SUBJECT: TECHNICAL REPORT ON MAINTENANCE OF


WINDOW TYPE AIR CONDITIONING EQUIPMENT.
LOCATION: SPARE PARTS WAREHOUSE

It is a great pleasure to contact you with the purpose of informing you of the results of the repair
carried out on the air conditioning equipment in question.

1.- SPECIFICATIONS
 Brand: Carrier
 Capacity: 18000 BTU/H
 Current: 9.5A
 Voltage: 208 - 230 V

2. BACKGROUND.
The equipment is operational and only the evaporator and air filter are dirty.

3.- WORK DONE.


The technical department, once the review of the various mechanisms of the equipment has been carried out,
has carried out the following work:
 Cleaning the evaporator coil with a hydro washer and 10% Acti Klean cleaning liquid.
 Cleaning the condenser coil with hydro washer with 10% Alkyfoam cleaning fluid
 Cleaning the air filters.
 .Cleaning and lubrication (greasing) of the electric fan motor bearings.
 Review of the electrical circuit.
 Funcionality test

4.- CHANGES MADE.


During the maintenance carried out, no defective elements were found that required changes.

5.- WORK PARAMETERS.


Once the repair work was completed, the functional tests were carried out and the following work parameters
were taken:
 Work intensity: 8.8 Amperes
 Voltage: 226 Volts.
 Low pressure: 62 PSIG
 Supply air temperature: 6°C

5.- RECOMMENDATIONS.
It is recommended to perform preventive maintenance quarterly to maintain the good state of conservation
and operation of the machine.

Sincerely.
SISEG EXIMPORT EIRL
JR SAN MARTIN 800 CASTILLA PIURA PIURA
AV GRAU N° 2207 CASTILLA PIURA
R.U.C. 20525578870
PHONE: 349532 CEL 947495210 RPM #0305210
E MAIL sisegnegociossac@hotmail.com

Piura, June 2, 2014


Sirs:
PRODUCT EXPORT
Attention:
Mr. Manuel Hidalgo.

SUBJECT: TECHNICAL REPORT ON REPAIR OF PACKAGE


TYPE AIR CONDITIONING EQUIPMENT.
LOCATION: Rancheros

It is a great pleasure to contact you with the purpose of informing you of the results of the repair
carried out on the air conditioning equipment in question.

1.- SPECIFICATIONS
 Brand: Carrier
 Capacity: 60000 BTU/H
 Current: 16A
 Voltage: 208 - 230 V

2. BACKGROUND.
The equipment is inoperative due to the lack of a centrifugal evaporator fan and the evaporator is
observed to be saturated with dirt.

3.- WORK DONE.


The technical department, once the review of the various mechanisms of the equipment has been carried out,
has carried out the following work:
 Cleaning the evaporator coil with a hydro washer and 10% Acti Klean cleaning liquid.
 Cleaning the condenser coil with hydro washer with 10% Alkyfoam cleaning fluid
 Cleaning the air filters.
 .Cleaning and lubrication of condenser fan motor
 Maintenance, varnishing, drying and washing of the evaporator fan motor
 Change of 02 6203 bearings to evaporator fan motor
 Installation of new centrifugal fan
 Removal of refrigerant from the cooling system due to excess load.
 Review of the electrical circuit.
 Funcionality test

4.- CHANGES MADE.


In the repair carried out the following was changed:
 02 bearings 6203 a evaporator fan motor
 01 metallic centrifugal evaporator fan

5.- WORK PARAMETERS.


Once the repair work was completed, the functional tests were carried out and the following work parameters
were taken:
 Work intensity: 15.2 Amperes
 Voltage: 220 Volts.
 Low pressure: 62 PSIG
 Supply air temperature: 5°C

5.- RECOMMENDATIONS.
It is recommended to perform preventive maintenance quarterly to maintain the good state of conservation
and operation of the machine.