You are on page 1of 4

Data sheet

__________________________________________________________________________________________________________________

ROLP SB / SIR 745F


Combined audible and optical LED signal
transmitter
Beginning with edition number 7002444 110311 VDA

Because of its rugged construction, the ROLP SB / SIR 745F is


suitable for universal use and can be operated directly on the fire
detector. The signal transmitter has 32 different sound types.

It complies with EN 54-3. Fig. 1 ROLP SB / SIR 745F


__________________________________________________________________________________________________________________

Description Dimensioned drawing


The ROLP SB / SIR 745F combined audible and optical LED sig-
nal transmitter can be connected to the SecuriFire
1000/2000/3000 fire detection systems and to SecuriPro.

The ROLP SB / SIR 745F signal transmitter audibly and optically


signals a fire alarm indoors; the IP 65 variant works as well out-
doors. The ROLP SB / SIR 745F can be connected directly to the
fire detector line along with other participants, including automatic
fire detectors and manual call points.

You can program 32 two different sound types with a DIL switch
and call them up under “1stSound” connection. Another signal can
be activated from other locations under “2ndSound”. This sound
type depends on the programming of the 1st sound.

The volume is regulated via a potentiometer.

Notice
To avoid damage, the DIL switch must not be switched
with a pointed object. Another, lower base with protec-
tion type IP 65 is optionally available.

ROLP SB / SIR 745F features


32 adjustable sound types Fig. 2 Dimensioned drawing in mm
Complies with EN 54-3
Environmental category Type A for indoor applications
Housing colours red and white Interfaces
Calotte colour: red
Low power consumption X1 connector plug for stub line
Termi Designation Description
1 + 24 V DC
2 + 24 V DC
3 - GND 1st sound
4 - GND 1st sound
5 - GND 2nd sound
6 - GND 2nd sound

X2 DIP switch for sound type setting


X3 potentiometer for sound pressure level attenuation
DIN sound effective current consumption
U (V) I (mA) U (V) I (mA)
09 8.7 20 20.5
10 11.9 22 22.1
12 13.0 24 23.5
14 15.7 26 25.0
16 17.2 28 26.1
18 18.7 30 27.5

ROLP SB / SIR 745 F T 811 036 en c 1/4


Data sheet

Connection
Monitored connection (primary line) of DIN setting and cable type
2 x 2 x 0.8 mm. If using a max. line length, the line length to the
external power supply must be taken into consideration. The con-
nections refer exclusively to one-sound connection. Multi-sound
actuation is not via monitored connections.

Via BX-IOM or B3-OM8/ B4-EIO


Number of signal Maximum Total power con-
transmitters line length sumption* (A)
1 3591 m 0.041
2 2144 m 0.068
Fig. 3 Connections 3 1528 m 0.096
4 1187 m 0.123
5 971 m 0.151
Planning 6 821 m 0.178
The guidelines for planning and installing automatic fire detector 7 711 m 0.206
systems apply when planning. The ROLP SB / SIR 745F audible 8 627 m 0.233
and optical signal transmitters can be used wherever audible and 9 561 m 0.261
optical signaling should be used to warn about fires. Because the 10 507 m 0.288
signal transmitter can be connected via the BX-IOM addressable 11 463 m 0.316
loop module at any position on an addressable loop, the lines do 12 426 m 0.343
not have to be conveyed to the fire alarm control panel. This 13 395 m 0.371
enables greater distances from the control panel. Alternatively, the
14 367 m 0.398
signal transmitter can be connected directly to the concerned cen-
15 344 m 0.426
tral component for monitored outputs. Power can be supplied by
16 323 m 0.453
the control panel or an external energy supply source.
17 304 m 0.481
18 288 m 0.508
Warning 19 273 m 0.536
An external voltage supply source is absolutely ne- 20 260 m 0.563
21 248 m 0.591
cessary for operating the BX-IOM as the module is
22 236 m 0.618
not supplied with power via the addressable loop! 23 226 m 0.646
24 217 m 0.673
The sound typesetting must be performed via the DIP switch. The 25 209 m 0.701
sound pressure level can be attenuated up to 20 dB (A) via the po- 26 201 m 0.728
tentiometer. 27 193 m 0.756
28 187 m 0.783
29 180 m 0.811
30 174 m 0.838
31 169 m 0.866
32 164 m 0.893
33 159 m 0.921
Fig. 4 DIP switch 34 154 m 0.948
35 150 m 0.976
36 146 m 1.003
37 142 m 1.031
Mounting and installation 38 138 m 1.058
To remove the ROLP SB / SIR 745F signal transmitter from the 39 134 m 1.086
base, screw out the safety screw clockwise and remove.
*incl. terminal resistor (680 Ohm)

Fig. 5 Removal

2/4 T 811 036 en c ROLP SB / SIR 745 F


First edition: 11.05.2011 / Std
Reference document: 7002444 110311.VMS (HEK)
The product specifications contained in this document are subject to change without notice.
© Copyright by Securiton
Data sheet

Via BX-IOM addressable loop (max. 39 pcs.) SecuriPro connection (max. 11 pcs.)
Number of signal Maximum Total power
transmitters line length consumption* (A)
1 2200 m 0.034
2 1400 m 0.068
3 1000 m 0.102
4 750 m 0.136
5 580 m 0.170
6 450 m 0.204
7 340 m 0.238
8 250 m 0.272
9 170 m 0.306
10 100 m 0.340
11 40 m 0.374
Fig. 6 BX-IOM *Incl. EoL terminal resistor (5.6 Ohm). Applies also to 2nd sound type control.

Via B3-OM8 or B4-EIO unit (max. 39 pcs.)

Abb. 8 SecuriPro
Fig. 7 B3-OM8 / B4-EIO

Article numbers / spare parts


Short designation Article number CH Article number
Combined Siren and Flash light, red ROLP SB-R --------------- 6300165
Combined Siren and Flash light, white ROLP SB-W / SIR 745F xxx.xxxxxx 6300158
Base (IP 65) white SO/ D/ W / SIR 745Z 001.227404 6800146
Base (IP 65) red SO/ D/ R --------------- 6800145

Technical data
Operating voltage range 9 – 28 V DC
Max. operating current when nominal voltage is 24 V DC (sound type 3) 16 mA
Volume when nominal voltage is 24 V DC with 1 metre spacing see sound table
Frequency range see sound table
Housing material ABS
Protection class 54 / 65 IP
Housing colour white RAL 9003; red RAL 3001
Ambient operating temperature -25...+70°C
Terminals 0.28 - 2.5 mm2
Weight 300 g
Mounting surface mounting
VdS approval G 206020
CPD certificate 0832-CPD-0132

ROLP SB / SIR 745 F T 811 036 en c 3/4


First edition: 11.05.2011 / Std
The product specifications contained in this document are subject to change without notice.
© Copyright by Securiton
Data sheet

Sound table

First sound Sound description


Second

ROLP SB /
sound
Code

SIR 745F

mA dB (A)
1 11111 14 Alternating 800 & 970 2 Hz (250 ms - 250 ms) 16 101
2 11110 14 Sweep 800 to 970 7 Hz (7/s) 16 102
3 11101 14 Sweep 800 to 970 1 Hz (1/s) 16 102
4 11100 14 Continuous 2850 Steady 30 111
5 11011 4 Sweep 2400 to 2850 7 Hz 28 111
6 11010 4 Sweep 2400 to 2850 1 Hz 28 111
7 11001 14 Slow whoop 300 to 1200 3 s sweep, 0.5 s silence, then repeat 18 99
8 11000 14 Sweep 1200 to 500 1 Hz 14 99
9 10111 4 Alternating 2400 & 2850 2 Hz (250 ms - 250 ms) 28 110
10 10110 14 Intermittent 970 0.5 Hz (1 s on / 1 s off) 10 101
11 10101 14 Alternating 800 & 970 1 Hz (500 ms - 500 ms) 16 101
12 10100 4 Intermittent 2850 0.5 Hz (1 s on / 1 s off) 22 110
13 10011 14 Intermittent 970 0.8 Hz (250 s on / 1 s off) 6 97
14 10010 14 Continuous 970 Steady 18 102
15 10001 14 Alternating 554 & 440 100 ms - 400 ms 10 94
16 10000 16 Intermittent 660 3.3 Hz (150 ms on / 150 ms off) 7 87
17 01111 17 Intermittent 660 0.28 Hz (1.8 s on / 1.8 s off) 10 89
18 01110 18 Intermittent 660 0.05 Hz (6.5 s On / 13 s off) 12 89
19 01101 19 Continuous 660 Steady 12 90
20 01100 20 Alternating 554 & 440 0.5 Hz (1 s on / 1 s off) 11 97
21 01011 21 Intermittent 660 1 Hz (500 ms - 500 ms) 8 88
22 01010 14 Intermittent 2850 4 Hz (150 s on / 100 s off) 20 110
23 01001 14 Sweep 800 to 970 50 Hz 16 102
24 01000 4 Sweep 2400 to 2850 50 Hz 23 111
25 00111 25 Intermittent 970 3 x 500 ms pulses followed by 1.5 s si- 12 100
lence then repeat
26 00110 26 Intermittent 2850 3 x 500 ms pulses followed by 1.5 s si- 18 109
lence then repeat
27 00101 27 Continuous 4000 Steady 33 84
28 00100 10 Alternating 800 & 970 2 Hz (250 ms - 250 ms) 15 101
29 00011 31 Alternating 990 & 650 2 Hz (250 ms - 250 ms) (Symphoni 19 100
sounds)
30 00010 14 Alternating 510 & 610 2 Hz (250 ms - 250 ms) 13 97
(Squashni Micro sounds)
31 00001 31 Sweep 300 to 1200 1 Hz 19 97
32 00101 32 Continuous 4000 Steady 33 84

ROLP SB / SIR 745 F T 811 036 en c 4/4