Professional Documents
Culture Documents
39TF-EC (G) Installation and Maintenance Manual-2021 R1
39TF-EC (G) Installation and Maintenance Manual-2021 R1
St
an
da
rd
Ai
r
H
an
dli
ng
U
nit
–
C
eil
in
g
Ty
pe
(E
C)
In
st
all
ati
on
an
d
M
ai
nt
en
an
ce
M
an
ua
l
AHU
Contents
1 Safety Precautions........................................................................................................... 3
2 Unit Outline Dimensions and Specifications.....................................................................5
3 Handling and Storage..........................................................................................................6
3.1 Handling and Lifting of the Unit.............................................................................6
3.2 Unit Storage............................................................................................................... 6
4 Installation............................................................................................................................8
4.1 Installation of the Unit............................................................................................8
4.2 Installation of Water Piping System.......................................................................8
4.3 Installation of the Ducting System.......................................................................10
4.4 Electrical Wiring........................................................................................................10
4.4.1 Connection Diagram for Single Phase, 200-277V EC Fan........................10
4.4.2 Connection Diagram for 3 Phase, 380-480V EC Fan (K3G355RG5602) ......11
4.4.3 Connection Diagram for 3 Phase, 380-480V EC Fan (K3G500RA2803) .......12
4.5 Integrated Protective Features.................................................................................16
5 Test Run............................................................................................................................ 17
5.1 Pre-Startup Inspection..............................................................................................17
5.2 Test Run Procedure.................................................................................................17
6 Routine Maintenance.........................................................................................................18
7 Troubleshooting.................................................................................................................20
8 Spare Part..........................................................................................................................21
AHU
1 Safety Precautions
Please read through the Safety Precautions carefully before installation and operation. Be
sure to understand and follow the instructions strictly.
WARNING
CAUTION
[Failure to follow the instructions may cause minor personal injury or property damage.]
· Installation and maintenance must be performed by qualified personnel who are
authorized by the supplier and are familiar with relevant local laws and regulations
and have experience in this type of equipment.
· Always keep the air inlet and supply paths unobstructed.
· Turn off the power supply if the unit will not be used for a long time.
· The air conditioning unit shall not operate in corrosive gas environment as it may
lead to damage to the unit enclosure, pipeline or electrical elements.
· Install and insulate the drain pipe according to the instructions to ensure smooth
water drainage and prevent condensation.
3
AHU
Note: Due to ordering difference, your unit may not have some functions contained in this
manual. Please inform us of the specific performance parameters before placing the order.
4
AH
2 Unit Outline Dimensions and Specifications
Junction Box
A 13 C 4
Chilled
Water
L
Chilled
Water Inlet
Condensa
Drain
E D
Lifting Hole
E-
C-
Model
39TF
Dimensions (mm)
Outlet
Note:
1. Abbreviation:
3. The company reserves the right to change the specifications without prior notice.
5
AHU
7
AHU
4 Installation
4.1 Installation of the Unit
1. Carefully check whether the unit is damaged before unit installation. If any of the
following cases occurs, contact the distributor as soon as possible for repairing or
replacement:
a. Impact or serious deformation of the unit.
b. Damage of internal parts;
c. Malfunction of the fan.
2. The installation of the unit shall be conducted by professionals who are familiar with
the product and understand related local regulations. Do not collide or scratch the
unit during installation.
3. For the sake of safety, the supporting structure of ceiling type unit must be strong
enough to bear the weight of the unit and the vibration during unit operation. The
unit must also be kept horizontal to prevent overflow of condensate water from the
drain pan.
4. Space of at least 700 - 800 mm should be reserved around the unit, especially at the
side of the access door (panel) and external water pipe to ease the maintenance
and installation work.
5. The drain piping and exhaust valve are set at the side of heat exchanger header.
Loosen the exhaust valve to discharge air when water is supplied and tighten it
after finish discharging. Drain all the accumulated water in the unit if the unit is to
be stopped operating for a period of time.
9
AHU
Interfac
Full Adjustable
P
1
P
8 8 2
+ PE
- 1-10 N
1 1
3 +
10 V → n = L
max 1 V → n 5 -
= min <1 V →
N
6
Speed CO
Adjustable via 7
1 0-10
8 0-10
V 47 47
RS 470
1
1 0 RS
10 RS
1 GN
1 0
1 10
10
Imax = 10
Connecti Fan /
Customer KL
RS
1
Full Adjustable
RS
1
RS
4 3/ 1 RS
+ RS
9 RS
- 1-10 GN
3 2/ 8 I
10 V - n = 0- 47
7
max 1 V - n 4- I O
= min <1 V - 6 1
+20
5 20
Set Value Speed +10
Requirement, eg. via Adjustable via 4 10
0- 3
3 10 47 2.2μ
5 GN
+ 4 2
OU
- 4-20 1 OU
6
3/
10
GN
2/ KL
N
3
CO
2
N
1
KL
L
3
L + P
2
L - N
1
P
PE1 /
1
AHU
No.
Conn.
Designation
Function/Assignment
PE
PE
Protective earth
KL1
1,2,3
L1, L2, L3
Power supply, voltage range (see nameplate), 50/60 Hz
KL2
1
NC
Floating status contact, break for failure
KL2
COM
floating status contact, changeover contact, common connection (2 A, max. 250 VAC, min. 10 mA, AC1)
KL2
3
NO
Floating status contact, make for failure
KL3
OUT
3,7
0-10 V
Use control / current sensor value input 0-10 VDC, impedance 100 kΩ only as alternative to 4-20 mA input,
SELV
KL3
+10 V
Voltage output 10 VDC (±3%), max. 10 mA, power supply for external devices (e.g. potentiometer), SELV
KL3
+20 V
Voltage output 20 VDC (+25%/-10%), max. 50 mA, power supply for external devices (e.g. sensors), SELV
KL3
4-20 mA
Use control / current sensor value input 4-20 mA, impedance 100 Ω only as alternative to 0-10 V input, SELV
KL3
9,11
RSB
RS485 interface for MODBUS, RSB
KL3
10,12
RSA
RS485 interface for MODBUS, RSA
1
AHU
D16C
D00C
D12E
D16A
(Selected
(Selected
D101
D147
D104
D148
D130
D130
D130
D130
D130
INP OUTPUT
Heating
Signal: Diagnostics
Source: Set value
Signal: Actual
Signal: Tach
MODBUS
Register for
IO Mode
CON2 Configurable IO Mode Electrical Specification Configuration
● ● ● ● ● ●
● ●
IO1 ●
●
D158 [0]
● ● ● ● ●
● ● ● ● ●
l Tach out (Open collector output) ●
Umax=50VDC, Imax=20mA, SELV
●
D158 [5]
● ● ● ● ● ●
l Diagnostics out (Open collector output)
Umax=50VDC, Imax=20mA, SELV
D158 [6]
1
AH
PE
1 N
2 L
Figure 4.2: Junction Box Connection Diagram for Single Phase, 200-277V EC Fan.
PE
Figure 4.3: Junction Box Connection Diagram for 3 Phase, 380-480V EC Fan
(K3G355RG5602). PE
Figure 4.4: Junction Box Connection Diagram for Single Phase, 200-277V EC Fan.
Note: The wiring will be connected as shown above unless otherwise specified by the
customer.
1
AHU
4.5
Integ
rated
Prote
ctive
Feat
ures
The
integr
ated
prote
ctive
functi
ons
caus
e the
EC
Fan
motor
to
switc
h off
auto
matic
ally in
the
event
of the
faults
descr
ibed
in the
table.
Fault
Rotor position de
Blocked rotor
Line undervoltage
voltage outside of
nominal voltage ra
Phase failure
16
AHU
5 Test Run
5.1 Pre-Startup Inspection
1. Ensure that the unit is mounted securely to the supporting structure and is kept
level.
2. Check that all the ducting and piping are connected correctly to the unit.
3. Check that the electrical wiring of the fan is complete and in accordance with the
wiring diagram. Make sure that the fan is grounded.
4. Open the exhaust valve on the water return pipe and close it after air is removed
from the coil and pipeline.
5. Rotate the fan impeller manually to check whether there is any abnormal friction
sound. If yes, eliminate the cause.
6. Ensure the condensate drainage is unobstructed and properly installed.
7. Verify that the interior of the unit is clean and free from dirt, tool, or any other
foreign objects.
8. Check the condition of the filter and make sure that the duct connected to the unit
is clean.
9. Make sure that the power supply matches the device voltage.
17
AHU
6 Routine Maintenance
Note: Maintenance work can only be carried out after the unit has been completely
stopped.
Check the unit operating status on an irregular basis, and implement long-term and
effective maintenance for the unit so as to greatly improve the unit operation reliability and
service life.
1. To ensure good ventilation and achieve high heat exchange efficiency, check the
condition of air filters on a monthly basis, or on a weekly basis in places where air
environment is poor. Once the maximum pressure drop has been reached, clean or
replace the filter. The factory recommended the following maximum pressure drop:
Filter Maximum Pressure Drop (Pa)
MERV 5 (Primary Efficiency) 100
2. Inspect the condition of coil quarterly to confirm whether it is necessary to clean the
coil. Clean when fouling is observed. After the unit has been used for 2-3 years,
clear the water scale inside the pipe.
3. Check that the condensate discharge has no clogging and leaking issues.
4. Clean the drain pan and water seal elbow on an annual basis.
5. Check the flexible connector of air duct regularly. In case of air leakage, repair it in
time.
6. Inspect the wiring to make sure that the connections are tight and well insulated.
7. After checking, make sure that the EC fan terminal box is completely closed and
that all screws and cable glands have been properly tightened.
8. Inspect the fan for proper operation and soiling. Only clean when the fan is not in
motion. Do not disconnect the fan from power supply, just switch it off via control
input to prevent startup of the fan.
9. Use dry cleaning method (e.g. compressed air) to clean the fan. Deposition of dirt
on the motor housing can cause overheating of the motor, and soiling of the
impeller can cause vibration that will shorten the service life of the fan. Do not use
aggressive cleaning agent such as acid, alkali, or solvent-based cleaning agent.
10. If cleaning does not eliminate vibrations, the fan may need to be rebalanced. To
have it rebalanced, contact the supplier.
11. The fan is equipped with maintenance-free ball bearings. The lifetime lubrication of
the ball bearings is designed for a service life of at least 40,000 hours. If bearing
replacement is necessary after that period, contact the supplier.
12. Do not perform any repairs on the fan. Send it to supplier for repair or replacement.
18
AH
13. If the unit is under prolonged downtime in winter, turn off the power supply and
fully drain the coil to prevent freezing. Compressed air can be utilized to remove
residue water in the coil. During the downtime, start and operate the EC fan at full
speed for one hour at least every four months to move the bearings and allow any
condensate that may have ingressed to evaporate.
14. To remove the service panel, do not pull it out from the bottom. Remove it slowly
from the top, otherwise the lining board of service panel would be damaged by
pulling.
Service
Heat
Service Heat
15. Before installing the removed service panel, clean the dried sealant at the side of
drain pan near to the service panel, and then apply it again for sealing to prevent
air and water leakage.
1
AHU
7 Troubleshooting
Common Fault
Possible Cause
Solution
Abnormal sound
5. Fasten them.
Low air supply
volume
1. Dirty filter.
1. Clean the filter.
2. Check whether the prepared drainage U-trap is properly installed, and clear the dirt from the drainage pipe.
2. Fouling of coil.
2. Clean the coil.
3. Eliminate the cause of insufficient air supply volume and increase the air supply volume.
Impeller not
running
smoothly
turning
1.Mechanical blockage
3.Faulty connection
5.Deficient cooling
5. Improve cooling. Let the device cool down. To reset the error message, switch off the line voltage for at least 25s and
then switch it on again. Alternatively, reset the error message by applying a control signal of < 0.5 V to Din1 or by shorting
Din1 to GND.
6. Reduce the ambient temperature. Let the device cool down. To reset the error message, switch off the line voltage for
at least 25 s and then switch it on again. Alternatively, reset the error message by applying a control signal of < 0.5 V to
Din1 or by shorting Din1 to GND.
8. Correct the operating point. Let the device cool down. To reset the error message, switch off the line voltage for at least
25 s and then switch it on again. Alternatively, reset the error message by applying a control signal of < 0.5 V to Din1 or by
shorting Din1 to GND.
20
AHU
8 Spare Part
EC Fan K3G500RA2803 1