
Standard version 1
International version (in preparation)
English plate description and documentation
in 5 languages on CD 2
Explosion protection
without explosion protection A
with explosion protection (CENELEC)
- Degree of protection "Intrinsic safety" (EEx ia) B
- Degree of protection "Explosion proof" (EEx d) 1) D
- Degree of prot. "Intr. safety and ex-proof" (EEx ia + EEx d) 1) P
Application in zone 2 n (TÜV) E
with explosion protection (FM + CSA)
- intrinsic safe und explosion proof (is + ep) 1) N
Electrical connection / cable inlet
Screwed gland PG 13.5 3) (Adapter) A
Female thread M 20 x 1.5 B
Female thread 1/2-14 NPT C
Han 7D plug 3) D
Housing cover / display
without window (digital display covered, setting: mA) 1
with window (digital display visible, setting: mA) 6
with window (digital display visible, setting: as specified,
short spec. Y21 necessary) 7
1) 3)
Version 7MF4333-1DY... Only up to max. span of 200 mbar Not in connection with "explosion-proof"
2) degree of protection
Without cable screwed gland
Scope of delivery:
Transmitter as ordered, 1 brief instructions (Leporello)
Ordering example:
Position line: 7MF4233-1HA00-1AA6-Z
B-line: A01+Y01
C-line: Y01: 0 ... 20 bar

SITRANS P, Series DS III


100 A5E00047092-01
SITRANS P transmitter for absolute pressure
from the pressure series
Other versions
Add "-Z" to order no. and add short spec. 7MF4233 - . . . . . - . . . . - Z
Transmitter with mounting bracket of
- steel A01
- stainless steel A02
Han 7D plug (metal, gray) A30
Han 8U plug (instead of Han 7D) A31
Labeling of the rating plate (instead of German)
- English B11
- French B12
- Spanish B13
- Italian B14
Manufacturer test certificate M acc. to DIN 55 350, Part 18, and
acc. to ISO 8402 C11
Acceptance test certificate B acc. to DIN 50 049 / EN 10 204-3.1 B C12
Works certificate acc. to DIN 50 049-2.2 / EN 10 204-2.2 C14
Setting of upper output signal limit to 22.0 mA D05
Acid gas version acc. to NACE
Only in connection with Hastelloy seal diaphragm D07
IP 68 (not in connection with Han 7D/Han 8U plug or
cable screwed gland Pg 13.5) D12
Application in zone 0 (basic device EEx ia) E02
Oxygen application (for oxygen measurement and
inert filling liquid max. 160 bar) E10
Measuring range to be set, specify in clear text:
Y01: 0 to ... mbar, bar, kPa, MPa, ... (maximum 27 characters) Y01
Measuring point number / description
(max. 16 characters) specify in clear text:
Y15:................ Y15
Meas. point message (max. 27 characters) specify in clear text:
Y16:........................... Y16
Setting digital display, specify in clear text
Y21: mbar, bar, kPa, MPa, ... Y21
Other factory pre-setings than "Y01", "Y21" and "D05" are not possible.

SITRANS P, Series DS III


A5E00047092-01 101
SITRANS P for absolute pressure
from differential pressure series
Product description Order no.
SITRANS P transmitter for absolute pressure 7MF4333-
from differential pressure transmitter series,
two-wire technology, series DS III -
Meas. cell filling Meas. cell cleaning
Silicone oil normal 1
Inert grease-free 3
Span
8.3 to 250 mbar D
43 to 1.300 mbar F
160 to 5.000 mbar G
1.000 to 30.000 mbar H
5.300 to 160.000 mbar K E
Material of the wetted parts (stainless steel process flanges)
Seal diaphragm Parts of the measuring cell
Stainless steel Stainless steel A
Stainless steel Hastelloy B
Hastelloy Hastelloy C
Tantalum Tantalum E
Monel Monel H
Gold 1) Gold L
2) Y
Version for diaphragm remote seal
Process connection
Female thread 1/4-18 NPT with flange connection
DIN 19213 with
venting against process connection
- Mounting thread M 10 0
7/16-20 UNF 2
Venting on side of process flange 3)
- Mounting thread M 10 4
7/16-20 UNF 6
Material of the non-wetted parts
Process flange screws Electronics housing
Steel Diecast aluminum 0
Stainless steel Diecast aluminum 2
Stainless steel Stainless steel precision casting 3
Version
Standard version 1
International version (in preparation)
English plate labeling and documentation
in 5 languages on CD 2
Explosion protection
without explosion protection A
with explosion protection (CENELEC)
- Degree of protection "Intrinsic safety" (EEx ia) B
- Degree of protection "Explosion-proof" (EEx d) 4) D
3) 4) P
- Degree of prot. "Intr. safety and ex-proof" (EEx ia + EEx d)
Application in zone 2 n (TÜV) E
with explosion protection (FM + CSA)
- intrinsic safe und explosion proof (is + ep) 3) 4) N C
Electrical connection / cable inlet
Screwed gland PG 13.5 5) (Adapter) A
Female thread M 20 x 1,5 B
Female thread 1/2-14 NPT C
Han 7D plug 5) D
Housing cover / display
without window (digital display covered, setting: mA) 1
with window (digital display visible, setting: mA) 6
with window (digital display visible, setting: as specified,
short spec. Y21 necessary) 7
1) 4)
Only in connection with stainless steel process flange screws Without cable screwed gland
2) 5)
Version 7MF4333-1DY... Only up to a max. span of 200 mbar Not in connection with "explosion proof"
3) degree of protection
Not for measuring cell 5.3 to 160 bar
Scope of delivery:
Transmitter as ordered, 1 brief instructions (Leporello)
1 sealing screw (same material as process flange)
Ordering example:
Position line: 7MF4333-1HA00-1AA6-Z
B-line: A01+Y01
C-line: Y01: 0 ... 20 bar
SITRANS P, Series DS III
102 A5E00047092-01
SITRANS P transmitter for absolute pressure
from differential pressure series
Other versions
Add "-Z" to order no. and add short spec. 7MF4334 - . . . . . - . . . . - Z
Transmitter with mounting bracket of
- steel A01
- stainless steel A02
Process flange O-ring (instead of FPM (Viton)) of
- PTFE (Teflon) A20
- FEP (with silicone core, foodstuff compatible) A21
- FFPM (Kalrez) A22
- NBR (buna N) A23
Han 7D plug (metal, gray) A30
Han 8U plug (instead of Han 7D) A31
Sealing screw (1/4-18 NPT) with valve
in same material as process flange A40
Labeling of rating plate (instead of German)
- English B11
- French B12
- Spanish B13
- Italian B14
Manufacturer test certificate M acc. to DIN 55 350, Part 18, and
acc. to ISO 8402 C11
Acceptance test certificate B acc. to DIN 50 049 / EN 10 204-3.1 B C12
Works certificate acc. to DIN 50 049-2.2 / EN 10 204-2.2 C14
Setting of the upper output signal limit to 22.0 mA D05
Acid gas version acc. to NACE
Only in connection with Hastelloy seal diaphragm and
stainless steel process flange screws D07
IP 68 (not in connection with Han 7D/Han 8U plug or
cable screwed gland Pg 13.5) D12
Application in zone 0 (basic device EEx ia) 4) E02
Side vent for gas measurement 4) H02
Process flange of:
- Hastelloy K01
- Monel K02
Measuring range to be set, specify in clear text:
Y01: 0 to ... mbar, bar, kPa, MPa, ... (maximum 27 characters) Y01
Measuring point number / description
(max. 16 characters), specify in clear text:
Y15:................ Y15
Meas. Point message (max. 27 characters) specify in clear text:
Y16:........................... Y16
Setting digital display, specify in clear text
Analog display, specify in clear text
Y21: mbar, bar, kPa, MPa, ... Y21
Other factory pre-settings than "Y01", "Y21" and "D05" are not possible.

SITRANS P, Series DS III


A5E00047092-01 103
SITRANS P transmitter for differential pressure and flow
PN 32/160
Product description Order no.
SITRANS P transmitter for differential pressure and flow 7MF4433-
Two-wire technology, series DS III, PN 32/160 -
Meas. cell filling Meas. cell cleaning
Silicone oil normal 1
Inert grease-free 3
PN 32, span 1 to 20 mbar 1) B
PN 160, span 1 to 60 mbar C
2.5 to 250 mbar D
6 to 600 mbar E
16 to 1.600 mbar F
50 to 5.000 mbar G
300 to 30.000 mbar H
Material of the wetted parts (stainless steel process flanges )
Seal diaphragm Parts of the meas. cell
Stainless steel Stainless steel A
Hastelloy Stainless steel B
Hastelloy Hastelloy C
Tantalum 2) Tantalum E
Monel 2) Monel H
Gold 2), 3) Gold L
Version for diaphragm remote seal Y
Process connection
Female thread 1/4-18 NPT and flange connection acc. to DIN 19 213
Venting against process connection,
- Mounting thread M 10 0
- Mounting thread 7/16-20 UNF 2
Venting on side of process flanges,
- Mounting thread M 10 4
- Mounting thread 7/16-20 UNF 6
Material of the non-wetted parts
Process flange screws Electronics housing
Steel Diecast aluminum 0
Stainless steel Diecast aluminum 2
Stainless steel Stainless steel precision casting 3
Version
Standard version 1
International version (in preparation)
English plate labeling and documentation
in 5 languages on CD 2
Explosion protection
without explosion protection A
with explosion protection (CENELEC)
- Degree of protection "Intrinsic safety" (EEx ia) B
- Degree of protection "Explosion-proof" (EEx d) 1) D
- Degree of prot. "Intr. Safety and ex-proof" (EEx ia + EEx d) 1) P
Application in zone 2 n (TÜV) E
with explosion protection (FM + CSA)
- intrinsic safe und explosion proof (is + ep) 1) N C
Electrical connection / cable inlet
Screwed gland PG 13.5 5) (Adapter) A
Female thread M 20 x 1.5 B
Female thread 1/2-14 NPT C
Han 7D plug 5) D
Housing cover / display
without window (digital display covered, setting: mA) 1
with window (digital display visible, setting: mA) 6
with window (digital display visible, setting: as specified,
short spec. Y21 necessary) 7
1) 3)
Not suitable for remote seal mounting Only in connection with stainless steel process flange screws
2) 4)
Only in connection with max. span 250, 1,600, 5,000 and 30,000 mbar Without cable screwed gland
5)
Not in connection with "explosion-proof" degree of protection
Scope of delivery: Ordering example:
Transmitter as ordered, 1 brief instructions (Leporello) Position line: 7MF4433-1DA00-1AA1-Z
2 sealing screws (same material as process flange), B-line: A01+B11+C14+Y01+Y15
C-line: Y01: 50 ... 150 mbar
C-line: Y15: PIC 1758

SITRANS P, Series DS III


104 A5E00047092-01
SITRANS P transmitter for differential pressure and flow
PN 32/160
Other versions
Add "-Z" to order no. and add short spec. 7MF4433 - . . . . . - . . . . - Z
Transmitter with mounting bracket of
- steel A01
- stainless steel A02
Process flange O-ring (instead of FPM (Viton)) of
- PTFE (Teflon) A20
- FEP (with silicone core, foodstuff compatible) A21
- FFPM (Kalrez) A22
- NBR (buna N) A23
Han 7D plug A30
Han 8U plug (instead of Han 7D) A31
Sealing screws (1/4-18 NPT) with valve
in same matereial as process flanges A40
Labeling of rating plate (instead of German)
- English B11
- French B12
- Spanish B13
- Italian B14
Manufacturer test certificate M acc. to DIN 55350, Part 18,
and acc. to ISO 8402 C11
Acceptance test certificate B acc. to DIN 50 049 / EN 10 204-3.1 B C12
Works certificate acc. to DIN 50 049-2.2 / EN 10 204-2.2 C14
Setting the upper output current limit to 22.0 mA D05
Acid gas version acc. to NACE
Only in connection with Hastelloy seal diaphragm and
stainless steel process flange screws D07
IP 68 (not in connection with Han 7D/Han 8U plug and
cable screwed gland Pg 13.5) D12
Application in zone 0 (basic device EEx ia) E02
Overfill protection for combustible and non-combustible liquids
(max. PN 32) (basic device EEx ia) E08
Oxygen application (for oxygen measurement and inert E10
liquid max. 160 bar)
Switching the process connection side
(HP side: left, LP side: right) H01
Lateral vent for gas measurement H02
Stainless steel process flanges for vertical active pressure lines
(not in connection with the supplements K01 or K02) H03
Process flanges of:
- Hastelloy K01
- Monel K02
Measuring range to be set, specify in clear text,
- for linear characteristic:
Y01: ... to ... mbar, bar, kPa, MPa, ... (maximum 27 characters) Y01
- for square rooting characteristic:
Y02: 0 to ... mbar, bar, kPa, MPa, ... (maximum 27 characters) Y02
Measuring point number / description
(max. 16 characters) specify in clear text:
Y15:................ Y15
Meas. Point message (max. 27 characters) specify in clear text:
Y16:........................... Y16
Setting digital display specify in clear text
Y21: mbar, bar, kPa, MPa, ... Y21
Other factory presettings than "Y01" or "Y02", "Y21" and "D05" are not possible.

SITRANS P, Series DS III


A5E00047092-01 105
SITRANS P transmitter for differential pressure and flow
PN 420
Product description Order no.
SITRANS P transmitter for differential pressure and flow 7MF4533-
Two-wire technology, series DS III 1 -
Span
2.5 to 250 mbar D
6 to 600 mbar E
16 to 1.600 mbar F
50 to 5.000 mbar G
300 to 30.000 mbar H
Material of the wetted parts (stainless steel process flanges)
Seal diaphragm Parts of the meas. cell
Stainless steel Stainless steel A
Hastelloy Stainless steel B
Gold 1) Gold L
Process connection
Female thread 1/4-18 NPTand flange connection
DIN 19 213
Venting against process connection
- Mounting thread M12 1
- Mounting thread 7/16-20 UNF 3
Material of the non-wetted parts
Process flange screws Electronics housing
Steel Diecast aluminum 0
Stainless steel (≤ PN 315) Diecast aluminum 2
Stainless steel (≤ PN 315) Stainless steel prec. casting 3
Version
Standard version 1
International version (in preparation)
English plate labeling and documentation
in 5 languages on CD 2
Explosion protection
without explosion protection A
with explosition protection (CENELEC)
Degree of protection "Intrinsic safety" (EEx ia) B
Degree of protection "Explosion proof" (EEx d) 2) D
Degree of prot. "Intr. Safety and ex-proof" (EEx ia + EEx d) 2) P
Application in zone 2 n (TÜV) E
with explosion protection (FM + CSA)
intrinsic safe and explosion proof (is + ep) 2) N C
Electrical connection / cable inlet
Screwed gland PG 13.5 3) (Adapter) A
Female thread M 20 x 1.5 B
Female thread 1/2-14 NPT C
Han 7D plug 3) D
Housing cover / Display
without window (digital display covered, setting: mA) 1
with window (digital display visible, setting: mA) 6
with window (digital display visible, setting: as specified,
short spec. Y21 necessary) 7
1)
Only in connection with max. span 250, 1,600, 5,000 und 30,000 mbar,
max. PN 315 and only in connection with stainless steel process flange screws
2)
Without cable screwed gland
3)
Not in connection with "explosion proof" degree of protection
Scope of delivery: Transmitter as ordered, 1 brief instructions (Leporello)
2 sealing screws (same material as process flanges)
Ordering example:
Position line: 7MF4533-1DA10-1AA1-Z
B-line: Y01
C-line: Y01: 90 ... 143 mbar

SITRANS P, Series DS III


106 A5E00047092-01
SITRANS P for differential pressure and flow
PN 420
Other versions
Add "-Z" to order no. and add short spec. 7MF4533 - . . . . . - . . . . -Z
Transmitter with mounting bracket of
- steel A01
- stainless steel A02
Process flange O-ring (instead of FPM (Viton)) of
- PTFE (Teflon) A20
- FEP (with silicone core, foodstuff compatible) A21
- FFPM (Kalrez) A22
- NBR (buna N) A23
Han 7D plug (metal, gray) A30
Han 8U plug (instead of Han 7D) A31
Sealing screw (1/4-18 NPT) with valve
in the same material as the process flanges A40
Labeling of the rating plate (instead of German)
- English B11
- French B12
- Spanish B13
- Italian B14
Manufacturer test certificate M acc. to DIN 55350, Part 18,
and acc. to ISO 8402 C11
Acceptance test certificate B acc. to DIN 50 049 / EN 10 204-3.1 B C12
Works certificate acc. to DIN 50 049-2.2 / EN 10 204-2.2 C14
Setting the upper output signal limit to 22.0 mA D05
Acid gas version acc. to NACE, only in connection with
Hastelloy seal diaphragm and stainless steel process flanges
max. PN 315 D07
Stainless steel process flange screws (PN 420),
Basic device with stainless steel process flange screws D09
IP 68 (not in connection with Han 7D/Han 8U plug and
cable screwed gland Pg 13.5) D12
Application in zone 0 (basic device EEx ia) E02
Switching the process connection side
(HP side: left, LP side: right) H01
Lateral vent for gas measurement H02
Stainless steel process flanges for vertical active pressure lines
(not in connection with the supplements K01 or K02) H03
Measuring range to be set, specify in clear text,
- with linear characteristic:
Y01: ... to ... mbar, bar, kPa, MPa, ... (maximum 27 characters) Y01
- with square rooting characteristic:
Y02: 0 to ... mbar, bar, kPa, MPa, ... (maximum 27 characters) Y02
Meas. Point number / description
(max. 16 characters) specify in clear text: Y15:................ Y15
Meas. point message (max. 27 characters) specify in clear text:
Y16:........................... Y16
Setting digital display, specify in clear text
Y21: mbar, bar, kPa, MPa, ... Y21
Other factory presettings than "Y01" or "Y02", "Y21" or "D05" are not possible.

SITRANS P, Series DS III


A5E00047092-01 107
SITRANS P Transmitter for Filling Level

Product description Order No.


SITRANS P transmitter for filling level
Two-wire technology 7MF4633-
Series DS III 1 Y -
Span
25 to 250 mbar D
25 to 600 mbar E
53 to 1.600 mbar F
160 to 5.000 mbar G
Process connection of low pressure side
Female thread 1/4-18 NPT and flange connection
DIN 19 213 with mounting thread
- M 10 0
- 7/16-20 UNF 2
Material of the non-wetted parts
Process flange screws Electronics housing
Steel Diecast aluminium 0
Stainless steel Diecast aluminum 2
Stainless steel Fine precision stainless steel 3
Version
Standard version 1
International version (in preparation)
English plate labeling and documentation
in 5 languages on CD 2
Explosion protection
without explosion protection A
with explosion protection (CENELEC)
- Degree of protection "Intrinsic safety" (EEx ia) B
- Degree of protection "Explosion proof" (EEx d) 1) D
- Degr. of protection "Intr. safety and ex. proof" (EEx ia + EEx d) 1) P
Application in zone 2 n (TÜV) E
Electrical connection / Cable inlet
Screwed gland PG 13.5 2) (Adapter) A
Female thread M 20 x 1,5 B
Female thread 1/2-14 NPT C
Han 7D plug 2) D
Housing cover / Display
without window (digital display covered, setting: mA) 1
with window (digital display, setting: mA) 6
with window (digital display visible, setting: as specified,
short spec. Y21 necessary) 7
1) 2)
Without cable screwed gland Not in connection with "explosion proof degree of protection"

Scope of delivery:
Transmitter as ordered, 1 brief instructions (Leporello)
1 sealing screw (same material as process flange)

Order example:
Pos. 1 Position line: 7MF4633-1DY10-1AA1-Z
B-line: Y01
C-line: Y01: 90 ... 143 mbar
Pos. 2 Position line: 7MF4912-3DA11

SITRANS P, Series DS III


108 A5E00047092-01
SITRANS P transmitter for filling level
Other versions
Add "-Z" to order no. and add short spec. 7MF4633 - . . . . . - . . . . -Z
Han 7D plug (metal, gray) A30
Han 8U plug (instead of Han 7D) A31
Sealing screw (1/4-18 NPT) with valve
in same material as process flanges A40
Labeling of rating plate (instead of German)
- English B11
- French B12
- Spanish B13
- Italian B14
Manufacturer test certificate M acc. to DIN 55350, Part 18,
and ISO 8402 C11
Acceptance test certificate B acc. to DIN 50 049 / EN 10 204-3.1 B C12
Works certificate acc. to DIN 50 049-2.2 / EN 10 204-2.2 C14
Setting the upper limit of the output signal to 22.0 mA D05
IP 68 (not in connection with Han 7D/Han 8U plug and
cable screwed gland Pg 13.5) D12
Allication in zone 0 (basic device EEx ia) E02
Overfill protection for combustible and non-combustible liquids
(max. PN 32) (basic device EEx ia) E08
Switching the process connection side
(HP side: left, LP side: right) H01
Specify meas. range to be set in clear text,
Y01: ... to ... mbar, bar, kPa, MPa, ... (maximum 27 characters) Y01
Specify meas. point number / description
(max. 16 characters) in clear text:
Y15:................ Y15
Specify meas. point message (max. 27 characters) in clear text:
Y16:........................... Y16
Specify setting digital display in clear text
Y21: mbar, bar, kPa, MPa, ... Y21
Other factory presettings than "Y01", "Y21" and "D05" are not possible.

SITRANS P, Series DS III


A5E00047092-01 109
Mounting flange for SITRANS P transmitter for filling level
Accessories Order no.
Mounting flange, mounted directly on transmitter 7MF4912-
SITRANS P for filling level 3
Flange Nom. Diameter Nom. pressure
Connection DN 80 PN 40 D
acc. to DN 100 PN 16 G
DIN 2501 PN 40 H
Connection 3 inch 150 lb/sq.in. Q
acc. to 300 lb/sq.in. R
ANSI B 16.5 4 inch 150 lb/sq.in. T
300 lb/sq.in. U
Special version according to customer specifications Z J1Y
Material of wetted parts
Stainless steel M.-No. 1.4571
without foil, uncoated A
with PTFE foil 1) E 0
with ECTFE coating 1) F
with PFA coating 1) D
Monel 400, M.-No. 2.4360 G
Hastelloy B2, M.-No. 2.4617 H
Hastelloy C276, M.-No. 2.4819 J
Tantalum K
Hastelloy C4, M.-No. 2.4610 U
Special version to customer specifications Z K1Y
Smooth sealing face according to DIN 2526, Form D
Tube length 2) 0 mm 0
50 mm 1
100 mm 2
150 mm 3
200 mm 4
Filling liquid
Silicone oil M5 1
Special version to customer specifications 9 M1Y
1) For vacuum on request
Connection flange with different nominal diameter, different material, different seal face or filling lqiuid on request
Other versions for mounting flange
Add "-Z" to the order no. and add short spec. 7MF4912 - . . . . . -Z
With flame barrier for mounting in zone 0 A01
(including documentation)
Manufacturer test certificate M acc. to DIN 55 350, Part 18, C11
and ISO 8402 (not in connection with supplement "P01")
Acceptance test certificate B acc. to DIN 50 049, C12
Section 3.1. and EN 10 204
Vacuum-proof version (use in vacuum pressure range) V04
Calculation of span of the corresponding transmitter, Y05
enclose filled out questionnaire!
(not in connection with supplement "P01")
2)
The prices for the named tube lengths are based on the material of the wetted parts
stainless steel M. No. 1.4571. For the other materials named on request!

SITRANS P, Series DS III


110 A5E00047092-01
Certificates
12

SITRANS P, Series DS III


A5E00047092-01 111
Certificates

12.1 EC Declaration of Conformity

SITRANS P, Series DS III


112 A5E00047092-01
Index
13
A View 29
Adjustment 52 Disable 51
Current transmiter 53 Display/Bargraph 52
Alarm text 28
Arrow
down 28 E
up 28 Electric damping 49
Assembly 63 Electrical connection 70
Equations
Set start of scale, full scale 33
B Error 28
Blanking plug 16 Error signaling 28
Blind setting 48 ET 200M 23
Block diagram 18, 19, 20 Examples
Physical units 43

C
Cable gland 16 F
Commissioning 75 Factory calibration 55
Configuration data 55 Failure current 49, 95
Connection 71 Fast measured value acquisition 49
to screw terminals 71 Fast Response Mode 49
with plug 72 Front view of the device 16
Connection diagram 71 Full scale
Constant current mode 49 adjust 31
Current limits 50 set 32
Current transmitter 49 Functional diagram 18, 19, 20, 21

D H
Diagnostic Information 28 Hardware error 95
Digital display HART
Design 26 Communicator 23

SITRANS P, Series DS III


A5E00047092-01 113
Index

modem 23 Position correction 48

I R
Input keys 29 Range of rotation. 68
Installation 14, 63 Rating plate 16
Rear view of device 16

K
Keyboard 29 S
Keyboard disable 31 Self test 95
Sensor adjustment 52
Sensor zero 48
Signal range 28
L
SIMATIC PDM 24
Locking screw 69
SIMATIC S7 23
Start of scale
adjust 31, 45
M set 32
Measured value display 26 Status display 27
Measuring System configuration 23
gases 77
liquid 78
vapor 78
T
Measuring operation 48
Technical Data
Measuring point plate 16
Dimensions 90
Measuring span 31, 32
Test plug 71
Message
Trimming 48
OVER 28
upper sensor adjustment point 53
UNDER 28
Turn-down 31
Mounting bracket 64
Type of unit 51

O U
Operation
Unit of pressure 51
Key functions 30
locally 25

W
Window 16
P
Write protection 31, 51
Plastic cover 16

SITRANS P, Series DS III


114 A5E00047092-01
Appendix
14

SITRANS P, Series DS III


A5E00047092-01 115
HART Communicator, HART Rev. 5 *) Measured value display
Operating structure

2 Online 1 Pressure
2 Type
3 Configure 1 Process variables *) 1 Pressure
2 % MR
3 Current
4 Sens-Temp
2 Diagnosis/Service 1 Diagnosis 1 Slave pointer 1 Slave pointer Press. 1 Press. max (N)
2 Press. min (N)
3 Press. max (R)
4 Press. min. (R)
5 Reset
2 Slave pointer El- T 1 El.temp max.(N)
2 El.temp min.(N)
3 El.temp max.(R)
4 El.temp min.(R)
5 Reset
3 Slave pointer Sens- T 1 Sens.temp max.(N)
2 Sens.temp min. (N)
3 Sens. temp max.(R)
4 Sens temp max (R)
5 Reset
2 Operating hours 1 Op. hr. counter El
2 Op. hr. counter S
3 Warnings/Alarms 1 Calib. Interval 1 Calib. timer 1 Calib. Time
2 Reset
2 Calib Warning
3 Calib Alarm
4 W/A activation
5 W/A calib status
6 W/A acknowledge
2 Service interval 1 Service timer 1 Service time
2 Reset
2 Service warning
3 Service alarm
4 W/A activate
5 W/A service status
6 W/A acknowledge
3 Current saturation 1 Saturation alarm
2 Alarm time
3 Alarm activate
4 Status 1 Sum status
2 Hardw/Firmw Status
3 Diag. Alarm Status
4 Diag. Warn Status
5 Simulation Status
2 Simulation/Test 1 Simulation 1 Current transmitter
2 Inputs 1 Pressure
2 Temp El.
3 Temp Sens.
4 Display process var.
5 All sims off
2 Test 1 Self-test
2 Reset
3 Access control 1 Local operation
2 Write prot. No
3 Set write prot.
4 Adjustment 1 Pos. error adjust.
2 Sensor adjust. 1 Adjust. Point
2 Zero adjustment
3 Lower adjustment
4 Upper adjustment
3 Sys. out. adjust. 1 D/A adj 4mA/20mA
2 D/A adj scaled
5 Reset factory adj 1 Strom
2 Sensor zero
3 Pressure
4 Complete
6 All measured values 1 Pressure
2 Basic value
3 Sens temp
4 El temp
5 Current
3 Quick setup 1 Meas tag (TAG)
2 Unit
3 Pos. error adj.
4 Start of scale
5 Full scale
6 Damping
7 Characteristic
4 Complete setup 1 Sensors 1 Pressure sensor 1 Pressure
2 Unit
2 Temperature sensor 1 Sens temp
2 El temp
2 Signal parameter 1 Process variables *) 1 Pressure
2 % MR
4 Current
5 Sens temp
2 Pos. error adj. 1 Current
3 Set zero/span 1 Keyboard input 1 Start of scale
2 Full scale
3 Unit
4 Low sens. limit
5 Up. sens. limit
2 Press. default
4 Damping
5 Characteristic
6 Start squ. Rooting
7 Meas. speed
8 Frequency meas.
3 Output parameters 1 Analog output 1 Current
2 Pressure % MR+L34
3 Alarms 1 Curr. alarm type
2 Low. alarm value
3 Up. alarm value
4 Low. current limit
5 Op. current limit
2 HART output 1 Call address
2 Dis call preamb.
3 Dis reply preamb.
4 Device info 1 Range & limits 1 Range cell
2 Press. up. sens. lim.
3 Press. low. sens. lim.
4 Press. min. span
2 Gen. device info 1 Made by Siemens
2 Model
3 Transmitter type
4 Order no.
5 Explosion prot.
6 Serial no.
7 Presssens ser. no.
8 Assembly no.
9 Electr connection
Electr. housing mat.
Write prot. No
Meas. tag (TAG)
MM/DD/YY
Description
Message
3 Sensor Info 1 Process conn.
2 Flange type
3 Flange mat.
4 Process fl. screw
5 Seal diaph. mat.
6 Cell filling med.
7 O-ring mat
8 Vent/plug mat.
9 Vent/plug pos.
4 Remote seal 1 Re. seal type
2 Seal diaph. mat.
3 Seal filling med.
4 No. of rem. Seals
5 Tube length
5 Local display 1 Display type
2 Up. Unit
3 Local unit display
4 Bargraph
6 Revision numbers 1 Universal Rev.
2 Field dev. Rev.
3 Software Rev.
4 Hardware Rev.
5 Overview
1P A5E00047092

Q1

Siemens AG
Bereich AutomatisierungsĆ und Antriebtechnik
Geschäftsgebiet A&D PA E Siemens AG 2000
Subject to change without prior notice
DĆ76181 Karlsruhe
Order No. A5E00047092
Siemens Aktiengesellschaft Printed in France
AG 0600 MG 120 GB