PROJECT TITLE: PROPOSED THREE-STOREY COMMERCIAL BUILDING

LOCATION: BGY. TINIGUIBAN, PUERTO PRINCESA CITY


SUBJECT: ELECTRICAL DESIGN ANALYSIS - SHORT CIRCUIT CALCULATION

BASE VALUES & DATA


1. BASE VALUE
MVAbase = 100
2. UTILITY DATA
MVASC = 86
X/R = 4
3. TRANSFORMER
kVATR = 225
%Z = 5.00
X/R = 2.5

PER UNIT IMPEDANCES


1. UTILITY PER UNIT IMPEDANCE
Zpu = 0.28202+1.12807j pu
2. TRANSFORMER PER UNIT IMPEDANCE
Zpu = 8.25313+20.63282j pu
3. MAIN FEEDER 1 PER UNIT IMPEDANCE
Z = 0.00025+0.00042j Ω
Zpu = (0.00025+0.00042j Ω) x [(100 MVA)/(0.23 kV)^2]
Zpu = 0.4793+0.79333j pu
3. MAIN FEEDER 2 PER UNIT IMPEDANCE
Z = 0.00074+0.00107j Ω
Zpu = (0.00074+0.00107j Ω) x [(100 MVA)/(0.23 kV)^2]
Zpu = 1.39453+2.01432j pu
3. FEEDER 1 PER UNIT IMPEDANCE
Z = 0.00492+0.00151j Ω
Zpu = (0.00492+0.00151j Ω) x [(100 MVA)/(0.23 kV)^2]
Zpu = 9.29685+2.85103j pu
3. FEEDER 2 PER UNIT IMPEDANCE
Z = 0.03534+0.00368j Ω
Zpu = (0.03534+0.00368j Ω) x [(100 MVA)/(0.23 kV)^2]
Zpu = 66.81335+6.95404j pu
3. FEEDER 3 PER UNIT IMPEDANCE
Z = 0.00393+0.00144j Ω
Zpu = (0.00393+0.00144j Ω) x [(100 MVA)/(0.23 kV)^2]
Zpu = 7.43748+2.72708j pu

3. FEEDER 4 PER UNIT IMPEDANCE


Z = 0.00252+0.00138j Ω
Zpu = (0.00252+0.00138j Ω) x [(100 MVA)/(0.23 kV)^2]
Zpu = 4.77238+2.60312j pu
3. FEEDER 5 PER UNIT IMPEDANCE
Z = 0.00443+0.0035j Ω
Zpu = (0.00443+0.0035j Ω) x [(100 MVA)/(0.23 kV)^2]
Zpu = 8.37956+6.60696j pu
3. FEEDER 6 PER UNIT IMPEDANCE
Z = 0.01993+0.00472j Ω
Zpu = (0.01993+0.00472j Ω) x [(100 MVA)/(0.23 kV)^2]
Zpu = 37.68323+8.92497j pu

IMPEDANCE DIAGRAM

ZU

ZTR

ZC101

F1
ZC102

F2

ZC111 ZC112 ZC113 ZC114 ZC115 ZC116

F3 F4 F5 F6 F7 F8

FOR SHORT CIRCUIT AT FAULT F1


1. TOTAL PER UNIT IMPEDANCE
Zpu = ZU + ZTR + ZC101
Zpu = 9.01445+22.55422j pu = 24.28895 ∟68.21° pu
2. SHORT CIRCUIT CURRENT AT FAULT F1
IF1 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(24.28895 ∟68.21° pu)]
IF1 = 10.33 kA

FOR SHORT CIRCUIT AT FAULT F2


1. TOTAL PER UNIT IMPEDANCE
Zpu = ZU + ZTR + ZC101 + ZC102
Zpu = 10.40898+24.56854j pu = 26.68258 ∟67.04° pu
2. SHORT CIRCUIT CURRENT AT FAULT F2
IF2 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(26.68258 ∟67.04° pu)]
IF2 = 9.41 kA

FOR SHORT CIRCUIT AT FAULT F3


1. TOTAL PER UNIT IMPEDANCE
Zpu = ZU + ZTR + ZC101 + ZC102 + ZC111
Zpu = 19.70583+27.41957j pu = 33.76615 ∟54.3° pu
2. SHORT CIRCUIT CURRENT AT FAULT F3
IF3 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(33.76615 ∟54.3° pu)]
IF3 = 7.43 kA
FOR SHORT CIRCUIT AT FAULT F4
1. TOTAL PER UNIT IMPEDANCE
Zpu = ZU + ZTR + ZC101 + ZC102 + ZC112
Zpu = 77.22233+31.52258j pu = 83.4084 ∟22.21° pu
2. SHORT CIRCUIT CURRENT AT FAULT F4
IF4 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(83.4084 ∟22.21° pu)]
IF4 = 3.01 kA

FOR SHORT CIRCUIT AT FAULT F5


1. TOTAL PER UNIT IMPEDANCE
Zpu = ZU + ZTR + ZC101 + ZC102 + ZC113
Zpu = 17.84646+27.29562j pu = 32.61207 ∟56.82° pu
2. SHORT CIRCUIT CURRENT AT FAULT F5
IF5 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(32.61207 ∟56.82° pu)]
IF5 = 7.7 kA

FOR SHORT CIRCUIT AT FAULT F6


1. TOTAL PER UNIT IMPEDANCE
Zpu = ZU + ZTR + ZC101 + ZC102 + ZC114
Zpu = 15.18136+27.17166j pu = 31.12512 ∟60.81° pu
2. SHORT CIRCUIT CURRENT AT FAULT F6
IF6 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(31.12512 ∟60.81° pu)]
IF6 = 8.06 kA

FOR SHORT CIRCUIT AT FAULT F7


1. TOTAL PER UNIT IMPEDANCE
Zpu = ZU + ZTR + ZC101 + ZC102 + ZC115
Zpu = 18.78854+31.1755j pu = 36.39946 ∟58.92° pu
2. SHORT CIRCUIT CURRENT AT FAULT F7
IF7 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(36.39946 ∟58.92° pu)]
IF7 = 6.9 kA

FOR SHORT CIRCUIT AT FAULT F8


1. TOTAL PER UNIT IMPEDANCE
Zpu = ZU + ZTR + ZC101 + ZC102 + ZC116
Zpu = 48.09221+33.49351j pu = 58.60611 ∟34.86° pu
2. SHORT CIRCUIT CURRENT AT FAULT F8
IF8 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(58.60611 ∟34.86° pu)]
IF8 = 4.28 kA