You are on page 1of 1

(2F-PB) SECOND FLOOR PANEL BOARD

:
MOUNTING LOCATION ELECTRICAL ROOM VOLTAGE SYSTEM : 230 V, 3Ø, 60Hz
AREA/EQPT SERVED : COMMERCIAL BLDG :
MOUNTING METHOD WALL MOUNTED WIRE : 3W + G
FEED FROM : TRANSFORMER FEED TYPE : CONDUIT ENCLOSURE : NEMA-1 ENCL.

CKT. RATING LOAD DISTRIBUTION, KVA CIRCUIT BREAKER WIRE SIZE GRD-WIRE SIZE CONDUIT LENGTH PERMIT I.L. VOLTAGE DROP
LOAD DESCRIPTION P.F. D.F.
NO. VA KW KVA V AB BC CA 3ø 1ø TYPE KAIC POLE AT AF xC (mm²) A(mm²) TYPE (mm²) TYPE mmØ TYPE Meter V-Drop Amp. e(V) %V
1 CONVENIENCE 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
OUTLET
CONVENIENCE
2 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
OUTLET
CONVENIENCE
3 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
OUTLET
AIR CONDITIONING
4 5,100 4.08 5.10 230 22.17 22.17 22.17 MCCB 10 3P 30A 50 3 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 22.17 0.85 1 1.04 0.45
UNITCONDITIONING
AIR
5 5,100 4.08 5.10 230 22.17 22.17 22.17 MCCB 10 3P 30A 50 3 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 22.17 0.85 1 1.04 0.45
UNITCONDITIONING
AIR
6 5,100 4.08 5.10 230 22.17 22.17 22.17 MCCB 10 3P 30A 50 3 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 22.17 0.85 1 1.04 0.45
UNITCONDITIONING
AIR
7 5,100 4.08 5.10 230 22.17 22.17 22.17 MCCB 10 3P 30A 50 3 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 22.17 0.85 1 1.04 0.45
UNITCONDITIONING
AIR
8 5,100 4.08 5.10 230 22.17 22.17 22.17 MCCB 10 3P 30A 50 3 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 22.17 0.85 1 1.04 0.45
UNITCONDITIONING
AIR
9 5,100 4.08 5.10 230 22.17 22.17 22.17 MCCB 10 3P 30A 50 3 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 22.17 0.85 1 1.04 0.45
UNIT
10 SPARE - - -
11 SPARE - - -
12 SPARE - - -
13 SPARE - - -
14 SPARE - - -
TOTAL 33,300 26.64 33.30 230 140.87 136.96 133.04 MCCB 10 3P 125A 200 3 38 38 THHN 14 THHN 40 uPVC

TOTAL PANEL LOAD = 33.30 KVA


DEMAND FACTOR = 100.00 % MAIN PROTECTION: 125A 200 AF MCCB, 60 hz, Bolt On
TOTAL DEMAND LOAD = 33.30 KVA MAIN FEEDER SIZE: 3 - 38 mm2 THHN + 14 mm2 (G) in 1 - 40 uPVC
TOTAL CURRENT LOAD = 86.89 AMPS

DESIGN COMPUTATION SAFETY FACTOR MAIN CB FEEDER CONDUCTOR


33,300 VA + (25% x 5,100 VA) ISF = 86.89 A x 1.25 125A , 200 AF THREE PHASE, 3 POLE, USE 3C-38mm² THHN Cu. Wire,
IL =
230 V x 1.73 ISF = 108.62 A 230 VOLTS, 10kAIC 1C-8.0mm² Grounding Wire
IL = 86.89 A BOLT ON TYPE, MCCB, with GROUNDING IN 40mmØ uPVC Pipe
TERMINAL