PROJECT TITLE: PROPOSED THREE-STOREY COMMERCIAL BUILDING
LOCATION: BGY. TINIGUIBAN, PUERTO PRINCESA CITY
SUBJECT: ELECTRICAL DESIGN ANALYSIS - SHORT CIRCUIT CALCULATION
BASE VALUES & DATA
1. BASE VALUE MVAbase = 100 2. UTILITY DATA MVASC = 86 X/R = 4 3. TRANSFORMER kVATR = 225 %Z = 5.00 X/R = 2.5
PER UNIT IMPEDANCES
1. UTILITY PER UNIT IMPEDANCE Zpu = 0.28202+1.12807j pu 2. TRANSFORMER PER UNIT IMPEDANCE Zpu = 8.25313+20.63282j pu 3. MAIN FEEDER 1 PER UNIT IMPEDANCE Z = 0.00025+0.00042j Ω Zpu = (0.00025+0.00042j Ω) x [(100 MVA)/(0.23 kV)^2] Zpu = 0.4793+0.79333j pu 3. MAIN FEEDER 2 PER UNIT IMPEDANCE Z = 0.00074+0.00107j Ω Zpu = (0.00074+0.00107j Ω) x [(100 MVA)/(0.23 kV)^2] Zpu = 1.39453+2.01432j pu 3. FEEDER 1 PER UNIT IMPEDANCE Z = 0.00492+0.00151j Ω Zpu = (0.00492+0.00151j Ω) x [(100 MVA)/(0.23 kV)^2] Zpu = 9.29685+2.85103j pu 3. FEEDER 2 PER UNIT IMPEDANCE Z = 0.03534+0.00368j Ω Zpu = (0.03534+0.00368j Ω) x [(100 MVA)/(0.23 kV)^2] Zpu = 66.81335+6.95404j pu 3. FEEDER 3 PER UNIT IMPEDANCE Z = 0.00393+0.00144j Ω Zpu = (0.00393+0.00144j Ω) x [(100 MVA)/(0.23 kV)^2] Zpu = 7.43748+2.72708j pu
3. FEEDER 4 PER UNIT IMPEDANCE
Z = 0.00252+0.00138j Ω Zpu = (0.00252+0.00138j Ω) x [(100 MVA)/(0.23 kV)^2] Zpu = 4.77238+2.60312j pu 3. FEEDER 5 PER UNIT IMPEDANCE Z = 0.00443+0.0035j Ω Zpu = (0.00443+0.0035j Ω) x [(100 MVA)/(0.23 kV)^2] Zpu = 8.37956+6.60696j pu 3. FEEDER 6 PER UNIT IMPEDANCE Z = 0.01993+0.00472j Ω Zpu = (0.01993+0.00472j Ω) x [(100 MVA)/(0.23 kV)^2] Zpu = 37.68323+8.92497j pu
IMPEDANCE DIAGRAM
ZU
ZTR
ZC101
F1 ZC102
F2
ZC111 ZC112 ZC113 ZC114 ZC115 ZC116
F3 F4 F5 F6 F7 F8
FOR SHORT CIRCUIT AT FAULT F1
1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 Zpu = 9.01445+22.55422j pu = 24.28895 ∟68.21° pu 2. SHORT CIRCUIT CURRENT AT FAULT F1 IF1 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(24.28895 ∟68.21° pu)] IF1 = 10.33 kA
FOR SHORT CIRCUIT AT FAULT F2
1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 + ZC102 Zpu = 10.40898+24.56854j pu = 26.68258 ∟67.04° pu 2. SHORT CIRCUIT CURRENT AT FAULT F2 IF2 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(26.68258 ∟67.04° pu)] IF2 = 9.41 kA
FOR SHORT CIRCUIT AT FAULT F3
1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 + ZC102 + ZC111 Zpu = 19.70583+27.41957j pu = 33.76615 ∟54.3° pu 2. SHORT CIRCUIT CURRENT AT FAULT F3 IF3 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(33.76615 ∟54.3° pu)] IF3 = 7.43 kA FOR SHORT CIRCUIT AT FAULT F4 1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 + ZC102 + ZC112 Zpu = 77.22233+31.52258j pu = 83.4084 ∟22.21° pu 2. SHORT CIRCUIT CURRENT AT FAULT F4 IF4 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(83.4084 ∟22.21° pu)] IF4 = 3.01 kA
FOR SHORT CIRCUIT AT FAULT F5
1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 + ZC102 + ZC113 Zpu = 17.84646+27.29562j pu = 32.61207 ∟56.82° pu 2. SHORT CIRCUIT CURRENT AT FAULT F5 IF5 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(32.61207 ∟56.82° pu)] IF5 = 7.7 kA
FOR SHORT CIRCUIT AT FAULT F6
1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 + ZC102 + ZC114 Zpu = 15.18136+27.17166j pu = 31.12512 ∟60.81° pu 2. SHORT CIRCUIT CURRENT AT FAULT F6 IF6 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(31.12512 ∟60.81° pu)] IF6 = 8.06 kA
FOR SHORT CIRCUIT AT FAULT F7
1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 + ZC102 + ZC115 Zpu = 18.78854+31.1755j pu = 36.39946 ∟58.92° pu 2. SHORT CIRCUIT CURRENT AT FAULT F7 IF7 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(36.39946 ∟58.92° pu)] IF7 = 6.9 kA
FOR SHORT CIRCUIT AT FAULT F8
1. TOTAL PER UNIT IMPEDANCE Zpu = ZU + ZTR + ZC101 + ZC102 + ZC116 Zpu = 48.09221+33.49351j pu = 58.60611 ∟34.86° pu 2. SHORT CIRCUIT CURRENT AT FAULT F8 IF8 = [(100 MVA)/√3(0.23 kV)] x [(1 ∟0° pu)/(58.60611 ∟34.86° pu)] IF8 = 4.28 kA