COOLTECH SOLUTIONS

CLIENT : ATC | Sheet No :1 Date :31.10.2023


Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Fourth Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : LOBBY - TOWER | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 549 6588 5.0 20 199
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.84
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 2356
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 4.77 TR
EAST 0 0 0.00 0 | AIR 2356 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 115
WAL.PARTITION 2367 30 0.24 17042
CEILING 0 0 0.00 0 | CFM/TR 494 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 4.29 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 199 35 0.10 1.08 752 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 36054
PEOPLE 20 285 5700 | RLH 6630
LIGHTS 1.0 549 3.4 1873 | RTH 42684
APPLIANCE 2.0 1.00 3412.0 6824 | GTH 57235 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 32191 | TR 4.77
ADD : 7% Fan + 5% Safety 3863 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 36054 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 5.89 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 199 64 0.10 0.68 865 | NOTES :
PEOPLE 20 245 4900 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 5765 |
ADD : 10% Fan + 5% Safety 865 |
TOTAL ROOM LATENT HEAT 6630 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 42684 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 199 35 0.90 1.08 6764 |
OA Latent 199 64 0.90 0.68 7787 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 4.77 TR 57235 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :2 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Fourth Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : SWITCH ROOM - TOWER | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 216 2592 5.0 1 44
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.97
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 1111
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 1.73 TR
EAST 0 0 0.00 0 | AIR 1111 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 125
WAL.PARTITION 758 30 0.24 5458
CEILING 0 0 0.00 0 | CFM/TR 644 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 5.14 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 44 35 0.10 1.08 166 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 16997
PEOPLE 1 285 285 | RLH 501
LIGHTS 1.0 216 3.4 737 | RTH 17498
APPLIANCE 2.5 1.00 3412.0 8530 | GTH 20709 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 15175 | TR 1.73
ADD : 7% Fan + 5% Safety 1821 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 16997 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 2.78 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 44 64 0.10 0.68 191 | NOTES :
PEOPLE 1 245 245 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 436 |
ADD : 10% Fan + 5% Safety 65 |
TOTAL ROOM LATENT HEAT 501 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 17498 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 44 35 0.90 1.08 1493 |
OA Latent 44 64 0.90 0.68 1719 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 1.73 TR 20709 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :3 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Fifth Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : CORRIDOR - TOWER | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 240 2880 5.0 10 93
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.82
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 979
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 2.09 TR
EAST 0 0 0.00 0 | AIR 979 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 115
WAL.PARTITION 826 30 0.24 5947
CEILING 0 0 0.00 0 | CFM/TR 468 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 4.08 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 93 35 0.10 1.08 352 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 14986
PEOPLE 10 285 2850 | RLH 3284
LIGHTS 1.0 240 3.4 819 | RTH 18270
APPLIANCE 1.0 1.00 3412.0 3412 | GTH 25091 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 13380 | TR 2.09
ADD : 7% Fan + 5% Safety 1606 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 14986 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 2.45 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 93 64 0.10 0.68 406 | NOTES :
PEOPLE 10 245 2450 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 2856 |
ADD : 10% Fan + 5% Safety 428 |
TOTAL ROOM LATENT HEAT 3284 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 18270 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 93 35 0.90 1.08 3171 |
OA Latent 93 64 0.90 0.68 3650 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 2.09 TR 25091 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :4 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Fifth Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : CORRIDOR - TOWER | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 216 2592 5.0 1 44
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.97
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 1111
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 1.73 TR
EAST 0 0 0.00 0 | AIR 1111 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 125
WAL.PARTITION 758 30 0.24 5458
CEILING 0 0 0.00 0 | CFM/TR 644 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 5.14 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 44 35 0.10 1.08 166 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 16997
PEOPLE 1 285 285 | RLH 501
LIGHTS 1.0 216 3.4 737 | RTH 17498
APPLIANCE 2.5 1.00 3412.0 8530 | GTH 20709 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 15175 | TR 1.73
ADD : 7% Fan + 5% Safety 1821 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 16997 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 2.78 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 44 64 0.10 0.68 191 | NOTES :
PEOPLE 1 245 245 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 436 |
ADD : 10% Fan + 5% Safety 65 |
TOTAL ROOM LATENT HEAT 501 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 17498 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 44 35 0.90 1.08 1493 |
OA Latent 44 64 0.90 0.68 1719 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 1.73 TR 20709 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :5 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Fifth Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : LADIES REST ROOM | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 150 1800 5.0 6 57
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.81
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 537
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 1.20 TR
EAST 0 0 0.00 0 | AIR 537 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 125
WAL.PARTITION 600 30 0.24 4320
CEILING 0 0 0.00 0 | CFM/TR 449 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 3.58 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 57 35 0.10 1.08 215 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 8218
PEOPLE 6 285 1710 | RLH 1976
LIGHTS 1.0 150 3.4 512 | RTH 10194
APPLIANCE 0.2 1.00 3412.0 580 | GTH 14365 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 7337 | TR 1.20
ADD : 7% Fan + 5% Safety 880 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 8218 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 1.34 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 57 64 0.10 0.68 248 | NOTES :
PEOPLE 6 245 1470 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 1718 |
ADD : 10% Fan + 5% Safety 258 |
TOTAL ROOM LATENT HEAT 1976 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 10194 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 57 35 0.90 1.08 1939 |
OA Latent 57 64 0.90 0.68 2233 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 1.20 TR 14365 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :6 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Fifth Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : GENTS REST ROOM | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 150 1800 5.0 6 57
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.81
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 537
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 1.20 TR
EAST 0 0 0.00 0 | AIR 537 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 125
WAL.PARTITION 600 30 0.24 4320
CEILING 0 0 0.00 0 | CFM/TR 449 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 3.58 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 57 35 0.10 1.08 215 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 8218
PEOPLE 6 285 1710 | RLH 1976
LIGHTS 1.0 150 3.4 512 | RTH 10194
APPLIANCE 0.2 1.00 3412.0 580 | GTH 14365 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 7337 | TR 1.20
ADD : 7% Fan + 5% Safety 880 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 8218 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 1.34 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 57 64 0.10 0.68 248 | NOTES :
PEOPLE 6 245 1470 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 1718 |
ADD : 10% Fan + 5% Safety 258 |
TOTAL ROOM LATENT HEAT 1976 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 10194 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 57 35 0.90 1.08 1939 |
OA Latent 57 64 0.90 0.68 2233 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 1.20 TR 14365 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :7 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Sixth Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : CORRIDOR - TOWER | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 240 2880 5.0 10 93
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.82
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 979
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 2.09 TR
EAST 0 0 0.00 0 | AIR 979 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 115
WAL.PARTITION 826 30 0.24 5947
CEILING 0 0 0.00 0 | CFM/TR 468 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 4.08 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 93 35 0.10 1.08 352 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 14986
PEOPLE 10 285 2850 | RLH 3284
LIGHTS 1.0 240 3.4 819 | RTH 18270
APPLIANCE 1.0 1.00 3412.0 3412 | GTH 25091 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 13380 | TR 2.09
ADD : 7% Fan + 5% Safety 1606 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 14986 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 2.45 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 93 64 0.10 0.68 406 | NOTES :
PEOPLE 10 245 2450 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 2856 |
ADD : 10% Fan + 5% Safety 428 |
TOTAL ROOM LATENT HEAT 3284 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 18270 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 93 35 0.90 1.08 3171 |
OA Latent 93 64 0.90 0.68 3650 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 2.09 TR 25091 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :8 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Sixth Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : CORRIDOR - TOWER | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 216 2592 5.0 1 44
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.97
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 1111
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 1.73 TR
EAST 0 0 0.00 0 | AIR 1111 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 125
WAL.PARTITION 758 30 0.24 5458
CEILING 0 0 0.00 0 | CFM/TR 644 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 5.14 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 44 35 0.10 1.08 166 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 16997
PEOPLE 1 285 285 | RLH 501
LIGHTS 1.0 216 3.4 737 | RTH 17498
APPLIANCE 2.5 1.00 3412.0 8530 | GTH 20709 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 15175 | TR 1.73
ADD : 7% Fan + 5% Safety 1821 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 16997 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 2.78 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 44 64 0.10 0.68 191 | NOTES :
PEOPLE 1 245 245 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 436 |
ADD : 10% Fan + 5% Safety 65 |
TOTAL ROOM LATENT HEAT 501 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 17498 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 44 35 0.90 1.08 1493 |
OA Latent 44 64 0.90 0.68 1719 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 1.73 TR 20709 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :9 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Seventh Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : CORRIDOR - TOWER | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 240 2880 5.0 10 93
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.82
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 979
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 2.09 TR
EAST 0 0 0.00 0 | AIR 979 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 115
WAL.PARTITION 826 30 0.24 5947
CEILING 0 0 0.00 0 | CFM/TR 468 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 4.08 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 93 35 0.10 1.08 352 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 14986
PEOPLE 10 285 2850 | RLH 3284
LIGHTS 1.0 240 3.4 819 | RTH 18270
APPLIANCE 1.0 1.00 3412.0 3412 | GTH 25091 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 13380 | TR 2.09
ADD : 7% Fan + 5% Safety 1606 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 14986 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 2.45 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 93 64 0.10 0.68 406 | NOTES :
PEOPLE 10 245 2450 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 2856 |
ADD : 10% Fan + 5% Safety 428 |
TOTAL ROOM LATENT HEAT 3284 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 18270 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 93 35 0.90 1.08 3171 |
OA Latent 93 64 0.90 0.68 3650 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 2.09 TR 25091 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :10 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Seventh Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : UPS & BATTERY ROOM | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 110 1320 5.0 1 25
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.97
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 765
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 1.16 TR
EAST 0 0 0.00 0 | AIR 765 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 95
WAL.PARTITION 504 30 0.24 3629
CEILING 0 0 0.00 0 | CFM/TR 659 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 6.96 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 25 35 0.10 1.08 94 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 11711
PEOPLE 1 285 285 | RLH 406
LIGHTS 1.0 110 3.4 375 | RTH 12117
APPLIANCE 1.8 1.00 3412.0 6073 | GTH 13932 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 10456 | TR 1.16
ADD : 7% Fan + 5% Safety 1255 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 11711 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 1.91 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 25 64 0.10 0.68 108 | NOTES :
PEOPLE 1 245 245 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 353 |
ADD : 10% Fan + 5% Safety 53 |
TOTAL ROOM LATENT HEAT 406 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 12117 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 25 35 0.90 1.08 844 |
OA Latent 25 64 0.90 0.68 971 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 1.16 TR 13932 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :11 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Seventh Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : APRON CONTROL ROOM | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 240 2880 5.0 2 53
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.97
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 1675
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 2.53 TR
EAST 0 0 0.00 0 | AIR 1675 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 95
WAL.PARTITION 816 30 0.24 5875
CEILING 0 0 0.00 0 | CFM/TR 662 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 6.98 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 53 35 0.10 1.08 201 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 25634
PEOPLE 2 285 570 | RLH 830
LIGHTS 1.0 240 3.4 819 | RTH 26464
APPLIANCE 4.5 1.00 3412.0 15422 | GTH 30357 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 22887 | TR 2.53
ADD : 7% Fan + 5% Safety 2746 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 25634 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 4.19 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 53 64 0.10 0.68 232 | NOTES :
PEOPLE 2 245 490 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 722 |
ADD : 10% Fan + 5% Safety 108 |
TOTAL ROOM LATENT HEAT 830 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 26464 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 53 35 0.90 1.08 1810 |
OA Latent 53 64 0.90 0.68 2084 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 2.53 TR 30357 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :12 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Seventh Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : DATIS | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 120 1440 5.0 2 32
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.94
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 793
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 1.26 TR
EAST 0 0 0.00 0 | AIR 793 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 95
WAL.PARTITION 528 30 0.24 3802
CEILING 0 0 0.00 0 | CFM/TR 627 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 6.61 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 32 35 0.10 1.08 119 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 12138
PEOPLE 2 285 570 | RLH 722
LIGHTS 1.0 120 3.4 409 | RTH 12860
APPLIANCE 1.7 1.00 3412.0 5937 | GTH 15172 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 10837 | TR 1.26
ADD : 7% Fan + 5% Safety 1300 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 12138 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 1.98 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 32 64 0.10 0.68 138 | NOTES :
PEOPLE 2 245 490 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 628 |
ADD : 10% Fan + 5% Safety 94 |
TOTAL ROOM LATENT HEAT 722 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 12860 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 32 35 0.90 1.08 1075 |
OA Latent 32 64 0.90 0.68 1238 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 1.26 TR 15172 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :13 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Seventh Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : UHF LINK ROOM | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 265 3180 5.0 2 58
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.97
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 1859
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 2.79 TR
EAST 0 0 0.00 0 | AIR 1859 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 95
WAL.PARTITION 876 30 0.24 6307
CEILING 0 0 0.00 0 | CFM/TR 666 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 7.02 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 58 35 0.10 1.08 218 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 28449
PEOPLE 2 285 570 | RLH 852
LIGHTS 1.0 265 3.4 904 | RTH 29301
APPLIANCE 5.1 1.00 3412.0 17401 | GTH 33524 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 25401 | TR 2.79
ADD : 7% Fan + 5% Safety 3048 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 28449 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 4.65 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 58 64 0.10 0.68 251 | NOTES :
PEOPLE 2 245 490 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 741 |
ADD : 10% Fan + 5% Safety 111 |
TOTAL ROOM LATENT HEAT 852 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 29301 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 58 35 0.90 1.08 1963 |
OA Latent 58 64 0.90 0.68 2260 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 2.79 TR 33524 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :14 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Seventh Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : IT & COMM. ROOM | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 188 2256 5.0 2 44
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.96
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 1289
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 1.98 TR
EAST 0 0 0.00 0 | AIR 1289 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 95
WAL.PARTITION 691 30 0.24 4975
CEILING 0 0 0.00 0 | CFM/TR 652 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 6.86 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 44 35 0.10 1.08 166 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 19725
PEOPLE 2 285 570 | RLH 783
LIGHTS 1.0 188 3.4 641 | RTH 20508
APPLIANCE 3.3 1.00 3412.0 11260 | GTH 23717 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 17612 | TR 1.98
ADD : 7% Fan + 5% Safety 2113 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 19725 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 3.22 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 44 64 0.10 0.68 191 | NOTES :
PEOPLE 2 245 490 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 681 |
ADD : 10% Fan + 5% Safety 102 |
TOTAL ROOM LATENT HEAT 783 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 20508 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 44 35 0.90 1.08 1491 |
OA Latent 44 64 0.90 0.68 1717 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 1.98 TR 23717 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :15 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Eigith Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : SERVICE BALCONY | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 213 2556 5.0 4 58
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.93
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 1298
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 2.13 TR
EAST 0 0 0.00 0 | AIR 1298 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 100
WAL.PARTITION 751 30 0.24 5407
CEILING 0 0 0.00 0 | CFM/TR 610 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 6.09 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 58 35 0.10 1.08 221 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 19858
PEOPLE 4 285 1140 | RLH 1419
LIGHTS 1.0 213 3.4 727 | RTH 21277
APPLIANCE 3.0 1.00 3412.0 10236 | GTH 25547 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 17730 | TR 2.13
ADD : 7% Fan + 5% Safety 2128 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 19858 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 3.24 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 58 64 0.10 0.68 254 | NOTES :
PEOPLE 4 245 980 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 1234 |
ADD : 10% Fan + 5% Safety 185 |
TOTAL ROOM LATENT HEAT 1419 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 21277 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 58 35 0.90 1.08 1985 |
OA Latent 58 64 0.90 0.68 2285 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 2.13 TR 25547 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
COOLTECH SOLUTIONS
CLIENT : ATC | Sheet No :16 Date :31.10.2023
Site : Trichy |------ ----------- --------------- ----------- --------------
Floor : Eigith Floor | DBT WBT RH GR/LB
Est.For : Summer/1600 Hrs | ODC 104 82 132
Area : AVIATION & COMM. ROOM | IDC 69.0 55 68
| Diff 35 64
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
L B H Area Volume AC/Hr Occup. F Air
Dimension : 12.0 2163 25956 5.0 16 469
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR GAIN FROM GLASS BTU/HR | WORKINGS
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | SHF 0.97
EAST 0 0 0.00 0 | ADP 52.00
WEST 0 0 0.00 0 | CFM 14269
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
SOLAR & TRAN. FROM WALL & ROOF | SUMMARY
NORTH 0 0 0.00 0 |
SOUTH 0 0 0.00 0 | LOAD 21.63 TR
EAST 0 0 0.00 0 | AIR 14269 cfm
WEST 0 0 0.00 0 | ADP 52.00 F
ROOF 0 0 0.00 0 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
TRANSMISSION GAIN | CHECK FIGURE
ALL GLASS 0 0 0.00 0 |
GL.PARTITION 0 0 0.00 0 | AREA/TR 100
WAL.PARTITION 5431 30 0.24 39103
CEILING 0 0 0.00 0 | CFM/TR 660 40500.00
FLOOR 0 0 0.00 0 | CFM/SFT 6.60 675.00
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------
INFILTRATION 0 | LOAD SUMMARY
OUTSIDE AIR 469 35 0.10 1.08 1774 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- | RSH 218319
PEOPLE 16 285 4560 | RLH 6857
LIGHTS 1.0 2163 3.4 7380 | RTH 225175
APPLIANCE 41.7 1.00 3412.0 142110 | GTH 259526 7.59
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM SENSIBLE HEAT 194927 | TR 21.63
ADD : 7% Fan + 5% Safety 23391 |-------- ----------- --------------
TOTAL ROOM SENSIBLE HEAT 218319 | TR Based on Air Qty
------------------------- ------------------------------- -------- --------- ------------------ ----------- | => 35.67 TR
INFILTRATION 0 |-------- ----------- --------------
OUTSIDE AIR 469 64 0.10 0.68 2043 | NOTES :
PEOPLE 16 245 3920 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
SUB TOTAL ROOM LATENT HEAT 5963 |
ADD : 10% Fan + 5% Safety 894 |
TOTAL ROOM LATENT HEAT 6857 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
ROOM TOTAL HEAT 225175 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
OA Sensible 469 35 0.90 1.08 15967 |
OA Latent 469 64 0.90 0.68 18383 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- |
GRAND TOTAL HEAT 21.63 TR 259526 |
------------------------- ------------------------------- -------- --------- ------------------ ----------- --------------- ----------- --------------