You are on page 1of 1

(2F-LP) SECOND FLOOR LIGHTING PANEL BOARD

:
MOUNTING LOCATION ELECTRICAL ROOM VOLTAGE SYSTEM : 230 V, 3Ø, 60Hz
AREA/EQPT SERVED : COMMERCIAL BLDG :
MOUNTING METHOD WALL MOUNTED WIRE : 3W + G
FEED FROM : TRANSFORMER FEED TYPE : CONDUIT ENCLOSURE : NEMA-1 ENCL.

CKT. RATING LOAD DISTRIBUTION, KVA CIRCUIT BREAKER WIRE SIZE GRD-WIRE SIZE CONDUIT LENGTH PERMIT I.L. VOLTAGE DROP
LOAD DESCRIPTION P.F. D.F.
NO. VA KW KVA V AB BC CA 3ø 1ø TYPE KAIC POLE AT AF xC (mm²) A(mm²) TYPE (mm²) TYPE mmØ TYPE Meter V-Drop Amp. e(V) %V
1 LIGHTING OUTLET 275 0.22 0.28 230 1.20 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.20 1 1 0.08 0.03
2 LIGHTING OUTLET 250 0.20 0.25 230 1.09 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.09 1 1 0.07 0.03
3 LIGHTING OUTLET 275 0.22 0.28 230 1.20 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.20 1 1 0.08 0.03
4 LIGHTING OUTLET 300 0.24 0.30 230 1.30 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.30 1 1 0.08 0.04
5 LIGHTING OUTLET 275 0.22 0.28 230 1.20 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.20 1 1 0.08 0.03
6 LIGHTING OUTLET 350 0.28 0.35 230 1.52 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.52 1 1 0.10 0.04
7 LIGHTING OUTLET 350 0.28 0.35 230 1.52 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.52 1 1 0.10 0.04
8 LIGHTING OUTLET 350 0.28 0.35 230 1.52 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.52 1 1 0.10 0.04
9 LIGHTING OUTLET 350 0.28 0.35 230 1.52 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.52 1 1 0.10 0.04
10 LIGHTING OUTLET 325 0.26 0.33 230 1.41 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.41 1 1 0.09 0.04
11 LIGHTING OUTLET 325 0.26 0.33 230 1.41 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.41 1 1 0.09 0.04
12 LIGHTING OUTLET 300 0.24 0.30 230 1.30 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.30 1 1 0.08 0.04
13 LIGHTING OUTLET 300 0.24 0.30 230 1.30 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 1.30 1 1 0.08 0.04
14 SPARE - - -
15 SPARE - - -
16 SPARE - - -
17 SPARE - - -
18 SPARE - - -
TOTAL 4,025 3.22 4.03 230 6.63 5.43 5.43 MCCB 10 3P 40A 50 3 5.5 5.5 THHN 5.5 THHN 25 uPVC

TOTAL PANEL LOAD = 4.03 KVA


DEMAND FACTOR = 100.00 % MAIN PROTECTION: 40A 50 AF MCCB, 60 hz, Bolt On
TOTAL DEMAND LOAD = 4.03 KVA MAIN FEEDER SIZE: 3 - 5.5 mm2 THHN + 5.5 mm2 (G) in 1 - 25 uPVC
TOTAL CURRENT LOAD = 10.12 AMPS

DESIGN COMPUTATION SAFETY FACTOR MAIN CB FEEDER CONDUCTOR


4,025 VA + (25% x - VA) ISF = 10.12 A x 1.25 40A , 100 AF THREE PHASE, 3 POLE, USE 3C-8.0mm² THHN Cu. Wire,
IL =
230 V x 1.73 ISF = 12.64 A 230 VOLTS, 10kAIC 1C-5.5mm² Grounding Wire
IL = 10.12 A BOLT ON TYPE, MCCB, with GROUNDING IN 25mmØ uPVC Pipe
TERMINAL