You are on page 1of 1

Wet Well Depth Calculation

Input Data

Pump Capacity Qpump = 37.72 l/s


= 0.038 cu.m/s
Inlet Pipe Invert Level, IL = ‐4.740 m ( refer to site layout drawing)
Minimum Pump
Submergence
(Shut off point) Smin = 0.54 m ( from Pump Selection + pump concrete base)

Minimum Wet Well


Minimum Wet Well
Live Volume per duty
pump Vmin = 0.25QT m³ (From ADSSC Design Guidelines)
where
T= Pump cycle time
Q= Pump flow capacity
then;
Pump cycle time, T = 240 s (15 starts/hr) (Agreed by ADSSC)
Vmin = 2.263 m³
Number of duty pump n = 1
Thus, total required
Minimum wet well live
volume Vtot = 2.263 m³
Wet Well Dimension
Diameter of Wet Well D = 2.40 m
Area A = 4.53 m²
Height of Liquid h = 0.500 m (as per ADSSC Standard)

Wet Well Depth

Finish Ground Level = 3.8 m

OD 225 HDPE

OD 315 mm
I.L of Incoming Pipe
DN200 DI

Maximum level = ‐4.740 m


Pump 1 Start = ‐4.94 m

Pump 1 Stop
Minimum Water Level= ‐5.440 m

Pump Suction Level= ‐5.722 m

Bottom Level= ‐5.985 m