Professional Documents
Culture Documents
Definition : Voltage reflection coefficient at a point on a line is defined as the ratio of reflected
voltage wave to incident wave at that point.
Current reflection coefficient at any point on a line is defined as the ratio of reflected current
wave to incident wave at that point.
➢ at the Load
where V+ & V– are the incident & reflected voltage waves at z = 0 i.e. at the load.
V − VL − Z0 IL VL /IL − Z0 ZL − Z0 ZL − Z0
L = + = = = or L =
V VL +Z0 IL VL / I L +Z0 ZL + Z0 ZL + Z0
Thus, the ratio of the reflected & incident waves is determined by the Load impedance only.
ZL − Z0 ZL − 1
L = = → in terms of normalized load
ZL + Z0 ZL + 1
1 + L ZL 1 + L
Then, ZL = Z0 and Normalized load impedance =
1 − L Z0 1 − L
LI = +=
( −
I − − V / Z0
=
)
−V − Z − ZL
= − L = 0 since Z0 =
V+
= −
V−
I +
V / Z0 V +
Z L + Z0 I+ I−
Thus, the current reflection coefficient at the load point is negative of the voltage reflection
coefficient at that point, i.e., LI = – L
L = –1 = 1ej = L ejL L = 1, L =
V+ + V– = 0 V– = –V+
Thus, the reflected voltage is equal to the incident voltage in magnitude but 1800 out of phase
with the incident voltage.
L = 1 = 1ej0 = L ejL L = 1, L = 00
I+ + I– = 0
or V+ – V– = 0 V– = +V+
Thus, the reflected voltage is equal to the incident voltage in both magnitude and phase.
L = 0 V– = 0
In this case all the power in the incident wave is transmitted to (or absorbed by) the load and
none of it is reflected back toward the generator.
➢ at the Source
V − e+z V − +2 z
(z) = Reflection coefficient at a distance z, ( z ) = + −z
= +e = Le+2 z
V e V
Voltage reflection coefficient at a distance l from the load or at z = –l distance, i.e. at the
source end,
V − e−l V −
(l ) = + +l = + e−2 l = L e−2 l or (l ) = Le−2l
V e V
• in terms of Zin
Conditions : At z = – l, V (z = – l) = VS I (z = – l) = IS
1 1
(3a) + (3c) gives V + e +l = (VS + Z 0 I S ) or V+ = (VS + Z 0 I S ) e−l (4a)
2 2
1 1
(3a) – (3c) gives V − e−l = (VS − Z 0 I S ) or V− = (VS − Z 0 I S ) e +l (4b)
2 2
where V+ & V– are the incident & reflected voltage waves at z = 0 i.e. at the load,
V+ e+l and V– e–l are the incident & reflected voltage waves at z = – l i.e. at the
source end.
Class Note by Santanu Das 3
Transmission Lines
1
− −l
V e (VS − Z0 I S ) V − Z I V / I − Z Z − Z
From (4a) and (4b), ( l ) = = 2 = S 0 S
= S S 0
= in 0
V + e+l 1 +
(VS + Z0 I S ) S 0 S S S 0 in 0
V Z I V / I + Z Z + Z
2
Zin − Z0
or ( l ) =
Zin + Z0
1 + ( l ) Z 1 + ( l )
From this, Input imp. Z in = Z 0 & Normalized Input imp. Zin = in =
1 − ( l ) Z 0 1 − ( l )
= 0 + j
V − e− jl V − −2 jl
( l ) = + + jl
= +e = Le− j2l
V e V
V−
where L = + denotes the reflection coefficient of the load.
V
Thus, the phase between (l) and L changes by TWICE the electrical length (2l) between
the load and observation point where (l) is measured.
(l) lags behind L by 2l. [Since the path difference between the reflected and
incident waves is 2l (l, to the right direction to the load, plus l, to the left direction from the
load)]
Therefore, the Phase difference between the reflected and incident voltages at a distance l
from the load is → ( – 2l)
So, the magnitude of reflection coefficient () is the SAME all along the line, i.e., (l) = L
for a loss-less line or low-loss high frequency line.
Definition : Voltage transmission coefficient (T) at any point on a line is the ratio of
transmitted voltage wave to incident wave at that point.
Transmitted voltage at a point
T (at a po int) =
Incident voltage at the same point
Current transmission coefficient at any point on a line is the ratio of transmitted current wave
to incident wave at that point.
VL V + + V −
Hence, Voltage transmission coefficient at the load, TL = = = 1 + L
V+ V+
TL = (1 + L) and VL = TL V+= (1 + L) V+
IL I+ + I− I−
Current transmission coefficient, TLI = = = 1 + = 1 + LI = 1 − L
I+ I+ I+
TLI = 1 – L = 1 – (TL – 1) = 2 – TL
L = –1 TL = 1 + L = 0
Thus, the incident voltage is fully reflected back, there is no transmitted voltage.
Thus, the incident current is fully reflected back, and the magnitude of the transmitted current
gets Doubled the magnitude of incident current.
Transmitted power PL = VL IL = 0
L = 1 TL = 1 + L = 2 VL = 2V+
Thus, the incident voltage is fully reflected back, and the magnitude of the transmitted voltage
becomes Twice the magnitude of incident voltage.
Class Note by Santanu Das 5
Transmission Lines
So, the incident current is fully reflected back with a phase reversal, and there is no
transmitted current.
Transmitted power PL = VL IL = 0
L = 0 TL = 1 + L = 1 VL = V+
LI = –L = 0 and I– = 0
TLI = 1 – L = 1 and IL = I+
The reflection coefficient is zero. All the power in the incident wave is transmitted to the load
and none of it is reflected back toward the generator.
Transmitted power PL = VL IL = V+ I+ = Incident power
Under this condition (ZL = Z0 and L = 0) the load is said to be MATCHED to the line.