Zpu = 8.37956+6.

60696j pu
3. FEEDER 6 PER UNIT IMPEDANCE
Z = 0.01993+0.00472j Ω
Zpu = (0.01993+0.00472j Ω) x [(100 MVA)/(0.23 kV)^2]
Zpu = 37.68323+8.92497j pu

IMPEDANCE DIAGRAM

ZU

ZTR

ZC101

F1
ZC102

F2

ZC111 ZC112 ZC113 ZC114 ZC115 ZC116

F3 F4 F5 F6 F7 F8

FOR SHORT CIRCUIT AT FAULT F1


1. TOTAL PER UNIT IMPEDANCE
Zpu = ZU + ZTR + ZC101
Zpu = 9.01445+22.55422j pu = 24.28895 ∟68.21° pu
2. SHORT CIRCUIT CURRENT AT FAULT F1
IF1 = [(100 MVA)/(0.23 kV)] x [(1 ∟0° pu)/(24.28895 ∟68.21° pu)]
IF1 = 10.33 kA

FOR SHORT CIRCUIT AT FAULT F2


1. TOTAL PER UNIT IMPEDANCE
Zpu = ZU + ZTR + ZC101 + ZC102
Zpu = 10.40898+24.56854j pu = 26.68258 ∟67.04° pu
2. SHORT CIRCUIT CURRENT AT FAULT F2
IF2 = [(100 MVA)/(0.23 kV)] x [(1 ∟0° pu)/(26.68258 ∟67.04° pu)]
IF2 = 9.41 kA

FOR SHORT CIRCUIT AT FAULT F3


1. TOTAL PER UNIT IMPEDANCE
Zpu = ZU + ZTR + ZC101 + ZC102 + ZC111
Zpu = 19.70583+27.41957j pu = 33.76615 ∟54.3° pu
2. SHORT CIRCUIT CURRENT AT FAULT F3
IF3 = [(100 MVA)/(0.23 kV)] x [(1 ∟0° pu)/(33.76615 ∟54.3° pu)]
IF3 = 7.43 kA