PKS™ - TDC 3000® TAB PD 15

CUSTOMER PAGE A10 (A)


RESOURCE MANUAL DATE 19 JUL 2013

LCN CABLE AND FITTINGS

Background There have been many problems caused by the LCN CABLING
instructions not being followed. The instructions are found in the Site
Planning & Installation Instructions for each release.
 Do not substitute unauthorized cables.
 Minimum LCN cable length between nodes is 2-meters.
 Maximum length is 300 meters and 40 nodes for any coaxial bus
segment.
 The BNC tee connectors used by the LCN are not the same as
used by the Data Hiway and must not be mixed.
 The 75 ohm terminators required at each end of the coax are the
same as those used by the Data Hiway.
 LCN coax cannot be routed outside of a building.
 LCN coax cable must never be spliced.
All LCN coax cables supplied by Honeywell now have cylindrical ferrites
installed at each end for EMI suppression to meet the European
Compliance “EC” standard. The cylindrical ferrites have no effect on
normal LCN communication so the new and old style cables can be used
together.

Cable The following cables come as pairs, the "A" cable has a Yellow band on
the BNC connectors and the "B" cable has a Green band on the
connectors (See PD23B03B). RG59 (20 awg) coax cable sets only come
in 2 meter lengths to be used between nodes in the same cabinet. See
Table 1. Table 2 on the next page shows the standard lengths that
Honeywell supplies RG11 (14 awg) coax cable sets.

Table 1
2-Meter 51308111-002 51109806-002
Cable Pair  

Notes:
 Currently supplied cable pair with cylindrical ferrites on both
ends.
 Discontinued cable pair without cylindrical ferrites. An order
for this cable will be filled with the new cable with cylindrical
ferrites.

Continued on next page

Honey wel l Aut omat i on and Cont r ol Sol ut i ons


TAB PD 15 A10 (A) PAGE 2 DATE 19 JUL 2013

LCN CABLE AND FITTINGS, Continued

Cable, Continued The RG11 coax cable should be used wherever the RG59 2-meter cable
cannot reach. The available standard lengths are shown in Table 2.
Custom lengths can also be ordered, but there will be a longer delivery time.
For a custom length, order 51308112-xxx, where xxx = the length in meters
of the cable pair desired.
Table 2
Length 51308112-TAB 51109181-TAB
Meters  
3 -003 -003
5 -005 -005
8 -008 -008
10 -010 -010
15 -015 -015
30 -030 -030
50 -050 -050
75 -075 -075
100 -100 -100
125 -125 -125
150 -150 -150
200 -200 -200
250 -250 -250
300 -300 -300

Notes  Currently supplied cable pair with cylindrical ferrites on both ends.
 Discontinued cable pair without cylindrical ferrites. An order for this
cable will be filled with the new cable with cylindrical ferrites.

Cable Fittings The parts listed in Table 3 can be used with LCN cable.
Table 3
FITTINGS BNC MS # PART NUMBER QUANTITY
Coax Tee set (LCN only)  None 51196041-100 2/pkg
Terminator 75 ohm + Ground  None 51305492-100 1/pkg
Terminator 75 ohm None 30732052-001 1/pkg
Terminator 75 ohm C-KCA02 30732107-009 2/pkg
Coax Conn. BNC to BNC C-KCA04 30732107-007 6/pkg

Notes  Standard 75 ohm terminator with 7" ground wire attached with ring lug.
Intended to provide ground for LCN coax cable when only GUS MAUs are
present on the LCN cable. See PD 19 A99 (B) for more details.
 Some LCN tees now come with a square body similar to Hiway tees. The LCN
body is smaller than the Hiway tee body. See "PD 07 C03 (D)" for instructions
on how to determine if the tee is for LCN or has resistors for the Hiway.

Continued on next page

Honey wel l Aut omat i on and Cont r ol Sol ut i ns


TAB PD 15 A10 (A) PAGE 3 DATE 19 JUL 2013

LCN CABLE AND FITTINGS, Continued

Ferrite Repair If a cylindrical ferrite breaks, a user can replace it with a split style ferrite
shown in Table 4. Because the ferrite is split, the BNC connector does not
have to be removed to install the new ferrite. If the cable is connected, it
does not have to be disconnected to install the new ferrite. The tab -101 will
fit all large cables and the tab -102 will fit all small cables.
Table 4
Cable Honeywell Steward
Size Part # Part #
RG11 (14 awg) 51191902-101 28B2024-0A0
RG59 (20 awg) 51191902-102 28B2025-0A0

Cylindrical If a user wants to replace a cylindrical ferrite with the same kind of ferrite, it
ferrites must be replaced by our cable vendor. Honeywell does not have the
cylindrical ferrites for the coax cable available. Table 5 lists suppliers of the
cylindrical ferrites. Any equivalent cylindrical ferrites could be used.

The current supplier is:

USA Scotland
Steward, Inc. Brucefield Industrial Estate
1200 East 36th Street 5 Cochrane Square
P.O. Box 510 Livingston EH54 9DR
Chattanooga, Tennessee 37401 Scotland, UK
Phone: 423-867-4100 Phone: 44 (0)1 506-414200
FAX: 423-867-4102 FAX: 44 (0)1 506-410694

Singapore
47 Hill Street, #08-07
SCCCI Building
Singapore 179365
Phone: 65-337-9667
FAX: 65-337-9686

The following Steward cylindrical ferrites are used:

Table 5
Cable Steward
Size Part #
RG59 28B0590-200
RG11 28B0736-000

Honey wel l Aut omat i on and Cont r ol Sol ut i ns