SECTION 16.10
Electrical Identifications & Labelling
Table of Contents
16.10.1 Part I – General ........................................................................................................................ 2
16.10.1.1 Section Includes
16.10.1.2 Scope and Description of Work
16.10.1.3 Submittals
Examine all other sections of the Specification for requirements which affect work of this
section whether or not such work is specifically mentioned in this section.
16.10.1.3 Submittals
Product catalogue data and samples for name plates, labels charts, tags, signs and markers
prior to commencing works.
a. Name plates and labels shall be engraved three layer 2mm traffolyte, securely screwed to
the housing and have black letters on white background in Arabic and English.
b. The locations are for each electrical distribution board, control equipment enclosures and
communication cabinets.
d. Labels using embossed adhesive tape, with 5mm white letters on black background for
identification of individual wall switches, receptacles, and control device stations shall be
used.
b. The location shall be for each conductor at panel board gutters, pull boxes, outlet and
junction boxes and each load connection.
c. Power and lighting circuit on branch or feeder circuits and control circuits shall require a
number.
a. Provide color bands 75mm wide for all trunking runs, applied at panel and junction box
locations and at 15m centers within an area.
b. Provide color bands 25mm wide for conduits up to 50mm in diameter and one half the
conduit diameter for larger conduits, applied at panel and pull box locations, within each
room, and at 6m centers within an area.
c. Color Banding:
a. Individual circuit identification charts shall be provided for all panel boards and
distribution boards.
b. Charts shall be typed on A4 size sheets. They shall be enclosed in a clear plastic envelope
and shall be securely fixed to the inside cover of the unit. Additional copies of the charts
shall be included in the Operation and Maintenance Manuals.
b. All cables which exit from manholes, vaults, hand-holes, and transformer or switch
enclosures shall be properly tagged or labeled. Tags shall be permanent, non-corrodible
and clearly readable. Tags should include the information listed below for the various
circuit categories:
Feeder Name
Voltage
Phase (Single Conductor Cables)
c. Cable identification for wire and cable circuits shall be of an opaque nylon material
arranged to include a marker plate, non-releasing nylon ties, and cable fastening tail. One
side shall be roughened to hold black nylon permanent ink. Identification shall be
permanent and waterproof. The holding device shall be designated to allow the fastening
tail to pass around the cable through the holding device, and prevent removal of the tail
without cutting it loose from the marker. Cable identification shall be inscribed in Arabic
and English.
a. For external use, pressure sensitive danger signs shall be used. Dimensions shall be
510mm by 710mm. The signs shall be heavy duty vinyl with a self adhesive backing which
can be applied to curved or irregular surfaces. Danger signs shall be weather resistant and
shall not discolor or deteriorate with edge.
b. Danger signs shall be inscribed with the equipment voltage level along with an
internationally recognized danger sign.
16.10.2.7 Language
The Arabic and English language shall be used for all labeling and charts.
16.10.3.1 Preparation
16.10.3.2 Inscription
a. All items of switch gear and control gear including all electrical components shall be
provided with labels giving the following information:
16.10.3.3 Installation
a. Metallic surfaces using stainless steel or chromium plated bolts and / or self tapping
screws.
b. Concrete surfaces or masonry walls using raw plugs and brass wood screws.