Name Title
Author John R. Baker Procedures and Investigations Manager
Checked by Stephen Booth Procedures and Investigations Engineer
Approved by Matt Thomas Head of Asset Management
Contents
1. Introduction ..................................................................................................................................................... 3
2. References ........................................................................................................................................................ 3
3. Deviations from this Data Sheet ...................................................................................................................... 3
4. Low Voltage cables ........................................................................................................................................... 4
5. 6.6kV Cables ..................................................................................................................................................... 6
6. 11kV Cables - Three core and single core in trefoil formation......................................................................... 7
7. 22kV Cables ...................................................................................................................................................... 8
8. 33kV Cables ...................................................................................................................................................... 9
9. Associated Documents ................................................................................................................................... 11
10. Applicable Standards .................................................................................................................................. 11
11. Revision History .......................................................................................................................................... 11
Page 2 of 11
1 Introduction
1.1 The tables in this document give the electrical constants for current and historical designs of
underground cables. The information is based on manufacturer’s data and other standards.
The R1 and X1 values are measured at the maximum conductor temperature for the design of
cable. Solid paper insulated at 65 oC. Fluid filled at 85 oC. Modern cables PVC 80 oC and
polymeric 90 oC.
2 References
2.1 The documents detailed in Table 2.1 – Scottish and Southern Electricity Networks Documents
shall be used in conjunction with this document.
Reference Title
TG-NET-CAB-009 Load Ratings of LV to 33 kV Underground Cables
TG-NET-CAB-011 Short Circuit Ratings of 6.6kV to 33kV Underground Cables
TG-NET-CAB-001 Installation of Electricity Service, Intake and Distributor Cables up to and
Including 33kV
Deviations from SSEN ‘G81’ Design Standards and Operational
TG-NET-ENG-011
Documents or Approved Designs - Design Standard
3.1 There may be times when it is necessary to propose a deviation from this Data Sheet.
3.2 Where this is required, a Deviation Request must be submitted to SSEN in accordance with
TG-NET-ENG-011. This process also applies to SSEN Connection Designers.
3.3 SSEN can refuse, or require, an alteration to a request. It is therefore imperative that signed
agreement is obtained before installation to avoid the possibility of rework or rejection of the
scheme. Requests for deviations which could compromise the safety of the Public or SSEN
staff will be rejected.
Page 3 of 11
Table 4.1
Phase conductor DC resistance Z1 (ohms/km)
size (ohms/km) at 20 oC
Material CSA mm² Phase Neutral R1 X1
Copper 4 4.52 4.8 5.41 0.054
Copper 16 1.13 1.20 1.36 0.042
Copper 25 0.712 0.75 0.855 0.041
Copper 3 × 16 1.15 1.21 1.38 0.088
Copper 3 × 25 0.727 0.765 0.87 0.087
Aluminium 25 1.18 1.24 1.42 0.043
Aluminium 35 0.851 0.900 1.02 0.041
Aluminium 3 × 35 0.868 0.912 1.05 0.082
Table 4.2
Page 4 of 11
Page 5 of 11
5 6.6kV Cables
Table 5.1
Conductor DC resistance Z1
Material Cross (ohms/km) Ohms/km Per unit/km on
Section at 20 oC 100 MVA base
R1 X1 R1 X1
Copper 0.0225 in² 1.257 1.552 0.104 3.56 0.238
Copper 0.06 in² 0.464 0.580 0.089 1.33 0.203
Copper 0.1 in² 0.276 0.339 0.083 0.779 0.190
Copper 0.15 in² 0.188 0.240 0.079 0.552 0.180
Copper 0.2 in² 0.141 0.186 0.077 0.426 0.176
Copper 0.25 in² 0.113 0.153 0.076 0.351 0.174
Copper 0.3 in² 0.092 0.131 0.074 0.302 0.172
Copper 0.4 in² 0.069 0.089 0.072 0.203 0.166
Copper 0.5 in² 0.056 0.073 0.071 0.168 0.163
Aluminium 70 mm²* 0.443 0.569 0.101 1.269 0.225
Aluminium 95 mm² 0.320 0.379 0.087 0.869 0.198
Aluminium 150 mm²* 0.206 0.265 0.091 0.591 0.203
Aluminium 185mm² 0.164 0.195 0.080 0.446 0.183
Aluminium 240 mm²* 0.125 0.161 0.085 0.359 0.190
Aluminium 300 mm² 0.100 0.120 0.077 0.274 0.176
Aluminium 300 mm²* 0.100 0.120 0.082 0.274 0.187
* 11kV polymeric cable
Page 6 of 11
* Polymeric Insulation
Page 7 of 11
7 22kV Cables
Table 7.1
Conductor DC resistance Z1
Material Cross (ohms/km) Ohms/km Per unit/km on
Section at 20 oC 100 MVA base
R1 X1 R1 X1
Copper 0.04 in² 0.702 0.799 0.118 0.165 0.0244
Copper 0.06 in² 0.464 0.525 0.110 0.109 0.0229
Copper 0.1 in² 0.276 0.317 0.102 0.0655 0.0210
Copper 0.15 in² 0.188 0.219 0.096 0.0452 0.0199
Copper 0.2 in² 0.141 0.164 0.092 0.0339 0.0190
Copper 0.25 in² 0.113 0.131 0.090 0.0271 0.0184
Copper 0.3 in² 0.092 0.106 0.088 0.0219 0.0180
Copper 185 mm² 0.099 0.118 0.091 0.0244 0.0188
Aluminium 95 mm² 0.320 0.379 0.101 0.078 0.0209
Aluminium 185 mm² 0.164 0.195 0.091 0.0403 0.0188
Aluminium 300 mm² 0.100 0.120 0.086 0.0248 0.0178
Page 8 of 11
8 33kV Cables
8.1 33kV Solid Paper Insulated Cables
Table 8.1
Conductor DC resistance Z1
Material Cross (ohms/km) Ohms/km Per unit/km on
Section at 20 oC 100 MVA base
R1 X1 R1 X1
Copper 0.06 in² 0.464 0.534 0.137 0.04904 0.01258
Copper 0.1 in² 0.276 0.328 0.139 0.03010 0.01275
Copper 0.15 in² 0.188 0.219 0.128 0.02010 0.01172
Copper 0.2 in² 0.141 0.164 0.123 0.01504 0.01127
Copper 0.25 in² 0.113 0.131 0.116 0.01203 0.01067
Copper 0.3 in² 0.092 0.109 0.113 0.01004 0.01034
Copper 0.4 in² 0.068 0.082 0.108 0.00753 0.00996
Copper 0.5 in² 0.056 0.068 0.105 0.00622 0.00963
Copper 50 mm² 0.387 0.456 0.126 0.03550 0.01157
Copper 70 mm² 0.268 0.316 0.119 0.02902 0.01093
Copper 95 mm² 0.193 0.228 0.112 0.02094 0.01025
Copper 185 mm² 0.099 0.118 0.101 0.0108 0.0093
Copper 240 mm² 0.075 0.090 0.097 0.0083 0.0089
Copper 300 mm² 0.060 0.073 0.094 0.0067 0.0086
Aluminium 95 mm² 0.318 0.379 0.112 0.0348 0.0103
Aluminium 185 mm² 0.164 0.195 0.101 0.01791 0.0093
Aluminium 240 mm² 0.125 0.149 0.097 0.0137 0.0089
Aluminium 300 mm² 0.100 0.120 0.094 0.0110 0.0086
Table 8.2
Conductor DC resistance Z1
Material Cross (ohms/km) Ohms/km Per unit/km on
Section at 20 oC 100 MVA base
R1 X1 R1 X1
Copper 0.1 in² 0.276 0.347 0.093 0.03184 0.00853
Copper 0.15 in² 0.188 0.238 0.088 0.02184 0.00804
Copper 0.2 in² 0.141 0.179 0.084 0.01652 0.00771
Copper 0.25 in² 0.113 0.143 0.083 0.01324 0.00763
Copper 0.3 in² 0.092 0.117 0.080 0.01074 0.00733
Page 9 of 11
Conductor DC resistance Z1
Material Cross (ohms/km) Ohms/km Per unit/km on
Section at 20 oC 100 MVA base
R1 X1 R1 X1
Copper 0.4 in² 0.068 0.089 0.078 0.00814 0.00711
Copper 0.5 in² 0.056 0.073 0.075 0.00673 0.00694
Copper 0.6 in² 0.046 0.061 0.074 0.00563 0.00684
Copper 185 mm² 0.099 0.127 0.078 0.01166 0.00711
Copper 240 mm² 0.075 0.097 0.083 0.0089 0.0076
Copper 300 mm² 0.060 0.078 0.081 0.0072 0.0074
Copper 400 mm² 0.047 0.063 0.079 0.0058 0.0073
Aluminium 185 mm² 0.164 0.211 0.085 0.0194 0.0078
Aluminium 240 mm² 0.125 0.160 0.083 0.0147 0.0076
Aluminium 300 mm² 0.100 0.130 0.081 0.0119 0.0074
Aluminium 400 mm² 0.078 0.102 0.079 0.0094 0.0073
Table 8.3
Conductor DC resistance Z1
Material Cross (ohms/km) Ohms/km Per unit/km on
Section at 20 oC 100 MVA base
R1 X1 R1 X1
Aluminium 95 mm² 0.3200 0.3894 0.137 0.0358 0.0126
Copper 185 mm² 0.0991 0.1274 0.124 0.0117 0.0139
Copper 240 mm² 0.0754 0.0976 0.118 0.0090 0.0108
Aluminium 300 mm² 0.1000 0.1293 0.114 0.0119 0.0105
Copper 300 mm² 0.0601 0.0785 0.114 0.0072 0.0105
Aluminium 400 mm² 0.0778 0.1013 0.110 0.0093 0.0101
Copper 400 mm² 0.0470 0.0624 0.110 0.0057 0.0101
Aluminium 500 mm² 0.0605 0.0797 0.106 0.0073 0.0097
Copper 500 mm² 0.0366 0.0500 0.106 0.0046 0.0097
Aluminium 630 mm² 0,0469 0,068 0,103 0,0063 0,0103
Copper 630 mm² 0.0283 0.0404 0.102 0.0037 0.0094
Copper 800 mm² 0.0221 0.0336 0.098 0.0031 0.0090
Aluminium 800 mm² 0.037 0.051 0.098 0.0047 0.0090
Aluminium 1000 mm² 0.029 0.042 0.095 0.0039 0.0087
Page 10 of 11
9 Associated Documents
9.1 Table 9.1 details the documents used in the compilation of this document.
Table 9.1
Document Reference Document Title Code Section
10 Applicable Standards
10.1 Third Parties must obtain copies of non SSEN Standards, such as BS or ENA documents, from
the issuing organisations at their own expense. These documents may be subject to copyright.
10.2 Documents for use by third parties are classified as Public and are available on the SSEN
website,
https://www.ssen.co.uk/competitioninconnections/
10.3 Documents not displayed on the internet are not publicly available as they are deemed not to
be needed by third parties. Where third parties require copies of these SSEN documents they
can be requested from the SSEN DMS Administrator, Inveralmond House, 200 Dunkeld Road,
Perth PH1 3AQ.
10.4 There will be a cost of £150 for each copy of each document (irrespective of size). This cost is
due to the administration required to ensure that updates to the documents (which are
controlled) are sent out to third parties.
11 Revision History