Test/Repair
Item Tag Location Size Intial Findings Work Performed Recommendation Status
Date
Test/Repair
Item Tag Location Size Intial Findings Work Performed Recommendation Status
Date
Final Configuration
Manufacturer Consolidated Valve Size Style
DN80
Model Number 1755-WB-5S-500-F1-LV Capacity
Pre-Test Data
Date Tested 2022/07/22 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1755 WB-5S-500-F1-LV DN80 J-17-005149 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
160.0 bar 110.0 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 109.5 bar 159.3 bar
Acceptable range
From 158.4 bar to 161.6 bar
- 1.00 % + 1.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Jetur Abrigo
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
150 1.0 20000
100 150 1.0 20000
90 0.6 12000
60 90 0.6 12000
75 0.5 10000
50 75 0.5 10000
60 0.4 8000
40 60 0.4 8000
45 0.3 6000
30 45 0.3 6000
30 0.2 4000
20 30 0.2 4000
15 0.1 2000
10 15 0.1 2000
0 0.0 0
0 0 0.0 0
Test 2
90 0.6 12000
Line pressure 109.5 bar
75 0.5 10000
Pulling force 16169 N
60 0.4 8000 Found set pressure 159.6 bar
45 0.3 6000
Test 3
30 0.2 4000 Line pressure 109.5 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
DN80
Model Number 1755-WB-5S-500-F1-LD Capacity
Pre-Test Data
Date Tested 2022/07/22 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1755WB-5-S-500-F1-LD DN80 J-17-005150 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
164.8 bar 110.0 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 108.7 bar 164.1 bar
Acceptable range
From 163.2 bar to 166.4 bar
- 1.00 % + 1.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Jetur Abrigo
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
150 1.0 20000
100 150 1.0 20000
90 0.6 12000
60 90 0.6 12000
75 0.5 10000
50 75 0.5 10000
60 0.4 8000
40 60 0.4 8000
45 0.3 6000
30 45 0.3 6000
30 0.2 4000
20 30 0.2 4000
15 0.1 2000
10 15 0.1 2000
0 0.0 0
0 0 0.0 0
Test 2
90 0.6 12000
Line pressure 108.7 bar
75 0.5 10000
Pulling force 17866 N
60 0.4 8000 Found set pressure 164.0 bar
45 0.3 6000
Test 3
30 0.2 4000 Line pressure 108.7 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
DN80
Model Number 1759-WD-5S-500-F3-LD Capacity
Pre-Test Data
Date Tested 2022/07/22 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1759WD-5-S-500-F3-LD DN80 J-16-011372 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
144.9 bar 101.4 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 103.9 bar 145.4 bar
Acceptable range
From 143.5 bar to 146.3 bar
- 1.00 % + 1.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Jetur Abrigo
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
150 1.0 20000
100 150 5.0 20000
90 0.6 12000
60 90 3.0 12000
75 0.5 10000
50 75 2.5 10000
60 0.4 8000
40 60 2.0 8000
45 0.3 6000
30 45 1.5 6000
30 0.2 4000
20 30 1.0 4000
15 0.1 2000
10 15 0.5 2000
0 0.0 0
0 0 0.0 0
Test 2
90 1.2 12000
Line pressure 103.4 bar
75 1.0 10000
Pulling force 13701 N
60 0.8 8000 Found set pressure 145.8 bar
45 0.6 6000
Test 3
30 0.4 4000 Line pressure 103.4 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
DN 150
Model Number 1785-WB-5S-500-F1-LD Capacity
Pre-Test Data
Date Tested 2022/07/20 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1785WB-5-S-500-F1-LD DN 150 J-17-002411 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
39.5 bar 27.6 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 27.1 bar 40.0 bar
Acceptable range
From 38.8 bar to 40.2 bar
- 1.75 % + 1.75 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Aries Bayog
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
40 5.0 20000
100 40 2.0 20000
36 4.5 18000
90 36 1.8 18000
32 4.0 16000
80 32 1.6 16000
28 3.5 14000
70 28 1.4 14000
24 3.0 12000
60 24 1.2 12000
20 2.5 10000
50 20 1.0 10000
16 2.0 8000
40 16 0.8 8000
12 1.5 6000
30 12 0.6 6000
8 1.0 4000
20 8 0.4 4000
4 0.5 2000
10 4 0.2 2000
0 0.0 0
0 0 0.0 0
Test 2
24 1.2 12000
Line pressure 27.1 bar
20 1.0 10000
Pulling force 16784 N
16 0.8 8000 Found set pressure 39.8 bar
12 0.6 6000
Test 3
8 0.4 4000 Line pressure 27.1 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
DN 150
Model Number 1785WB-5-S-500-F1-LD Capacity
Pre-Test Data
Date Tested 2022/07/20 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1785WB-5-S-500-F1-LD DN 150 J-17-002412 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
40.6 bar 28.4 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 26.5 bar 40.7 bar
Acceptable range
From 39.9 bar to 41.3 bar
- 1.70 % + 1.70 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Aries Bayog
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
40 2.3 20000
100 40 1.2 20000
36 2.1 18000
90 36 1.0 18000
32 1.9 16000
80 32 0.9 16000
28 1.6 14000
70 28 0.8 14000
24 1.4 12000
60 24 0.7 12000
20 1.2 10000
50 20 0.6 10000
16 0.9 8000
40 16 0.5 8000
12 0.7 6000
30 12 0.3 6000
8 0.5 4000
20 8 0.2 4000
4 0.2 2000
10 4 0.1 2000
0 0.0 0
0 0 0.0 0
Test 2
24 0.6 12000
Line pressure 26.5 bar
20 0.5 10000
Pulling force 19005 N
16 0.4 8000 Found set pressure 40.9 bar
12 0.3 6000
Test 3
8 0.2 4000 Line pressure 26.5 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
DN 100
Model Number 1765WD-5-S-500-F1-LD Capacity
Pre-Test Data
Date Tested 2022/07/21 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1765WD-5-S-500-F1-LD DN100 J-16-010204 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
37.2 bar 26.0 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 26.9 bar 37.3 bar
Acceptable range
From 36.5 bar to 37.9 bar
- 1.85 % + 1.85 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Aries Bayog
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
40 1.0 10000
100 40 1.0 10000
36 0.9 9000
90 36 0.9 9000
32 0.8 8000
80 32 0.8 8000
28 0.7 7000
70 28 0.7 7000
24 0.6 6000
60 24 0.6 6000
20 0.5 5000
50 20 0.5 5000
16 0.4 4000
40 16 0.4 4000
12 0.3 3000
30 12 0.3 3000
8 0.2 2000
20 8 0.2 2000
4 0.1 1000
10 4 0.1 1000
0 0.0 0
0 0 0.0 0
Test 2
24 0.6 6000
Line pressure 26.9 bar
20 0.5 5000
Pulling force 6400 N
16 0.4 4000 Found set pressure 36.6 bar
12 0.3 3000
Test 3
8 0.2 2000 Line pressure 26.9 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
DN 100
Model Number 1765WD-5-S-500-F1-LD Capacity
Pre-Test Data
Date Tested 2022/07/21 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1765WD-5-S-500-F1-LD DN100 J-16-010203 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
37.2 bar 26.0 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 26.9 bar 37.1 bar
Acceptable range
From 36.5 bar to 37.9 bar
- 1.85 % + 1.85 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Aries Bayog
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
40 1.0 10000
100 40 1.0 10000
36 0.9 9000
90 36 0.9 9000
32 0.8 8000
80 32 0.8 8000
28 0.7 7000
70 28 0.7 7000
24 0.6 6000
60 24 0.6 6000
20 0.5 5000
50 20 0.5 5000
16 0.4 4000
40 16 0.4 4000
12 0.3 3000
30 12 0.3 3000
8 0.2 2000
20 8 0.2 2000
4 0.1 1000
10 4 0.1 1000
0 0.0 0
0 0 0.0 0
Test 2
24 0.6 6000
Line pressure 26.9 bar
20 0.5 5000
Pulling force 6791 N
16 0.4 4000 Found set pressure 37.2 bar
12 0.3 3000
Test 3
8 0.2 2000 Line pressure 26.9 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
6"
Model Number 1910-00Q-2CC-TD-33-RF-SS-HP Capacity
Pre-Test Data
Date Tested 2022/07/19 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1910-00Q-2CC-TD-33-RF-SS-HP 6'' SD25098 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
8.9 bar 6.0 bar ASME sec. 8 0.0 bar
Test results
Inlet pressure Set pressure
As found 6.8 bar 9.0 bar
Acceptable range
From 8.6 bar to 9.2 bar
- 3.00 % + 3.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Uzziel Monisit
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
10 1.0 5000
100 10 1.0 5000
9 0.9 4500
90 9 0.9 4500
8 0.8 4000
80 8 0.8 4000
7 0.7 3500
70 7 0.7 3500
6 0.6 3000
60 6 0.6 3000
5 0.5 2500
50 5 0.5 2500
4 0.4 2000
40 4 0.4 2000
3 0.3 1500
30 3 0.3 1500
2 0.2 1000
20 2 0.2 1000
1 0.1 500
10 1 0.1 500
0 0.0 0
0 0 0.0 0
Test 2
6 0.6 3000
Line pressure 6.8 bar
5 0.5 2500
Pulling force 1936 N
4 0.4 2000 Found set pressure 8.9 bar
3 0.3 1500
Test 3
2 0.2 1000 Line pressure 6.8 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
6"
Model Number 1910-00Q-2CC-TD-33-RF-SS-HP Capacity
Pre-Test Data
Date Tested 2022/07/19 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1910-00Q-2-CC-TD-33-RF-SS-HP 6'' SD25096 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
8.9 bar 6.0 bar ASME sec. 8 0.0 bar
Test results
Inlet pressure Set pressure
As found 6.7 bar 9.0 bar
Acceptable range
From 8.6 bar to 9.2 bar
- 3.00 % + 3.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. John Carlo Cañete
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
10 2.0 5000
100 10 1.0 5000
9 1.8 4500
90 9 0.9 4500
8 1.6 4000
80 8 0.8 4000
7 1.4 3500
70 7 0.7 3500
6 1.2 3000
60 6 0.6 3000
5 1.0 2500
50 5 0.5 2500
4 0.8 2000
40 4 0.4 2000
3 0.6 1500
30 3 0.3 1500
2 0.4 1000
20 2 0.2 1000
1 0.2 500
10 1 0.1 500
0 0.0 0
0 0 0.0 0
Test 2
6 0.6 3000
Line pressure 6.7 bar
5 0.5 2500
Pulling force 2063 N
4 0.4 2000 Found set pressure 9.0 bar
3 0.3 1500
Test 3
2 0.2 1000 Line pressure 6.7 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
6"
Model Number 1910-00Q-2CC-TD-33-RF-SS-HP Capacity
Pre-Test Data
Date Tested 2022/07/19 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1910-00Q-2CC-TD-33-RF-SS-HP 6'' SD25097 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
8.9 bar 6.0 bar ASME sec. 8 0.0 bar
Test results
Inlet pressure Set pressure
As found 6.8 bar 9.1 bar
Acceptable range
From 8.6 bar to 9.2 bar
- 3.00 % + 3.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. John Carlo Cañete
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
10 5.0 5000
100 10 5.0 5000
9 4.5 4500
90 9 4.5 4500
8 4.0 4000
80 8 4.0 4000
7 3.5 3500
70 7 3.5 3500
6 3.0 3000
60 6 3.0 3000
5 2.5 2500
50 5 2.5 2500
4 2.0 2000
40 4 2.0 2000
3 1.5 1500
30 3 1.5 1500
2 1.0 1000
20 2 1.0 1000
1 0.5 500
10 1 0.5 500
0 0.0 0
0 0 0.0 0
Test 2
6 0.6 3000
Line pressure 6.8 bar
5 0.5 2500
Pulling force 2078 N
4 0.4 2000 Found set pressure 9.1 bar
3 0.3 1500
Test 3
2 0.2 1000 Line pressure 6.8 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
DN150
Model Number 1910-00Q-3-CC-TD-33-RF-SS-HP Capacity
Pre-Test Data
Date Tested 2022/07/22 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1910-00Q-3-CC-TD-34-RF-SS-HP DN150 SD41230 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
14.1 bar 12.0 bar ASME sec. 8 0.0 bar
Test results
Inlet pressure Set pressure
As found 11.2 bar 13.9 bar
Acceptable range
From 13.7 bar to 14.5 bar
- 3.00 % + 3.00 %
18 1.8 4500
90 18 1.8 4500
16 1.6 4000
80 16 1.6 4000
14 1.4 3500
70 14 1.4 3500
12 1.2 3000
60 12 1.2 3000
10 1.0 2500
50 10 1.0 2500
8 0.8 2000
40 8 0.8 2000
6 0.6 1500
30 6 0.6 1500
4 0.4 1000
20 4 0.4 1000
2 0.2 500
10 2 0.2 500
0 0.0 0
0 0 0.0 0
Test 2
12 1.2 3000
Line pressure 11.2 bar
10 1.0 2500
Pulling force 2728 N
8 0.8 2000 Found set pressure 14.2 bar
6 0.6 1500
Test 3
4 0.4 1000 Line pressure 11.2 bar
Test/Repair
Item Tag Location Size Intial Findings Work Performed Recommendation Status
Date
Light deposits on disc, nozzle Clean, re‐used all parts. Lapped, polished
HP HEATER 3 WATER and internal parts. Good both disc and nozzle. Tested in accordance For yearly preventive 100%,
6 17/08/2022 30LAD30AA192 DN25
SIDE condition disc holder, guide, wit API 527 Standard. Final Test Result: maintenance inspection Completed
spindle, spring & washers. 20.25 MPA.
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN 80
Model Number 1910-30-4-CC-MS-33-RF Capacity
Pre-Test Data
Date Tested 2022/08/19 Popped@ 4.01 MPA Pretest Notes PASSED
Pretested Yes Leaked/@
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Calibration only, Set at CDTP 583 PSI (4.01 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1-19226-HCF-2-CC-MS-33 Capacity 1187 KG/HR
Pre-Test Data
Date Tested 2022/08/17 Popped@ 20.25 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 2940 Psi (20.25 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Chatter Marks Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN80
Model Number 1910-30K-4-CC-4-MS-33-RF Capacity 3728 KG/HR
Pre-Test Data
Date Tested 2022/08/22 Popped@ 20.6 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 420 Psi (2.89 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Corrosions Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 30LAD20AA191
Valve Description HP Heater #2 DN80
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1-19226-HCF-2-CC-MS-33 Capacity 1187 KG/HR
Pre-Test Data
Date Tested 2022/08/18 Popped@ 20.27 MPA Pretest Notes Passed
Pretested Yes Leaked/@
Comments/ Remarks
Calibration only. Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 2940 Psi (20.25 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN100
Model Number 1910-30K-4-CC-4-MS-33-RF Capacity 4558 KG/HR
Pre-Test Data
Date Tested 2022/08/22 Popped@ 1.6 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 265 Psi (1.83 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Corrosions Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 30LAD30AA191
Valve Description HP Heater #3 DN100
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1-19226-HCF-2-CC-MS-33 Capacity 1277 KG/HR
Pre-Test Data
Date Tested 2022/08/17 Popped@ 20.25 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 2940 Psi (20.25 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Good condition Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN80
Model Number 1910-30K-4-CC-4-MS-33-RF Capacity 14025 KG/HR
Pre-Test Data
Date Tested 2022/08/22 Popped@ 2.3 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 425 Psi (2.93 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Corrosions Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 30LAD21AA191
Valve Description NC Heater DN80
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1-19226-HCF-2-CC-MS-33 Capacity 1255 KG/HR
Pre-Test Data
Date Tested 2022/08/18 Popped@ 19.85 MPA Pretest Notes PASSED
Pretested Yes Leaked/@
Comments/ Remarks
Calibration only. Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 20.25 MPA
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Test/Repair
Item Tag Location Size Intial Findings Work Performed Recommendation Status
Date
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN80
Model Number Capacity 2069 KG/HR
Pre-Test Data
Date Tested 2022/08/19 Popped@ 0.37 MPA Pretest Notes PASSED
Pretested Yes Leaked/@
Comments/ Remarks
Calibration only. Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 58 PSI (0.39 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number Capacity
Pre-Test Data
Date Tested 2022/08/22 Popped@ 2.8 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 3.14 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Corrosions Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, polished and re-used.
No damage on stud threads. Lapped bearing points.
Valve Tag 30LCC50AA192
Valve Description LP Heater #5 1”x 1”1/2
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN80
Model Number 1910-30K-4-CC-4-MS-33-RF Capacity 1535 KG/HR
Pre-Test Data
Date Tested 2022/08/19 Popped@ 0.15 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 2.89 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Corrosions Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 30LCC60AA191
Valve Description LP Heater #6 DN80
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1922 Capacity 477 KG/HR
Pre-Test Data
Date Tested 2022/08/17 Popped@ 3.13 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Leaking @ 2.06 MPA
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 3.16 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Chatter marks Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1922 Capacity 470 KG/HR
Pre-Test Data
Date Tested 2022/08/17 Popped@ 3.1 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Leaking @ 3.03 MPA
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 3.07 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Chatter marks Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
As Found As Left
As Found As Left
Test/Repair
Item Tag Location Size Intial Findings Work Performed Recommendation Status
Date
Test/Repair
Item Tag Location Size Intial Findings Work Performed Recommendation Status
Date
Final Configuration
Manufacturer Consolidated Valve Size Style
DN80
Model Number 1755-WB-5-S-500-F1-LV Capacity
Pre-Test Data
Date Tested 2022/07/27 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1755WB-5-S-500-F1-LD DN80 J-17-005175 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
160.0 bar 99.0 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 108.3 bar 160.6 bar
Acceptable range
From 158.4 bar to 161.6 bar
- 1.00 % + 1.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Jeric Caasalan
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
150 1.0 20000
100 150 1.0 20000
90 0.6 12000
60 90 0.6 12000
75 0.5 10000
50 75 0.5 10000
60 0.4 8000
40 60 0.4 8000
45 0.3 6000
30 45 0.3 6000
30 0.2 4000
20 30 0.2 4000
15 0.1 2000
10 15 0.1 2000
0 0.0 0
0 0 0.0 0
Test 2
90 0.6 12000
Line pressure 108.3 bar
75 0.5 10000
Pulling force 16962 N
60 0.4 8000 Found set pressure 160.8 bar
45 0.3 6000
Test 3
30 0.2 4000 Line pressure 108.3 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
DN80
Model Number 1755-WB-5-S-500-F1-LD Capacity
Pre-Test Data
Date Tested 2022/07/27 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1755WB-5-S-500-F1-LD DN80 J-17-005176 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
164.8 bar 115.0 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 108.7 bar 165.5 bar
Acceptable range
From 163.2 bar to 166.4 bar
- 1.00 % + 1.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Jeric Caasalan
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
150 2.0 20000
100 150 2.0 20000
90 1.2 12000
60 90 1.2 12000
75 1.0 10000
50 75 1.0 10000
60 0.8 8000
40 60 0.8 8000
45 0.6 6000
30 45 0.6 6000
30 0.4 4000
20 30 0.4 4000
15 0.2 2000
10 15 0.2 2000
0 0.0 0
0 0 0.0 0
Test 2
90 1.2 12000
Line pressure 108.7 bar
75 1.0 10000
Pulling force 18320 N
60 0.8 8000 Found set pressure 165.4 bar
45 0.6 6000
Test 3
30 0.4 4000 Line pressure 108.7 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
DN80
Model Number 1759-WD-5-S-500-F3-LD Capacity
Pre-Test Data
Date Tested 2022/07/27 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1759WD-5-S-500-F3-LD DN 80 J-17-001540 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
144.9 bar 100.0 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 103.1 bar 145.4 bar
Acceptable range
From 143.5 bar to 146.3 bar
- 1.00 % + 1.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Jeric Caasalan
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
150 2.0 20000
100 150 2.0 20000
90 1.2 12000
60 90 1.2 12000
75 1.0 10000
50 75 1.0 10000
60 0.8 8000
40 60 0.8 8000
45 0.6 6000
30 45 0.6 6000
30 0.4 4000
20 30 0.4 4000
15 0.2 2000
10 15 0.2 2000
0 0.0 0
0 0 0.0 0
Test 2
90 1.2 12000
Line pressure 103.1 bar
75 1.0 10000
Pulling force 13342 N
60 0.8 8000 Found set pressure 144.4 bar
45 0.6 6000
Test 3
30 0.4 4000 Line pressure 103.1 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
4"
Model Number 1765-WB-5-S-500-F1-LD Capacity
Pre-Test Data
Date Tested 2022/07/26 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1765WB-5-S-500-F1-LD 4'' J-17-000251 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
37.2 bar 26.0 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 27.5 bar 37.1 bar
Acceptable range
From 36.5 bar to 37.9 bar
- 1.85 % + 1.85 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Armonds Pantallano
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
40 5.0 10000
100 40 2.0 10000
36 4.5 9000
90 36 1.8 9000
32 4.0 8000
80 32 1.6 8000
28 3.5 7000
70 28 1.4 7000
24 3.0 6000
60 24 1.2 6000
20 2.5 5000
50 20 1.0 5000
16 2.0 4000
40 16 0.8 4000
12 1.5 3000
30 12 0.6 3000
8 1.0 2000
20 8 0.4 2000
4 0.5 1000
10 4 0.2 1000
0 0.0 0
0 0 0.0 0
Test 2
24 0.6 6000
Line pressure 27.4 bar
20 0.5 5000
Pulling force 6171 N
16 0.4 4000 Found set pressure 36.8 bar
12 0.3 3000
Test 3
8 0.2 2000 Line pressure 27.4 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
4"
Model Number 1765-WB-5-S-500-F1-LD Capacity
Pre-Test Data
Date Tested 2022/07/26 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1765WB-5-S-500-F1-LD 4'' J-17-000252 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
37.2 bar 26.0 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 27.5 bar 37.1 bar
Acceptable range
From 36.5 bar to 37.9 bar
- 1.85 % + 1.85 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Armonds Pantallano
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
40 2.0 10000
100 40 1.0 10000
36 1.8 9000
90 36 0.9 9000
32 1.6 8000
80 32 0.8 8000
28 1.4 7000
70 28 0.7 7000
24 1.2 6000
60 24 0.6 6000
20 1.0 5000
50 20 0.5 5000
16 0.8 4000
40 16 0.4 4000
12 0.6 3000
30 12 0.3 3000
8 0.4 2000
20 8 0.2 2000
4 0.2 1000
10 4 0.1 1000
0 0.0 0
0 0 0.0 0
Test 2
24 0.6 6000
Line pressure 27.5 bar
20 0.5 5000
Pulling force 6234 N
16 0.4 4000 Found set pressure 37.0 bar
12 0.3 3000
Test 3
8 0.2 2000 Line pressure 27.5 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
DN 150
Model Number 1785-WB-5-S-500-F1-LD Capacity
Pre-Test Data
Date Tested 2022/07/26 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1785WB-5-S-500-F1-LD DN150 J-17-005178 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
39.5 bar 27.0 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 26.8 bar 39.7 bar
Acceptable range
From 38.8 bar to 40.2 bar
- 1.75 % + 1.75 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Armonds Pantallano
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
40 2.0 20000
100 40 2.0 20000
36 1.8 18000
90 36 1.8 18000
32 1.6 16000
80 32 1.6 16000
28 1.4 14000
70 28 1.4 14000
24 1.2 12000
60 24 1.2 12000
20 1.0 10000
50 20 1.0 10000
16 0.8 8000
40 16 0.8 8000
12 0.6 6000
30 12 0.6 6000
8 0.4 4000
20 8 0.4 4000
4 0.2 2000
10 4 0.2 2000
0 0.0 0
0 0 0.0 0
Test 2
24 1.2 12000
Line pressure 26.8 bar
20 1.0 10000
Pulling force 17068 N
16 0.8 8000 Found set pressure 39.7 bar
12 0.6 6000
Test 3
8 0.4 4000 Line pressure 26.8 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
DN 150
Model Number 1785-WB-5-S-500-F1-LD Capacity
Pre-Test Data
Date Tested 2022/07/26 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1785WB-5-S-500-F1-LD DN150 J-17-005177 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
40.6 bar 28.0 bar ASME sec. 1 0.0 bar
Test results
Inlet pressure Set pressure
As found 26.0 bar 41.1 bar
Acceptable range
From 39.9 bar to 41.3 bar
- 1.70 % + 1.70 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Armonds Pantallano
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
40 2.0 20000
100 40 2.0 20000
36 1.8 18000
90 36 1.8 18000
32 1.6 16000
80 32 1.6 16000
28 1.4 14000
70 28 1.4 14000
24 1.2 12000
60 24 1.2 12000
20 1.0 10000
50 20 1.0 10000
16 0.8 8000
40 16 0.8 8000
12 0.6 6000
30 12 0.6 6000
8 0.4 4000
20 8 0.4 4000
4 0.2 2000
10 4 0.2 2000
0 0.0 0
0 0 0.0 0
Test 2
24 1.2 30000
Line pressure 26.0 bar
20 1.0 25000
Pulling force 19060 N
16 0.8 20000 Found set pressure 40.4 bar
12 0.6 15000
Test 3
8 0.4 10000 Line pressure 26.0 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
6"
Model Number 1910-00Q-2-CC-TD-33-RF-SS-HP Capacity
Pre-Test Data
Date Tested 2022/07/19 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1910-00Q-2-CC-TD-33-RF-SS-HP 6'' SD25101 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
8.9 bar 6.2 bar ASME sec. 8 0.0 bar
Test results
Inlet pressure Set pressure
As found 7.5 bar 9.2 bar
Acceptable range
From 8.6 bar to 9.2 bar
- 3.00 % + 3.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Armonds Pantallano
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
10 1.0 2000
100 10 1.0 2000
9 0.9 1800
90 9 0.9 1800
8 0.8 1600
80 8 0.8 1600
7 0.7 1400
70 7 0.7 1400
6 0.6 1200
60 6 0.6 1200
5 0.5 1000
50 5 0.5 1000
4 0.4 800
40 4 0.4 800
3 0.3 600
30 3 0.3 600
2 0.2 400
20 2 0.2 400
1 0.1 200
10 1 0.1 200
0 0.0 0
0 0 0.0 0
Test 2
6 0.6 1200
Line pressure 7.5 bar
5 0.5 1000
Pulling force 1450 N
4 0.4 800 Found set pressure 9.1 bar
3 0.3 600
Test 3
2 0.2 400 Line pressure 7.5 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
6"
Model Number 1910-00Q-2-CC-TD-33-RF-SS-HP Capacity
Pre-Test Data
Date Tested 2022/07/19 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1910-00Q-2-CC-TD-33-RF-SS-HP 6'' SD25100 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
8.9 bar 6.2 bar ASME sec. 8 0.0 bar
Test results
Inlet pressure Set pressure
As found 7.4 bar 9.0 bar
Acceptable range
From 8.6 bar to 9.2 bar
- 3.00 % + 3.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Armonds Pantallano
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
10 1.0 2000
100 10 1.0 2000
9 0.9 1800
90 9 0.9 1800
8 0.8 1600
80 8 0.8 1600
7 0.7 1400
70 7 0.7 1400
6 0.6 1200
60 6 0.6 1200
5 0.5 1000
50 5 0.5 1000
4 0.4 800
40 4 0.4 800
3 0.3 600
30 3 0.3 600
2 0.2 400
20 2 0.2 400
1 0.1 200
10 1 0.1 200
0 0.0 0
0 0 0.0 0
Test 2
6 1.2 1200
Line pressure 7.4 bar
5 1.0 1000
Pulling force 1579 N
4 0.8 800 Found set pressure 9.2 bar
3 0.6 600
Test 3
2 0.4 400 Line pressure 7.4 bar
Final Configuration
Manufacturer Consolidated Valve Size Style
6"
Model Number 1910-00Q-2-CC-TD-33-RF-SS-HP Capacity
Pre-Test Data
Date Tested 2022/07/19 Popped@ Pretest Notes See EVT Report
Pretested No Leaked/@
Comments/ Remarks
Valve tested using auxiliary device tetsing equipment (EVT).
Performed online calibration. See EVT Report.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Valve data
Type Size Serial no. Service
1910-00Q-2-CC-TD-33-RF-SS-HP 6'' SD25099 STEAM
Test data
Expected set pressure Process pressure Norm Back pressure
8.9 bar 6.2 bar ASME sec. 8 0.0 bar
Test results
Inlet pressure Set pressure
As found 7.4 bar 9.1 bar
Acceptable range
From 8.6 bar to 9.2 bar
- 3.00 % + 3.00 %
Restituto P. Doculan
TECHNICIAN_________________ Mr. Armonds Pantallano
CUSTOMER_________________
[bar] [mm] [N]
Test 1 Graph [%] [bar] [mm] [N] Test 2 Graph
10 1.0 2000
100 10 1.0 2000
9 0.9 1800
90 9 0.9 1800
8 0.8 1600
80 8 0.8 1600
7 0.7 1400
70 7 0.7 1400
6 0.6 1200
60 6 0.6 1200
5 0.5 1000
50 5 0.5 1000
4 0.4 800
40 4 0.4 800
3 0.3 600
30 3 0.3 600
2 0.2 400
20 2 0.2 400
1 0.1 200
10 1 0.1 200
0 0.0 0
0 0 0.0 0
Test 2
6 0.6 1200
Line pressure 7.4 bar
5 0.5 1000
Pulling force 1398 N
4 0.4 800 Found set pressure 9.0 bar
3 0.3 600
Test 3
2 0.2 400 Line pressure 7.4 bar
Test/Repair
Item Tag Location Size Intial Findings Work Performed Recommendation Status
Date
Light deposits on disc, nozzle Clean, re‐used all parts. Lapped, polished
and internal parts. Good both disc and nozzle. Tested in accordance For yearly preventive 100%,
1 07/09/2022 40LBG11AA192 Auxiliary Steam Header DN150
condition disc holder, guide, wit API 527 Standard. Final Test Result: maintenance inspection Completed
spindle, spring & washers. 1.5 MPA.
Light deposits on disc, nozzle Clean, re‐used all parts. Lapped, polished
HP HEATER 1 WATER and internal parts. Good both disc and nozzle. Tested in accordance For yearly preventive 100%,
5 05/09/2022 40LAD10AA192 DN25
SIDE condition disc holder, guide, wit API 527 Standard. Final Test Result: maintenance inspection Completed
spindle, spring & washers. 20.25 MPA.
HP HEATER 2 WATER Valve passed on inspection and testing. For yearly preventive 100%,
7 05/08/2022 40LAD20AA192 DN25 For calibration only.
SIDE Calibration only, Set at CDTP 20.25 MPA. maintenance inspection Completed
HP HEATER 3 WATER Valve passed on inspection and testing. For yearly preventive 100%,
9 08/09/2022 40LAD30AA192 DN25 For calibration only.
SIDE Calibration only, Set at CDTP 20.25 MPA. maintenance inspection Completed
CERTIFICATE NO.: 1026 PSV 1026-22
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN150
Model Number 1910-000-3CC Capacity 61508 KG/HR
Pre-Test Data
Date Tested 2022/09/07 Popped@ 1.3 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 1.5 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Good condition Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 40LBG11AA192
Valve Description Auxilary Steam Heater Safety Valve
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN80
Model Number 1910-30K-4-CC-MS-33-RF Capacity 14025 KG/HR
Pre-Test Data
Date Tested 2022/09/07 Popped@ 2.7 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 3.0 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Corrosions Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 40LAD21AA191
Valve Description NC Heater DN80
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1-19226-HCF-2-CC-MS-33 Capacity 1255 KG/HR
Pre-Test Data
Date Tested 2022/09/05 Popped@ 19.85 MPA Pretest Notes Passed
Pretested Yes Leaked/@
Comments/ Remarks
Calibration only. Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 20.25 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN 80
Model Number 1910-30-4-CC-MS-33-RF Capacity 3201 LPM
Pre-Test Data
Date Tested 2022/09/06 Popped@ 2.9 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 4.01 MPA
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Disc Light deposits Clean, lapped re-used
Nozzle Light deposits Clean, lapped re-used
Disc Hoilder/ Guide Chatter marks Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Washers Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 40LAD10AA191
Valve Description HP Heater #1 DN80
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1-19226-HCF-2-CC-MS-33 Capacity 1187 KG/HR
Pre-Test Data
Date Tested 2022/09/05 Popped@ 20.25 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 20.25 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Chatter Marks Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN80
Model Number 1910-30K-4-CC-4-MS-33-RF Capacity 3728 KG/HR
Pre-Test Data
Date Tested 2022/09/08 Popped@ 20.6 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 420 Psi (2.89 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Corrosions Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 40LAD20AA191
Valve Description HP Heater #2 DN80
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1-19226-HCF-2-CC-MS-33 Capacity 1187 KG/HR
Pre-Test Data
Date Tested 2022/08/18 Popped@ 20.27 MPA Pretest Notes Passed
Pretested Yes Leaked/@
Comments/ Remarks
Calibration only. Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 2940 Psi (20.25 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN100
Model Number 1910-30K-4-CC-4-MS-33-RF Capacity 4558 KG/HR
Pre-Test Data
Date Tested 2022/09/08 Popped@ 1.65 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 265 Psi (1.83 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Corrosions Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 40LAD30AA191
Valve Description HP Heater #3 DN100
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1-19226-HCF-2-CC-MS-33 Capacity 1277 KG/HR
Pre-Test Data
Date Tested 2022/09/08 Popped@ 20.25 MPA Pretest Notes Passed
Pretested Yes Leaked/@
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Calibration only. Set at CDTP 2940 Psi (20.25 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
Test/Repair
Item Tag Location Size Intial Findings Work Performed Recommendation Status
Date
Test/Repair
Item Tag Location Size Intial Findings Work Performed Recommendation Status
Date
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN80
Model Number Capacity 2069 KG/HR
Pre-Test Data
Date Tested 2022/09/07 Popped@ 0.37 MPA Pretest Notes PASSED
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Calibration only. Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 58 PSI (0.39 MPA)
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 40LCC50AA191
Valve Description LP Heater #5 DN80
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number Capacity 470 LPM
Pre-Test Data
Date Tested 2022/09/07 Popped@ 3.06 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Stucked
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 3.07 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Corrosions Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN80
Model Number 1910-30K-4-CC-4-MS-33-RF Capacity 1535 KG/HR
Pre-Test Data
Date Tested 2022/09/07 Popped@ 0.16 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 0.16 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Corrosions Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 40LCC60AA191
Valve Description LP Heater #6 DN80
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN100
Model Number 1905 Capacity 1687 KG/HR
Pre-Test Data
Date Tested 2022/09/08 Popped@ 0.10 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 0.10 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Chatter marks Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1922 Capacity 470 KG/HR
Pre-Test Data
Date Tested 2022/09/05 Popped@ 3.06 MPA Pretest Notes Failed
Pretested Yes Leaked/@ Passing
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 3.07 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Chatter marks Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
Light Deposit in Nozzle and Ring Pin. Cleaned, lapped and re-used.
No damage on stud threads.
Valve Tag 40LCC70AA191
Valve Description LP Heater #7 DN100
Part Description Nozzle
As Found As Left
As Found As Left
Final Configuration
Manufacturer Consolidated Valve Size Style FLG-Conv
DN25
Model Number 1922 Capacity 477 KG/HR
Pre-Test Data
Date Tested 2022/09/05 Popped@ Stuck-up Pretest Notes Failed
Pretested Yes Leaked/@
Comments/ Remarks
Final Test Result: PASSED
Valve tested and calibrated in accordance with API 527 Standard.
Note: Set at CDTP 3.16 MPA.
Parts Details
Part Name Condition(s) Received Work Performed Recommendation
Body/Bonnet Light deposits Clean, re-used
Nozzle Light deposits Clean, polished, lapped
Disc Light deposits Clean, polished, lapped
Disc Holder/ Guide Chatter marks Clean, re-used
Spindle Good condition Clean, re-used
Spring/ Spring washer Good condition Clean, re-used
Approvals
As Found As Left
As Found As Left
As Found As Left