(GF PB) GROUND FLOOR PANEL BOARD

:
MOUNTING LOCATION ELECTRICAL ROOM VOLTAGE SYSTEM : 230 V, 3Ø, 60Hz
AREA/EQPT SERVED : COMMERCIAL BLDG :
MOUNTING METHOD WALL MOUNTED WIRE : 3W + G
FEED FROM : TRANSFORMER FEED TYPE : CONDUIT ENCLOSURE : NEMA-1 ENCL.

CKT. RATING LOAD DISTRIBUTION, KVA CIRCUIT BREAKER WIRE SIZE GRD-WIRE SIZE CONDUIT LENGTH PERMIT I.L. VOLTAGE DROP
LOAD DESCRIPTION P.F. D.F.
NO. VA KW KVA V AB BC CA 3ø 1ø TYPE KAIC POLE AT AF xC (mm²) A(mm²) TYPE (mm²) TYPE mmØ TYPE Meter V-Drop Amp. e(V) %V
1 CONVENIENCE 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
OUTLET
CONVENIENCE
2 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
OUTLET
CONVENIENCE
3 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
OUTLET
CONVENIENCE
4 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
OUTLET
CONVENIENCE
5 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
OUTLET
CONVENIENCE
6 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
OUTLET
CONVENIENCE
7 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
OUTLET
8 EMERGENCY LIGHT 180 0.14 0.18 230 0.78 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 0.78 1 1 0.05 0.02
9 FDAS PANEL BOARD 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
10 CCTV PANEL BOARD 900 0.72 0.90 230 3.91 MCCB 10 2P 30A 50 2 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 3.91 1 1 0.25 0.11
11 AIR CONDITIONING 5,100 4.08 5.10 230 22.17 22.17 22.17 MCCB 10 3P 30A 50 3 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 22.17 0.85 1 1.04 0.45
UNITCONDITIONING
AIR
12 5,100 4.08 5.10 230 22.17 22.17 22.17 MCCB 10 3P 30A 50 3 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 22.17 0.85 1 1.04 0.45
UNITCONDITIONING
AIR
13 5,100 4.08 5.10 230 22.17 22.17 22.17 MCCB 10 3P 30A 50 3 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 22.17 0.85 1 1.04 0.45
UNITCONDITIONING
AIR
14 5,100 4.08 5.10 230 22.17 22.17 22.17 MCCB 10 3P 30A 50 3 5.5 5.5 THHN 5.5 THHN 25 uPVC 10 4.6 22.17 0.85 1 1.04 0.45
UNIT
15 SPARE - - -
16 SPARE - - -
17 SPARE - - -
18 SPARE - - -
TOTAL 28,680 22.94 28.68 230 101.22 104.35 96.52 MCCB 10 3P 100A 200 3 30 30 THHN 8 THHN 40 uPVC

TOTAL PANEL LOAD = 28.68 KVA


DEMAND FACTOR = 100.00 % MAIN PROTECTION: 100A 200 AF MCCB, 60 hz, Bolt On
TOTAL DEMAND LOAD = 28.68 KVA MAIN FEEDER SIZE: 3 - 30 mm2 THHN + 8 mm2 (G) in 1 - 40 uPVC
TOTAL CURRENT LOAD = 75.28 AMPS

DESIGN COMPUTATION SAFETY FACTOR MAIN CB FEEDER CONDUCTOR


28,680 VA + (25% x 5,100 VA) ISF = 75.28 A x 1.25 100A , 200 AF THREE PHASE, 3 POLE, USE 3C-30mm² THHN Cu. Wire,
IL =
230 V x 1.73 ISF = 94.10 A 230 VOLTS, 10kAIC 1C-8.0mm² Grounding Wire
IL = 75.28 A BOLT ON TYPE, MCCB, with GROUNDING IN 40mmØ uPVC Pipe
TERMINAL